- Modbus Gateway (Mini) ME30-24/E6(M) for GMV multi VRF systems
VRF / split AC gateway · Modbus register map
Gree Modbus Gateway (Mini) ME30-24/E6(M) for GMV multi VRF systems Modbus register map
Updated 19 November 2026
The Gree Modbus Gateway (Mini) sits on the CAN bus of a GMV multi VRF system and serves up to 16 outdoor systems and 128 indoor units to a BMS over Modbus RTU. Holding registers carry per-indoor-unit on/off, mode, setpoint, fan speed and temperatures plus per-system outdoor data; coils carry feature flags, shields, locks and fault bits. Every indoor unit and system has an identical block, so this map lists indoor unit 1 and system 1 and gives the address rule for the rest.
This page lists 65 Modbus registers for the Gree Modbus Gateway (Mini) ME30-24/E6(M) for GMV multi VRF systems — 38 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Gree’s own free documentation (linked below) and checked against it.
- Manufacturer
- Gree
- Model
- Modbus Gateway (Mini) ME30-24/E6(M) for GMV multi VRF systems
- Equipment type
- VRF / split AC gateway
- Registers
- 65 (38 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Default serial
- 9600 baud, 8N1
- Documented addressing
- 0-based (the number printed is the address on the wire)
- Also known as
- ME30-24/E6(M), Modbus Gateway(Mini), GMV5 Modbus gateway
Integration notes: Gree Modbus Gateway (Mini) ME30-24/E6(M) for GMV multi VRF systems
Set the gateway address on DIP switches S1/S2, wire RS485 at 9600 8N1, then read coils from 120 to see which indoor units exist. Control each unit with its on/off, mode, setpoint and fan words (102-105 for unit 1) using function 0x10, and read fault coils 318-319 and system coils 8488-8495.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 102 | IDU 1 power on/off | UINT16 | IDU 1 on/off | Read/write |
| HR 103 | IDU 1 operation mode | UINT16 | IDU 1 mode | Read/write |
| HR 104 | IDU 1 temperature setpoint | UINT16 | IDU 1 setpoint | Read/write |
| HR 105 | IDU 1 fan speed | UINT16 | IDU 1 fan speed | Read/write |
| CO 120 | IDU 1 present | BIT | IDU 1 present | Read |
| CO 319 | IDU 1 general error | BIT | IDU 1 general error | Read |
| CO 8495 | System 1 general outdoor unit error | BIT | System 1 outdoor error | Read |
| CO 8494 | System 1 compressor operation status | BIT | System 1 compressor running | Read |
Enable Modbus control & writes
No software enable: set the Modbus address (1-255) on DIP switches S1 and S2 inside the gateway, and S3 switch 4 for the CAN2 terminating resistor, before use.
Byte order & addressing
- Power on/off uses 0xAA (on) and 0x55 (off), not 1/0.
- Exception code 0x04 means the gateway has no contact with the air-conditioning units; it is also returned after power-up until valid data has been collected.
- A read of more than 127 words is refused with exception 0x03.
- Writes that conflict with the outdoor unit capability, the master indoor unit mode or active energy-saving limits are ignored; read back to confirm.
Network setup
- RS485, 9600 baud, 8 data bits, no parity, 1 stop bit (fixed in the protocol).
- Gateway address 1-255 on DIP switches S1/S2; address 0 is broadcast (writes only, no reply).
- One gateway serves up to 16 outdoor systems and 128 indoor units; beyond 128 indoor units use a second gateway (starting unit 129).
- S3 switch 2 sets the first indoor unit the gateway serves: engineering code 1 (units 1-128) or 129 (units 129-255); word 101 reports the setting.
- S3 switch 3 switches in the gateway's own RS485 terminating resistor; normally the BMS master end carries it and the gateway is left without.
- If the gateway is at either end of the CAN2 bus, set S3 switch 4 to 0 to switch in the terminating resistor.
Watch out for
- Re-commission the gateway whenever the unit engineering data (addresses, number of units) changes.
- Keep communication wiring at least 15 cm from power cabling.
Gree Modbus Gateway (Mini) ME30-24/E6(M) for GMV multi VRF systems Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| CO | 88doc Bit 88 | System 1 present | BIT | Read | 0 = Without; 1 = With | ||||
| CO | 120doc Bit 120 | IDU 1 present | BIT | Read | 0 = Without; 1 = With | ||||
| CO | 248doc Bit 248 | System 1 remote emergency stop | BIT | Read/write | 0 = Off; 1 = On | ||||
| CO | 280doc Bit 280 | Set all IDUs on | Group command. | BIT | Write | 0 = No; 1 = Yes | |||
| CO | 281doc Bit 281 | Set all IDUs off | Group command. | BIT | Write | 0 = No; 1 = Yes | |||
| CO | 282doc Bit 282 | Set all IDUs remotely locked | Group command. | BIT | Write | 0 = No; 1 = Yes | |||
| CO | 288doc Bit 288 | IDU 1 remote shield: energy saving | BIT | Read/write | 0 = Not shielded; 1 = Shielded | ||||
| CO | 289doc Bit 289 | IDU 1 remote shield: temperature setting | BIT | Read/write | 0 = Not shielded; 1 = Shielded | ||||
| CO | 290doc Bit 290 | IDU 1 remote shield: mode | BIT | Read/write | 0 = Not shielded; 1 = Shielded | ||||
| CO | 291doc Bit 291 | IDU 1 remote shield: on/off | BIT | Read/write | 0 = Not shielded; 1 = Shielded | ||||
| CO | 292doc Bit 292 | IDU 1 remote lock | BIT | Read/write | 0 = Unlocked; 1 = Locked | ||||
| CO | 293doc Bit 293 | IDU 1 priority power supply | Used in the power-shortage mode of the supply system. | BIT | Read/write | 0 = No; 1 = Yes | |||
| CO | 294doc Bit 294 | IDU 1 up-down swing | BIT | Read/write | 0 = Off; 1 = On | ||||
| CO | 295doc Bit 295 | IDU 1 left-right swing | BIT | Read/write | 0 = Off; 1 = On | ||||
| CO | 296doc Bit 296 | IDU 1 energy saving | BIT | Read/write | 0 = Off; 1 = On | ||||
| CO | 297doc Bit 297 | IDU 1 forbid auxiliary heater | BIT | Read/write | 0 = Auxiliary heater allowed; 1 = Auxiliary heater forbidden | ||||
| CO | 298doc Bit 298 | IDU 1 power failure memory | BIT | Read/write | 0 = Standby after power loss; 1 = Power failure memory | ||||
| CO | 299doc Bit 299 | IDU 1 cancel filter cleaning reminder | BIT | Read/write | 0 = No; 1 = Yes | ||||
| CO | 300doc Bit 300 | IDU 1 dry (X-fan) | BIT | Read/write | 0 = Off; 1 = On | ||||
| CO | 301doc Bit 301 | IDU 1 sleep | BIT | Read/write | 0 = Off; 1 = On | ||||
| CO | 302doc Bit 302 | IDU 1 quiet | BIT | Read/write | 0 = Off; 1 = On | ||||
| CO | 303doc Bit 303 | IDU 1 ventilation (air) | BIT | Read/write | 0 = Off; 1 = On | ||||
| CO | 304doc Bit 304 | IDU 1 low-temperature dehumidification | BIT | Read/write | 0 = Cancel; 1 = Start | ||||
| CO | 305doc Bit 305 | IDU 1 shield on command | BIT | Read/write | 0 = No shielding; 1 = Shielding | ||||
| CO | 306doc Bit 306 | IDU 1 shield off command | BIT | Read/write | 0 = No shielding; 1 = Shielding | ||||
| CO | 307doc Bit 307 | IDU 1 shield timer | BIT | Read/write | 0 = No shielding; 1 = Shielding | ||||
| CO | 308doc Bit 308 | IDU 1 8 °C heating (absence) function | BIT | Read/write | 0 = Cancel; 1 = Start | ||||
| CO | 315doc Bit 315 | IDU 1 master/slave | BIT | Read | 0 = Slave IDU; 1 = Master IDU | ||||
| CO | 316doc Bit 316 | IDU 1 auxiliary electric heater | BIT | Read | 0 = Off; 1 = On | ||||
| CO | 318doc Bit 318 | IDU 1 air outlet temperature sensor error | BIT | Read | 0 = No; 1 = Yes | ||||
| CO | 319doc Bit 319 | IDU 1 general error | BIT | Read | 0 = No; 1 = Yes | ||||
| CO | 8488doc Bit 8488 | System 1 communication error | BIT | Read | 0 = No; 1 = Yes | ||||
| CO | 8489doc Bit 8489 | System 1 refrigerant loss protection | BIT | Read | 0 = No; 1 = Yes | ||||
| CO | 8491doc Bit 8491 | System 1 power phase sequence protection | BIT | Read | 0 = No; 1 = Yes | ||||
| CO | 8492doc Bit 8492 | System 1 VIP power supply mode started | BIT | Read | 0 = No; 1 = Yes | ||||
| CO | 8493doc Bit 8493 | System 1 unit debugging status | BIT | Read | 0 = Normal; 1 = Debugging | ||||
| CO | 8494doc Bit 8494 | System 1 compressor operation status | BIT | Read | 0 = Off; 1 = On | ||||
| CO | 8495doc Bit 8495 | System 1 general outdoor unit error | BIT | Read | 0 = No; 1 = Yes | ||||
| CO | 8526doc Bit 8526 | System 1 outdoor EEPROM read/write error | Often a poorly connected outdoor main board. | BIT | Read | 0 = No; 1 = Yes | |||
| CO | 9776doc Bit 9776 | Subway IDU 1 on/off status | BIT | Read/write | 0 = Off; 1 = On | ||||
| CO | 9777doc Bit 9777 | Subway IDU 1 error status | BIT | Read | 0 = No; 1 = Yes | ||||
| CO | 10800doc Bit 10800 | Subway system 1 ODU on/off / remote emergency stop | BIT | Read/write | 0 = Off; 1 = On | ||||
| CO | 10801doc Bit 10801 | Subway system 1 ODU error status | BIT | Read | 0 = No; 1 = Yes | ||||
| HR | 101doc Word 101 | Project no. of starting indoor unit | First indoor unit number served by this gateway: 1 or 129. | UINT16 | Read | ||||
| HR | 102doc Word 102 | IDU 1 power on/off | 0xAA (170) = on, 0x55 (85) = off. | UINT16 | Read/write | 85 = Off (0x55); 170 = On (0xAA) | |||
| HR | 103doc Word 103 | IDU 1 operation mode | Write and read codes differ; see values. | UINT16 | Read/write | 0 = Write: invalid; 1 = Cooling (write and read); 2 = Dehumidifying (write and read); 3 = Fan / air supply (write and read); 4 = Heating (write and read); 5 = Write: auto / read: auto cooling; 6 = Write: floor heating / read: auto heating; 7 = Write: fast heat / read: floor heating; 8 = Write: heat supply / read: fast heat; 9 = Read: heat supply; 10 = Read: clothes drying; 11 = Read: air discharge; 12 = Read: cool; 13 = Read: auto dehumidifying | |||
| HR | 104doc Word 104 | IDU 1 temperature setpoint | Value x10, 16.0-30.0 °C. | UINT16 | × 0.1 | °C | Read/write | ||
| HR | 105doc Word 105 | IDU 1 fan speed | Write and read codes differ; see values. | UINT16 | Read/write | 0 = Write: invalid; 1 = Write: auto / read: fan stopped; 2 = Write: low / read: super low; 3 = Write: medium-low / read: low; 4 = Write: medium / read: medium-low; 5 = Write: medium-high / read: medium; 6 = Write: high / read: medium-high; 7 = Write: turbo / read: high; 8 = Read: super high; 9 = Read: quiet R1; 10 = Read: quiet R2; 11 = Read: quiet R3 | |||
| HR | 106doc Word 106 | IDU 1 cooling energy-saving lower limit | Value x10, 16.0-30.0 °C. | UINT16 | × 0.1 | °C | Read/write | ||
| HR | 107doc Word 107 | IDU 1 heating energy-saving upper limit | Value x10, 16.0-30.0 °C. | UINT16 | × 0.1 | °C | Read/write | ||
| HR | 108doc Word 108 | IDU 1 dehumidifying energy-saving lower limit | Value x10, 16.0-30.0 °C. | UINT16 | × 0.1 | °C | Read/write | ||
| HR | 115doc Word 115 | IDU 1 air outlet temperature | Sent as actual + 100; range -30 to 138 °C. | UINT16 | − 100 | °C | Read | ||
| HR | 117doc Word 117 | IDU 1 gate (key card) control status | UINT16 | Read | 0 = Invalid; 1 = No gate control; 2 = Card inserted; 3 = Card removed | ||||
| HR | 118doc Word 118 | IDU 1 outdoor unit number | Outdoor system (1-16) this indoor unit belongs to. | UINT16 | Read | ||||
| HR | 119doc Word 119 | IDU 1 indoor unit category | UINT16 | Read | 1 = Duct type; 2 = Cassette; 3 = Wall mounted; 4 = Floor ceiling; 5 = Floor standing; 6 = Multi VRF fresh air indoor unit; 7 = Water heater; 8 = Water adaptor; 9 = Total heat recovery fresh air; 10 = Total heat recovery fresh air + heat exchanger; 11 = AHU-KIT; 12 = Air handler; 13 = Console type; 14 = Concealed floor standing type; 255 = Other (0xFF) | ||||
| HR | 123doc Word 123 | IDU 1 rated capacity | Rated capacity in hectowatts (22, 25 ... 560). | UINT16 | hW | Read | |||
| HR | 124doc Word 124 | IDU 1 static pressure (AC fan motor) | Static pressure step for AC-motor models. | UINT16 | Read | 0 = Invalid; 1 = Static pressure 1; 2 = Static pressure 2; 3 = Static pressure 3; 4 = Static pressure 4; 5 = Static pressure 5; 6 = Static pressure 6; 7 = Static pressure 7; 8 = Static pressure 8; 9 = Static pressure 9 | |||
| HR | 125doc Word 125 | IDU 1 static pressure (DC fan motor) | Static pressure step for DC-motor models. | UINT16 | Read | 0 = Invalid; 1 = Static pressure 1; 2 = Static pressure 2; 3 = Static pressure 3; 4 = Static pressure 4; 5 = Static pressure 5; 6 = Static pressure 6; 7 = Static pressure 7; 8 = Static pressure 8; 9 = Static pressure 9; 10 = Static pressure 10; 11 = Static pressure 11; 12 = Static pressure 12; 13 = Static pressure 13 | |||
| HR | 3302doc Word 3302 | System 1 outdoor capacity upper limit | Upper capacity limit of outdoor system 1, 30-100 %. | UINT16 | % | Read/write | |||
| HR | 3303doc Word 3303 | System 1 running indoor unit count | Number of general indoor units started, 0-255. | UINT16 | Read | ||||
| HR | 3306doc Word 3306 | System 1 cooling/heating capability | UINT16 | Read | 0 = Invalid; 1 = Cooling only; 2 = Heating; 3 = Cooling and heating; 4 = Fan | ||||
| HR | 3308doc Word 3308 | System 1 emergency operation mode | UINT16 | Read | 0 = Invalid; 1 = No emergency operation; 2 = Compressor emergency operation; 3 = Fan emergency operation; 4 = Module emergency operation | ||||
| HR | 3463doc Word 3463 | All indoor units: mode setting | Group command to every indoor unit on the gateway. | UINT16 | Write | 0 = Invalid (no change); 1 = Cooling; 2 = Dehumidifying; 3 = Fan / air supply; 4 = Heating; 5 = Auto; 6 = Floor heating; 7 = Fast heat; 8 = Heat supply | |||
| HR | 3464doc Word 3464 | All indoor units: setpoint | Group command, value x10, 16.0-30.0 °C. | UINT16 | × 0.1 | °C | Write | ||
| HR | 3465doc Word 3465 | All indoor units: fan speed | Group command to every indoor unit on the gateway. | UINT16 | Write | 0 = Invalid (no change); 1 = Auto; 2 = Low; 3 = Medium-low; 4 = Medium; 5 = Medium-high; 6 = High; 7 = Turbo |
Notes on this map
- Gree does not host this protocol publicly; the link is a copy on a Lithuanian distributor's site (Asami) and appears to be the unaltered Gree document.
- Only indoor unit 1 and outdoor system 1 are listed. The source prints identical blocks for indoor units 2-128 (words +25 per unit, coils +64 per unit), systems 2-16 (words +10, coils +48) and the 'subway' on/off blocks (coils +8 per unit or system).
- Left out: indoor ambient temperature (word 116) and outdoor ambient temperature (word 3307). Both are sent as x10 with negative ranges, but word 116 is typed 'floating-point' and word 3307 has no data type at all, so the 16-bit encoding is not settled.
- Words the source skips with '...' (for example 109-114 and 120-122) are not printed there and are not listed.
- Mode and fan words use one set of codes for writing and another for reading; the values list shows both.
- The fresh air unit sections (words 4200-13159, bits 11200-27583) are not included in this map.
- The protocol lists function codes 0x01, 0x03, 0x0F and 0x10 only; single writes (0x05/0x06) are not listed.
- The ME30-24/E6(M) part number comes from the distributor's product listing; the protocol document itself only calls the device 'Modbus Gateway(Mini)'.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Gree Modbus Gateway (Mini) ME30-24/E6(M) for GMV multi VRF systems
What Modbus registers does the Gree Modbus Gateway (Mini) ME30-24/E6(M) for GMV multi VRF systems have?
This map lists 65 registers: 43 coils, 22 holding registers. 38 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Gree Modbus Gateway (Mini) ME30-24/E6(M) for GMV multi VRF systems Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The protocol numbers words from 0 and coils (bits) from 0, and its example frames send the printed number unchanged (read word 1 sends 00 01, read coil 5 sends 00 05). Word n and Bit n are wire address n. Indoor unit n uses words from 102+25*(n-1) and coils from 288+64*(n-1); system m uses words from 3302+10*(m-1) and coils from 8488+48*(m-1).
What are the minimum Modbus registers to integrate the Gree Modbus Gateway (Mini) ME30-24/E6(M) for GMV multi VRF systems?
Start with HR 102 IDU 1 power on/off (IDU 1 on/off); HR 103 IDU 1 operation mode (IDU 1 mode); HR 104 IDU 1 temperature setpoint (IDU 1 setpoint); HR 105 IDU 1 fan speed (IDU 1 fan speed); CO 120 IDU 1 present (IDU 1 present); CO 319 IDU 1 general error (IDU 1 general error); CO 8495 System 1 general outdoor unit error (System 1 outdoor error); CO 8494 System 1 compressor operation status (System 1 compressor running).
How do I enable Modbus control of the Gree Modbus Gateway (Mini) ME30-24/E6(M) for GMV multi VRF systems?
No software enable: set the Modbus address (1-255) on DIP switches S1 and S2 inside the gateway, and S3 switch 4 for the CAN2 terminating resistor, before use.
Where is the official Gree Modbus Gateway (Mini) ME30-24/E6(M) for GMV multi VRF systems Modbus documentation?
The source is Modbus Gateway(Mini) Communication Protocol V2.0 (V2.0). Gree doesn't publish it on its own website, so this map was re-typed from a free copy at https://www.asami.lt/uploads/Products/product_78/me30-24_e6-m-_mini_modbus_variable_list_en_1708354351.pdf. It may be an older revision, so check it against the live unit.
More Gree Modbus register maps
- Split AC unit (VRF / split AC gateway built in)
Gree Export residential split air conditioners (built-in Modbus on indoor unit / wired controller)
Gree export residential air conditioners whose indoor-unit controller or wired controller has the integrated Modbus RTU interface; protocol PDF dated 2023-05.
Also known as: Gree residential split Modbus, Gree wall split Modbus, Gree wired controller Modbus - Split AC unit (VRF / split AC gateway built in)
Gree U-Match all-DC-inverter duct / cassette / floor-ceiling units (built-in Modbus)
Gree U-Match fourth-generation all-DC-inverter light-commercial units whose controller has the integrated Modbus RTU interface; Chinese-English protocol dated 2018-03-07.
Also known as: U-Match, Gree U-Match 4th generation DC inverter, U-Match BMS Modbus - Heat pump (air-to-water)
Gree Versati heat pump water heater (wired-controller Modbus RTU, protocol V1.5)
Gree Versati air-to-water heat pumps through the BMS port of the wired controller, per 'Modbus Protocol (V1.5) for the Versati Heat Pump Water Heater'. The document itself does not name a generation or refrigerant; the distributor files it as the R32 Versati III protocol.
Also known as: Versati III, R32 Versati, Versati heat pump water heater, Gree Versati Modbus V1.5
Other ac & vrf gateways register maps
- VRF / split AC gateway
Intesis (HMS Networks) IN770AIR***O000 700 Series Air Gateway, Mitsubishi Electric City Multi application (Modbus)
Intesis 700 Series Air Gateway IN770AIR***O000 with the Mitsubishi Electric City Multi application (M-NET centralised controllers (AE-200, EW-50, G-50 and others)), Modbus RTU / TCP server, user manual version 1.0.19 (2026-03-16).
Also known as: IN770AIR00MO000, IN770AIR00SO000, IN770AIRXXSO000 - VRF / split AC gateway
Intesis (HMS Networks) INMBSFGL001I000 Fujitsu domestic AC to Modbus RTU gateway
One Fujitsu domestic (RAC) or compatible VRF indoor unit, connected to the CN65/CN12/CN6 socket on the indoor board via INMBSFGL001I000, user manual v1.5 (01/2024).
Also known as: INMBSFGL001I000, FJ-AC-MBS-1, Intesis Fujitsu domestic Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSLGE001R000 LG AC to Modbus RTU gateway
One LG indoor unit on the BYR (wired remote) bus via INMBSLGE001R000 (legacy code LG-RC-MBS-1), user manual v1.9 (01/2024).
Also known as: INMBSLGE001R000, LG-RC-MBS-1, Intesis LG Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSMIT050C000 / INMBSMIT100C000 Mitsubishi Electric City Multi centralised controller to Modbus gateway
Intesis Modbus Server - Mitsubishi Electric CC, order codes INMBSMIT050C000 / INMBSMIT100C000 (legacy ME-AC-MBS-50 / -100), user manual r1.4 (05/2021); talks to City Multi centralised controllers (G-50A, GB-50A, AG-150A, EB-50, EW-50, AE-200 and newer) through their XML interface over Ethernet.
Also known as: INMBSMIT050C000, INMBSMIT100C000, ME-AC-MBS-50, ME-AC-MBS-100, Intesis Modbus Server Mitsubishi Electric CC - VRF / split AC gateway
Intesis (HMS Networks) INMBSSAM016O000 Samsung NASA (R1/R2) VRF to Modbus gateway (4 to 64 units)
Intesis Modbus Server - Samsung NASA, order codes INMBSSAM004O000 / 008O000 / 016O000 / 064O000 (legacy SM-ACN-MBS-4/8/16/64), user manual r1.4 (12/2020); Samsung NASA R1/R2 bus.
Also known as: INMBSSAM004O000, INMBSSAM008O000, INMBSSAM016O000, INMBSSAM064O000, SM-ACN-MBS-4, SM-ACN-MBS-8, SM-ACN-MBS-16, SM-ACN-MBS-64 - Heat pump (VRF / split AC gateway)
Mitsubishi Electric MelcoBEMS MINI (A1M+) gateway for Ecodan FTC4/FTC5/FTC6 air-to-water systems
Procon MelcoBEMS MINI (A1M+) firmware 4.1.0 connected to an Ecodan FTC4, FTC5 or FTC6 air-to-water controller; holding-register table only.
Also known as: A1M+, MelcoBEMS MINI, Procon A1M+, Ecodan FTC4, Ecodan FTC5, Ecodan FTC6
All ac & vrf gateways Modbus register maps →
Source: Modbus Gateway(Mini) Communication Protocol V2.0 · V2.0 · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.