Split AC unit (VRF / split AC gateway built in) · Modbus register map

Gree U-Match all-DC-inverter duct / cassette / floor-ceiling units (built-in Modbus) Modbus register map

Updated 19 November 2026

Short answer

Gree U-Match units answer Modbus RTU from the indoor controller, so no gateway is needed. Holding registers carry on/off, mode, fan, setpoint, louvres, sleep, clean function and energy-saving limits plus indoor, return-air, display-board and outdoor temperatures; coils carry feature flags, locks, component status and indoor, outdoor and inverter-drive fault bits. Up to 255 units can share a BMS line.

This page lists 121 Modbus registers for the Gree U-Match all-DC-inverter duct / cassette / floor-ceiling units (built-in Modbus) — 31 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Gree’s own free documentation (linked below) and checked against it.

Manufacturer
Gree
Model
U-Match all-DC-inverter duct / cassette / floor-ceiling units (built-in Modbus)
Equipment type
Split AC unit (VRF / split AC gateway built in)
Registers
121 (31 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Default serial
9600 baud, 8N1
Documented addressing
0-based (the number printed is the address on the wire)
Also known as
U-Match, Gree U-Match 4th generation DC inverter, U-Match BMS Modbus
Source document
Modbus Protocal For All DC Inverter U-Match (U-Match BMS MODBUS) · rev. 2018-03-07 · unofficial copy
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Gree U-Match all-DC-inverter duct / cassette / floor-ceiling units (built-in Modbus)

Integration in brief

Poll words 2-36 for on/off, mode, fan, setpoint and louvres and words 4, 49 and 82 for temperatures; read coils 8-215 for status and faults. Write word 2 (0xAA on / 0x55 off), 17, 19 and 20 to control the unit.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 2Unit On/OffUINT16On/offRead/write
HR 17Set modeUINT16ModeRead/write
HR 19Set fan speedUINT16Fan speedRead/write
HR 20Set temperatureUINT16SetpointRead/write
HR 4Ambient temperatureINT16Room temperatureRead
HR 49Outdoor ambient temperatureINT16Outdoor temperatureRead
CO 151Compressor statusBITCompressor runningRead
CO 95Error output statusBITError outputRead

Enable Modbus control & writes

The Modbus interface is built into the unit controller; set each unit's address (1-255 in PC address mode) and power-cycle after changing the outdoor chip or DIP switches.

Byte order & addressing

Network setup

Watch out for

Gree U-Match all-DC-inverter duct / cassette / floor-ceiling units (built-in Modbus) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

121 of 121 shown
Gree U-Match all-DC-inverter duct / cassette / floor-ceiling units (built-in Modbus) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
CO8doc Bit8Outdoor unit presentBITRead0 = No; 1 = Yes
CO9doc Bit9Master wired controller presentBITRead0 = No; 1 = Yes
CO13doc Bit13Slave wired controller presentBITRead0 = No; 1 = Yes
CO17doc Bit17Remote lockUnit locked by remote monitoring or a hotel charging system.BITRead/write0 = Unlocked; 1 = Locked
CO18doc Bit18Remote temperature shieldName printed in Chinese only in the table.BITRead/write0 = Not shielded; 1 = Shielded
CO19doc Bit19Remote mode shieldBITRead/write0 = Not shielded; 1 = Shielded
CO20doc Bit20Remote On/Off shieldBITRead/write0 = Not shielded; 1 = Shielded
CO21doc Bit21Remote energy-saving shieldBITRead/write0 = Not shielded; 1 = Shielded
CO24doc Bit24Absence modeBITRead/write0 = Off; 1 = On
CO25doc Bit25Healthy functionBITRead/write0 = Off; 1 = On
CO26doc Bit26I-Demand energy-saving comfortBITRead/write0 = Off; 1 = On
CO27doc Bit27TurboBITRead/write0 = Off; 1 = On
CO28doc Bit28Electric heater permissionBITRead/write0 = Electric heater allowed; 1 = Electric heater not allowed
CO29doc Bit29X-fanBITRead/write0 = Off; 1 = On
CO30doc Bit30SilentBITRead/write0 = Off; 1 = On
CO31doc Bit31Low-temperature drying modeBITRead/write0 = Off; 1 = On
CO32doc Bit32Energy saving in cooling activeWrite together with bit 33.BITRead/write0 = Off; 1 = On
CO33doc Bit33Energy saving in heating activeWrite together with bit 32.BITRead/write0 = Off; 1 = On
CO34doc Bit34Button lock (child lock)BITRead/write0 = Off; 1 = On
CO35doc Bit35On/Off memoryWhether the unit restores its on/off state after power loss.BITRead/write0 = Memorize; 1 = Do not memorize
CO36doc Bit36°C/°F flagBITRead/write0 = °C; 1 = °F
CO40doc Bit40Timer statusBITRead0 = No timer; 1 = Timer set
CO46doc Bit46Gate control system fittedBITRead0 = No; 1 = Yes
CO47doc Bit47Human-presence sensor module fittedBITRead0 = No; 1 = Yes
CO49doc Bit49Timer On flagBITRead0 = Not active; 1 = Active
CO50doc Bit50Timer Off flagBITRead0 = Not active; 1 = Active
CO51doc Bit51Room temperature source in current modeBITRead0 = Return-air sensor; 1 = Wired-controller sensor
CO55doc Bit551 W low-standby control modeBITRead0 = Mode 1; 1 = Mode 2
CO65doc Bit65Wired controller temperature sensor errorBITRead0 = Normal; 1 = Fault
CO70doc Bit70Wired controller memory chip errorBITRead0 = Normal; 1 = Fault
CO72doc Bit72Cancel timerWrite 1 to cancel the timer.BITRead/write0 = Do not cancel; 1 = Cancel
CO74doc Bit74Up and down swing modeBITRead/write0 = Mode 1, simple swing; 1 = Mode 2, fixed angle and small-area swing
CO91doc Bit91Electric heatingBITRead0 = No; 1 = Yes
CO92doc Bit92Water pumpBITRead0 = Off; 1 = On
CO93doc Bit93Fresh air valve switchBITRead0 = Off; 1 = On
CO94doc Bit94Cold plasma generatorBITRead0 = Off; 1 = On
CO95doc Bit95Error output statusBITRead0 = No; 1 = Yes
CO97doc Bit97Indoor evaporator temperature sensor errorBITRead0 = Normal; 1 = Fault
CO98doc Bit98Indoor return-air temperature sensor errorBITRead0 = Normal; 1 = Fault
CO99doc Bit99Display board ambient sensor errorBITRead0 = Normal; 1 = Fault
CO101doc Bit101Water overflow protectionBITRead0 = Normal; 1 = Fault
CO102doc Bit102Indoor unit memory chip errorBITRead0 = Normal; 1 = Fault
CO104doc Bit104Jumper cap error (indoor)BITRead0 = Normal; 1 = Fault
CO105doc Bit105Indoor fan errorBITRead0 = Normal; 1 = Fault
CO108doc Bit108Unit needs cleaningBITRead0 = No; 1 = Yes
CO112doc Bit112Card in/out statusHotel key-card switch.BITRead0 = Card out; 1 = Card in
CO113doc Bit113Room occupiedFrom the human-presence sensor.BITRead0 = Nobody; 1 = Occupied
CO114doc Bit114Static pressure typeBITRead0 = Low static pressure; 1 = High static pressure
CO120doc Bit120Communication failure with master wired controllerBITRead0 = Normal; 1 = Fault
CO121doc Bit121Communication failure with slave wired controllerBITRead0 = Normal; 1 = Fault
CO122doc Bit122Communication failure with outdoor unitBITRead0 = Normal; 1 = Fault
CO147doc Bit147Outdoor fan statusBITRead0 = Off; 1 = On
CO150doc Bit1504-way valve statusBITRead0 = Off; 1 = On
CO151doc Bit151Compressor statusBITRead0 = Off; 1 = On
CO152doc Bit152Compressor discharge temperature protectionBITRead0 = Normal; 1 = Fault
CO153doc Bit153Refrigerant shortage protectionBITRead0 = Normal; 1 = Fault
CO154doc Bit154DC fan motor protectionBITRead0 = Normal; 1 = Fault
CO155doc Bit1554-way valve reversing errorName printed in Chinese only in the table.BITRead0 = Normal; 1 = Fault
CO156doc Bit156Overpower protectionBITRead0 = Normal; 1 = Fault
CO157doc Bit157Overload protectionBITRead0 = Normal; 1 = Fault
CO158doc Bit158Low pressure protectionBITRead0 = Normal; 1 = Fault
CO159doc Bit159High pressure protectionBITRead0 = Normal; 1 = Fault
CO160doc Bit160Evaporator anti-freeze protectionBITRead0 = Normal; 1 = Fault
CO161doc Bit161Outdoor ambient temperature sensor errorBITRead0 = Normal; 1 = Fault
CO162doc Bit162Discharge temperature sensor errorBITRead0 = Normal; 1 = Fault
CO163doc Bit163Condenser temperature sensor errorBITRead0 = Normal; 1 = Fault
CO164doc Bit164Outdoor heat-exchanger pipe sensor errorBITRead0 = Normal; 1 = Fault
CO165doc Bit165Jumper cap error (outdoor)BITRead0 = Normal; 1 = Fault
CO166doc Bit166Outdoor unit memory chip errorBITRead0 = Normal; 1 = Fault
CO174doc Bit174Drive communication failureBITRead0 = Normal; 1 = Fault
CO176doc Bit176SAVE statusBITRead0 = No; 1 = Yes
CO177doc Bit177Cooling-only flagHeating commands have no effect on cooling-only units.BITRead0 = Cooling and heating; 1 = Cooling only
CO179doc Bit179System defrostingBITRead0 = No; 1 = Yes
CO182doc Bit182Low power consumption statusBITRead0 = Not ready; 1 = Ready
CO183doc Bit183AC input phase-sequence protectionPhase loss or reversed phase.BITRead0 = Normal; 1 = Fault
CO184doc Bit184Drive DC bus undervoltage or voltage-drop errorBITRead0 = Normal; 1 = Fault
CO185doc Bit185Drive DC bus overvoltage protectionBITRead0 = Normal; 1 = Fault
CO186doc Bit186Drive AC input current protectionBITRead0 = Normal; 1 = Fault
CO187doc Bit187Drive IPM protectionBITRead0 = Normal; 1 = Fault
CO188doc Bit188Drive PFC protectionBITRead0 = Normal; 1 = Fault
CO189doc Bit189Inverter compressor start-up failureBITRead0 = Normal; 1 = Fault
CO190doc Bit190Inverter compressor phase-loss protectionBITRead0 = Normal; 1 = Fault
CO191doc Bit191Drive module resetBITRead0 = Normal; 1 = Fault
CO192doc Bit192Inverter compressor overcurrent protectionBITRead0 = Normal; 1 = Fault
CO193doc Bit193Inverter compressor power protectionBITRead0 = Normal; 1 = Fault
CO194doc Bit194Drive current-detection circuit failureBITRead0 = Normal; 1 = Fault
CO195doc Bit195Inverter compressor out-of-step protectionBITRead0 = Normal; 1 = Fault
CO196doc Bit196Compressor stallingBITRead0 = Normal; 1 = Fault
CO198doc Bit198Drive module high-temperature protectionBITRead0 = Normal; 1 = Fault
CO199doc Bit199Drive module temperature sensor failureBITRead0 = Normal; 1 = Fault
CO201doc Bit201Inverter compressor field weakeningBITRead0 = No field weakening; 1 = Field weakening active
CO202doc Bit202Drive frequency limitBITRead0 = Normal; 1 = Frequency limited
CO203doc Bit203Drive frequency reductionBITRead0 = Normal; 1 = Frequency reduced
CO204doc Bit204Drive AC input low-voltage frequency limitBITRead0 = Normal; 1 = Low-voltage limit active
CO205doc Bit205Drive charging incompleteBITRead0 = Charged; 1 = Not charged
CO207doc Bit207Drive AC input power typeBITRead0 = Single phase; 1 = Three phase
CO208doc Bit208Drive memory chip failureBITRead0 = Normal; 1 = Fault
CO210doc Bit210Drive charging circuit failureBITRead0 = Normal; 1 = Fault
CO211doc Bit211Drive AC input voltage abnormalBITRead0 = Normal; 1 = Fault
CO212doc Bit212Inverter compressor temperature sensor failureBITRead0 = Normal; 1 = Fault
CO213doc Bit213Drive AC input zero-crossing protectionBITRead0 = Normal; 1 = Fault
CO214doc Bit214Temperature drift protectionBITRead0 = Normal; 1 = Fault
CO215doc Bit215Current sensor connection protectionCurrent sensor not on the matching U or V phase.BITRead0 = Normal; 1 = Fault
HR2doc Word 2Unit On/OffWrite 0xAA (170) to switch on, 0x55 (85) to switch off.UINT16Read/write85 = Off; 170 = On
HR4doc Word 4Ambient temperatureIndoor ambient temperature in tenths of a degree.INT16× 0.1°CRead
HR5doc Word 5IDU address1-16 when a central controller is used, 1-255 in PC address mode.UINT16Read
HR17doc Word 17Set modeUINT16Read/write1 = Cooling; 2 = Heating; 3 = Drying; 4 = Fan only; 5 = Auto
HR19doc Word 19Set fan speedUINT16Read/write0 = Auto; 1 = Speed 1; 2 = Speed 2; 3 = Speed 3; 4 = Speed 4; 5 = Speed 5; 6 = Turbo
HR20doc Word 20Set temperature16-30; reads 12 in low-temperature drying and 8 in absence mode.UINT16°CRead/write
HR22doc Word 22Up and down swingVertical louvre: off, fixed position or swing between two positions.UINT16Read/write0 = Off; 1 = Swing positions 1-5; 2 = Position 1; 3 = Position 2; 4 = Position 3; 5 = Position 4; 6 = Position 5; 7 = Swing positions 3-5; 8 = Swing positions 2-5; 9 = Swing positions 2-4; 10 = Swing positions 1-4; 11 = Swing positions 1-3
HR23doc Word 23Left and right swingHorizontal louvre; off is the default after power-up.UINT16Read/write0 = Off; 1 = Swing in same direction; 2 = Position 1; 3 = Position 2; 4 = Position 3; 5 = Position 4; 6 = Position 5; 12 = Printed as "15 position" (meaning not explained); 13 = Swing in opposite direction
HR24doc Word 24Fresh air valveFresh-air valve mode 0-10.UINT16Read/write
HR25doc Word 25Sleep modeUINT16Read/write0 = No sleep; 1 = Sleep mode 1; 2 = Sleep mode 2; 3 = Sleep mode 3
HR34doc Word 34Clean function0 = no clean function; 10-39 = contamination grade.UINT16Read/write
HR35doc Word 35Cooling energy-saving lower limitLowest setpoint allowed in cooling while energy saving is active, 16-30.UINT16°CRead/write
HR36doc Word 36Heating energy-saving upper limitHighest setpoint allowed in heating while energy saving is active, 16-30.UINT16°CRead/write
HR39doc Word 39Ambient sensor selectionWhich sensor gives room temperature.UINT16Read1 = Return-air sensor; 2 = Wired-controller sensor; 3 = Return air in cool/dry/fan, wired controller in heat/auto
HR49doc Word 49Outdoor ambient temperatureWhole degrees.INT16°CRead
HR77doc Word 77DRED functionDemand-response mode.UINT16Read0 = No DRED; 1 = DRED 1; 2 = DRED 2; 3 = DRED 3
HR82doc Word 82Return-air temperatureTemperature at the indoor-unit air return, tenths of a degree.INT16× 0.1°CRead
HR83doc Word 83Display board ambient temperatureAmbient temperature at the light (display) board, tenths of a degree.INT16× 0.1°CRead

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Gree U-Match all-DC-inverter duct / cassette / floor-ceiling units (built-in Modbus)

What Modbus registers does the Gree U-Match all-DC-inverter duct / cassette / floor-ceiling units (built-in Modbus) have?

This map lists 121 registers: 103 coils, 18 holding registers. 31 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Gree U-Match all-DC-inverter duct / cassette / floor-ceiling units (built-in Modbus) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Registers are words numbered from 0 and coils are bits numbered from 0 (Bit0 = Byte0.0). Word n is wire address n and Bit n is coil n; the protocol's example frames read coils from start address 00 05 for coil 5 and words from 00 01 for word 1.

What are the minimum Modbus registers to integrate the Gree U-Match all-DC-inverter duct / cassette / floor-ceiling units (built-in Modbus)?

Start with HR 2 Unit On/Off (On/off); HR 17 Set mode (Mode); HR 19 Set fan speed (Fan speed); HR 20 Set temperature (Setpoint); HR 4 Ambient temperature (Room temperature); HR 49 Outdoor ambient temperature (Outdoor temperature); CO 151 Compressor status (Compressor running); CO 95 Error output status (Error output).

How do I enable Modbus control of the Gree U-Match all-DC-inverter duct / cassette / floor-ceiling units (built-in Modbus)?

The Modbus interface is built into the unit controller; set each unit's address (1-255 in PC address mode) and power-cycle after changing the outdoor chip or DIP switches.

Where is the official Gree U-Match all-DC-inverter duct / cassette / floor-ceiling units (built-in Modbus) Modbus documentation?

The source is Modbus Protocal For All DC Inverter U-Match (U-Match BMS MODBUS), revision 2018-03-07. Gree doesn't publish it on its own website, so this map was re-typed from a free copy at https://man.kievclimate.com/man/Gree/U-Match/U-Match%20BMS%20MODBUS%202018.03.07.pdf. It may be an older revision, so check it against the live unit.

More Gree Modbus register maps

Other ac & vrf gateways register maps

All ac & vrf gateways Modbus register maps →

Source: Modbus Protocal For All DC Inverter U-Match (U-Match BMS MODBUS) · rev. 2018-03-07 · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.