- U-Match all-DC-inverter duct / cassette / floor-ceiling units (built-in Modbus)
Split AC unit (VRF / split AC gateway built in) · Modbus register map
Gree U-Match all-DC-inverter duct / cassette / floor-ceiling units (built-in Modbus) Modbus register map
Updated 19 November 2026
Gree U-Match units answer Modbus RTU from the indoor controller, so no gateway is needed. Holding registers carry on/off, mode, fan, setpoint, louvres, sleep, clean function and energy-saving limits plus indoor, return-air, display-board and outdoor temperatures; coils carry feature flags, locks, component status and indoor, outdoor and inverter-drive fault bits. Up to 255 units can share a BMS line.
This page lists 121 Modbus registers for the Gree U-Match all-DC-inverter duct / cassette / floor-ceiling units (built-in Modbus) — 31 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Gree’s own free documentation (linked below) and checked against it.
- Manufacturer
- Gree
- Model
- U-Match all-DC-inverter duct / cassette / floor-ceiling units (built-in Modbus)
- Equipment type
- Split AC unit (VRF / split AC gateway built in)
- Registers
- 121 (31 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Default serial
- 9600 baud, 8N1
- Documented addressing
- 0-based (the number printed is the address on the wire)
- Also known as
- U-Match, Gree U-Match 4th generation DC inverter, U-Match BMS Modbus
Integration notes: Gree U-Match all-DC-inverter duct / cassette / floor-ceiling units (built-in Modbus)
Poll words 2-36 for on/off, mode, fan, setpoint and louvres and words 4, 49 and 82 for temperatures; read coils 8-215 for status and faults. Write word 2 (0xAA on / 0x55 off), 17, 19 and 20 to control the unit.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 2 | Unit On/Off | UINT16 | On/off | Read/write |
| HR 17 | Set mode | UINT16 | Mode | Read/write |
| HR 19 | Set fan speed | UINT16 | Fan speed | Read/write |
| HR 20 | Set temperature | UINT16 | Setpoint | Read/write |
| HR 4 | Ambient temperature | INT16 | Room temperature | Read |
| HR 49 | Outdoor ambient temperature | INT16 | Outdoor temperature | Read |
| CO 151 | Compressor status | BIT | Compressor running | Read |
| CO 95 | Error output status | BIT | Error output | Read |
Enable Modbus control & writes
The Modbus interface is built into the unit controller; set each unit's address (1-255 in PC address mode) and power-cycle after changing the outdoor chip or DIP switches.
Byte order & addressing
- On/off uses 0xAA and 0x55, not 1 and 0.
- Energy-saving bits 32 and 33 must be written together.
- Exception code 04 means the interface has lost contact with the air conditioner.
Network setup
- RS485, 9600 baud, 8 data bits, no parity, 1 stop bit.
- Twisted pair at least 15 cm from power cables; use repeaters on long lines; A to A, B to B.
Watch out for
- Setpoints outside an active energy-saving limit are ignored; read back after writing.
- With a central controller connected the address range is only 1-16.
Gree U-Match all-DC-inverter duct / cassette / floor-ceiling units (built-in Modbus) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| CO | 8doc Bit8 | Outdoor unit present | BIT | Read | 0 = No; 1 = Yes | ||||
| CO | 9doc Bit9 | Master wired controller present | BIT | Read | 0 = No; 1 = Yes | ||||
| CO | 13doc Bit13 | Slave wired controller present | BIT | Read | 0 = No; 1 = Yes | ||||
| CO | 17doc Bit17 | Remote lock | Unit locked by remote monitoring or a hotel charging system. | BIT | Read/write | 0 = Unlocked; 1 = Locked | |||
| CO | 18doc Bit18 | Remote temperature shield | Name printed in Chinese only in the table. | BIT | Read/write | 0 = Not shielded; 1 = Shielded | |||
| CO | 19doc Bit19 | Remote mode shield | BIT | Read/write | 0 = Not shielded; 1 = Shielded | ||||
| CO | 20doc Bit20 | Remote On/Off shield | BIT | Read/write | 0 = Not shielded; 1 = Shielded | ||||
| CO | 21doc Bit21 | Remote energy-saving shield | BIT | Read/write | 0 = Not shielded; 1 = Shielded | ||||
| CO | 24doc Bit24 | Absence mode | BIT | Read/write | 0 = Off; 1 = On | ||||
| CO | 25doc Bit25 | Healthy function | BIT | Read/write | 0 = Off; 1 = On | ||||
| CO | 26doc Bit26 | I-Demand energy-saving comfort | BIT | Read/write | 0 = Off; 1 = On | ||||
| CO | 27doc Bit27 | Turbo | BIT | Read/write | 0 = Off; 1 = On | ||||
| CO | 28doc Bit28 | Electric heater permission | BIT | Read/write | 0 = Electric heater allowed; 1 = Electric heater not allowed | ||||
| CO | 29doc Bit29 | X-fan | BIT | Read/write | 0 = Off; 1 = On | ||||
| CO | 30doc Bit30 | Silent | BIT | Read/write | 0 = Off; 1 = On | ||||
| CO | 31doc Bit31 | Low-temperature drying mode | BIT | Read/write | 0 = Off; 1 = On | ||||
| CO | 32doc Bit32 | Energy saving in cooling active | Write together with bit 33. | BIT | Read/write | 0 = Off; 1 = On | |||
| CO | 33doc Bit33 | Energy saving in heating active | Write together with bit 32. | BIT | Read/write | 0 = Off; 1 = On | |||
| CO | 34doc Bit34 | Button lock (child lock) | BIT | Read/write | 0 = Off; 1 = On | ||||
| CO | 35doc Bit35 | On/Off memory | Whether the unit restores its on/off state after power loss. | BIT | Read/write | 0 = Memorize; 1 = Do not memorize | |||
| CO | 36doc Bit36 | °C/°F flag | BIT | Read/write | 0 = °C; 1 = °F | ||||
| CO | 40doc Bit40 | Timer status | BIT | Read | 0 = No timer; 1 = Timer set | ||||
| CO | 46doc Bit46 | Gate control system fitted | BIT | Read | 0 = No; 1 = Yes | ||||
| CO | 47doc Bit47 | Human-presence sensor module fitted | BIT | Read | 0 = No; 1 = Yes | ||||
| CO | 49doc Bit49 | Timer On flag | BIT | Read | 0 = Not active; 1 = Active | ||||
| CO | 50doc Bit50 | Timer Off flag | BIT | Read | 0 = Not active; 1 = Active | ||||
| CO | 51doc Bit51 | Room temperature source in current mode | BIT | Read | 0 = Return-air sensor; 1 = Wired-controller sensor | ||||
| CO | 55doc Bit55 | 1 W low-standby control mode | BIT | Read | 0 = Mode 1; 1 = Mode 2 | ||||
| CO | 65doc Bit65 | Wired controller temperature sensor error | BIT | Read | 0 = Normal; 1 = Fault | ||||
| CO | 70doc Bit70 | Wired controller memory chip error | BIT | Read | 0 = Normal; 1 = Fault | ||||
| CO | 72doc Bit72 | Cancel timer | Write 1 to cancel the timer. | BIT | Read/write | 0 = Do not cancel; 1 = Cancel | |||
| CO | 74doc Bit74 | Up and down swing mode | BIT | Read/write | 0 = Mode 1, simple swing; 1 = Mode 2, fixed angle and small-area swing | ||||
| CO | 91doc Bit91 | Electric heating | BIT | Read | 0 = No; 1 = Yes | ||||
| CO | 92doc Bit92 | Water pump | BIT | Read | 0 = Off; 1 = On | ||||
| CO | 93doc Bit93 | Fresh air valve switch | BIT | Read | 0 = Off; 1 = On | ||||
| CO | 94doc Bit94 | Cold plasma generator | BIT | Read | 0 = Off; 1 = On | ||||
| CO | 95doc Bit95 | Error output status | BIT | Read | 0 = No; 1 = Yes | ||||
| CO | 97doc Bit97 | Indoor evaporator temperature sensor error | BIT | Read | 0 = Normal; 1 = Fault | ||||
| CO | 98doc Bit98 | Indoor return-air temperature sensor error | BIT | Read | 0 = Normal; 1 = Fault | ||||
| CO | 99doc Bit99 | Display board ambient sensor error | BIT | Read | 0 = Normal; 1 = Fault | ||||
| CO | 101doc Bit101 | Water overflow protection | BIT | Read | 0 = Normal; 1 = Fault | ||||
| CO | 102doc Bit102 | Indoor unit memory chip error | BIT | Read | 0 = Normal; 1 = Fault | ||||
| CO | 104doc Bit104 | Jumper cap error (indoor) | BIT | Read | 0 = Normal; 1 = Fault | ||||
| CO | 105doc Bit105 | Indoor fan error | BIT | Read | 0 = Normal; 1 = Fault | ||||
| CO | 108doc Bit108 | Unit needs cleaning | BIT | Read | 0 = No; 1 = Yes | ||||
| CO | 112doc Bit112 | Card in/out status | Hotel key-card switch. | BIT | Read | 0 = Card out; 1 = Card in | |||
| CO | 113doc Bit113 | Room occupied | From the human-presence sensor. | BIT | Read | 0 = Nobody; 1 = Occupied | |||
| CO | 114doc Bit114 | Static pressure type | BIT | Read | 0 = Low static pressure; 1 = High static pressure | ||||
| CO | 120doc Bit120 | Communication failure with master wired controller | BIT | Read | 0 = Normal; 1 = Fault | ||||
| CO | 121doc Bit121 | Communication failure with slave wired controller | BIT | Read | 0 = Normal; 1 = Fault | ||||
| CO | 122doc Bit122 | Communication failure with outdoor unit | BIT | Read | 0 = Normal; 1 = Fault | ||||
| CO | 147doc Bit147 | Outdoor fan status | BIT | Read | 0 = Off; 1 = On | ||||
| CO | 150doc Bit150 | 4-way valve status | BIT | Read | 0 = Off; 1 = On | ||||
| CO | 151doc Bit151 | Compressor status | BIT | Read | 0 = Off; 1 = On | ||||
| CO | 152doc Bit152 | Compressor discharge temperature protection | BIT | Read | 0 = Normal; 1 = Fault | ||||
| CO | 153doc Bit153 | Refrigerant shortage protection | BIT | Read | 0 = Normal; 1 = Fault | ||||
| CO | 154doc Bit154 | DC fan motor protection | BIT | Read | 0 = Normal; 1 = Fault | ||||
| CO | 155doc Bit155 | 4-way valve reversing error | Name printed in Chinese only in the table. | BIT | Read | 0 = Normal; 1 = Fault | |||
| CO | 156doc Bit156 | Overpower protection | BIT | Read | 0 = Normal; 1 = Fault | ||||
| CO | 157doc Bit157 | Overload protection | BIT | Read | 0 = Normal; 1 = Fault | ||||
| CO | 158doc Bit158 | Low pressure protection | BIT | Read | 0 = Normal; 1 = Fault | ||||
| CO | 159doc Bit159 | High pressure protection | BIT | Read | 0 = Normal; 1 = Fault | ||||
| CO | 160doc Bit160 | Evaporator anti-freeze protection | BIT | Read | 0 = Normal; 1 = Fault | ||||
| CO | 161doc Bit161 | Outdoor ambient temperature sensor error | BIT | Read | 0 = Normal; 1 = Fault | ||||
| CO | 162doc Bit162 | Discharge temperature sensor error | BIT | Read | 0 = Normal; 1 = Fault | ||||
| CO | 163doc Bit163 | Condenser temperature sensor error | BIT | Read | 0 = Normal; 1 = Fault | ||||
| CO | 164doc Bit164 | Outdoor heat-exchanger pipe sensor error | BIT | Read | 0 = Normal; 1 = Fault | ||||
| CO | 165doc Bit165 | Jumper cap error (outdoor) | BIT | Read | 0 = Normal; 1 = Fault | ||||
| CO | 166doc Bit166 | Outdoor unit memory chip error | BIT | Read | 0 = Normal; 1 = Fault | ||||
| CO | 174doc Bit174 | Drive communication failure | BIT | Read | 0 = Normal; 1 = Fault | ||||
| CO | 176doc Bit176 | SAVE status | BIT | Read | 0 = No; 1 = Yes | ||||
| CO | 177doc Bit177 | Cooling-only flag | Heating commands have no effect on cooling-only units. | BIT | Read | 0 = Cooling and heating; 1 = Cooling only | |||
| CO | 179doc Bit179 | System defrosting | BIT | Read | 0 = No; 1 = Yes | ||||
| CO | 182doc Bit182 | Low power consumption status | BIT | Read | 0 = Not ready; 1 = Ready | ||||
| CO | 183doc Bit183 | AC input phase-sequence protection | Phase loss or reversed phase. | BIT | Read | 0 = Normal; 1 = Fault | |||
| CO | 184doc Bit184 | Drive DC bus undervoltage or voltage-drop error | BIT | Read | 0 = Normal; 1 = Fault | ||||
| CO | 185doc Bit185 | Drive DC bus overvoltage protection | BIT | Read | 0 = Normal; 1 = Fault | ||||
| CO | 186doc Bit186 | Drive AC input current protection | BIT | Read | 0 = Normal; 1 = Fault | ||||
| CO | 187doc Bit187 | Drive IPM protection | BIT | Read | 0 = Normal; 1 = Fault | ||||
| CO | 188doc Bit188 | Drive PFC protection | BIT | Read | 0 = Normal; 1 = Fault | ||||
| CO | 189doc Bit189 | Inverter compressor start-up failure | BIT | Read | 0 = Normal; 1 = Fault | ||||
| CO | 190doc Bit190 | Inverter compressor phase-loss protection | BIT | Read | 0 = Normal; 1 = Fault | ||||
| CO | 191doc Bit191 | Drive module reset | BIT | Read | 0 = Normal; 1 = Fault | ||||
| CO | 192doc Bit192 | Inverter compressor overcurrent protection | BIT | Read | 0 = Normal; 1 = Fault | ||||
| CO | 193doc Bit193 | Inverter compressor power protection | BIT | Read | 0 = Normal; 1 = Fault | ||||
| CO | 194doc Bit194 | Drive current-detection circuit failure | BIT | Read | 0 = Normal; 1 = Fault | ||||
| CO | 195doc Bit195 | Inverter compressor out-of-step protection | BIT | Read | 0 = Normal; 1 = Fault | ||||
| CO | 196doc Bit196 | Compressor stalling | BIT | Read | 0 = Normal; 1 = Fault | ||||
| CO | 198doc Bit198 | Drive module high-temperature protection | BIT | Read | 0 = Normal; 1 = Fault | ||||
| CO | 199doc Bit199 | Drive module temperature sensor failure | BIT | Read | 0 = Normal; 1 = Fault | ||||
| CO | 201doc Bit201 | Inverter compressor field weakening | BIT | Read | 0 = No field weakening; 1 = Field weakening active | ||||
| CO | 202doc Bit202 | Drive frequency limit | BIT | Read | 0 = Normal; 1 = Frequency limited | ||||
| CO | 203doc Bit203 | Drive frequency reduction | BIT | Read | 0 = Normal; 1 = Frequency reduced | ||||
| CO | 204doc Bit204 | Drive AC input low-voltage frequency limit | BIT | Read | 0 = Normal; 1 = Low-voltage limit active | ||||
| CO | 205doc Bit205 | Drive charging incomplete | BIT | Read | 0 = Charged; 1 = Not charged | ||||
| CO | 207doc Bit207 | Drive AC input power type | BIT | Read | 0 = Single phase; 1 = Three phase | ||||
| CO | 208doc Bit208 | Drive memory chip failure | BIT | Read | 0 = Normal; 1 = Fault | ||||
| CO | 210doc Bit210 | Drive charging circuit failure | BIT | Read | 0 = Normal; 1 = Fault | ||||
| CO | 211doc Bit211 | Drive AC input voltage abnormal | BIT | Read | 0 = Normal; 1 = Fault | ||||
| CO | 212doc Bit212 | Inverter compressor temperature sensor failure | BIT | Read | 0 = Normal; 1 = Fault | ||||
| CO | 213doc Bit213 | Drive AC input zero-crossing protection | BIT | Read | 0 = Normal; 1 = Fault | ||||
| CO | 214doc Bit214 | Temperature drift protection | BIT | Read | 0 = Normal; 1 = Fault | ||||
| CO | 215doc Bit215 | Current sensor connection protection | Current sensor not on the matching U or V phase. | BIT | Read | 0 = Normal; 1 = Fault | |||
| HR | 2doc Word 2 | Unit On/Off | Write 0xAA (170) to switch on, 0x55 (85) to switch off. | UINT16 | Read/write | 85 = Off; 170 = On | |||
| HR | 4doc Word 4 | Ambient temperature | Indoor ambient temperature in tenths of a degree. | INT16 | × 0.1 | °C | Read | ||
| HR | 5doc Word 5 | IDU address | 1-16 when a central controller is used, 1-255 in PC address mode. | UINT16 | Read | ||||
| HR | 17doc Word 17 | Set mode | UINT16 | Read/write | 1 = Cooling; 2 = Heating; 3 = Drying; 4 = Fan only; 5 = Auto | ||||
| HR | 19doc Word 19 | Set fan speed | UINT16 | Read/write | 0 = Auto; 1 = Speed 1; 2 = Speed 2; 3 = Speed 3; 4 = Speed 4; 5 = Speed 5; 6 = Turbo | ||||
| HR | 20doc Word 20 | Set temperature | 16-30; reads 12 in low-temperature drying and 8 in absence mode. | UINT16 | °C | Read/write | |||
| HR | 22doc Word 22 | Up and down swing | Vertical louvre: off, fixed position or swing between two positions. | UINT16 | Read/write | 0 = Off; 1 = Swing positions 1-5; 2 = Position 1; 3 = Position 2; 4 = Position 3; 5 = Position 4; 6 = Position 5; 7 = Swing positions 3-5; 8 = Swing positions 2-5; 9 = Swing positions 2-4; 10 = Swing positions 1-4; 11 = Swing positions 1-3 | |||
| HR | 23doc Word 23 | Left and right swing | Horizontal louvre; off is the default after power-up. | UINT16 | Read/write | 0 = Off; 1 = Swing in same direction; 2 = Position 1; 3 = Position 2; 4 = Position 3; 5 = Position 4; 6 = Position 5; 12 = Printed as "15 position" (meaning not explained); 13 = Swing in opposite direction | |||
| HR | 24doc Word 24 | Fresh air valve | Fresh-air valve mode 0-10. | UINT16 | Read/write | ||||
| HR | 25doc Word 25 | Sleep mode | UINT16 | Read/write | 0 = No sleep; 1 = Sleep mode 1; 2 = Sleep mode 2; 3 = Sleep mode 3 | ||||
| HR | 34doc Word 34 | Clean function | 0 = no clean function; 10-39 = contamination grade. | UINT16 | Read/write | ||||
| HR | 35doc Word 35 | Cooling energy-saving lower limit | Lowest setpoint allowed in cooling while energy saving is active, 16-30. | UINT16 | °C | Read/write | |||
| HR | 36doc Word 36 | Heating energy-saving upper limit | Highest setpoint allowed in heating while energy saving is active, 16-30. | UINT16 | °C | Read/write | |||
| HR | 39doc Word 39 | Ambient sensor selection | Which sensor gives room temperature. | UINT16 | Read | 1 = Return-air sensor; 2 = Wired-controller sensor; 3 = Return air in cool/dry/fan, wired controller in heat/auto | |||
| HR | 49doc Word 49 | Outdoor ambient temperature | Whole degrees. | INT16 | °C | Read | |||
| HR | 77doc Word 77 | DRED function | Demand-response mode. | UINT16 | Read | 0 = No DRED; 1 = DRED 1; 2 = DRED 2; 3 = DRED 3 | |||
| HR | 82doc Word 82 | Return-air temperature | Temperature at the indoor-unit air return, tenths of a degree. | INT16 | × 0.1 | °C | Read | ||
| HR | 83doc Word 83 | Display board ambient temperature | Ambient temperature at the light (display) board, tenths of a degree. | INT16 | × 0.1 | °C | Read |
Notes on this map
- Gree does not host this protocol publicly. The link is the unaltered Gree PDF in the open document archive of Gree's Ukrainian distributor (the same file is also posted on the Wiren Board support forum). The date comes from the file name.
- Registers are read with function 03 and written with 16; coils are read with 01 and written with 15.
- Only named points are listed; reserved words and bits, and bits 216-247 (no name in the table), are left out.
- Bits 18, 155 and 196 have no English name in the table; their names are translated from the Chinese column.
- Many fault bits print the English legend '1: yes 0: on'; the Chinese column reads 1 = yes, 0 = no, so 0 is listed as normal.
- Mode and swing values are printed in binary (for example 001 = cooling); they are given here as decimal. Left/right value 1100 (12) is printed only as '15 position' and is kept as printed.
- The outdoor-ambient range is printed as -100 to 155 in whole degrees, signed.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Gree U-Match all-DC-inverter duct / cassette / floor-ceiling units (built-in Modbus)
What Modbus registers does the Gree U-Match all-DC-inverter duct / cassette / floor-ceiling units (built-in Modbus) have?
This map lists 121 registers: 103 coils, 18 holding registers. 31 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Gree U-Match all-DC-inverter duct / cassette / floor-ceiling units (built-in Modbus) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Registers are words numbered from 0 and coils are bits numbered from 0 (Bit0 = Byte0.0). Word n is wire address n and Bit n is coil n; the protocol's example frames read coils from start address 00 05 for coil 5 and words from 00 01 for word 1.
What are the minimum Modbus registers to integrate the Gree U-Match all-DC-inverter duct / cassette / floor-ceiling units (built-in Modbus)?
Start with HR 2 Unit On/Off (On/off); HR 17 Set mode (Mode); HR 19 Set fan speed (Fan speed); HR 20 Set temperature (Setpoint); HR 4 Ambient temperature (Room temperature); HR 49 Outdoor ambient temperature (Outdoor temperature); CO 151 Compressor status (Compressor running); CO 95 Error output status (Error output).
How do I enable Modbus control of the Gree U-Match all-DC-inverter duct / cassette / floor-ceiling units (built-in Modbus)?
The Modbus interface is built into the unit controller; set each unit's address (1-255 in PC address mode) and power-cycle after changing the outdoor chip or DIP switches.
Where is the official Gree U-Match all-DC-inverter duct / cassette / floor-ceiling units (built-in Modbus) Modbus documentation?
The source is Modbus Protocal For All DC Inverter U-Match (U-Match BMS MODBUS), revision 2018-03-07. Gree doesn't publish it on its own website, so this map was re-typed from a free copy at https://man.kievclimate.com/man/Gree/U-Match/U-Match%20BMS%20MODBUS%202018.03.07.pdf. It may be an older revision, so check it against the live unit.
More Gree Modbus register maps
- Split AC unit (VRF / split AC gateway built in)
Gree Export residential split air conditioners (built-in Modbus on indoor unit / wired controller)
Gree export residential air conditioners whose indoor-unit controller or wired controller has the integrated Modbus RTU interface; protocol PDF dated 2023-05.
Also known as: Gree residential split Modbus, Gree wall split Modbus, Gree wired controller Modbus - VRF / split AC gateway
Gree Modbus Gateway (Mini) ME30-24/E6(M) for GMV multi VRF systems
Gree Modbus Gateway (Mini) on CAN-bus multi VRF systems (GMV5, GMV5 C/E/HR/MAX/MINI/SLIM, GMV Water, energy-recovery ventilation); Communication Protocol V2.0, multi VRF part only.
Also known as: ME30-24/E6(M), Modbus Gateway(Mini), GMV5 Modbus gateway - Heat pump (air-to-water)
Gree Versati heat pump water heater (wired-controller Modbus RTU, protocol V1.5)
Gree Versati air-to-water heat pumps through the BMS port of the wired controller, per 'Modbus Protocol (V1.5) for the Versati Heat Pump Water Heater'. The document itself does not name a generation or refrigerant; the distributor files it as the R32 Versati III protocol.
Also known as: Versati III, R32 Versati, Versati heat pump water heater, Gree Versati Modbus V1.5
Other ac & vrf gateways register maps
- VRF / split AC gateway
Intesis (HMS Networks) IN770AIR***O000 700 Series Air Gateway, Panasonic application (Modbus)
Intesis 700 Series Air Gateway IN770AIR***O000 with the Panasonic application (U1U2 P-Link / S-Link), Modbus RTU / TCP server, user manual version 1.1.7 (2025-12-09).
Also known as: IN770AIR00MO000, IN770AIR00SO000, IN770AIRXXSO000 - VRF / split AC gateway
Intesis (HMS Networks) INMBSFGL001R000 Fujitsu AC to Modbus RTU gateway
One Fujitsu indoor unit, or a group of up to 16 controlled together as one, on the 3-wire BWR remote-controller bus via INMBSFGL001R000, user manual v2.4 (02/2025).
Also known as: INMBSFGL001R000, Intesis Fujitsu Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSLGE016O000 LG VRF to Modbus RTU / TCP gateway (16 / 64 indoor units)
Intesis Modbus - LG VRF, order codes INMBSLGE016O000 / INMBSLGE064O000 (legacy LG-AC-MBS-16 / -64), user manual r1.0 (04/2020); LG PI485 bus.
Also known as: INMBSLGE016O000, INMBSLGE064O000, LG-AC-MBS-16, LG-AC-MBS-64, Intesis Modbus LG VRF - Heat pump gateway (VRF / split AC gateway)
Intesis (HMS Networks) INMBSPAN001A100 Panasonic Aquarea H/J/K/L/M air-to-water to Modbus RTU gateway
Intesis (HMS Networks) INMBSPAN001A100 gateway connected to Panasonic Aquarea H, J, K, L and M series air-to-water heat pumps, per user manual version 1.0.2 (2026-02-04).
Also known as: INMBSPAN001A100, Aquarea Modbus, Panasonic Aquarea Modbus RTU, Intesis Aquarea, INMBSPAN001A000 (legacy order code) - VRF / split AC gateway
Intesis (HMS Networks) INMBSTOS001R000 Toshiba AC to Modbus RTU gateway
Toshiba Digital Inverter (RAV) and VRF indoor units on the AB remote bus via INMBSTOS001R0xx, user manual r2.9 (01/2024).
Also known as: INMBSTOS001R000, INMBSTOS001R0xx, Intesis Toshiba Modbus - Air handler DX interface (VRF / split AC gateway)
Mitsubishi Electric PAC-IF013B-E / PAC-SIF013B-E air handling unit interface (Modbus RTU)
PAC-IF013B-E and PAC-SIF013B-E interface controllers linking a Mitsubishi Electric outdoor unit to an AHU coil, Modbus manual dated September 2015 (RG79F084H01).
Also known as: PAC-IF013B-E, PAC-SIF013B-E, PAC-(S)IF013B-E
All ac & vrf gateways Modbus register maps →
Source: Modbus Protocal For All DC Inverter U-Match (U-Match BMS MODBUS) · rev. 2018-03-07 · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.