VRF / split AC gateway · Modbus register map

Intesis (HMS Networks) INMBSLGE001R000 LG AC to Modbus RTU gateway Modbus register map

Updated 16 October 2026

Short answer

Modbus RTU server that sits on the 3-wire remote-controller bus of an LG indoor unit, alongside or instead of the LG wired remote. Holding registers cover on/off, mode, fan, vanes, setpoint, room temperature, compressor status and run hours, alarm and error code, and window-contact / virtual-temperature features.

This page lists 32 Modbus registers for the Intesis (HMS Networks) INMBSLGE001R000 LG AC to Modbus RTU gateway — 17 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Intesis (HMS Networks)’s own free documentation (linked below) and checked against it.

Manufacturer
Intesis (HMS Networks)
Model
INMBSLGE001R000 LG AC to Modbus RTU gateway
Equipment type
VRF / split AC gateway
Registers
32 (17 writable)
Transport
Modbus RTU
Default unit ID
1
Default serial
9600 baud, 8N2
Documented addressing
0-based (the number printed is the address on the wire)
Also known as
INMBSLGE001R000, LG-RC-MBS-1, Intesis LG Modbus
Source document
Intesis INMBSLGE001R000 Modbus RTU (EIA-485) Interface for LG air conditioners - User's Manual · User's Manual v1.9 EN · rev. 2024-01
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Intesis (HMS Networks) INMBSLGE001R000 LG AC to Modbus RTU gateway

Integration in brief

Decide the BYR-bus role first (SW1: slave next to an LG wired remote, master if there is none), set address and baud on SW3/SW4, power-cycle, then poll holding registers 0-11 with function 03 and write with 06.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 0AC unit On/OffUINT16On/offRead/write
HR 1AC unit modeUINT16ModeRead/write
HR 2AC unit fan speedUINT16Fan speedRead/write
HR 4AC unit temperature setpointUINT16SetpointRead/write
HR 5AC unit temperature referenceUINT16Room temperatureRead
HR 11Error codeUINT16Error codeRead
HR 53Compressor statusUINT16Compressor statusRead

Enable Modbus control & writes

No enable step; register 7 (gateway disablement) must be 0 for commands to reach the unit.

Byte order & addressing

Network setup

Watch out for

Intesis (HMS Networks) INMBSLGE001R000 LG AC to Modbus RTU gateway Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

32 of 32 shown
Intesis (HMS Networks) INMBSLGE001R000 LG AC to Modbus RTU gateway Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0AC unit On/OffUINT16Read/write0 = Off; 1 = On
HR1AC unit modeAvailable modes depend on the indoor unit.UINT16Read/write0 = Auto; 1 = Heat; 2 = Dry; 3 = Fan; 4 = Cool
HR2AC unit fan speed0 = Auto, 1..7 = fan positions 1..7; availability depends on unit.UINT16Read/write0 = Auto; 1 = Pos. 1; 2 = Pos. 2; 3 = Pos. 3; 4 = Pos. 4; 5 = Pos. 5; 6 = Pos. 6; 7 = Pos. 7
HR3AC unit vane positionAvailability depends on the indoor unit.UINT16Read/write0 = No Swing; 1 = Pos. 1; 2 = Pos. 2; 3 = Pos. 3; 4 = Pos. 4; 10 = Swing; 11 = Swirl
HR4AC unit temperature setpointSetpoint 16..30 °C (61..86 °F). SW4 x1 °C assumed (x10: 0.1, or °F).UINT16°CRead/write32768 = Not initialised / no value (0x8000; manual writes -32768)
HR5AC unit temperature referenceUnit room temperature, 10..38 °C. SW4 x1 °C assumed (x10: 0.1, or °F).UINT16°CRead32768 = Not initialised / no value (0x8000; manual writes -32768)
HR6Window contactVirtual window contact written from Modbus.UINT16Read/write0 = Closed; 1 = Open
HR7Gateway disablementStops the gateway passing commands; stored in NVM.UINT16Read/write0 = INMBSLGE001R000 enabled; 1 = INMBSLGE001R000 disabled
HR8AC remote control disablementBlocks the LG wired remote; stored in NVM.UINT16Read/write0 = Remote controller enabled; 1 = Remote controller disabled
HR9AC unit operation timeHours the unit has been on; stored in NVM.UINT16hRead/write
HR10AC unit alarm statusUINT16Read0 = No alarm condition; 1 = Alarm condition
HR11Error codeLG error number (manual section 7); 65535 = no comms with AC unit or remote.UINT16Read0 = No error present; 65535 = Communication error with AC unit or remote controller
HR13Open window switch-off timeoutCountdown after window opens before switch-off (0..30, default 30).UINT16minRead/write
HR14Modbus RTU baud rateBaud rate in use (set on DIP switches).UINT16Read
HR15Modbus slave addressRange 1..63.UINT16Read
HR21Max number of fan speedsUINT16Read
HR22External ambient temperature (Modbus)Room temperature written from Modbus (virtual temperature). SW4 x1 °C assumed (x10: 0.1, or °F).UINT16°CRead/write32768 = Not initialised / no value (0x8000; manual writes -32768)
HR23AC real setpoint temperatureSetpoint actually applied in the indoor unit. SW4 x1 °C assumed (x10: 0.1, or °F).UINT16°CRead
HR24Current AC max setpointUpper setpoint limit reported by the unit. SW4 x1 °C assumed (x10: 0.1, or °F).UINT16°CRead32768 = Not initialised / no value (0x8000; manual writes -32768)
HR25Current AC min setpointLower setpoint limit reported by the unit. SW4 x1 °C assumed (x10: 0.1, or °F).UINT16°CRead32768 = Not initialised / no value (0x8000; manual writes -32768)
HR26AC unit left/right vane positionUINT16Read/write0 = Auto; 1 = Pos. 1; 2 = Pos. 2; 3 = Pos. 3; 4 = Pos. 4; 5 = Pos. 5; 6 = Pos. 6; 7 = Pos. 7; 8 = Pos. 8; 9 = Pos. 9; 10 = Swing
HR27Up/down vane positionWrite 1 to send a pulse command to the up/down vane.UINT16Read/write1 = Pulse
HR31Window contact status (feedback)UINT16Read0 = Not active; 1 = Active (window open)
HR48Switch valueCurrent DIP switch settings.UINT16Read
HR49Device IDReads 0x1000.UINT16Read
HR50Software versionUINT16Read
HR53Compressor statusUINT16Read0 = Off; 1 = To Off; 2 = To On; 3 = On
HR54Compressor on timeCompressor running hours; stored in NVM.UINT16hRead/write
HR65Input reference temperature (feedback)Reference temperature feedback. SW4 x1 °C assumed (x10: 0.1, or °F).UINT16°CRead32768 = Not initialised / no value (0x8000; manual writes -32768)
HR97Block periodic sendings1 = only forward Modbus writes that change the value (FW 1.7+).UINT16Read/write0 = Non-blocked; 1 = Blocked
HR98Master/Slave (gateway role)Gateway role on the LG BYR bus.UINT16Read/write0 = Slave; 1 = Master
HR99ResetWrite 1 to restart the gateway.UINT16Read/write1 = Reset

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Intesis (HMS Networks) INMBSLGE001R000 LG AC to Modbus RTU gateway

What Modbus registers does the Intesis (HMS Networks) INMBSLGE001R000 LG AC to Modbus RTU gateway have?

This map lists 32 registers: 32 holding registers. 17 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Intesis (HMS Networks) INMBSLGE001R000 LG AC to Modbus RTU gateway Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Tables give a 'protocol address' (base 0) and a 'PLC address' (base 1); the protocol address is the wire address and is used for 'documented'.

What are the minimum Modbus registers to integrate the Intesis (HMS Networks) INMBSLGE001R000 LG AC to Modbus RTU gateway?

Start with HR 0 AC unit On/Off (On/off); HR 1 AC unit mode (Mode); HR 2 AC unit fan speed (Fan speed); HR 4 AC unit temperature setpoint (Setpoint); HR 5 AC unit temperature reference (Room temperature); HR 11 Error code (Error code); HR 53 Compressor status (Compressor status).

How do I enable Modbus control of the Intesis (HMS Networks) INMBSLGE001R000 LG AC to Modbus RTU gateway?

No enable step; register 7 (gateway disablement) must be 0 for commands to reach the unit.

Where is the official Intesis (HMS Networks) INMBSLGE001R000 LG AC to Modbus RTU gateway Modbus documentation?

The source is Intesis INMBSLGE001R000 Modbus RTU (EIA-485) Interface for LG air conditioners - User's Manual (User's Manual v1.9 EN), revision 2024-01, published free by Intesis (HMS Networks) at https://www.hms-networks.com/docs/default-source/products/intesis/manuals-and-guides---manuals/user-manual-inmbslge001r000.pdf.