VRF / split AC gateway · Modbus register map

Intesis (HMS Networks) INMBSMID001I000 Midea AC to Modbus RTU gateway Modbus register map

Updated 17 November 2026

Short answer

Modbus RTU server that talks to one Midea indoor unit over the XYE bus. Holding registers cover on/off, mode, fan, vane, setpoint, external temperature input, window contact, alarm and error code, return-air temperature, machine mode and the Midea indoor-unit address the gateway controls.

This page lists 24 Modbus registers for the Intesis (HMS Networks) INMBSMID001I000 Midea AC to Modbus RTU gateway — 15 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Intesis (HMS Networks)’s own free documentation (linked below) and checked against it.

Manufacturer
Intesis (HMS Networks)
Model
INMBSMID001I000 Midea AC to Modbus RTU gateway
Equipment type
VRF / split AC gateway
Registers
24 (15 writable)
Transport
Modbus RTU
Default unit ID
1
Default serial
9600 baud, 8N2
Documented addressing
0-based (the number printed is the address on the wire)
Also known as
INMBSMID001I000, Intesis Midea Modbus
Source document
Intesis INMBSMID001I000 User Manual · User Manual v1.11 EN · rev. 2026-04
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Intesis (HMS Networks) INMBSMID001I000 Midea AC to Modbus RTU gateway

Integration in brief

Set the Midea indoor-unit address in register 1210, then write 0-4 and poll 5, 10, 11 and 66. Write room temperature to 22 to make a Modbus-side sensor drive the unit.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 0AC unit On/OffUINT16On/offRead/write
HR 1AC unit modeUINT16ModeRead/write
HR 4AC unit temperature setpointUINT16SetpointRead/write
HR 5AC unit temperature referenceUINT16Control temperatureRead
HR 10AC unit alarm statusUINT16Alarm flagRead
HR 11Error codeUINT16Error codeRead
HR 1210Indoor unit addressUINT16Target indoor unit addressRead/write

Enable Modbus control & writes

No enable step; register 7 = 1 disables the gateway. Register 1210 must hold the Midea address of the unit.

Byte order & addressing

Network setup

Watch out for

Intesis (HMS Networks) INMBSMID001I000 Midea AC to Modbus RTU gateway Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

24 of 24 shown
Intesis (HMS Networks) INMBSMID001I000 Midea AC to Modbus RTU gateway Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0AC unit On/OffUINT16Read/write0 = Off; 1 = On
HR1AC unit modeAvailable modes depend on the indoor unit.UINT16Read/write0 = Auto; 1 = Heat; 2 = Dry; 3 = Fan; 4 = Cool
HR2AC unit fan speedAvailable speeds depend on the indoor unit.UINT16Read/write0 = Auto; 1 = SP1; 2 = SP2; 3 = SP3
HR3AC unit up/down vane positionUINT16Read/write0 = Off; 10 = Swing
HR4AC unit temperature setpoint17..30 °C (63..86 °F). SW4 x1 °C assumed (x10: 0.1, or °F).UINT16°CRead/write32768 = Initialisation value / no value (0x8000)
HR5AC unit temperature referenceTemperature the indoor unit controls on. SW4 x1 °C assumed (x10: 0.1, or °F).UINT16°CRead32768 = Initialisation value / no value (0x8000)
HR6Window contactVirtual window contact written from Modbus.UINT16Read/write0 = Closed; 1 = Open
HR7Gateway disablementNon-volatile.UINT16Read/write0 = Gateway enabled; 1 = Gateway disabled
HR8Remote control disablementBlocks a remote on the MD-RC bus (XYE extension kit). Non-volatile.UINT16Read/write0 = Remote enabled; 1 = Remote disabled
HR9AC unit operation timeHours in On state, 0..65535. Non-volatile.UINT16hRead/write
HR10AC unit alarm statusUINT16Read0 = No alarm; 1 = Alarm
HR11Error codeMidea error code; see manual section 7.UINT16Read0 = No error; 65535 = Gateway cannot talk to the AC unit (-1)
HR13Open Window switch-off timeoutMinutes from window open to unit off, 0..30 (default 30).UINT16minRead/write
HR14Modbus RTU baud rateRate set on SW3/SW4 (2400..115200, default 9600).UINT16Read
HR15Modbus slave addressAddress set on SW3, 1..63.UINT16Read
HR21Max number of fan speedsUINT16Read
HR22External ambient temperature (from Modbus)Modbus-side room temperature; 0x8000 = none. SW4 x1 °C assumed (x10: 0.1, or °F).UINT16°CRead/write32768 = Initialisation value / no value (0x8000)
HR23AC real temperature setpointSetpoint actually applied to the unit. SW4 x1 °C assumed (x10: 0.1, or °F).UINT16°CRead32768 = Initialisation value / no value (0x8000)
HR66Return path temperatureSW4 x1 °C assumed (x10: 0.1, or °F).UINT16°CRead32768 = Initialisation value / no value (0x8000)
HR97Block periodic sendingsBlocked = Modbus writes are passed on only when the value changes. Firmware 1.0+.UINT16Read/write0 = Non-blocked; 1 = Blocked
HR99Reset / reboot deviceUINT16Write1 = Reset
HR1150Machine modeLimited setpoint uses the custom limits 1153-1156.UINT16Read/write0 = Normal; 1 = Autochangeover; 2 = Limited setpoint
HR1210Indoor unit addressMidea address (0..63) of the indoor unit this gateway controls.UINT16Read/write
HR2031CapacityUINT16Read1 = INMBSMID001I000 (1 indoor unit)

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Intesis (HMS Networks) INMBSMID001I000 Midea AC to Modbus RTU gateway

What Modbus registers does the Intesis (HMS Networks) INMBSMID001I000 Midea AC to Modbus RTU gateway have?

This map lists 24 registers: 24 holding registers. 15 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Intesis (HMS Networks) INMBSMID001I000 Midea AC to Modbus RTU gateway Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Tables give a 'protocol address' (base 0) and a 'PLC address' (base 1); the protocol address is the wire address and is used for 'documented'.

What are the minimum Modbus registers to integrate the Intesis (HMS Networks) INMBSMID001I000 Midea AC to Modbus RTU gateway?

Start with HR 0 AC unit On/Off (On/off); HR 1 AC unit mode (Mode); HR 4 AC unit temperature setpoint (Setpoint); HR 5 AC unit temperature reference (Control temperature); HR 10 AC unit alarm status (Alarm flag); HR 11 Error code (Error code); HR 1210 Indoor unit address (Target indoor unit address).

How do I enable Modbus control of the Intesis (HMS Networks) INMBSMID001I000 Midea AC to Modbus RTU gateway?

No enable step; register 7 = 1 disables the gateway. Register 1210 must hold the Midea address of the unit.

Where is the official Intesis (HMS Networks) INMBSMID001I000 Midea AC to Modbus RTU gateway Modbus documentation?

The source is Intesis INMBSMID001I000 User Manual (User Manual v1.11 EN), revision 2026-04, published free by Intesis (HMS Networks) at https://www.hms-networks.com/docs/default-source/products/intesis/manuals-and-guides---manuals/user-manual-inmbsmid001i000.pdf.