  3. Intesis (HMS Networks)
  4. INMBSMIT050C000 / INMBSMIT100C000 Mitsubishi Electric City Multi centralised controller to Modbus gateway

VRF / split AC gateway · Modbus register map

Intesis (HMS Networks) INMBSMIT050C000 / INMBSMIT100C000 Mitsubishi Electric City Multi centralised controller to Modbus gateway Modbus register map

Updated 19 November 2026

Short answer

Modbus server that reads Mitsubishi Electric City Multi groups through one or two centralised controllers (XML over Ethernet). Each group (1..50 per controller) gets a 100-register block with on/off, mode, fan, vane, run hours, errors and local-panel permissions; each controller also has 26 all-group command registers. Covers indoor units, Lossnay, OA processing, ATW booster/HEX and CEh heat pumps.

This page lists 49 Modbus registers for the Intesis (HMS Networks) INMBSMIT050C000 / INMBSMIT100C000 Mitsubishi Electric City Multi centralised controller to Modbus gateway — 39 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Intesis (HMS Networks)’s own free documentation (linked below) and checked against it.

Manufacturer
Intesis (HMS Networks)
Model
INMBSMIT050C000 / INMBSMIT100C000 Mitsubishi Electric City Multi centralised controller to Modbus gateway
Equipment type
VRF / split AC gateway
Registers
49 (39 writable)
Transport
Modbus RTU, Modbus TCP
Default unit ID
Not stated
TCP port
502
Documented addressing
0-based (the number printed is the address on the wire)
Also known as
INMBSMIT050C000, INMBSMIT100C000, ME-AC-MBS-50, ME-AC-MBS-100, Intesis Modbus Server Mitsubishi Electric CC
Source document
Intesis Modbus Server - Mitsubishi Electric CC User Manual · User Manual r1.4 EN · rev. 2021-05
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Intesis (HMS Networks) INMBSMIT050C000 / INMBSMIT100C000 Mitsubishi Electric City Multi centralised controller to Modbus gateway

Integration in brief

Point the gateway at the centralised controller(s) in Intesis MAPS, import the groups, send the project, then poll each group's 100-register block for on/off, mode, fan, vane and errors.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 0CC communication errorINT16Controller communication errorRead
HR 100Group on/offINT16Group on/offRead/write
HR 101Group operation modeINT16Group modeRead/write
HR 102Group fan speedINT16Group fan speedRead/write
HR 109Group error statusINT16Group error statusRead
HR 110Group error codeINT16Group error codeRead
HR 136Filter statusINT16Filter statusRead

Enable Modbus control & writes

The centralised controller XML interface must be active (it may need a licence from Mitsubishi Electric) and the groups must be configured in MAPS (unit type per group).

Byte order & addressing

Network setup

Watch out for

Intesis (HMS Networks) INMBSMIT050C000 / INMBSMIT100C000 Mitsubishi Electric City Multi centralised controller to Modbus gateway Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

49 of 49 shown
Intesis (HMS Networks) INMBSMIT050C000 / INMBSMIT100C000 Mitsubishi Electric City Multi centralised controller to Modbus gateway Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0doc (cc x 30) + 0CC communication errorCentralised controller 0 shown; see notes.INT16Read0 = OK; 1 = Communication error
HR1doc (cc x 30) + 1Reset errors (all groups)INT16Write1 = Reset the errors
HR2doc (cc x 30) + 2On (all groups)INT16Write1 = Set groups on
HR3doc (cc x 30) + 3Off (all groups)INT16Write1 = Set groups off
HR4doc (cc x 30) + 4Mode Auto (all IC groups)INT16Write1 = Execute
HR5doc (cc x 30) + 5Mode Heat (all IC groups)INT16Write1 = Execute
HR6doc (cc x 30) + 6Mode Dry (all IC groups)INT16Write1 = Execute
HR7doc (cc x 30) + 7Mode Fan (all IC groups)INT16Write1 = Execute
HR8doc (cc x 30) + 8Mode Cool (all IC groups)INT16Write1 = Execute
HR9doc (cc x 30) + 9Mode Setback (all IC groups)INT16Write1 = Execute
HR10doc (cc x 30) + 10Mode LC Auto (all Lossnay groups)INT16Write1 = Execute
HR11doc (cc x 30) + 11Mode Heat Recovery (all Lossnay groups)INT16Write1 = Execute
HR12doc (cc x 30) + 12Mode Bypass (all Lossnay groups)INT16Write1 = Execute
HR13doc (cc x 30) + 13Fan speed Auto (all IC groups)INT16Write1 = Execute
HR14doc (cc x 30) + 14Fan speed Low (all IC and Lossnay groups)INT16Write1 = Execute
HR15doc (cc x 30) + 15Fan speed Mid-1 (all IC groups)INT16Write1 = Execute
HR16doc (cc x 30) + 16Fan speed Mid-2 (all IC groups)INT16Write1 = Execute
HR17doc (cc x 30) + 17Fan speed High (all IC and Lossnay groups)INT16Write1 = Execute
HR18doc (cc x 30) + 18Vanes Auto (all IC groups)INT16Write1 = Execute
HR19doc (cc x 30) + 19Vanes Horizontal (all IC groups)INT16Write1 = Execute
HR20doc (cc x 30) + 20Vanes Position-2 (all IC groups)INT16Write1 = Execute
HR21doc (cc x 30) + 21Vanes Position-3 (all IC groups)INT16Write1 = Execute
HR22doc (cc x 30) + 22Vanes Position-4 (all IC groups)INT16Write1 = Execute
HR23doc (cc x 30) + 23Vanes Vertical (all IC groups)INT16Write1 = Execute
HR24doc (cc x 30) + 24Vanes Swing (all IC groups)INT16Write1 = Execute
HR100doc ((cc x 50) + g) x 100 + 0Group on/offCC 0, group 1 shown; see notes.INT16Read/write0 = Off; 1 = On
HR101doc ((cc x 50) + g) x 100 + 1Group operation modeIndoor-unit (IC) codes shown; Lossnay and ATW groups use other codes (see notes).INT16Read/write0 = Auto; 1 = Heat; 2 = Dry; 3 = Fan; 4 = Cool; 5 = Auto Heat; 6 = Auto Cool; 7 = Setback; 8 = Setback Heat; 9 = Setback Cool
HR102doc ((cc x 50) + g) x 100 + 2Group fan speedIC groups: 0 Auto, 1 Low, 4 High; mid codes printed inconsistently (see notes).INT16Read/write0 = Auto; 1 = Low; 4 = High
HR103doc ((cc x 50) + g) x 100 + 3Group vane positionINT16Read/write0 = Auto; 1 = Horizontal; 2 = Position-2; 3 = Position-3; 4 = Position-4; 5 = Vertical; 6 = Swing
HR106doc ((cc x 50) + g) x 100 + 6Lossnay / OA operational statusINT16Read/write0 = Off; 1 = Low; 2 = High
HR107doc ((cc x 50) + g) x 100 + 7Group operation time, hundreds of hoursRun hours = this x 100 + next register; 0..9999.INT16× 100hRead
HR108doc ((cc x 50) + g) x 100 + 8Group operation time, hours remainderRun hours modulo 100; 0..99.INT16hRead
HR109doc ((cc x 50) + g) x 100 + 9Group error statusINT16Read0 = No error; 1 = Group error
HR110doc ((cc x 50) + g) x 100 + 10Group error codeMitsubishi Electric 4-digit error code number.INT16Read
HR111doc ((cc x 50) + g) x 100 + 11Group error resetINT16Write1 = Reset the error
HR112doc ((cc x 50) + g) x 100 + 12Group modelModel of units connected to the group.INT16Read
HR113doc ((cc x 50) + g) x 100 + 13Allow on/off from local panelINT16Read/write0 = Allow; 1 = Not allow
HR114doc ((cc x 50) + g) x 100 + 14Allow mode from local panelINT16Read/write0 = Allow; 1 = Not allow
HR115doc ((cc x 50) + g) x 100 + 15Allow setpoint from local panelINT16Read/write0 = Allow; 1 = Not allow
HR116doc ((cc x 50) + g) x 100 + 16Allow filter reset from local panelINT16Read/write0 = Allow; 1 = Not allow
HR117doc ((cc x 50) + g) x 100 + 17Allow air direction from local panelOnly with 'Old Model Compatibility' = New model.INT16Read/write0 = Allow; 1 = Not allow
HR118doc ((cc x 50) + g) x 100 + 18Allow fan speed from local panelOnly with 'Old Model Compatibility' = New model.INT16Read/write0 = Allow; 1 = Not allow
HR119doc ((cc x 50) + g) x 100 + 19Allow timer from local panelOnly with 'Old Model Compatibility' = New model.INT16Read/write0 = Allow; 1 = Not allow
HR120doc ((cc x 50) + g) x 100 + 20Setback controlOnly with controller model EB-50GU or AE-200 or newer.INT16Read/write0 = Disable; 1 = Enable
HR132doc ((cc x 50) + g) x 100 + 32Room humidityOnly when 'URC Controller' = Available.INT16%Read
HR133doc ((cc x 50) + g) x 100 + 33Brightness statusINT16Read0 = Dark; 1 = Bright
HR134doc ((cc x 50) + g) x 100 + 34OccupancyINT16Read0 = Absence; 1 = Occupancy
HR136doc ((cc x 50) + g) x 100 + 36Filter statusINT16Read0 = OK; 1 = Dirty
HR137doc ((cc x 50) + g) x 100 + 37Dirty filter indication resetINT16Write1 = Reset the filter

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Intesis (HMS Networks) INMBSMIT050C000 / INMBSMIT100C000 Mitsubishi Electric City Multi centralised controller to Modbus gateway

What Modbus registers does the Intesis (HMS Networks) INMBSMIT050C000 / INMBSMIT100C000 Mitsubishi Electric City Multi centralised controller to Modbus gateway have?

This map lists 49 registers: 49 holding registers. 39 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Intesis (HMS Networks) INMBSMIT050C000 / INMBSMIT100C000 Mitsubishi Electric City Multi centralised controller to Modbus gateway Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual states formula results are link-layer addresses with the first register at 0. Controller signals: cc x 30 + signal; group signals: ((cc x 50) + g) x 100 + signal, with cc = 0 or 1 and g = group 1..50. This file lists cc = 0 (0..24) and cc 0 group 1 (100..137).

What are the minimum Modbus registers to integrate the Intesis (HMS Networks) INMBSMIT050C000 / INMBSMIT100C000 Mitsubishi Electric City Multi centralised controller to Modbus gateway?

Start with HR 0 CC communication error (Controller communication error); HR 100 Group on/off (Group on/off); HR 101 Group operation mode (Group mode); HR 102 Group fan speed (Group fan speed); HR 109 Group error status (Group error status); HR 110 Group error code (Group error code); HR 136 Filter status (Filter status).

How do I enable Modbus control of the Intesis (HMS Networks) INMBSMIT050C000 / INMBSMIT100C000 Mitsubishi Electric City Multi centralised controller to Modbus gateway?

The centralised controller XML interface must be active (it may need a licence from Mitsubishi Electric) and the groups must be configured in MAPS (unit type per group).

Where is the official Intesis (HMS Networks) INMBSMIT050C000 / INMBSMIT100C000 Mitsubishi Electric City Multi centralised controller to Modbus gateway Modbus documentation?

The source is Intesis Modbus Server - Mitsubishi Electric CC User Manual (User Manual r1.4 EN), revision 2021-05, published free by Intesis (HMS Networks) at https://www.hms-networks.com/docs/default-source/products/intesis/manuals-and-guides---manuals/user-manual-inmbsmitxxxc000.pdf.

More Intesis (HMS Networks) Modbus register maps

Other ac & vrf gateways register maps

All ac & vrf gateways Modbus register maps →

Source: Intesis Modbus Server - Mitsubishi Electric CC User Manual · User Manual r1.4 EN · rev. 2021-05. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.