- Export residential split air conditioners (built-in Modbus on indoor unit / wired controller)
Split AC unit (VRF / split AC gateway built in) · Modbus register map
Gree Export residential split air conditioners (built-in Modbus on indoor unit / wired controller) Modbus register map
Updated 19 November 2026
On these Gree residential units the Modbus RTU slave lives in the indoor-unit controller or wired controller, so no extra module is needed. Holding registers carry on/off, mode, fan speed, setpoint, louvres, sleep and energy-saving limits plus indoor, return-air and outdoor temperatures; coils carry feature flags, locks and a long list of indoor, outdoor and inverter-drive fault bits. Up to 255 units can share one BMS line.
This page lists 113 Modbus registers for the Gree Export residential split air conditioners (built-in Modbus on indoor unit / wired controller) — 28 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Gree’s own free documentation (linked below) and checked against it.
- Manufacturer
- Gree
- Model
- Export residential split air conditioners (built-in Modbus on indoor unit / wired controller)
- Equipment type
- Split AC unit (VRF / split AC gateway built in)
- Registers
- 113 (28 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Default serial
- 9600 baud, 8N1
- Documented addressing
- 0-based (the number printed is the address on the wire)
- Also known as
- Gree residential split Modbus, Gree wall split Modbus, Gree wired controller Modbus
Integration notes: Gree Export residential split air conditioners (built-in Modbus on indoor unit / wired controller)
Poll words 2-25 for on/off, mode, fan, setpoint and louvres and words 4, 49 and 82 for temperatures; read coils 17-236 for status and fault bits. Write word 2 (0xAA on / 0x55 off), 17, 19 and 20 to control the unit.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 2 | Unit On/Off | UINT16 | On/off | Read/write |
| HR 17 | Set mode | UINT16 | Mode | Read/write |
| HR 19 | Set fan speed | UINT16 | Fan speed | Read/write |
| HR 20 | Set temperature | UINT16 | Setpoint | Read/write |
| HR 4 | Ambient temperature | INT16 | Room temperature | Read |
| HR 49 | Outdoor ambient temperature | INT16 | Outdoor temperature | Read |
| CO 151 | Compressor status | BIT | Compressor running | Read |
| CO 122 | Communication failure with outdoor unit | BIT | Outdoor-unit communication fault | Read |
Enable Modbus control & writes
The Modbus interface is built into the indoor-unit controller or wired controller; each unit needs its own address (1-255) set before connecting the BMS. Power-cycle the unit after connecting the controller.
Byte order & addressing
- On/off uses 0xAA and 0x55, not 1 and 0.
- The two energy-saving flags (bits 32 and 33) must be set or cleared together.
- A setpoint outside the active energy-saving limit is silently ignored; check by reading back.
- Exception code 03 is returned for an out-of-range read (for example 128 words; the maximum is 127 per request).
Network setup
- RS485, 9600 baud, 8 data bits, no parity, 1 stop bit.
- Use twisted pair kept at least 15 cm from power cables; repeaters may be needed on long lines.
- Match A to A and B to B; a constantly lit TX lamp on the converter points to swapped A/B.
Watch out for
- Sleep is ignored in fan and auto modes.
- The remote temperature shield is ignored in auto mode unless the unit allows setpoint adjustment in auto (bit 75).
- Heating commands to cooling-only units (bit 177 = 1) do nothing.
Gree Export residential split air conditioners (built-in Modbus on indoor unit / wired controller) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| CO | 17doc Bit17 | Remote lock | Unit locked by remote monitoring or a hotel charging system. | BIT | Read/write | 0 = Unlocked; 1 = Locked | |||
| CO | 18doc Bit18 | Remote temperature shield | Blocks setpoint changes at the unit. | BIT | Read/write | 0 = Not shielded; 1 = Shielded | |||
| CO | 19doc Bit19 | Remote mode shield | BIT | Read/write | 0 = Not shielded; 1 = Shielded | ||||
| CO | 20doc Bit20 | Remote On/Off shield | BIT | Read/write | 0 = Not shielded; 1 = Shielded | ||||
| CO | 21doc Bit21 | Remote energy-saving shield | BIT | Read/write | 0 = Not shielded; 1 = Shielded | ||||
| CO | 24doc Bit24 | Absence mode (8 °C heating) | BIT | Read/write | 0 = Off; 1 = On | ||||
| CO | 25doc Bit25 | Healthy function | BIT | Read/write | 0 = Off; 1 = On | ||||
| CO | 26doc Bit26 | I-Demand / energy-saving comfort | BIT | Read/write | 0 = Off; 1 = On | ||||
| CO | 27doc Bit27 | Turbo | BIT | Read/write | 0 = Off; 1 = On | ||||
| CO | 28doc Bit28 | Electric heater permission | BIT | Read/write | 0 = Electric heater allowed; 1 = Electric heater not allowed | ||||
| CO | 29doc Bit29 | X-fan | BIT | Read/write | 0 = Off; 1 = On | ||||
| CO | 30doc Bit30 | Silent | BIT | Read/write | 0 = Off; 1 = On | ||||
| CO | 32doc Bit32 | Energy saving in cooling active | Write together with bit 33. | BIT | Read/write | 0 = Off; 1 = On | |||
| CO | 33doc Bit33 | Energy saving in heating active | Write together with bit 32. | BIT | Read/write | 0 = Off; 1 = On | |||
| CO | 34doc Bit34 | Button lock (child lock) | BIT | Read/write | 0 = Off; 1 = On | ||||
| CO | 35doc Bit35 | On/Off memory | Whether the unit restores its on/off state after power loss. | BIT | Read/write | 0 = Memorize; 1 = Do not memorize | |||
| CO | 36doc Bit36 | °C/°F flag | BIT | Read/write | 0 = °C; 1 = °F | ||||
| CO | 37doc Bit37 | 1 °F flag | BIT | Read | 0 = No; 1 = Yes | ||||
| CO | 38doc Bit38 | 1 °F flag, cooling energy-saving limit | BIT | Read | 0 = No; 1 = Yes | ||||
| CO | 39doc Bit39 | 1 °F flag, heating energy-saving limit | BIT | Read | 0 = No; 1 = Yes | ||||
| CO | 40doc Bit40 | Timer status | BIT | Read | 0 = No timer; 1 = Timer set | ||||
| CO | 46doc Bit46 | Gate control system fitted | BIT | Read | 0 = No; 1 = Yes | ||||
| CO | 49doc Bit49 | Timer On flag | BIT | Read | 0 = Not active; 1 = Active | ||||
| CO | 50doc Bit50 | Timer Off flag | BIT | Read | 0 = Not active; 1 = Active | ||||
| CO | 51doc Bit51 | Room temperature source in current mode | BIT | Read | 0 = Return-air sensor; 1 = Wired-controller sensor | ||||
| CO | 65doc Bit65 | Wired controller temperature sensor error | BIT | Read | 0 = Normal; 1 = Error | ||||
| CO | 74doc Bit74 | Up and down swing mode | BIT | Read/write | 0 = Mode 1, simple swing; 1 = Mode 2, fixed angle and small-area swing | ||||
| CO | 75doc Bit75 | Setpoint adjustable in auto mode | BIT | Read | 0 = No; 1 = Yes | ||||
| CO | 97doc Bit97 | Indoor evaporator temperature sensor error | BIT | Read | 0 = Normal; 1 = Error | ||||
| CO | 98doc Bit98 | Indoor return-air temperature sensor error | BIT | Read | 0 = Normal; 1 = Error | ||||
| CO | 101doc Bit101 | Water overflow protection | BIT | Read | 0 = Normal; 1 = Error | ||||
| CO | 104doc Bit104 | Jumper cap error (indoor) | BIT | Read | 0 = Normal; 1 = Error | ||||
| CO | 105doc Bit105 | Indoor fan error | BIT | Read | 0 = Normal; 1 = Error | ||||
| CO | 112doc Bit112 | Card in/out status | Hotel key-card switch. | BIT | Read | 0 = Card out; 1 = Card in | |||
| CO | 120doc Bit120 | Communication failure with master wired controller | BIT | Read | 0 = Normal; 1 = Error | ||||
| CO | 122doc Bit122 | Communication failure with outdoor unit | BIT | Read | 0 = Normal; 1 = Error | ||||
| CO | 147doc Bit147 | Outdoor fan status | BIT | Read | 0 = Off; 1 = On | ||||
| CO | 150doc Bit150 | 4-way valve status | BIT | Read | 0 = Off; 1 = On | ||||
| CO | 151doc Bit151 | Compressor status | BIT | Read | 0 = Off; 1 = On | ||||
| CO | 152doc Bit152 | Compressor discharge temperature protection | BIT | Read | 0 = Normal; 1 = Error | ||||
| CO | 153doc Bit153 | Refrigerant shortage protection | BIT | Read | 0 = Normal; 1 = Error | ||||
| CO | 154doc Bit154 | DC fan motor protection | BIT | Read | 0 = Normal; 1 = Error | ||||
| CO | 155doc Bit155 | 4-way valve reversing error | BIT | Read | 0 = Normal; 1 = Error | ||||
| CO | 156doc Bit156 | Overpower protection | BIT | Read | 0 = Normal; 1 = Error | ||||
| CO | 157doc Bit157 | Overload protection | BIT | Read | 0 = Normal; 1 = Error | ||||
| CO | 158doc Bit158 | Low pressure protection | BIT | Read | 0 = Normal; 1 = Error | ||||
| CO | 159doc Bit159 | High pressure protection | BIT | Read | 0 = Normal; 1 = Error | ||||
| CO | 160doc Bit160 | Evaporator anti-freeze protection | BIT | Read | 0 = Normal; 1 = Error | ||||
| CO | 161doc Bit161 | Outdoor ambient temperature sensor error | BIT | Read | 0 = Normal; 1 = Error | ||||
| CO | 162doc Bit162 | Discharge temperature sensor error | BIT | Read | 0 = Normal; 1 = Error | ||||
| CO | 163doc Bit163 | Condenser temperature sensor error | BIT | Read | 0 = Normal; 1 = Error | ||||
| CO | 165doc Bit165 | Jumper cap error (outdoor) | BIT | Read | 0 = Normal; 1 = Error | ||||
| CO | 166doc Bit166 | Outdoor unit memory chip error | BIT | Read | 0 = Normal; 1 = Error | ||||
| CO | 173doc Bit173 | Indoor and outdoor units mismatched | BIT | Read | 0 = Normal; 1 = Error | ||||
| CO | 174doc Bit174 | Drive communication failure | BIT | Read | 0 = Normal; 1 = Error | ||||
| CO | 177doc Bit177 | Cooling-only flag | Heating commands have no effect on cooling-only units. | BIT | Read | 0 = Cooling and heating; 1 = Cooling only | |||
| CO | 179doc Bit179 | System defrosting | BIT | Read | 0 = No; 1 = Yes | ||||
| CO | 184doc Bit184 | Drive DC bus undervoltage or voltage-drop error | BIT | Read | 0 = Normal; 1 = Error | ||||
| CO | 185doc Bit185 | Drive DC bus overvoltage protection | BIT | Read | 0 = Normal; 1 = Error | ||||
| CO | 186doc Bit186 | Drive AC input current protection | BIT | Read | 0 = Normal; 1 = Error | ||||
| CO | 187doc Bit187 | Drive IPM protection | BIT | Read | 0 = Normal; 1 = Error | ||||
| CO | 188doc Bit188 | Drive PFC protection | BIT | Read | 0 = Normal; 1 = Error | ||||
| CO | 189doc Bit189 | Inverter compressor start-up failure | BIT | Read | 0 = Normal; 1 = Error | ||||
| CO | 190doc Bit190 | Inverter compressor phase-loss protection | BIT | Read | 0 = Normal; 1 = Error | ||||
| CO | 191doc Bit191 | Drive module reset | BIT | Read | 0 = Normal; 1 = Error | ||||
| CO | 192doc Bit192 | Inverter compressor overcurrent protection | BIT | Read | 0 = Normal; 1 = Error | ||||
| CO | 193doc Bit193 | Inverter compressor power protection | BIT | Read | 0 = Normal; 1 = Error | ||||
| CO | 194doc Bit194 | Drive current-detection circuit failure | BIT | Read | 0 = Normal; 1 = Error | ||||
| CO | 195doc Bit195 | Inverter compressor out-of-step protection | BIT | Read | 0 = Normal; 1 = Error | ||||
| CO | 196doc Bit196 | Compressor stalling | BIT | Read | 0 = Normal; 1 = Error | ||||
| CO | 198doc Bit198 | Drive module high-temperature protection | BIT | Read | 0 = Normal; 1 = Error | ||||
| CO | 199doc Bit199 | Drive module temperature sensor failure | BIT | Read | 0 = Normal; 1 = Error | ||||
| CO | 210doc Bit210 | Drive charging circuit failure | BIT | Read | 0 = Normal; 1 = Error | ||||
| CO | 211doc Bit211 | Drive AC input voltage abnormal | BIT | Read | 0 = Normal; 1 = Error | ||||
| CO | 214doc Bit214 | Temperature drift protection | BIT | Read | 0 = Normal; 1 = Error | ||||
| CO | 215doc Bit215 | Current sensor connection protection | Current sensor not on the matching U or V phase. | BIT | Read | 0 = Normal; 1 = Error | |||
| CO | 216doc Bit216 | Indoor outlet pipe (gas side) sensor error | BIT | Read | 0 = Normal; 1 = Error | ||||
| CO | 217doc Bit217 | Indoor inlet pipe (liquid side) sensor error | BIT | Read | 0 = Normal; 1 = Error | ||||
| CO | 218doc Bit218 | Drive board ambient sensor error | BIT | Read | 0 = Normal; 1 = Error | ||||
| CO | 219doc Bit219 | Condenser inlet pipe sensor open/short | BIT | Read | 0 = Normal; 1 = Error | ||||
| CO | 220doc Bit220 | Condenser outlet pipe sensor open/short | BIT | Read | 0 = Normal; 1 = Error | ||||
| CO | 221doc Bit221 | Wiring error or expansion valve error | BIT | Read | 0 = Normal; 1 = Error | ||||
| CO | 222doc Bit222 | Mode conflict protection | BIT | Read | 0 = Normal; 1 = Error | ||||
| CO | 223doc Bit223 | Compressor demagnetization protection | BIT | Read | 0 = Normal; 1 = Error | ||||
| CO | 224doc Bit224 | Whole-unit current detection error | BIT | Read | 0 = Normal; 1 = Error | ||||
| CO | 225doc Bit225 | AC contactor protection | BIT | Read | 0 = Normal; 1 = Error | ||||
| CO | 226doc Bit226 | Overspeed | BIT | Read | 0 = Normal; 1 = Error | ||||
| CO | 227doc Bit227 | Outdoor fan 2 error | BIT | Read | 0 = Normal; 1 = Error | ||||
| CO | 228doc Bit228 | PG motor zero-crossing protection | BIT | Read | 0 = Normal; 1 = Error | ||||
| CO | 229doc Bit229 | Compressor suction temperature sensor error | BIT | Read | 0 = Normal; 1 = Error | ||||
| CO | 230doc Bit230 | Indoor fan tripping error | BIT | Read | 0 = Normal; 1 = Error | ||||
| CO | 231doc Bit231 | Communication error between indoor unit and grid | BIT | Read | 0 = Normal; 1 = Error | ||||
| CO | 232doc Bit232 | Communication error between outdoor unit and grid | BIT | Read | 0 = Normal; 1 = Error | ||||
| CO | 233doc Bit233 | Main error at grid side | BIT | Read | 0 = Normal; 1 = Error | ||||
| CO | 234doc Bit234 | Indoor network address error | BIT | Read | 0 = Normal; 1 = Error | ||||
| CO | 235doc Bit235 | IP address allocation overflow | BIT | Read | 0 = Normal; 1 = Error | ||||
| CO | 236doc Bit236 | Other error or protection | BIT | Read | 0 = Normal; 1 = Error | ||||
| HR | 2doc Word2 | Unit On/Off | Write 0xAA (170) to switch on, 0x55 (85) to switch off. | UINT16 | Read/write | 85 = Off; 170 = On | |||
| HR | 4doc Word4 | Ambient temperature | Indoor ambient temperature in tenths of a degree. | INT16 | × 0.1 | °C | Read | ||
| HR | 5doc Word5 | IDU address | Modbus address of this indoor unit, 1-255. | UINT16 | Read | ||||
| HR | 17doc Word17 | Set mode | UINT16 | Read/write | 1 = Cooling; 2 = Heating; 3 = Drying; 4 = Fan only; 5 = Auto | ||||
| HR | 19doc Word19 | Set fan speed | UINT16 | Read/write | 0 = Auto; 1 = Speed 1; 2 = Speed 2; 3 = Speed 3; 4 = Speed 4; 5 = Speed 5; 6 = Turbo | ||||
| HR | 20doc Word20 | Set temperature | Range 16-30. | UINT16 | °C | Read/write | |||
| HR | 22doc Word22 | Up and down swing | Vertical louvre: off, fixed position or swing between two positions. | UINT16 | Read/write | 0 = Off; 1 = Swing positions 1-5; 2 = Position 1; 3 = Position 2; 4 = Position 3; 5 = Position 4; 6 = Position 5; 7 = Swing positions 3-5; 8 = Swing positions 2-5; 9 = Swing positions 2-4; 10 = Swing positions 1-4; 11 = Swing positions 1-3 | |||
| HR | 23doc Word23 | Left and right swing | Horizontal louvre; off is the default after power-up. | UINT16 | Read/write | 0 = Off; 1 = Swing in same direction; 2 = Position 1; 3 = Position 2; 4 = Position 3; 5 = Position 4; 6 = Position 5; 12 = Printed as "15 position" (meaning not explained); 13 = Swing in opposite direction | |||
| HR | 24doc Word24 | Fresh air valve | Fresh-air valve mode 0-10. | UINT16 | Read/write | ||||
| HR | 25doc Word25 | Sleep mode | Ignored in fan and auto modes. | UINT16 | Read/write | 0 = No sleep; 1 = Sleep mode 1; 2 = Sleep mode 2; 3 = Sleep mode 3 | |||
| HR | 35doc Word35 | Cooling energy-saving lower limit | Lowest setpoint allowed in cooling while energy saving is active, 16-30. | UINT16 | °C | Read/write | |||
| HR | 36doc Word36 | Heating energy-saving upper limit | Highest setpoint allowed in heating while energy saving is active, 16-30. | UINT16 | °C | Read/write | |||
| HR | 39doc Word39 | Ambient sensor selection | Which sensor gives room temperature in each mode. | UINT16 | Read | 1 = Return-air sensor always; 2 = Wired-controller sensor always; 3 = Return air in cool/dry/fan, wired controller in heat/auto; 4 = Wired controller in cool/dry/fan, return air in heat/auto | |||
| HR | 49doc Word49 | Outdoor ambient temperature | Whole degrees. | INT16 | °C | Read | |||
| HR | 77doc Word77 | DRED function | Demand-response mode. | UINT16 | Read | 0 = No DRED; 1 = DRED 1; 2 = DRED 2; 3 = DRED 3 | |||
| HR | 82doc Word82 | Return-air temperature | Temperature at the indoor-unit air return, tenths of a degree. | INT16 | × 0.1 | °C | Read |
Notes on this map
- Gree does not host this protocol publicly; the link is the unaltered Gree PDF in the product-document store of the Finnish wholesaler Onninen (Kesko). No document number is printed; the date is the PDF creation date.
- Registers are read with function 03 and written with 16; coils are read with 01 and written with 15. Points marked R in the table are read-only.
- Only named points are listed; reserved words and bits are left out. Bits 237-239 have no name in the table and are left out.
- Mode and swing values are printed in binary in the source (for example 001 = cooling, 1011 = swing positions 1-3); they are given here as decimal.
- Left/right swing value 1100 (12) is printed only as '15 position'; the manual does not explain it, so the label is kept as printed.
- The outdoor-ambient range is printed as -100 to 155 in whole degrees and is listed as a signed 16-bit value as the table states.
- Several fault and status bits apply only to units that have that function (fresh-air valve, gate control, card switch, DRED).
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Gree Export residential split air conditioners (built-in Modbus on indoor unit / wired controller)
What Modbus registers does the Gree Export residential split air conditioners (built-in Modbus on indoor unit / wired controller) have?
This map lists 113 registers: 97 coils, 16 holding registers. 28 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Gree Export residential split air conditioners (built-in Modbus on indoor unit / wired controller) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Registers are words numbered from 0 and coils are bits numbered from 0 (Bit0 = Byte0.0). Word n is wire address n and Bit n is coil n. The example frames agree: reading ten bits from coil 5 sends start address 00 05, and reading two words from address 1 sends 00 01.
What are the minimum Modbus registers to integrate the Gree Export residential split air conditioners (built-in Modbus on indoor unit / wired controller)?
Start with HR 2 Unit On/Off (On/off); HR 17 Set mode (Mode); HR 19 Set fan speed (Fan speed); HR 20 Set temperature (Setpoint); HR 4 Ambient temperature (Room temperature); HR 49 Outdoor ambient temperature (Outdoor temperature); CO 151 Compressor status (Compressor running); CO 122 Communication failure with outdoor unit (Outdoor-unit communication fault).
How do I enable Modbus control of the Gree Export residential split air conditioners (built-in Modbus on indoor unit / wired controller)?
The Modbus interface is built into the indoor-unit controller or wired controller; each unit needs its own address (1-255) set before connecting the BMS. Power-cycle the unit after connecting the controller.
Where is the official Gree Export residential split air conditioners (built-in Modbus on indoor unit / wired controller) Modbus documentation?
The source is Modbus Protocol for export residential air conditioners, revision 2023-05. Gree doesn't publish it on its own website, so this map was re-typed from a free copy at https://kesko-onninen-pim-resources-production.s3-eu-west-1.amazonaws.com/pimdocuments/26148852.pdf. It may be an older revision, so check it against the live unit.
More Gree Modbus register maps
- VRF / split AC gateway
Gree Modbus Gateway (Mini) ME30-24/E6(M) for GMV multi VRF systems
Gree Modbus Gateway (Mini) on CAN-bus multi VRF systems (GMV5, GMV5 C/E/HR/MAX/MINI/SLIM, GMV Water, energy-recovery ventilation); Communication Protocol V2.0, multi VRF part only.
Also known as: ME30-24/E6(M), Modbus Gateway(Mini), GMV5 Modbus gateway - Split AC unit (VRF / split AC gateway built in)
Gree U-Match all-DC-inverter duct / cassette / floor-ceiling units (built-in Modbus)
Gree U-Match fourth-generation all-DC-inverter light-commercial units whose controller has the integrated Modbus RTU interface; Chinese-English protocol dated 2018-03-07.
Also known as: U-Match, Gree U-Match 4th generation DC inverter, U-Match BMS Modbus - Heat pump (air-to-water)
Gree Versati heat pump water heater (wired-controller Modbus RTU, protocol V1.5)
Gree Versati air-to-water heat pumps through the BMS port of the wired controller, per 'Modbus Protocol (V1.5) for the Versati Heat Pump Water Heater'. The document itself does not name a generation or refrigerant; the distributor files it as the R32 Versati III protocol.
Also known as: Versati III, R32 Versati, Versati heat pump water heater, Gree Versati Modbus V1.5
Other ac & vrf gateways register maps
- VRF / split AC gateway
Intesis (HMS Networks) IN770AIR***O000 700 Series Air Gateway, Midea application (Modbus)
Intesis 700 Series Air Gateway IN770AIR***O000 with the Midea application (XYE bus), Modbus RTU / TCP server, user manual version 1.0.22 (2025-12-09).
Also known as: IN770AIR00MO000, IN770AIR00SO000, IN770AIRXXSO000 - Lighting gateway (DALI-2 to Modbus)
Intesis (HMS Networks) INMBSDAL0640000 / INMBSDAL1280000 DALI-2 to Modbus RTU / TCP server
Intesis Modbus Server - DALI with one (0640000, RTU + TCP) or two (1280000, TCP only) DALI channels, Modbus Addresses parameter set to Fixed; user manual r1.2 (09/2021).
Also known as: INMBSDAL0640000, INMBSDAL1280000, Intesis Modbus Server - DALI, Intesis DALI-2 Modbus gateway - VRF / split AC gateway
Intesis (HMS Networks) INMBSHIT016O000 Hitachi VRF to Modbus RTU / TCP gateway (16 / 64 indoor units)
Intesis Modbus Server - Hitachi VRF, order codes INMBSHIT016O000 / INMBSHIT064O000 (legacy HI-AC-MBS-16 / HI-AC-MBS-64), user manual User Manual r1.2 EN.
Also known as: INMBSHIT016O000, INMBSHIT064O000, HI-AC-MBS-16, HI-AC-MBS-64, Intesis Modbus Server Hitachi VRF - VRF / split AC gateway
Intesis (HMS Networks) INMBSMIT001I000 Mitsubishi Electric AC to Modbus RTU gateway
One Mitsubishi Electric Domestic, Mr. Slim or City Multi indoor unit via INMBSMIT001I000, user manual r2.8 (11/2024).
Also known as: INMBSMIT001I000, Intesis Mitsubishi Electric Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSSAM001R100 Samsung NASA AC to Modbus RTU gateway
Samsung NASA-protocol commercial indoor units on the remote-controller bus, user's manual r1.4 (01/2024).
Also known as: INMBSSAM001R100, Intesis Samsung NASA Modbus - Chiller / heat pump gateway (VRF / split AC gateway)
Mitsubishi Electric MelcoBEMS MINI (A1M+) gateway for CAHV / CRHV / QAHV heat pumps and EAHV / EACV e-series chillers
Procon MelcoBEMS MINI (A1M+) firmware 4.1.0 on Mitsubishi Electric CAHV and CRHV heat pumps, QAHV CO2 heat pumps and EAHV / EACV e-series chillers (master and slave units); holding-register table only.
Also known as: A1M+, MelcoBEMS MINI, Procon A1M+, CAHV, CRHV, QAHV, EAHV, EACV, e-series chiller
All ac & vrf gateways Modbus register maps →
Source: Modbus Protocol for export residential air conditioners · rev. 2023-05 · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.