  4. INMBSDAL0640000 / INMBSDAL1280000 DALI-2 to Modbus RTU / TCP server

Lighting gateway (DALI-2 to Modbus) · Modbus register map

Intesis (HMS Networks) INMBSDAL0640000 / INMBSDAL1280000 DALI-2 to Modbus RTU / TCP server Modbus register map

Updated 17 November 2026

Short answer

Gateway that exposes DALI / DALI-2 control gear on one or two DALI lines as Modbus holding registers. Addresses follow fixed formulas: per ballast short address (100 registers each), per DALI group (from 6400) and broadcast (from 6800), plus a 7000 offset for the second line. Signals cover levels, on/off, step, scenes, fade and limit settings, status and failure bits.

This page lists 38 Modbus registers for the Intesis (HMS Networks) INMBSDAL0640000 / INMBSDAL1280000 DALI-2 to Modbus RTU / TCP server — 23 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Intesis (HMS Networks)’s own free documentation (linked below) and checked against it.

Manufacturer
Intesis (HMS Networks)
Model
INMBSDAL0640000 / INMBSDAL1280000 DALI-2 to Modbus RTU / TCP server
Equipment type
Lighting gateway (DALI-2 to Modbus)
Registers
38 (23 writable)
Transport
Modbus RTU, Modbus TCP
Default unit ID
Not stated
TCP port
502
Documented addressing
derived from parameter numbers
Also known as
INMBSDAL0640000, INMBSDAL1280000, Intesis Modbus Server - DALI, Intesis DALI-2 Modbus gateway
Source document
Intesis Modbus Server - DALI (DALI-2) User Manual · User Manual r1.2 EN (page headers read r1.1) · rev. 2021-09 · unofficial copy
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Intesis (HMS Networks) INMBSDAL0640000 / INMBSDAL1280000 DALI-2 to Modbus RTU / TCP server

Integration in brief

Configure the gateway in Intesis MAPS with fixed Modbus addresses, then write arc power level (sa x 100 + 15) or the group/broadcast level registers and read actual level (sa x 100 + 6) and ballast status (+5).

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 15Arc power level (sa 0)INT16Set level of short address 0Read/write
HR 6Actual level (sa 0)INT16Actual level of short address 0Read
HR 5Ballast status (sa 0)BITMAP16Ballast statusRead
HR 0Ballast / lamp failure bit field (ECG15-ECG0)BITMAP16Failure bits for sa 0-15Read
HR 6400Group 0: Arc power levelINT16Group 0 levelRead/write
HR 6800Broadcast: arc power levelINT16Broadcast levelRead/write

Enable Modbus control & writes

All settings (Modbus RTU/TCP parameters, slave number, IP, Fixed address mode) are made in the Intesis MAPS configuration tool.

Byte order & addressing

Network setup

Watch out for

Intesis (HMS Networks) INMBSDAL0640000 / INMBSDAL1280000 DALI-2 to Modbus RTU / TCP server Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

38 of 38 shown
Intesis (HMS Networks) INMBSDAL0640000 / INMBSDAL1280000 DALI-2 to Modbus RTU / TCP server Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0doc 7000 x channel + (100 x sa) + 0Ballast / lamp failure bit field (ECG15-ECG0)Bit set = that short address reports ballast or lamp failure.BITMAP16Read
HR1doc 7000 x channel + (100 x sa) + 1Ballast / lamp failure bit field (ECG31-ECG16)Bit set = that short address reports ballast or lamp failure.BITMAP16Read
HR2doc 7000 x channel + (100 x sa) + 2Ballast / lamp failure bit field (ECG47-ECG32)Bit set = that short address reports ballast or lamp failure.BITMAP16Read
HR3doc 7000 x channel + (100 x sa) + 3Ballast / lamp failure bit field (ECG63-ECG48)Bit set = that short address reports ballast or lamp failure.BITMAP16Read
HR4doc 7000 x channel + (100 x sa) + 4Update all ECG statusWrite 1 to trigger a status refresh of all gear.INT16Read/write0 = Update finished; 1 = Trigger update
HR5doc 7000 x channel + (100 x sa) + 5Ballast status (sa 0)BITMAP16Readbit 0 = BallFail; bit 1 = LampFail; bit 2 = LampPwrOn; bit 3 = BallLimErr; bit 4 = FadeRun; bit 5 = ResetSt; bit 6 = MissShAdd; bit 7 = PwrCycle
HR6doc 7000 x channel + (100 x sa) + 6Actual level (sa 0)0..100 %.INT16%Read
HR7doc 7000 x channel + (100 x sa) + 7Device type (sa 0)INT16Read0 = Fluorescent; 1 = Emergency; 2 = Discharge; 3 = Halogen; 4 = Incandescent; 5 = Digital signal; 6 = LED; 7 = Switching; 8 = Colour control
HR8doc 7000 x channel + (100 x sa) + 8Physical minimum level (sa 0)0..100 %.INT16%Read
HR9doc 7000 x channel + (100 x sa) + 9Min level (sa 0)0..100 %.INT16%Read
HR10doc 7000 x channel + (100 x sa) + 10Max level (sa 0)0..100 %.INT16%Read
HR11doc 7000 x channel + (100 x sa) + 11Power on level (sa 0)0..100 %.INT16%Read
HR12doc 7000 x channel + (100 x sa) + 12System failure level (sa 0)0..100 %.INT16%Read
HR13doc 7000 x channel + (100 x sa) + 13Fade time (sa 0)DALI fade time code 0..15.INT16Read
HR14doc 7000 x channel + (100 x sa) + 14Fade rate (sa 0)DALI fade rate code 1..15.INT16Read
HR15doc 7000 x channel + (100 x sa) + 15Arc power level (sa 0)Dim level 0..100 %.INT16%Read/write
HR16doc 7000 x channel + (100 x sa) + 16Arc power off / on (sa 0)INT16Read/write0 = Off; 1 = 100 %
HR17doc 7000 x channel + (100 x sa) + 17Step down / up (sa 0)INT16Read/write0 = Step down; 1 = Step up
HR18doc 7000 x channel + (100 x sa) + 18Recall min level (sa 0)INT16Write1 = Recall min level
HR19doc 7000 x channel + (100 x sa) + 19Recall max level (sa 0)INT16Write1 = Recall max level
HR20doc 7000 x channel + (100 x sa) + 20Go to scene (sa 0)Scene 0..15.INT16Read/write
HR21doc 7000 x channel + (100 x sa) + 21Store current level as scene (sa 0)Scene 0..15.INT16Read/write
HR22doc 7000 x channel + (100 x sa) + 22Clear / remove scene (sa 0)Scene 0..15.INT16Read/write
HR23doc 7000 x channel + (100 x sa) + 23Set fade time (sa 0)0..15.INT16Read/write
HR24doc 7000 x channel + (100 x sa) + 24Set fade rate (sa 0)1..15.INT16Read/write
HR25doc 7000 x channel + (100 x sa) + 25Set min level (sa 0)0..100 %.INT16%Read/write
HR26doc 7000 x channel + (100 x sa) + 26Set max level (sa 0)0..100 %.INT16%Read/write
HR27doc 7000 x channel + (100 x sa) + 27Set power-on level (sa 0)0..100 %.INT16%Read/write
HR28doc 7000 x channel + (100 x sa) + 28Set system-failure level (sa 0)0..100 %.INT16%Read/write
HR31doc 7000 x channel + (100 x sa) + 31Multicontrol (sa 0)Coded command: 0 off, 1 100%, 2 up, 3 down, 1XX scene, 2XX store, 3XX remove, 1XXX-6XXX settings.INT16Read
HR6400doc 7000 * line + (20 * gr) + 6400Group 0: Arc power level0..100 %.INT16%Read/write
HR6401doc 7000 * line + (20 * gr) + 6401Group 0: Arc power off / onINT16Read/write0 = Off; 1 = 100 %
HR6402doc 7000 * line + (20 * gr) + 6402Group 0: Step down / upINT16Read/write0 = Step down; 1 = Step up
HR6403doc 7000 * line + (20 * gr) + 6403Group 0: Recall min levelINT16Write1 = Recall min level
HR6404doc 7000 * line + (20 * gr) + 6404Group 0: Recall max levelINT16Write1 = Recall max level
HR6405doc 7000 * line + (20 * gr) + 6405Group 0: Go to sceneScene 0..15.INT16Read/write
HR6800doc 7000 * line + 6800Broadcast: arc power levelAll gear on the line, 0..100 %.INT16%Read/write
HR6801doc 7000 * line + 6801Broadcast: arc power off / onINT16Read/write0 = Off; 1 = 100 %

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Intesis (HMS Networks) INMBSDAL0640000 / INMBSDAL1280000 DALI-2 to Modbus RTU / TCP server

What Modbus registers does the Intesis (HMS Networks) INMBSDAL0640000 / INMBSDAL1280000 DALI-2 to Modbus RTU / TCP server have?

This map lists 38 registers: 38 holding registers. 23 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Intesis (HMS Networks) INMBSDAL0640000 / INMBSDAL1280000 DALI-2 to Modbus RTU / TCP server Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers derived from parameter numbers. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Address = 7000 x channel + 100 x short address + signal (ballasts), 7000 x line + 20 x group + 6400..6415 (groups), 7000 x line + 6800..6815 (broadcast). The manual states the result is in link-layer format with the first register at 0, so it is the wire address. Only short address 0, group 0 and two broadcast signals of channel 0 are listed.

What are the minimum Modbus registers to integrate the Intesis (HMS Networks) INMBSDAL0640000 / INMBSDAL1280000 DALI-2 to Modbus RTU / TCP server?

Start with HR 15 Arc power level (sa 0) (Set level of short address 0); HR 6 Actual level (sa 0) (Actual level of short address 0); HR 5 Ballast status (sa 0) (Ballast status); HR 0 Ballast / lamp failure bit field (ECG15-ECG0) (Failure bits for sa 0-15); HR 6400 Group 0: Arc power level (Group 0 level); HR 6800 Broadcast: arc power level (Broadcast level).

How do I enable Modbus control of the Intesis (HMS Networks) INMBSDAL0640000 / INMBSDAL1280000 DALI-2 to Modbus RTU / TCP server?

All settings (Modbus RTU/TCP parameters, slave number, IP, Fixed address mode) are made in the Intesis MAPS configuration tool.

Where is the official Intesis (HMS Networks) INMBSDAL0640000 / INMBSDAL1280000 DALI-2 to Modbus RTU / TCP server Modbus documentation?

The source is Intesis Modbus Server - DALI (DALI-2) User Manual (User Manual r1.2 EN (page headers read r1.1)), revision 2021-09. Intesis (HMS Networks) doesn't publish it on its own website, so this map was re-typed from a free copy at https://cdn.chipkin.com/assets/uploads/2022/Feb/user-manual-inmbsdalxxx0000_17-21-45-17.pdf. It may be an older revision, so check it against the live unit.