- INMBSMIT050C000 / INMBSMIT100C000 Mitsubishi Electric City Multi centralised controller to Modbus gateway
VRF / split AC gateway · Modbus register map
Intesis (HMS Networks) INMBSMIT050C000 / INMBSMIT100C000 Mitsubishi Electric City Multi centralised controller to Modbus gateway Modbus register map
Updated 19 November 2026
Modbus server that reads Mitsubishi Electric City Multi groups through one or two centralised controllers (XML over Ethernet). Each group (1..50 per controller) gets a 100-register block with on/off, mode, fan, vane, run hours, errors and local-panel permissions; each controller also has 26 all-group command registers. Covers indoor units, Lossnay, OA processing, ATW booster/HEX and CEh heat pumps.
This page lists 49 Modbus registers for the Intesis (HMS Networks) INMBSMIT050C000 / INMBSMIT100C000 Mitsubishi Electric City Multi centralised controller to Modbus gateway — 39 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Intesis (HMS Networks)’s own free documentation (linked below) and checked against it.
- Manufacturer
- Intesis (HMS Networks)
- Model
- INMBSMIT050C000 / INMBSMIT100C000 Mitsubishi Electric City Multi centralised controller to Modbus gateway
- Equipment type
- VRF / split AC gateway
- Registers
- 49 (39 writable)
- Transport
- Modbus RTU, Modbus TCP
- Default unit ID
- Not stated
- TCP port
- 502
- Documented addressing
- 0-based (the number printed is the address on the wire)
- Also known as
- INMBSMIT050C000, INMBSMIT100C000, ME-AC-MBS-50, ME-AC-MBS-100, Intesis Modbus Server Mitsubishi Electric CC
Integration notes: Intesis (HMS Networks) INMBSMIT050C000 / INMBSMIT100C000 Mitsubishi Electric City Multi centralised controller to Modbus gateway
Point the gateway at the centralised controller(s) in Intesis MAPS, import the groups, send the project, then poll each group's 100-register block for on/off, mode, fan, vane and errors.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 0 | CC communication error | INT16 | Controller communication error | Read |
| HR 100 | Group on/off | INT16 | Group on/off | Read/write |
| HR 101 | Group operation mode | INT16 | Group mode | Read/write |
| HR 102 | Group fan speed | INT16 | Group fan speed | Read/write |
| HR 109 | Group error status | INT16 | Group error status | Read |
| HR 110 | Group error code | INT16 | Group error code | Read |
| HR 136 | Filter status | INT16 | Filter status | Read |
Enable Modbus control & writes
The centralised controller XML interface must be active (it may need a licence from Mitsubishi Electric) and the groups must be configured in MAPS (unit type per group).
Byte order & addressing
- Every register is a 16-bit signed integer; there are no 32-bit values (unless stated in this file).
- Read with FC03 or FC04; write with FC06 or FC16.
- Undefined addresses in the 0..20000 poll range read back 0; the manual also says invalid addresses return a Modbus exception code.
- Controller command registers (cc x 30 + 1..25) are write-only broadcasts to every group of that controller.
Network setup
- All Modbus settings (RTU slave number, baud 1200..115200, parity, stop bits, RS-485 or RS-232, TCP port, IP) are set with the Intesis MAPS tool over the USB console port or Ethernet.
- Factory IP is 192.168.100.246 with DHCP enabled.
- Modbus RTU and Modbus TCP can be used at the same time.
- Port B carries Modbus RTU on B1, B2 and B3 (SGND). The manual prints the B1/B2 polarity both ways in two sections, so check the terminal label. The gateway has built-in bias and termination; do not add another resistor at its end of the bus.
- The centralised controller(s) must be reachable over Ethernet from the gateway.
Watch out for
- Some permission registers only work when MAPS 'Old Model Compatibility' is set to New model; setback control needs EB-50GU or AE-200 and newer.
Intesis (HMS Networks) INMBSMIT050C000 / INMBSMIT100C000 Mitsubishi Electric City Multi centralised controller to Modbus gateway Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0doc (cc x 30) + 0 | CC communication error | Centralised controller 0 shown; see notes. | INT16 | Read | 0 = OK; 1 = Communication error | |||
| HR | 1doc (cc x 30) + 1 | Reset errors (all groups) | INT16 | Write | 1 = Reset the errors | ||||
| HR | 2doc (cc x 30) + 2 | On (all groups) | INT16 | Write | 1 = Set groups on | ||||
| HR | 3doc (cc x 30) + 3 | Off (all groups) | INT16 | Write | 1 = Set groups off | ||||
| HR | 4doc (cc x 30) + 4 | Mode Auto (all IC groups) | INT16 | Write | 1 = Execute | ||||
| HR | 5doc (cc x 30) + 5 | Mode Heat (all IC groups) | INT16 | Write | 1 = Execute | ||||
| HR | 6doc (cc x 30) + 6 | Mode Dry (all IC groups) | INT16 | Write | 1 = Execute | ||||
| HR | 7doc (cc x 30) + 7 | Mode Fan (all IC groups) | INT16 | Write | 1 = Execute | ||||
| HR | 8doc (cc x 30) + 8 | Mode Cool (all IC groups) | INT16 | Write | 1 = Execute | ||||
| HR | 9doc (cc x 30) + 9 | Mode Setback (all IC groups) | INT16 | Write | 1 = Execute | ||||
| HR | 10doc (cc x 30) + 10 | Mode LC Auto (all Lossnay groups) | INT16 | Write | 1 = Execute | ||||
| HR | 11doc (cc x 30) + 11 | Mode Heat Recovery (all Lossnay groups) | INT16 | Write | 1 = Execute | ||||
| HR | 12doc (cc x 30) + 12 | Mode Bypass (all Lossnay groups) | INT16 | Write | 1 = Execute | ||||
| HR | 13doc (cc x 30) + 13 | Fan speed Auto (all IC groups) | INT16 | Write | 1 = Execute | ||||
| HR | 14doc (cc x 30) + 14 | Fan speed Low (all IC and Lossnay groups) | INT16 | Write | 1 = Execute | ||||
| HR | 15doc (cc x 30) + 15 | Fan speed Mid-1 (all IC groups) | INT16 | Write | 1 = Execute | ||||
| HR | 16doc (cc x 30) + 16 | Fan speed Mid-2 (all IC groups) | INT16 | Write | 1 = Execute | ||||
| HR | 17doc (cc x 30) + 17 | Fan speed High (all IC and Lossnay groups) | INT16 | Write | 1 = Execute | ||||
| HR | 18doc (cc x 30) + 18 | Vanes Auto (all IC groups) | INT16 | Write | 1 = Execute | ||||
| HR | 19doc (cc x 30) + 19 | Vanes Horizontal (all IC groups) | INT16 | Write | 1 = Execute | ||||
| HR | 20doc (cc x 30) + 20 | Vanes Position-2 (all IC groups) | INT16 | Write | 1 = Execute | ||||
| HR | 21doc (cc x 30) + 21 | Vanes Position-3 (all IC groups) | INT16 | Write | 1 = Execute | ||||
| HR | 22doc (cc x 30) + 22 | Vanes Position-4 (all IC groups) | INT16 | Write | 1 = Execute | ||||
| HR | 23doc (cc x 30) + 23 | Vanes Vertical (all IC groups) | INT16 | Write | 1 = Execute | ||||
| HR | 24doc (cc x 30) + 24 | Vanes Swing (all IC groups) | INT16 | Write | 1 = Execute | ||||
| HR | 100doc ((cc x 50) + g) x 100 + 0 | Group on/off | CC 0, group 1 shown; see notes. | INT16 | Read/write | 0 = Off; 1 = On | |||
| HR | 101doc ((cc x 50) + g) x 100 + 1 | Group operation mode | Indoor-unit (IC) codes shown; Lossnay and ATW groups use other codes (see notes). | INT16 | Read/write | 0 = Auto; 1 = Heat; 2 = Dry; 3 = Fan; 4 = Cool; 5 = Auto Heat; 6 = Auto Cool; 7 = Setback; 8 = Setback Heat; 9 = Setback Cool | |||
| HR | 102doc ((cc x 50) + g) x 100 + 2 | Group fan speed | IC groups: 0 Auto, 1 Low, 4 High; mid codes printed inconsistently (see notes). | INT16 | Read/write | 0 = Auto; 1 = Low; 4 = High | |||
| HR | 103doc ((cc x 50) + g) x 100 + 3 | Group vane position | INT16 | Read/write | 0 = Auto; 1 = Horizontal; 2 = Position-2; 3 = Position-3; 4 = Position-4; 5 = Vertical; 6 = Swing | ||||
| HR | 106doc ((cc x 50) + g) x 100 + 6 | Lossnay / OA operational status | INT16 | Read/write | 0 = Off; 1 = Low; 2 = High | ||||
| HR | 107doc ((cc x 50) + g) x 100 + 7 | Group operation time, hundreds of hours | Run hours = this x 100 + next register; 0..9999. | INT16 | × 100 | h | Read | ||
| HR | 108doc ((cc x 50) + g) x 100 + 8 | Group operation time, hours remainder | Run hours modulo 100; 0..99. | INT16 | h | Read | |||
| HR | 109doc ((cc x 50) + g) x 100 + 9 | Group error status | INT16 | Read | 0 = No error; 1 = Group error | ||||
| HR | 110doc ((cc x 50) + g) x 100 + 10 | Group error code | Mitsubishi Electric 4-digit error code number. | INT16 | Read | ||||
| HR | 111doc ((cc x 50) + g) x 100 + 11 | Group error reset | INT16 | Write | 1 = Reset the error | ||||
| HR | 112doc ((cc x 50) + g) x 100 + 12 | Group model | Model of units connected to the group. | INT16 | Read | ||||
| HR | 113doc ((cc x 50) + g) x 100 + 13 | Allow on/off from local panel | INT16 | Read/write | 0 = Allow; 1 = Not allow | ||||
| HR | 114doc ((cc x 50) + g) x 100 + 14 | Allow mode from local panel | INT16 | Read/write | 0 = Allow; 1 = Not allow | ||||
| HR | 115doc ((cc x 50) + g) x 100 + 15 | Allow setpoint from local panel | INT16 | Read/write | 0 = Allow; 1 = Not allow | ||||
| HR | 116doc ((cc x 50) + g) x 100 + 16 | Allow filter reset from local panel | INT16 | Read/write | 0 = Allow; 1 = Not allow | ||||
| HR | 117doc ((cc x 50) + g) x 100 + 17 | Allow air direction from local panel | Only with 'Old Model Compatibility' = New model. | INT16 | Read/write | 0 = Allow; 1 = Not allow | |||
| HR | 118doc ((cc x 50) + g) x 100 + 18 | Allow fan speed from local panel | Only with 'Old Model Compatibility' = New model. | INT16 | Read/write | 0 = Allow; 1 = Not allow | |||
| HR | 119doc ((cc x 50) + g) x 100 + 19 | Allow timer from local panel | Only with 'Old Model Compatibility' = New model. | INT16 | Read/write | 0 = Allow; 1 = Not allow | |||
| HR | 120doc ((cc x 50) + g) x 100 + 20 | Setback control | Only with controller model EB-50GU or AE-200 or newer. | INT16 | Read/write | 0 = Disable; 1 = Enable | |||
| HR | 132doc ((cc x 50) + g) x 100 + 32 | Room humidity | Only when 'URC Controller' = Available. | INT16 | % | Read | |||
| HR | 133doc ((cc x 50) + g) x 100 + 33 | Brightness status | INT16 | Read | 0 = Dark; 1 = Bright | ||||
| HR | 134doc ((cc x 50) + g) x 100 + 34 | Occupancy | INT16 | Read | 0 = Absence; 1 = Occupancy | ||||
| HR | 136doc ((cc x 50) + g) x 100 + 36 | Filter status | INT16 | Read | 0 = OK; 1 = Dirty | ||||
| HR | 137doc ((cc x 50) + g) x 100 + 37 | Dirty filter indication reset | INT16 | Write | 1 = Reset the filter |
Notes on this map
- Only controller 0 and its group 1 are listed. Group g on controller cc: add ((cc x 50) + g - 1) x 100 (cc 0 group 2 on/off = 200; cc 1 group 1 = 5100). Controller 1 signals: add 30.
- All temperature registers are left out (all-group setpoint cc x 30 + 25, group setpoint +4, ambient +5, setpoint restrictions +21..+26, multiple setpoints +27..+31, outdoor temperature +35): setpoints are printed as whole '°C' yet with half-degree ranges such as 4.5..35 °C, and ambient is printed '°C/x10°C' with a 0.0..99.9 range, so the scale cannot be fixed from the document.
- Mode, fan and setpoint registers have different meanings for Lossnay (LC), ATW booster/HEX and CEh heat-pump groups; only indoor-unit (IC) codes are decoded. Lossnay mode: 0 LC Auto, 1 Heat Recovery, 2 Bypass. ATW/HWHP mode: 0 Hot water, 1 Heating, 2 Heating Eco, 3 Anti-freeze, 4 Cooling.
- The IC fan-speed value list is printed as '0-Auto, 1-Low, 2-Mid-1, 3-Mid-2, 2-Mid2, 3-Mid1, 4-High', which assigns 2 and 3 twice; only 0, 1 and 4 are decoded. The Lossnay fan list is equally garbled and is not decoded.
- Which registers exist depends on the unit type selected in MAPS (IC, LC, FU, BU, WH, CEh); the manual's applicability matrix is not reproduced.
- Brightness and occupancy (+33 / +34) carry the same 'Setpoint Type = Multiple Setpoint' availability note as the setpoint rows in the manual.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Intesis (HMS Networks) INMBSMIT050C000 / INMBSMIT100C000 Mitsubishi Electric City Multi centralised controller to Modbus gateway
What Modbus registers does the Intesis (HMS Networks) INMBSMIT050C000 / INMBSMIT100C000 Mitsubishi Electric City Multi centralised controller to Modbus gateway have?
This map lists 49 registers: 49 holding registers. 39 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Intesis (HMS Networks) INMBSMIT050C000 / INMBSMIT100C000 Mitsubishi Electric City Multi centralised controller to Modbus gateway Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual states formula results are link-layer addresses with the first register at 0. Controller signals: cc x 30 + signal; group signals: ((cc x 50) + g) x 100 + signal, with cc = 0 or 1 and g = group 1..50. This file lists cc = 0 (0..24) and cc 0 group 1 (100..137).
What are the minimum Modbus registers to integrate the Intesis (HMS Networks) INMBSMIT050C000 / INMBSMIT100C000 Mitsubishi Electric City Multi centralised controller to Modbus gateway?
Start with HR 0 CC communication error (Controller communication error); HR 100 Group on/off (Group on/off); HR 101 Group operation mode (Group mode); HR 102 Group fan speed (Group fan speed); HR 109 Group error status (Group error status); HR 110 Group error code (Group error code); HR 136 Filter status (Filter status).
How do I enable Modbus control of the Intesis (HMS Networks) INMBSMIT050C000 / INMBSMIT100C000 Mitsubishi Electric City Multi centralised controller to Modbus gateway?
The centralised controller XML interface must be active (it may need a licence from Mitsubishi Electric) and the groups must be configured in MAPS (unit type per group).
Where is the official Intesis (HMS Networks) INMBSMIT050C000 / INMBSMIT100C000 Mitsubishi Electric City Multi centralised controller to Modbus gateway Modbus documentation?
The source is Intesis Modbus Server - Mitsubishi Electric CC User Manual (User Manual r1.4 EN), revision 2021-05, published free by Intesis (HMS Networks) at https://www.hms-networks.com/docs/default-source/products/intesis/manuals-and-guides---manuals/user-manual-inmbsmitxxxc000.pdf.
More Intesis (HMS Networks) Modbus register maps
- Heat pump gateway (VRF / split AC gateway)
Intesis (HMS Networks) IN485DAI001A000 Daikin Altherma 3 air-to-water to Modbus RTU / BACnet MS/TP gateway
Intesis (HMS Networks) IN485DAI001A000 gateway for Daikin Altherma 3 air-to-water heat pumps, set to Modbus RTU, per user manual version 1.0.2 (2025-07-18).
Also known as: IN485DAI001A000, Daikin Altherma 3 Modbus, Intesis Altherma 3, HMS Daikin Altherma gateway - Heat pump gateway (VRF / split AC gateway)
Intesis (HMS Networks) IN485MIT001A000 Mitsubishi Electric Ecodan air-to-water to Modbus RTU / BACnet MS/TP gateway
Intesis (HMS Networks) IN485MIT001A000 gateway on the CN105 socket of Mitsubishi Electric Ecodan air-to-water heat pumps, set to Modbus RTU, per user manual version 1.0.3 (2025-12-02).
Also known as: IN485MIT001A000, Ecodan Modbus, Mitsubishi Ecodan Modbus RTU, Intesis Ecodan, HMS Ecodan gateway - VRF / split AC gateway
Intesis (HMS Networks) IN485SAM001R000 Samsung AC to Modbus RTU / BACnet MS/TP gateway
Samsung indoor units on the F3F4 remote-controller bus, gateway set to Modbus RTU (SW1-5 ON); user manual version 1.0.0.
Also known as: IN485SAM001R000, Intesis Samsung BACnet MS/TP Modbus - VRF / split AC gateway
Intesis (HMS Networks) IN770AIR***O000 700 Series Air Gateway, Bosch application (Modbus)
Intesis 700 Series Air Gateway IN770AIR***O000 with the Bosch application (XYE bus), Modbus RTU / TCP server, user manual version 1.0.13 (2025-12-09).
Also known as: IN770AIR00MO000, IN770AIR00SO000, IN770AIRXXSO000 - VRF / split AC gateway
Intesis (HMS Networks) IN770AIR***O000 700 Series Air Gateway, Midea application (Modbus)
Intesis 700 Series Air Gateway IN770AIR***O000 with the Midea application (XYE bus), Modbus RTU / TCP server, user manual version 1.0.22 (2025-12-09).
Also known as: IN770AIR00MO000, IN770AIR00SO000, IN770AIRXXSO000 - VRF / split AC gateway
Intesis (HMS Networks) IN770AIR***O000 700 Series Air Gateway, Mitsubishi Electric City Multi application (Modbus)
Intesis 700 Series Air Gateway IN770AIR***O000 with the Mitsubishi Electric City Multi application (M-NET centralised controllers (AE-200, EW-50, G-50 and others)), Modbus RTU / TCP server, user manual version 1.0.19 (2026-03-16).
Also known as: IN770AIR00MO000, IN770AIR00SO000, IN770AIRXXSO000 - VRF / split AC gateway
Intesis (HMS Networks) IN770AIR***O000 700 Series Air Gateway, Panasonic application (Modbus)
Intesis 700 Series Air Gateway IN770AIR***O000 with the Panasonic application (U1U2 P-Link / S-Link), Modbus RTU / TCP server, user manual version 1.1.7 (2025-12-09).
Also known as: IN770AIR00MO000, IN770AIR00SO000, IN770AIRXXSO000 - VRF / split AC gateway
Intesis (HMS Networks) INMBSACA001I000 XYE-bus air conditioner to Modbus RTU interface (1 unit)
INMBSACA001I000, user manual v1.8 EN; one indoor unit at unit address 0 on its own XYE bus.
Also known as: INMBSACA001I000 - VRF / split AC gateway
Intesis (HMS Networks) INMBSACA004I000 / 008I000 / 032I000 XYE-bus air conditioner to Modbus RTU interface (4 to 32 units)
INMBSACA004I000 / INMBSACA008I000 / INMBSACA032I000, user manual v1.8 EN; up to 4, 8 or 32 indoor units on one XYE bus.
Also known as: INMBSACA004I000, INMBSACA008I000, INMBSACA032I000 - VRF / split AC gateway
Intesis (HMS Networks) INMBSDAI001I000 Daikin domestic AC to Modbus RTU gateway
Single Daikin domestic (S21-connector) indoor unit via INMBSDAI001I000, user manual v1.0.2.
Also known as: INMBSDAI001I000, Intesis Daikin domestic Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSDAI001R000 Daikin VRV / Sky Air to Modbus RTU gateway
One Daikin VRV or Sky Air indoor unit (or group) on the P1P2 bus via INMBSDAI001R000, user manual v1.0.1.
Also known as: INMBSDAI001R000, Intesis Daikin VRV Modbus - Lighting gateway (DALI-2 to Modbus)
Intesis (HMS Networks) INMBSDAL0640000 / INMBSDAL1280000 DALI-2 to Modbus RTU / TCP server
Intesis Modbus Server - DALI with one (0640000, RTU + TCP) or two (1280000, TCP only) DALI channels, Modbus Addresses parameter set to Fixed; user manual r1.2 (09/2021).
Also known as: INMBSDAL0640000, INMBSDAL1280000, Intesis Modbus Server - DALI, Intesis DALI-2 Modbus gateway - VRF / split AC gateway
Intesis (HMS Networks) INMBSFGL001I000 Fujitsu domestic AC to Modbus RTU gateway
One Fujitsu domestic (RAC) or compatible VRF indoor unit, connected to the CN65/CN12/CN6 socket on the indoor board via INMBSFGL001I000, user manual v1.5 (01/2024).
Also known as: INMBSFGL001I000, FJ-AC-MBS-1, Intesis Fujitsu domestic Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSFGL001R000 Fujitsu AC to Modbus RTU gateway
One Fujitsu indoor unit, or a group of up to 16 controlled together as one, on the 3-wire BWR remote-controller bus via INMBSFGL001R000, user manual v2.4 (02/2025).
Also known as: INMBSFGL001R000, Intesis Fujitsu Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSFGL016O000 Fujitsu VRF to Modbus RTU / TCP gateway (up to 16 indoor units)
Intesis Modbus Server - Fujitsu VRF, order code INMBSFGL016O000 (legacy FJ-AC-MBS-16), user manual r1.0 (02/2020); up to 16 indoor units configured in MAPS.
Also known as: INMBSFGL016O000, FJ-AC-MBS-16, Intesis Modbus Server Fujitsu VRF - VRF / split AC gateway
Intesis (HMS Networks) INMBSHIS001R000 Hisense AC to Modbus RTU gateway
Hisense commercial-line indoor units on the AB remote-controller bus, user manual v1.6 (01/2024).
Also known as: INMBSHIS001R000, HS-RC-MBS-1, Intesis Hisense Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSHIS016O000 Hisense VRF to Modbus RTU / TCP gateway (16 / 64 indoor units)
Intesis Modbus Server - Hisense VRF, order codes INMBSHIS016O000 / INMBSHIS064O000 (legacy HS-AC-MBS-16 / HS-AC-MBS-64), user manual User Manual r1.0 EN.
Also known as: INMBSHIS016O000, INMBSHIS064O000, HS-AC-MBS-16, HS-AC-MBS-64, Intesis Modbus Server Hisense VRF - VRF / split AC gateway
Intesis (HMS Networks) INMBSHIT001R000 Hitachi AC to Modbus RTU gateway
Intesis (HMS Networks) INMBSHIT001R000 interface on the AB bus of one Hitachi commercial-line indoor unit (or group), per user manual v1.6 (01/2024).
Also known as: INMBSHIT001R000, Hitachi Modbus gateway, Intesis Hitachi - VRF / split AC gateway
Intesis (HMS Networks) INMBSHIT016O000 Hitachi VRF to Modbus RTU / TCP gateway (16 / 64 indoor units)
Intesis Modbus Server - Hitachi VRF, order codes INMBSHIT016O000 / INMBSHIT064O000 (legacy HI-AC-MBS-16 / HI-AC-MBS-64), user manual User Manual r1.2 EN.
Also known as: INMBSHIT016O000, INMBSHIT064O000, HI-AC-MBS-16, HI-AC-MBS-64, Intesis Modbus Server Hitachi VRF - VRF / split AC gateway
Intesis (HMS Networks) INMBSLGE001R000 LG AC to Modbus RTU gateway
One LG indoor unit on the BYR (wired remote) bus via INMBSLGE001R000 (legacy code LG-RC-MBS-1), user manual v1.9 (01/2024).
Also known as: INMBSLGE001R000, LG-RC-MBS-1, Intesis LG Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSLGE016O000 LG VRF to Modbus RTU / TCP gateway (16 / 64 indoor units)
Intesis Modbus - LG VRF, order codes INMBSLGE016O000 / INMBSLGE064O000 (legacy LG-AC-MBS-16 / -64), user manual r1.0 (04/2020); LG PI485 bus.
Also known as: INMBSLGE016O000, INMBSLGE064O000, LG-AC-MBS-16, LG-AC-MBS-64, Intesis Modbus LG VRF - VRF / split AC gateway
Intesis (HMS Networks) INMBSMHI001R000 Mitsubishi Heavy Industries AC to Modbus RTU gateway
Mitsubishi Heavy Industries indoor units (one, or up to 16 controlled together as one) on the XY remote-controller bus, user manual r6.4 (01/2024).
Also known as: INMBSMHI001R000, MH-RC-MBS-1, Intesis Mitsubishi Heavy Industries Modbus, Intesis MHI Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSMHI128O000 / INMBSMHI048O000 Mitsubishi Heavy Industries Superlink to Modbus gateway
Intesis Modbus Server - Mitsubishi Heavy Industries AC, order codes INMBSMHI128O000 (128 units, Superlink-II) and INMBSMHI048O000 (48 units, Superlink-I or II), user's manual r1.0 (05/2012).
Also known as: INMBSMHI128O000, INMBSMHI048O000, MH-AC-MBS-128, MH-AC-MBS-48, Intesis Modbus Server MHI Superlink - VRF / split AC gateway
Intesis (HMS Networks) INMBSMID001I000 Midea AC to Modbus RTU gateway
One Midea commercial / VRF indoor unit on the XYE bus, user manual v1.11.
Also known as: INMBSMID001I000, Intesis Midea Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSMID004I000 / 008I000 / 032I000 Midea AC to Modbus RTU interface (4 to 32 units)
INMBSMID004I000 / INMBSMID008I000 / INMBSMID032I000 / MD-AC-MBS-4 / MD-AC-MBS-8 / MD-AC-MBS-32, user manual v1.7 EN; up to 4, 8 or 32 indoor units on one XYE bus.
Also known as: INMBSMID004I000, INMBSMID008I000, INMBSMID032I000, MD-AC-MBS-4, MD-AC-MBS-8, MD-AC-MBS-32 - VRF / split AC gateway
Intesis (HMS Networks) INMBSMIT001I000 Mitsubishi Electric AC to Modbus RTU gateway
One Mitsubishi Electric Domestic, Mr. Slim or City Multi indoor unit via INMBSMIT001I000, user manual r2.8 (11/2024).
Also known as: INMBSMIT001I000, Intesis Mitsubishi Electric Modbus - Heat pump gateway (VRF / split AC gateway)
Intesis (HMS Networks) INMBSPAN001A100 Panasonic Aquarea H/J/K/L/M air-to-water to Modbus RTU gateway
Intesis (HMS Networks) INMBSPAN001A100 gateway connected to Panasonic Aquarea H, J, K, L and M series air-to-water heat pumps, per user manual version 1.0.2 (2026-02-04).
Also known as: INMBSPAN001A100, Aquarea Modbus, Panasonic Aquarea Modbus RTU, Intesis Aquarea, INMBSPAN001A000 (legacy order code) - VRF / split AC gateway
Intesis (HMS Networks) INMBSPAN001I100 Panasonic Etherea (domestic) AC to Modbus RTU gateway
Panasonic Etherea-line domestic split units, user's manual r1.5 (09/2025). Some registers only on 2013 (PKE series) and later models.
Also known as: INMBSPAN001I100, Intesis Panasonic Etherea Modbus, Intesis Panasonic domestic Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSPAN001R000 Panasonic AC to Modbus RTU gateway
Panasonic / Sanyo ECOi and PACi indoor units (one, or up to 16 controlled together as one) on the R1R2 remote-controller bus, user manual v2.8 (09/2025).
Also known as: INMBSPAN001R000, PA-RC2-MBS-1, Intesis Panasonic Modbus, Intesis Sanyo Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSPAN016O000 / 064O000 / 128O000 Panasonic VRF (P-Link) to Modbus gateway
Intesis Modbus Server - Panasonic, order codes INMBSPAN016O000 / 064O000 / 128O000 (legacy PA-AC-MBS-16 / -64 / -128), user manual r1.1 (11/2020); Panasonic P-Link systems.
Also known as: INMBSPAN016O000, INMBSPAN064O000, INMBSPAN128O000, PA-AC-MBS-16, PA-AC-MBS-64, PA-AC-MBS-128, Intesis Modbus Server Panasonic VRF - VRF / split AC gateway
Intesis (HMS Networks) INMBSSAM001R000 Samsung AC to Modbus RTU gateway
Samsung commercial indoor units on the F3F4/V1V2 remote-controller bus, user's manual v1.5 (01/2024).
Also known as: INMBSSAM001R000, Intesis Samsung Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSSAM001R100 Samsung NASA AC to Modbus RTU gateway
Samsung NASA-protocol commercial indoor units on the remote-controller bus, user's manual r1.4 (01/2024).
Also known as: INMBSSAM001R100, Intesis Samsung NASA Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSSAM016O000 Samsung NASA (R1/R2) VRF to Modbus gateway (4 to 64 units)
Intesis Modbus Server - Samsung NASA, order codes INMBSSAM004O000 / 008O000 / 016O000 / 064O000 (legacy SM-ACN-MBS-4/8/16/64), user manual r1.4 (12/2020); Samsung NASA R1/R2 bus.
Also known as: INMBSSAM004O000, INMBSSAM008O000, INMBSSAM016O000, INMBSSAM064O000, SM-ACN-MBS-4, SM-ACN-MBS-8, SM-ACN-MBS-16, SM-ACN-MBS-64 - VRF / split AC gateway
Intesis (HMS Networks) INMBSTOS001R000 Toshiba AC to Modbus RTU gateway
Toshiba Digital Inverter (RAV) and VRF indoor units on the AB remote bus via INMBSTOS001R0xx, user manual r2.9 (01/2024).
Also known as: INMBSTOS001R000, INMBSTOS001R0xx, Intesis Toshiba Modbus
Other ac & vrf gateways register maps
- Heat pump (VRF / split AC gateway)
Mitsubishi Electric MelcoBEMS MINI (A1M+) gateway for Ecodan FTC4/FTC5/FTC6 air-to-water systems
Procon MelcoBEMS MINI (A1M+) firmware 4.1.0 connected to an Ecodan FTC4, FTC5 or FTC6 air-to-water controller; holding-register table only.
Also known as: A1M+, MelcoBEMS MINI, Procon A1M+, Ecodan FTC4, Ecodan FTC5, Ecodan FTC6 - VRF / split AC gateway
Samsung MIM-B19N Modbus interface module (DVM / EHS / indoor units)
Samsung MIM-B19N Modbus interface module on the R1/R2 bus of one outdoor system with up to 48 indoor units (installation manual DB68-07538A-00).
Also known as: MIM-B19N, Samsung Modbus interface module - Sensor (1-Wire temperature gateway)
Unipi Technology Unipi Extension xG18 1-Wire temperature gateway
Unipi Extension xG18 RS-485 module per the Unipi Extension xG18 Modbus map v1.1.
Also known as: Unipi Extension xG18, xG18 - VRF / split AC gateway
Daikin EKMBDXB Modbus Interface DIII
EKMBDXB7V1 Modbus RTU interface on the DIII-net of Daikin VRV, Sky Air, split (via KRP928), VAM/VKM ventilation, VRV hydrobox, air curtains, ERQ control box, heating and applied units; design guide 4P642495-1A (2022.02).
Also known as: EKMBDXB7V1, Modbus Interface DIII - Air handler DX kit (VRF / split AC gateway built in)
LG PAHCMR000 AHU Communication Kit (Multi V DX kit, Modbus to DDC)
LG PAHCMR000 AHU Communication Kit (R32 and R410A Multi V / single split outdoor units with a PRLK EEV kit), installation manual IM_AHU_Comm_Kit_PAHCMR000_R32_06_26.
Also known as: PAHCMR000, LG AHU Communication Kit R32, LG AHU comm kit Modbus - VRF / split AC gateway (retail controller)
Mitsubishi Electric Procon MelcoRETAIL MINI controller for Air-To-Air split units
Procon MelcoRETAIL MINI on the CN105/CN92 connector of Mitsubishi Electric M, S and P series Air-To-Air indoor units, installation manual v1.0.6, firmware 1.0.3.
Also known as: MelcoRETAIL MINI, Procon MelcoRETAIL MINI
All ac & vrf gateways Modbus register maps →
Source: Intesis Modbus Server - Mitsubishi Electric CC User Manual · User Manual r1.4 EN · rev. 2021-05. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.