VRF / split AC gateway · Modbus register map

Gree Modbus Gateway (Mini) ME30-24/E6(M) for GMV multi VRF systems Modbus register map

Updated 19 November 2026

Short answer

The Gree Modbus Gateway (Mini) sits on the CAN bus of a GMV multi VRF system and serves up to 16 outdoor systems and 128 indoor units to a BMS over Modbus RTU. Holding registers carry per-indoor-unit on/off, mode, setpoint, fan speed and temperatures plus per-system outdoor data; coils carry feature flags, shields, locks and fault bits. Every indoor unit and system has an identical block, so this map lists indoor unit 1 and system 1 and gives the address rule for the rest.

This page lists 65 Modbus registers for the Gree Modbus Gateway (Mini) ME30-24/E6(M) for GMV multi VRF systems — 38 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Gree’s own free documentation (linked below) and checked against it.

Manufacturer
Gree
Model
Modbus Gateway (Mini) ME30-24/E6(M) for GMV multi VRF systems
Equipment type
VRF / split AC gateway
Registers
65 (38 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Default serial
9600 baud, 8N1
Documented addressing
0-based (the number printed is the address on the wire)
Also known as
ME30-24/E6(M), Modbus Gateway(Mini), GMV5 Modbus gateway
Source document
Modbus Gateway(Mini) Communication Protocol V2.0 · V2.0 · unofficial copy
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Gree Modbus Gateway (Mini) ME30-24/E6(M) for GMV multi VRF systems

Integration in brief

Set the gateway address on DIP switches S1/S2, wire RS485 at 9600 8N1, then read coils from 120 to see which indoor units exist. Control each unit with its on/off, mode, setpoint and fan words (102-105 for unit 1) using function 0x10, and read fault coils 318-319 and system coils 8488-8495.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 102IDU 1 power on/offUINT16IDU 1 on/offRead/write
HR 103IDU 1 operation modeUINT16IDU 1 modeRead/write
HR 104IDU 1 temperature setpointUINT16IDU 1 setpointRead/write
HR 105IDU 1 fan speedUINT16IDU 1 fan speedRead/write
CO 120IDU 1 presentBITIDU 1 presentRead
CO 319IDU 1 general errorBITIDU 1 general errorRead
CO 8495System 1 general outdoor unit errorBITSystem 1 outdoor errorRead
CO 8494System 1 compressor operation statusBITSystem 1 compressor runningRead

Enable Modbus control & writes

No software enable: set the Modbus address (1-255) on DIP switches S1 and S2 inside the gateway, and S3 switch 4 for the CAN2 terminating resistor, before use.

Byte order & addressing

Network setup

Watch out for

Gree Modbus Gateway (Mini) ME30-24/E6(M) for GMV multi VRF systems Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

65 of 65 shown
Gree Modbus Gateway (Mini) ME30-24/E6(M) for GMV multi VRF systems Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
CO88doc Bit 88System 1 presentBITRead0 = Without; 1 = With
CO120doc Bit 120IDU 1 presentBITRead0 = Without; 1 = With
CO248doc Bit 248System 1 remote emergency stopBITRead/write0 = Off; 1 = On
CO280doc Bit 280Set all IDUs onGroup command.BITWrite0 = No; 1 = Yes
CO281doc Bit 281Set all IDUs offGroup command.BITWrite0 = No; 1 = Yes
CO282doc Bit 282Set all IDUs remotely lockedGroup command.BITWrite0 = No; 1 = Yes
CO288doc Bit 288IDU 1 remote shield: energy savingBITRead/write0 = Not shielded; 1 = Shielded
CO289doc Bit 289IDU 1 remote shield: temperature settingBITRead/write0 = Not shielded; 1 = Shielded
CO290doc Bit 290IDU 1 remote shield: modeBITRead/write0 = Not shielded; 1 = Shielded
CO291doc Bit 291IDU 1 remote shield: on/offBITRead/write0 = Not shielded; 1 = Shielded
CO292doc Bit 292IDU 1 remote lockBITRead/write0 = Unlocked; 1 = Locked
CO293doc Bit 293IDU 1 priority power supplyUsed in the power-shortage mode of the supply system.BITRead/write0 = No; 1 = Yes
CO294doc Bit 294IDU 1 up-down swingBITRead/write0 = Off; 1 = On
CO295doc Bit 295IDU 1 left-right swingBITRead/write0 = Off; 1 = On
CO296doc Bit 296IDU 1 energy savingBITRead/write0 = Off; 1 = On
CO297doc Bit 297IDU 1 forbid auxiliary heaterBITRead/write0 = Auxiliary heater allowed; 1 = Auxiliary heater forbidden
CO298doc Bit 298IDU 1 power failure memoryBITRead/write0 = Standby after power loss; 1 = Power failure memory
CO299doc Bit 299IDU 1 cancel filter cleaning reminderBITRead/write0 = No; 1 = Yes
CO300doc Bit 300IDU 1 dry (X-fan)BITRead/write0 = Off; 1 = On
CO301doc Bit 301IDU 1 sleepBITRead/write0 = Off; 1 = On
CO302doc Bit 302IDU 1 quietBITRead/write0 = Off; 1 = On
CO303doc Bit 303IDU 1 ventilation (air)BITRead/write0 = Off; 1 = On
CO304doc Bit 304IDU 1 low-temperature dehumidificationBITRead/write0 = Cancel; 1 = Start
CO305doc Bit 305IDU 1 shield on commandBITRead/write0 = No shielding; 1 = Shielding
CO306doc Bit 306IDU 1 shield off commandBITRead/write0 = No shielding; 1 = Shielding
CO307doc Bit 307IDU 1 shield timerBITRead/write0 = No shielding; 1 = Shielding
CO308doc Bit 308IDU 1 8 °C heating (absence) functionBITRead/write0 = Cancel; 1 = Start
CO315doc Bit 315IDU 1 master/slaveBITRead0 = Slave IDU; 1 = Master IDU
CO316doc Bit 316IDU 1 auxiliary electric heaterBITRead0 = Off; 1 = On
CO318doc Bit 318IDU 1 air outlet temperature sensor errorBITRead0 = No; 1 = Yes
CO319doc Bit 319IDU 1 general errorBITRead0 = No; 1 = Yes
CO8488doc Bit 8488System 1 communication errorBITRead0 = No; 1 = Yes
CO8489doc Bit 8489System 1 refrigerant loss protectionBITRead0 = No; 1 = Yes
CO8491doc Bit 8491System 1 power phase sequence protectionBITRead0 = No; 1 = Yes
CO8492doc Bit 8492System 1 VIP power supply mode startedBITRead0 = No; 1 = Yes
CO8493doc Bit 8493System 1 unit debugging statusBITRead0 = Normal; 1 = Debugging
CO8494doc Bit 8494System 1 compressor operation statusBITRead0 = Off; 1 = On
CO8495doc Bit 8495System 1 general outdoor unit errorBITRead0 = No; 1 = Yes
CO8526doc Bit 8526System 1 outdoor EEPROM read/write errorOften a poorly connected outdoor main board.BITRead0 = No; 1 = Yes
CO9776doc Bit 9776Subway IDU 1 on/off statusBITRead/write0 = Off; 1 = On
CO9777doc Bit 9777Subway IDU 1 error statusBITRead0 = No; 1 = Yes
CO10800doc Bit 10800Subway system 1 ODU on/off / remote emergency stopBITRead/write0 = Off; 1 = On
CO10801doc Bit 10801Subway system 1 ODU error statusBITRead0 = No; 1 = Yes
HR101doc Word 101Project no. of starting indoor unitFirst indoor unit number served by this gateway: 1 or 129.UINT16Read
HR102doc Word 102IDU 1 power on/off0xAA (170) = on, 0x55 (85) = off.UINT16Read/write85 = Off (0x55); 170 = On (0xAA)
HR103doc Word 103IDU 1 operation modeWrite and read codes differ; see values.UINT16Read/write0 = Write: invalid; 1 = Cooling (write and read); 2 = Dehumidifying (write and read); 3 = Fan / air supply (write and read); 4 = Heating (write and read); 5 = Write: auto / read: auto cooling; 6 = Write: floor heating / read: auto heating; 7 = Write: fast heat / read: floor heating; 8 = Write: heat supply / read: fast heat; 9 = Read: heat supply; 10 = Read: clothes drying; 11 = Read: air discharge; 12 = Read: cool; 13 = Read: auto dehumidifying
HR104doc Word 104IDU 1 temperature setpointValue x10, 16.0-30.0 °C.UINT16× 0.1°CRead/write
HR105doc Word 105IDU 1 fan speedWrite and read codes differ; see values.UINT16Read/write0 = Write: invalid; 1 = Write: auto / read: fan stopped; 2 = Write: low / read: super low; 3 = Write: medium-low / read: low; 4 = Write: medium / read: medium-low; 5 = Write: medium-high / read: medium; 6 = Write: high / read: medium-high; 7 = Write: turbo / read: high; 8 = Read: super high; 9 = Read: quiet R1; 10 = Read: quiet R2; 11 = Read: quiet R3
HR106doc Word 106IDU 1 cooling energy-saving lower limitValue x10, 16.0-30.0 °C.UINT16× 0.1°CRead/write
HR107doc Word 107IDU 1 heating energy-saving upper limitValue x10, 16.0-30.0 °C.UINT16× 0.1°CRead/write
HR108doc Word 108IDU 1 dehumidifying energy-saving lower limitValue x10, 16.0-30.0 °C.UINT16× 0.1°CRead/write
HR115doc Word 115IDU 1 air outlet temperatureSent as actual + 100; range -30 to 138 °C.UINT16 − 100°CRead
HR117doc Word 117IDU 1 gate (key card) control statusUINT16Read0 = Invalid; 1 = No gate control; 2 = Card inserted; 3 = Card removed
HR118doc Word 118IDU 1 outdoor unit numberOutdoor system (1-16) this indoor unit belongs to.UINT16Read
HR119doc Word 119IDU 1 indoor unit categoryUINT16Read1 = Duct type; 2 = Cassette; 3 = Wall mounted; 4 = Floor ceiling; 5 = Floor standing; 6 = Multi VRF fresh air indoor unit; 7 = Water heater; 8 = Water adaptor; 9 = Total heat recovery fresh air; 10 = Total heat recovery fresh air + heat exchanger; 11 = AHU-KIT; 12 = Air handler; 13 = Console type; 14 = Concealed floor standing type; 255 = Other (0xFF)
HR123doc Word 123IDU 1 rated capacityRated capacity in hectowatts (22, 25 ... 560).UINT16hWRead
HR124doc Word 124IDU 1 static pressure (AC fan motor)Static pressure step for AC-motor models.UINT16Read0 = Invalid; 1 = Static pressure 1; 2 = Static pressure 2; 3 = Static pressure 3; 4 = Static pressure 4; 5 = Static pressure 5; 6 = Static pressure 6; 7 = Static pressure 7; 8 = Static pressure 8; 9 = Static pressure 9
HR125doc Word 125IDU 1 static pressure (DC fan motor)Static pressure step for DC-motor models.UINT16Read0 = Invalid; 1 = Static pressure 1; 2 = Static pressure 2; 3 = Static pressure 3; 4 = Static pressure 4; 5 = Static pressure 5; 6 = Static pressure 6; 7 = Static pressure 7; 8 = Static pressure 8; 9 = Static pressure 9; 10 = Static pressure 10; 11 = Static pressure 11; 12 = Static pressure 12; 13 = Static pressure 13
HR3302doc Word 3302System 1 outdoor capacity upper limitUpper capacity limit of outdoor system 1, 30-100 %.UINT16%Read/write
HR3303doc Word 3303System 1 running indoor unit countNumber of general indoor units started, 0-255.UINT16Read
HR3306doc Word 3306System 1 cooling/heating capabilityUINT16Read0 = Invalid; 1 = Cooling only; 2 = Heating; 3 = Cooling and heating; 4 = Fan
HR3308doc Word 3308System 1 emergency operation modeUINT16Read0 = Invalid; 1 = No emergency operation; 2 = Compressor emergency operation; 3 = Fan emergency operation; 4 = Module emergency operation
HR3463doc Word 3463All indoor units: mode settingGroup command to every indoor unit on the gateway.UINT16Write0 = Invalid (no change); 1 = Cooling; 2 = Dehumidifying; 3 = Fan / air supply; 4 = Heating; 5 = Auto; 6 = Floor heating; 7 = Fast heat; 8 = Heat supply
HR3464doc Word 3464All indoor units: setpointGroup command, value x10, 16.0-30.0 °C.UINT16× 0.1°CWrite
HR3465doc Word 3465All indoor units: fan speedGroup command to every indoor unit on the gateway.UINT16Write0 = Invalid (no change); 1 = Auto; 2 = Low; 3 = Medium-low; 4 = Medium; 5 = Medium-high; 6 = High; 7 = Turbo

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Gree Modbus Gateway (Mini) ME30-24/E6(M) for GMV multi VRF systems

What Modbus registers does the Gree Modbus Gateway (Mini) ME30-24/E6(M) for GMV multi VRF systems have?

This map lists 65 registers: 43 coils, 22 holding registers. 38 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Gree Modbus Gateway (Mini) ME30-24/E6(M) for GMV multi VRF systems Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The protocol numbers words from 0 and coils (bits) from 0, and its example frames send the printed number unchanged (read word 1 sends 00 01, read coil 5 sends 00 05). Word n and Bit n are wire address n. Indoor unit n uses words from 102+25*(n-1) and coils from 288+64*(n-1); system m uses words from 3302+10*(m-1) and coils from 8488+48*(m-1).

What are the minimum Modbus registers to integrate the Gree Modbus Gateway (Mini) ME30-24/E6(M) for GMV multi VRF systems?

Start with HR 102 IDU 1 power on/off (IDU 1 on/off); HR 103 IDU 1 operation mode (IDU 1 mode); HR 104 IDU 1 temperature setpoint (IDU 1 setpoint); HR 105 IDU 1 fan speed (IDU 1 fan speed); CO 120 IDU 1 present (IDU 1 present); CO 319 IDU 1 general error (IDU 1 general error); CO 8495 System 1 general outdoor unit error (System 1 outdoor error); CO 8494 System 1 compressor operation status (System 1 compressor running).

How do I enable Modbus control of the Gree Modbus Gateway (Mini) ME30-24/E6(M) for GMV multi VRF systems?

No software enable: set the Modbus address (1-255) on DIP switches S1 and S2 inside the gateway, and S3 switch 4 for the CAN2 terminating resistor, before use.

Where is the official Gree Modbus Gateway (Mini) ME30-24/E6(M) for GMV multi VRF systems Modbus documentation?

The source is Modbus Gateway(Mini) Communication Protocol V2.0 (V2.0). Gree doesn't publish it on its own website, so this map was re-typed from a free copy at https://www.asami.lt/uploads/Products/product_78/me30-24_e6-m-_mini_modbus_variable_list_en_1708354351.pdf. It may be an older revision, so check it against the live unit.

More Gree Modbus register maps

Other ac & vrf gateways register maps

All ac & vrf gateways Modbus register maps →

Source: Modbus Gateway(Mini) Communication Protocol V2.0 · V2.0 · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.