  4. INMBSMIT001I000 Mitsubishi Electric AC to Modbus RTU gateway

VRF / split AC gateway · Modbus register map

Intesis (HMS Networks) INMBSMIT001I000 Mitsubishi Electric AC to Modbus RTU gateway Modbus register map

Updated 16 October 2026

Short answer

Modbus RTU server that connects to the CN105 port of a single Mitsubishi Electric indoor unit. Points are 16-bit holding registers for on/off, mode, fan, vane, setpoint, room temperature, alarm and error code, with window-contact and external-temperature (virtual temperature) features.

This page lists 21 Modbus registers for the Intesis (HMS Networks) INMBSMIT001I000 Mitsubishi Electric AC to Modbus RTU gateway — 12 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Intesis (HMS Networks)’s own free documentation (linked below) and checked against it.

Manufacturer
Intesis (HMS Networks)
Model
INMBSMIT001I000 Mitsubishi Electric AC to Modbus RTU gateway
Equipment type
VRF / split AC gateway
Registers
21 (12 writable)
Transport
Modbus RTU
Default unit ID
1
Default serial
9600 baud, 8N2
Documented addressing
0-based (the number printed is the address on the wire)
Also known as
INMBSMIT001I000, Intesis Mitsubishi Electric Modbus
Source document
Intesis INMBSMIT001I000 Modbus RTU (EIA-485) Interface for Mitsubishi Electric air conditioners - User's Manual · User's Manual r2.8 EN · rev. 2024-11
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Intesis (HMS Networks) INMBSMIT001I000 Mitsubishi Electric AC to Modbus RTU gateway

Integration in brief

Set the address on SW3 and the baud on SW3/SW4, set SW1 to match the unit's fan speeds, power-cycle, then read holding registers 0-11 with function 03 and write with 06. Confirm the temperature scale on SW4 first.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 0AC unit On/OffUINT16On/offRead/write
HR 1AC unit modeUINT16ModeRead/write
HR 2AC unit fan speedUINT16Fan speedRead/write
HR 4AC unit temperature setpointUINT16SetpointRead/write
HR 5AC unit temperature referenceUINT16Room temperatureRead
HR 10AC unit alarm statusUINT16Alarm flagRead
HR 11Error codeUINT16Error codeRead

Enable Modbus control & writes

No enable step; register 7 (gateway disablement) must be 0 for commands to reach the unit.

Byte order & addressing

Network setup

Watch out for

Intesis (HMS Networks) INMBSMIT001I000 Mitsubishi Electric AC to Modbus RTU gateway Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

21 of 21 shown
Intesis (HMS Networks) INMBSMIT001I000 Mitsubishi Electric AC to Modbus RTU gateway Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0AC unit On/OffUINT16Read/write0 = Off; 1 = On
HR1AC unit modeAvailable modes depend on the indoor unit.UINT16Read/write0 = Auto; 1 = Heat; 2 = Dry; 3 = Fan; 4 = Cool
HR2AC unit fan speedAvailable speeds depend on unit and SW1 setting.UINT16Read/write0 = Auto; 1 = Low; 2 = Mid-1; 3 = Mid-2; 4 = High
HR3AC unit vane positionAvailable positions depend on the indoor unit.UINT16Read/write0 = Auto; 1 = Horizontal; 2 = Position-2; 3 = Position-3; 4 = Position-4; 5 = Vertical; 10 = Swing
HR4AC unit temperature setpointSetpoint 16..32 °C (61..90 °F). SW4 x1 °C assumed (x10: 0.1, or °F).UINT16°CRead/write
HR5AC unit temperature referenceUnit room temperature, 10..38 °C. SW4 x1 °C assumed (x10: 0.1, or °F).UINT16°CRead
HR6Window contactVirtual window contact written from Modbus.UINT16Read/write0 = Closed; 1 = Open
HR7Gateway disablementStops the gateway passing commands; stored in NVM.UINT16Read/write0 = INMBSMIT001I000 enabled; 1 = INMBSMIT001I000 disabled
HR8AC remote control disablementBlocks the unit's remote control; stored in NVM.UINT16Read/write0 = Remote control enabled; 1 = Remote control disabled
HR9AC unit operation timeHours the unit has been on; stored in NVM.UINT16hRead/write
HR10AC unit alarm statusUINT16Read0 = No alarm condition; 1 = Alarm condition
HR11Error codeMitsubishi error number (manual section 7); 65535 = no comms with AC unit.UINT16Read0 = No error present; 65535 = Communication error with the AC unit
HR13Open window switch-off timeoutCountdown after window opens before switch-off (0..30, default 30).UINT16minRead/write
HR14Modbus RTU baud rateBaud rate in use (set on DIP switches).UINT16Read
HR15Device Modbus slave addressRange 1..63.UINT16Read
HR21Max number of fan speedsFollows DIP SW1 position 4.UINT16Read
HR22External ambient temperature (Modbus)Room temperature written from Modbus (virtual temperature). SW4 x1 °C assumed (x10: 0.1, or °F).UINT16°CRead/write32768 = Not initialised / no value (0x8000; manual writes -32768)
HR23AC real setpoint temperatureSetpoint actually applied in the indoor unit. SW4 x1 °C assumed (x10: 0.1, or °F).UINT16°CRead
HR49Device IDReads 0x0500.UINT16Read
HR50Software versionUINT16Read
HR97Block periodic sendings1 = only forward Modbus writes that change the value (FW 2.1+).UINT16Read/write0 = Non-blocked; 1 = Blocked

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Intesis (HMS Networks) INMBSMIT001I000 Mitsubishi Electric AC to Modbus RTU gateway

What Modbus registers does the Intesis (HMS Networks) INMBSMIT001I000 Mitsubishi Electric AC to Modbus RTU gateway have?

This map lists 21 registers: 21 holding registers. 12 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Intesis (HMS Networks) INMBSMIT001I000 Mitsubishi Electric AC to Modbus RTU gateway Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Each table gives a 'protocol address' (base 0) and a 'PLC address' (base 1). The protocol address is the wire address and is used for 'documented'.

What are the minimum Modbus registers to integrate the Intesis (HMS Networks) INMBSMIT001I000 Mitsubishi Electric AC to Modbus RTU gateway?

Start with HR 0 AC unit On/Off (On/off); HR 1 AC unit mode (Mode); HR 2 AC unit fan speed (Fan speed); HR 4 AC unit temperature setpoint (Setpoint); HR 5 AC unit temperature reference (Room temperature); HR 10 AC unit alarm status (Alarm flag); HR 11 Error code (Error code).

How do I enable Modbus control of the Intesis (HMS Networks) INMBSMIT001I000 Mitsubishi Electric AC to Modbus RTU gateway?

No enable step; register 7 (gateway disablement) must be 0 for commands to reach the unit.

Where is the official Intesis (HMS Networks) INMBSMIT001I000 Mitsubishi Electric AC to Modbus RTU gateway Modbus documentation?

The source is Intesis INMBSMIT001I000 Modbus RTU (EIA-485) Interface for Mitsubishi Electric air conditioners - User's Manual (User's Manual r2.8 EN), revision 2024-11, published free by Intesis (HMS Networks) at https://www.hms-networks.com/docs/default-source/products/intesis/manuals-and-guides---manuals/user-manual-inmbsmit001i000.pdf.

More Intesis (HMS Networks) Modbus register maps

Source: Intesis INMBSMIT001I000 Modbus RTU (EIA-485) Interface for Mitsubishi Electric air conditioners - User's Manual · User's Manual r2.8 EN · rev. 2024-11. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.