- Home
- Modbus register maps
- Intesis (HMS Networks)
- IN770AIR***O000 700 Series Air Gateway, Midea application (Modbus)
VRF / split AC gateway · Modbus register map
Intesis (HMS Networks) IN770AIR***O000 700 Series Air Gateway, Midea application (Modbus) Modbus register map
Updated 19 November 2026
Intesis 700 Series gateway on the Midea commercial / VRF XYE bus serving Modbus RTU and TCP. Each unit index gets a 100-register block with on/off, mode, setpoint, fan, vanes, room temperature, errors and locks; outdoor registers exist for Midea V8 systems; low addresses hold all-unit commands.
This page lists 38 Modbus registers for the Intesis (HMS Networks) IN770AIR***O000 700 Series Air Gateway, Midea application (Modbus) — 33 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Intesis (HMS Networks)’s own free documentation (linked below) and checked against it.
- Manufacturer
- Intesis (HMS Networks)
- Model
- IN770AIR***O000 700 Series Air Gateway, Midea application (Modbus)
- Equipment type
- VRF / split AC gateway
- Registers
- 38 (33 writable)
- Transport
- Modbus RTU, Modbus TCP
- Default unit ID
- Not stated
- Documented addressing
- 0-based (the number printed is the address on the wire)
- Also known as
- IN770AIR00MO000, IN770AIR00SO000, IN770AIRXXSO000
Integration notes: Intesis (HMS Networks) IN770AIR***O000 700 Series Air Gateway, Midea application (Modbus)
Pick the Midea application and the Modbus interface in Intesis MAPS, discover or add the units, send the project, then read and write each unit's block.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 100 | IU on/off | UINT16 | On/off | Read/write |
| HR 101 | IU operation mode | UINT16 | Mode | Read/write |
| HR 102 | IU temperature setpoint | UINT16 | Setpoint (x10) | Read/write |
| HR 103 | IU fan speed | UINT16 | Fan speed | Read/write |
| HR 105 | IU room temperature | INT16 | Room temperature (x10) | Read |
| HR 106 | IU unit error code | UINT16 | Error code | Read |
| HR 107 | IU communication error | UINT16 | Communication error | Read |
Enable Modbus control & writes
The units must be set up in Intesis MAPS; the unit index used in the formulas is the one shown on the Signals tab.
Byte order & addressing
- Writes accept FC06 (single register) only.
- All-unit (T) registers are trigger-only commands.
Network setup
- All Modbus settings (RTU or TCP, slave address, baud, parity) are made with the Intesis MAPS tool; the manual gives no factory serial settings.
- On first power-up DHCP is tried for 30 seconds, then the gateway falls back to 192.168.100.246.
- Modbus RTU uses the EIA-485 port (A+, B-); bias and 120 ohm termination are on DIP switch block SW A.
Watch out for
- The unit index n is the one shown in the Unit column of the MAPS Signals tab.
Intesis (HMS Networks) IN770AIR***O000 700 Series Air Gateway, Midea application (Modbus) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0 | On (all units) | UINT16 | Write | 1 = Set the units on | ||||
| HR | 1 | Off (all units) | UINT16 | Write | 1 = Set the units off | ||||
| HR | 2 | Mode Auto (all units) | UINT16 | Write | 1 = Execute | ||||
| HR | 3 | Mode Heat (all units) | UINT16 | Write | 1 = Execute | ||||
| HR | 4 | Mode Dry (all units) | UINT16 | Write | 1 = Execute | ||||
| HR | 5 | Mode Fan (all units) | UINT16 | Write | 1 = Execute | ||||
| HR | 6 | Mode Cool (all units) | UINT16 | Write | 1 = Execute | ||||
| HR | 7 | Fan speed Auto (all units) | UINT16 | Write | 1 = Execute | ||||
| HR | 8 | Fan speed Low (all units) | UINT16 | Write | 1 = Execute | ||||
| HR | 9 | Fan speed Mid (all units) | UINT16 | Write | 1 = Execute | ||||
| HR | 10 | Fan speed High (all units) | UINT16 | Write | 1 = Execute | ||||
| HR | 11 | Swing on (all units) | UINT16 | Write | 1 = Execute | ||||
| HR | 12 | Swing off (all units) | UINT16 | Write | 1 = Execute | ||||
| HR | 13 | Temperature setpoint (all units) | Tenths of °C, 17..30. | UINT16 | × 0.1 | °C | Write | ||
| HR | 14 | Operating mode force on (all units) | UINT16 | Write | 1 = Force operating mode | ||||
| HR | 15 | Operating mode force off (all units) | UINT16 | Write | 1 = Unforce operating mode | ||||
| HR | 16 | Remote control lock on (all units) | UINT16 | Write | 1 = Lock remote control | ||||
| HR | 17 | Remote control lock off (all units) | UINT16 | Write | 1 = Unlock remote control | ||||
| HR | 18 | Fan speed (all units) | UINT16 | Write | 0 = Auto; 1 = Speed 1; 2 = Speed 2; 3 = Speed 3; 4 = Speed 4; 5 = Speed 5; 6 = Speed 6; 7 = Speed 7 | ||||
| HR | 19 | Vane left/right (all units) | UINT16 | Write | 0 = Stop; 1 = Step 1; 2 = Step 2; 3 = Step 3; 4 = Step 4; 5 = Step 5; 6 = Swing | ||||
| HR | 20 | Vane up/down (all units) | UINT16 | Write | 0 = Stop; 1 = Step 1; 2 = Step 2; 3 = Step 3; 4 = Step 4; 5 = Step 5; 6 = Swing | ||||
| HR | 100doc (IU address[1..N] × 100) + 0 | IU on/off | Unit index 1 shown; see notes. | UINT16 | Read/write | 0 = Off; 1 = On | |||
| HR | 101doc (IU address[1..N] × 100) + 1 | IU operation mode | Codes 5..8 are read-only. | UINT16 | Read/write | 0 = Heat; 1 = Cool; 2 = Fan; 3 = Dry; 4 = Auto; 5 = AutoHeat; 6 = AutoCool; 7 = AutoDry; 8 = AutoFan | |||
| HR | 102doc (IU address[1..N] × 100) + 2 | IU temperature setpoint | Tenths of °C, 17..30. | UINT16 | × 0.1 | °C | Read/write | ||
| HR | 103doc (IU address[1..N] × 100) + 3 | IU fan speed | UINT16 | Read/write | 0 = Auto; 1 = Low; 2 = Med; 3 = High | ||||
| HR | 104doc (IU address[1..N] × 100) + 4 | IU vane swing | UINT16 | Read/write | 0 = Swing off; 1 = Swing on | ||||
| HR | 105doc (IU address[1..N] × 100) + 5 | IU room temperature | Tenths of °C, -20..100. | INT16 | × 0.1 | °C | Read | ||
| HR | 106doc (IU address[1..N] × 100) + 6 | IU unit error code | 0 = no error, 1..255 = error. | UINT16 | Read | 0 = No error | |||
| HR | 107doc (IU address[1..N] × 100) + 7 | IU communication error | UINT16 | Read | 0 = No error; 1 = Error | ||||
| HR | 108doc (IU address[1..N] × 100) + 8 | IU remote control lock | UINT16 | Read/write | 0 = Unlock; 1 = Lock | ||||
| HR | 109doc (IU address[1..N] × 100) + 9 | IU force operating mode | UINT16 | Read/write | 0 = No force; 1 = Force | ||||
| HR | 128doc (IU address[1..N] × 100) + 28 | IU vane left/right | UINT16 | Read/write | 0 = Stop; 1 = Step 1; 2 = Step 2; 3 = Step 3; 4 = Step 4; 5 = Step 5; 6 = Swing | ||||
| HR | 129doc (IU address[1..N] × 100) + 29 | IU vane up/down | UINT16 | Read/write | 0 = Stop; 1 = Step 1; 2 = Step 2; 3 = Step 3; 4 = Step 4; 5 = Step 5; 6 = Swing | ||||
| HR | 132doc (IU address[1..N] × 100) + 32 | IU control lock, mode Heat | UINT16 | Read/write | 0 = Unlock; 1 = Lock | ||||
| HR | 133doc (IU address[1..N] × 100) + 33 | IU control lock, mode Cool | UINT16 | Read/write | 0 = Unlock; 1 = Lock | ||||
| HR | 134doc (IU address[1..N] × 100) + 34 | IU control lock, mode Fan | UINT16 | Read/write | 0 = Unlock; 1 = Lock | ||||
| HR | 10000doc (OU address[1..N] × 10000) + 0 | OU 1 error code | 0 = no error, 1..260 = error. Outdoor index 1 shown. | UINT16 | Read | 0 = No error | |||
| HR | 10001doc (OU address[1..N] × 10000) + 1 | OU 1 communication error | UINT16 | Read | 0 = No error; 1 = Error |
Notes on this map
- For unit index n add (n-1) x 100 to the listed indoor addresses (unit 2 on/off = 200).
- Mode codes in the per-unit block (0 Heat, 1 Cool, 2 Fan, 3 Dry, 4 Auto) differ from the order of the all-unit mode commands.
- Outdoor unit registers are only available when the indoor unit is a Midea V8 system.
- One manual covers the three licence sizes of the same hardware: IN770AIRXXSO000 (up to 4 indoor units), IN770AIR00SO000 (16) and IN770AIR00MO000 (64). The brand application is chosen in Intesis MAPS.
- The manual states no data type for any register. INT16 is used only where it prints a negative range (room temperature); everything else is listed as UINT16.
- The consumption registers (yesterday / today / total, also per heat and cool) are left out: each takes two addresses, but the manual gives no word order, and the unit is printed as Wh/kWh (selectable).
- Reads use FC03 or FC04; writes use FC06 only. 'T' registers are trigger-only: write the printed value (1, or the setpoint / speed) to send the command.
- Addressing: the manual has no addressing statement or example frame; 0-based is taken from the global On register printed at Modbus address 0 (no 1-based scheme has a register 0), with no overlap against the unit blocks.
- Temperature ranges are printed in both °C and °F; the manual's Modbus section does not say how the unit is chosen. °C is listed here.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Intesis (HMS Networks) IN770AIR***O000 700 Series Air Gateway, Midea application (Modbus)
What Modbus registers does the Intesis (HMS Networks) IN770AIR***O000 700 Series Air Gateway, Midea application (Modbus) have?
This map lists 38 registers: 38 holding registers. 33 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Intesis (HMS Networks) IN770AIR***O000 700 Series Air Gateway, Midea application (Modbus) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual states no address base and gives no example frame; the first all-unit register is printed at Modbus address 0 and nothing in the tables contradicts that, so printed addresses are taken as wire addresses. Unit index n (1..N, as shown in MAPS) uses n x 100 + offset; outdoor index n uses n x 10000 + offset. This file lists unit 1 (100..134) and outdoor unit 1 (10000..10001).
What are the minimum Modbus registers to integrate the Intesis (HMS Networks) IN770AIR***O000 700 Series Air Gateway, Midea application (Modbus)?
Start with HR 100 IU on/off (On/off); HR 101 IU operation mode (Mode); HR 102 IU temperature setpoint (Setpoint (x10)); HR 103 IU fan speed (Fan speed); HR 105 IU room temperature (Room temperature (x10)); HR 106 IU unit error code (Error code); HR 107 IU communication error (Communication error).
How do I enable Modbus control of the Intesis (HMS Networks) IN770AIR***O000 700 Series Air Gateway, Midea application (Modbus)?
The units must be set up in Intesis MAPS; the unit index used in the formulas is the one shown on the Signals tab.
Where is the official Intesis (HMS Networks) IN770AIR***O000 700 Series Air Gateway, Midea application (Modbus) Modbus documentation?
The source is 700 Series Air Gateway - IN770AIR***O000, Midea to Modbus, KNX, BACnet, MQTT and Home Automation - User Manual (User Manual Version 1.0.22), revision 2025-12-09, published free by Intesis (HMS Networks) at https://www.hms-networks.com/docs/default-source/products/intesis/manuals-and-guides---manuals/user-manual-in770midxxxo000.pdf.
More Intesis (HMS Networks) Modbus register maps
- Heat pump gateway (VRF / split AC gateway)
Intesis (HMS Networks) IN485DAI001A000 Daikin Altherma 3 air-to-water to Modbus RTU / BACnet MS/TP gateway
Intesis (HMS Networks) IN485DAI001A000 gateway for Daikin Altherma 3 air-to-water heat pumps, set to Modbus RTU, per user manual version 1.0.2 (2025-07-18).
Also known as: IN485DAI001A000, Daikin Altherma 3 Modbus, Intesis Altherma 3, HMS Daikin Altherma gateway - Heat pump gateway (VRF / split AC gateway)
Intesis (HMS Networks) IN485MIT001A000 Mitsubishi Electric Ecodan air-to-water to Modbus RTU / BACnet MS/TP gateway
Intesis (HMS Networks) IN485MIT001A000 gateway on the CN105 socket of Mitsubishi Electric Ecodan air-to-water heat pumps, set to Modbus RTU, per user manual version 1.0.3 (2025-12-02).
Also known as: IN485MIT001A000, Ecodan Modbus, Mitsubishi Ecodan Modbus RTU, Intesis Ecodan, HMS Ecodan gateway - VRF / split AC gateway
Intesis (HMS Networks) IN485SAM001R000 Samsung AC to Modbus RTU / BACnet MS/TP gateway
Samsung indoor units on the F3F4 remote-controller bus, gateway set to Modbus RTU (SW1-5 ON); user manual version 1.0.0.
Also known as: IN485SAM001R000, Intesis Samsung BACnet MS/TP Modbus - VRF / split AC gateway
Intesis (HMS Networks) IN770AIR***O000 700 Series Air Gateway, Bosch application (Modbus)
Intesis 700 Series Air Gateway IN770AIR***O000 with the Bosch application (XYE bus), Modbus RTU / TCP server, user manual version 1.0.13 (2025-12-09).
Also known as: IN770AIR00MO000, IN770AIR00SO000, IN770AIRXXSO000 - VRF / split AC gateway
Intesis (HMS Networks) IN770AIR***O000 700 Series Air Gateway, Mitsubishi Electric City Multi application (Modbus)
Intesis 700 Series Air Gateway IN770AIR***O000 with the Mitsubishi Electric City Multi application (M-NET centralised controllers (AE-200, EW-50, G-50 and others)), Modbus RTU / TCP server, user manual version 1.0.19 (2026-03-16).
Also known as: IN770AIR00MO000, IN770AIR00SO000, IN770AIRXXSO000 - VRF / split AC gateway
Intesis (HMS Networks) IN770AIR***O000 700 Series Air Gateway, Panasonic application (Modbus)
Intesis 700 Series Air Gateway IN770AIR***O000 with the Panasonic application (U1U2 P-Link / S-Link), Modbus RTU / TCP server, user manual version 1.1.7 (2025-12-09).
Also known as: IN770AIR00MO000, IN770AIR00SO000, IN770AIRXXSO000 - VRF / split AC gateway
Intesis (HMS Networks) INMBSACA001I000 XYE-bus air conditioner to Modbus RTU interface (1 unit)
INMBSACA001I000, user manual v1.8 EN; one indoor unit at unit address 0 on its own XYE bus.
Also known as: INMBSACA001I000 - VRF / split AC gateway
Intesis (HMS Networks) INMBSACA004I000 / 008I000 / 032I000 XYE-bus air conditioner to Modbus RTU interface (4 to 32 units)
INMBSACA004I000 / INMBSACA008I000 / INMBSACA032I000, user manual v1.8 EN; up to 4, 8 or 32 indoor units on one XYE bus.
Also known as: INMBSACA004I000, INMBSACA008I000, INMBSACA032I000 - VRF / split AC gateway
Intesis (HMS Networks) INMBSDAI001I000 Daikin domestic AC to Modbus RTU gateway
Single Daikin domestic (S21-connector) indoor unit via INMBSDAI001I000, user manual v1.0.2.
Also known as: INMBSDAI001I000, Intesis Daikin domestic Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSDAI001R000 Daikin VRV / Sky Air to Modbus RTU gateway
One Daikin VRV or Sky Air indoor unit (or group) on the P1P2 bus via INMBSDAI001R000, user manual v1.0.1.
Also known as: INMBSDAI001R000, Intesis Daikin VRV Modbus - Lighting gateway (DALI-2 to Modbus)
Intesis (HMS Networks) INMBSDAL0640000 / INMBSDAL1280000 DALI-2 to Modbus RTU / TCP server
Intesis Modbus Server - DALI with one (0640000, RTU + TCP) or two (1280000, TCP only) DALI channels, Modbus Addresses parameter set to Fixed; user manual r1.2 (09/2021).
Also known as: INMBSDAL0640000, INMBSDAL1280000, Intesis Modbus Server - DALI, Intesis DALI-2 Modbus gateway - VRF / split AC gateway
Intesis (HMS Networks) INMBSFGL001I000 Fujitsu domestic AC to Modbus RTU gateway
One Fujitsu domestic (RAC) or compatible VRF indoor unit, connected to the CN65/CN12/CN6 socket on the indoor board via INMBSFGL001I000, user manual v1.5 (01/2024).
Also known as: INMBSFGL001I000, FJ-AC-MBS-1, Intesis Fujitsu domestic Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSFGL001R000 Fujitsu AC to Modbus RTU gateway
One Fujitsu indoor unit, or a group of up to 16 controlled together as one, on the 3-wire BWR remote-controller bus via INMBSFGL001R000, user manual v2.4 (02/2025).
Also known as: INMBSFGL001R000, Intesis Fujitsu Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSFGL016O000 Fujitsu VRF to Modbus RTU / TCP gateway (up to 16 indoor units)
Intesis Modbus Server - Fujitsu VRF, order code INMBSFGL016O000 (legacy FJ-AC-MBS-16), user manual r1.0 (02/2020); up to 16 indoor units configured in MAPS.
Also known as: INMBSFGL016O000, FJ-AC-MBS-16, Intesis Modbus Server Fujitsu VRF - VRF / split AC gateway
Intesis (HMS Networks) INMBSHIS001R000 Hisense AC to Modbus RTU gateway
Hisense commercial-line indoor units on the AB remote-controller bus, user manual v1.6 (01/2024).
Also known as: INMBSHIS001R000, HS-RC-MBS-1, Intesis Hisense Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSHIS016O000 Hisense VRF to Modbus RTU / TCP gateway (16 / 64 indoor units)
Intesis Modbus Server - Hisense VRF, order codes INMBSHIS016O000 / INMBSHIS064O000 (legacy HS-AC-MBS-16 / HS-AC-MBS-64), user manual User Manual r1.0 EN.
Also known as: INMBSHIS016O000, INMBSHIS064O000, HS-AC-MBS-16, HS-AC-MBS-64, Intesis Modbus Server Hisense VRF - VRF / split AC gateway
Intesis (HMS Networks) INMBSHIT001R000 Hitachi AC to Modbus RTU gateway
Intesis (HMS Networks) INMBSHIT001R000 interface on the AB bus of one Hitachi commercial-line indoor unit (or group), per user manual v1.6 (01/2024).
Also known as: INMBSHIT001R000, Hitachi Modbus gateway, Intesis Hitachi - VRF / split AC gateway
Intesis (HMS Networks) INMBSHIT016O000 Hitachi VRF to Modbus RTU / TCP gateway (16 / 64 indoor units)
Intesis Modbus Server - Hitachi VRF, order codes INMBSHIT016O000 / INMBSHIT064O000 (legacy HI-AC-MBS-16 / HI-AC-MBS-64), user manual User Manual r1.2 EN.
Also known as: INMBSHIT016O000, INMBSHIT064O000, HI-AC-MBS-16, HI-AC-MBS-64, Intesis Modbus Server Hitachi VRF - VRF / split AC gateway
Intesis (HMS Networks) INMBSLGE001R000 LG AC to Modbus RTU gateway
One LG indoor unit on the BYR (wired remote) bus via INMBSLGE001R000 (legacy code LG-RC-MBS-1), user manual v1.9 (01/2024).
Also known as: INMBSLGE001R000, LG-RC-MBS-1, Intesis LG Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSLGE016O000 LG VRF to Modbus RTU / TCP gateway (16 / 64 indoor units)
Intesis Modbus - LG VRF, order codes INMBSLGE016O000 / INMBSLGE064O000 (legacy LG-AC-MBS-16 / -64), user manual r1.0 (04/2020); LG PI485 bus.
Also known as: INMBSLGE016O000, INMBSLGE064O000, LG-AC-MBS-16, LG-AC-MBS-64, Intesis Modbus LG VRF - VRF / split AC gateway
Intesis (HMS Networks) INMBSMHI001R000 Mitsubishi Heavy Industries AC to Modbus RTU gateway
Mitsubishi Heavy Industries indoor units (one, or up to 16 controlled together as one) on the XY remote-controller bus, user manual r6.4 (01/2024).
Also known as: INMBSMHI001R000, MH-RC-MBS-1, Intesis Mitsubishi Heavy Industries Modbus, Intesis MHI Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSMHI128O000 / INMBSMHI048O000 Mitsubishi Heavy Industries Superlink to Modbus gateway
Intesis Modbus Server - Mitsubishi Heavy Industries AC, order codes INMBSMHI128O000 (128 units, Superlink-II) and INMBSMHI048O000 (48 units, Superlink-I or II), user's manual r1.0 (05/2012).
Also known as: INMBSMHI128O000, INMBSMHI048O000, MH-AC-MBS-128, MH-AC-MBS-48, Intesis Modbus Server MHI Superlink - VRF / split AC gateway
Intesis (HMS Networks) INMBSMID001I000 Midea AC to Modbus RTU gateway
One Midea commercial / VRF indoor unit on the XYE bus, user manual v1.11.
Also known as: INMBSMID001I000, Intesis Midea Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSMID004I000 / 008I000 / 032I000 Midea AC to Modbus RTU interface (4 to 32 units)
INMBSMID004I000 / INMBSMID008I000 / INMBSMID032I000 / MD-AC-MBS-4 / MD-AC-MBS-8 / MD-AC-MBS-32, user manual v1.7 EN; up to 4, 8 or 32 indoor units on one XYE bus.
Also known as: INMBSMID004I000, INMBSMID008I000, INMBSMID032I000, MD-AC-MBS-4, MD-AC-MBS-8, MD-AC-MBS-32 - VRF / split AC gateway
Intesis (HMS Networks) INMBSMIT001I000 Mitsubishi Electric AC to Modbus RTU gateway
One Mitsubishi Electric Domestic, Mr. Slim or City Multi indoor unit via INMBSMIT001I000, user manual r2.8 (11/2024).
Also known as: INMBSMIT001I000, Intesis Mitsubishi Electric Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSMIT050C000 / INMBSMIT100C000 Mitsubishi Electric City Multi centralised controller to Modbus gateway
Intesis Modbus Server - Mitsubishi Electric CC, order codes INMBSMIT050C000 / INMBSMIT100C000 (legacy ME-AC-MBS-50 / -100), user manual r1.4 (05/2021); talks to City Multi centralised controllers (G-50A, GB-50A, AG-150A, EB-50, EW-50, AE-200 and newer) through their XML interface over Ethernet.
Also known as: INMBSMIT050C000, INMBSMIT100C000, ME-AC-MBS-50, ME-AC-MBS-100, Intesis Modbus Server Mitsubishi Electric CC - Heat pump gateway (VRF / split AC gateway)
Intesis (HMS Networks) INMBSPAN001A100 Panasonic Aquarea H/J/K/L/M air-to-water to Modbus RTU gateway
Intesis (HMS Networks) INMBSPAN001A100 gateway connected to Panasonic Aquarea H, J, K, L and M series air-to-water heat pumps, per user manual version 1.0.2 (2026-02-04).
Also known as: INMBSPAN001A100, Aquarea Modbus, Panasonic Aquarea Modbus RTU, Intesis Aquarea, INMBSPAN001A000 (legacy order code) - VRF / split AC gateway
Intesis (HMS Networks) INMBSPAN001I100 Panasonic Etherea (domestic) AC to Modbus RTU gateway
Panasonic Etherea-line domestic split units, user's manual r1.5 (09/2025). Some registers only on 2013 (PKE series) and later models.
Also known as: INMBSPAN001I100, Intesis Panasonic Etherea Modbus, Intesis Panasonic domestic Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSPAN001R000 Panasonic AC to Modbus RTU gateway
Panasonic / Sanyo ECOi and PACi indoor units (one, or up to 16 controlled together as one) on the R1R2 remote-controller bus, user manual v2.8 (09/2025).
Also known as: INMBSPAN001R000, PA-RC2-MBS-1, Intesis Panasonic Modbus, Intesis Sanyo Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSPAN016O000 / 064O000 / 128O000 Panasonic VRF (P-Link) to Modbus gateway
Intesis Modbus Server - Panasonic, order codes INMBSPAN016O000 / 064O000 / 128O000 (legacy PA-AC-MBS-16 / -64 / -128), user manual r1.1 (11/2020); Panasonic P-Link systems.
Also known as: INMBSPAN016O000, INMBSPAN064O000, INMBSPAN128O000, PA-AC-MBS-16, PA-AC-MBS-64, PA-AC-MBS-128, Intesis Modbus Server Panasonic VRF - VRF / split AC gateway
Intesis (HMS Networks) INMBSSAM001R000 Samsung AC to Modbus RTU gateway
Samsung commercial indoor units on the F3F4/V1V2 remote-controller bus, user's manual v1.5 (01/2024).
Also known as: INMBSSAM001R000, Intesis Samsung Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSSAM001R100 Samsung NASA AC to Modbus RTU gateway
Samsung NASA-protocol commercial indoor units on the remote-controller bus, user's manual r1.4 (01/2024).
Also known as: INMBSSAM001R100, Intesis Samsung NASA Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSSAM016O000 Samsung NASA (R1/R2) VRF to Modbus gateway (4 to 64 units)
Intesis Modbus Server - Samsung NASA, order codes INMBSSAM004O000 / 008O000 / 016O000 / 064O000 (legacy SM-ACN-MBS-4/8/16/64), user manual r1.4 (12/2020); Samsung NASA R1/R2 bus.
Also known as: INMBSSAM004O000, INMBSSAM008O000, INMBSSAM016O000, INMBSSAM064O000, SM-ACN-MBS-4, SM-ACN-MBS-8, SM-ACN-MBS-16, SM-ACN-MBS-64 - VRF / split AC gateway
Intesis (HMS Networks) INMBSTOS001R000 Toshiba AC to Modbus RTU gateway
Toshiba Digital Inverter (RAV) and VRF indoor units on the AB remote bus via INMBSTOS001R0xx, user manual r2.9 (01/2024).
Also known as: INMBSTOS001R000, INMBSTOS001R0xx, Intesis Toshiba Modbus
Other ac & vrf gateways register maps
- Chiller / heat pump gateway (VRF / split AC gateway)
Mitsubishi Electric MelcoBEMS MINI (A1M+) gateway for CAHV / CRHV / QAHV heat pumps and EAHV / EACV e-series chillers
Procon MelcoBEMS MINI (A1M+) firmware 4.1.0 on Mitsubishi Electric CAHV and CRHV heat pumps, QAHV CO2 heat pumps and EAHV / EACV e-series chillers (master and slave units); holding-register table only.
Also known as: A1M+, MelcoBEMS MINI, Procon A1M+, CAHV, CRHV, QAHV, EAHV, EACV, e-series chiller - VRF / split AC gateway
Samsung CycloGic CL-MC03 Modbus interface module (Samsung DVM / CAC / RAC)
CycloGic CL-MC03*** series Modbus interface modules (1 to 64 indoor units) for Samsung DVM, CAC, FJM and RAC units, instruction manual Rev. 2 (Oct. 2017).
Also known as: CL-MC0301C, CL-MC0308C, CL-MC0316C, CL-MC0332C, CL-MC0364C, CycloGic Modbus Interface Module - Boiler gateway (OpenTherm to Modbus RTU)
Unipi Technology MM-OT101 Modbus / OpenTherm gateway
Unipi MM-OT101 DIN-rail gateway between Modbus RTU (RS-485) and OpenTherm/Plus boilers and thermostats, per its technical documentation.
Also known as: MM-OT101, MM-OT1010, Unipi OpenTherm gateway - VRF / split AC gateway
Daikin DTA116A51 D-NET / Modbus communication adaptor (VRV)
DTA116A51 adaptor with up to 16 VRV indoor units (D-NET 1-00 to 1-15), per functional specification CB13A033 first edition.
Also known as: DTA116A51, DIII-NET Modbus adaptor, D3NET Modbus adapter - Split AC unit (VRF / split AC gateway built in)
Gree U-Match all-DC-inverter duct / cassette / floor-ceiling units (built-in Modbus)
Gree U-Match fourth-generation all-DC-inverter light-commercial units whose controller has the integrated Modbus RTU interface; Chinese-English protocol dated 2018-03-07.
Also known as: U-Match, Gree U-Match 4th generation DC inverter, U-Match BMS Modbus - Air handler DX interface (VRF / split AC gateway)
Mitsubishi Electric PAC-IF013B-E / PAC-SIF013B-E air handling unit interface (Modbus RTU)
PAC-IF013B-E and PAC-SIF013B-E interface controllers linking a Mitsubishi Electric outdoor unit to an AHU coil, Modbus manual dated September 2015 (RG79F084H01).
Also known as: PAC-IF013B-E, PAC-SIF013B-E, PAC-(S)IF013B-E
All ac & vrf gateways Modbus register maps →
Source: 700 Series Air Gateway - IN770AIR***O000, Midea to Modbus, KNX, BACnet, MQTT and Home Automation - User Manual · User Manual Version 1.0.22 · rev. 2025-12-09. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.