Mitsubishi Electric MelcoBEMS MINI (A1M+) gateway for Ecodan FTC4/FTC5/FTC6 air-to-water systems Modbus register map
Updated 17 November 2026
The MelcoBEMS MINI (A1M+) is a Procon-built RS-485 Modbus RTU gateway for Mitsubishi Electric units, documented by Mitsubishi Electric UK. With an Ecodan FTC controller it exposes on/off, zone modes, tank and zone setpoints, temperatures, heater and pump states and energy totals. This map lists the holding registers that the register tables mark as applicable to FTC4, FTC5 or FTC6.
This page lists 85 Modbus registers for the Mitsubishi Electric MelcoBEMS MINI (A1M+) gateway for Ecodan FTC4/FTC5/FTC6 air-to-water systems — 18 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Mitsubishi Electric’s own free documentation (linked below) and checked against it.
- Manufacturer
- Mitsubishi Electric
- Model
- MelcoBEMS MINI (A1M+) gateway for Ecodan FTC4/FTC5/FTC6 air-to-water systems
- Equipment type
- Heat pump (VRF / split AC gateway)
- Registers
- 85 (18 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- Firmware
- A1M+ firmware 4.1.0
- Also known as
- A1M+, MelcoBEMS MINI, Procon A1M+, Ecodan FTC4, Ecodan FTC5, Ecodan FTC6
Integration notes: Mitsubishi Electric MelcoBEMS MINI (A1M+) gateway for Ecodan FTC4/FTC5/FTC6 air-to-water systems
Connect the A1M+ to the FTC controller as described in its installation instructions and to the BMS RS-485 line, then read 40014 to confirm an ATW system is detected and 40010 for faults. Switch the system with 40026, set the tank and zone targets at 40031/40055/40057, and poll flow, return, tank and room temperatures from 40094-40118.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 13 | System Type Detected | UINT16 | System type detected (1 = ATW) | Read |
| HR 9 | Fault/Error Code (hex) | UINT16 | Fault code, 0x8000 = no error | Read |
| HR 25 | System On/Off | UINT16 | System on/off | Read/write |
| HR 30 | Set Tank Water Temperature (signed) | INT16 | DHW tank setpoint | Read/write |
| HR 54 | Thermostat Target Temperature - Zone 1 (signed) | INT16 | Zone 1 thermostat target | Read/write |
| HR 101 | Flow Temperature (signed) | INT16 | Flow temperature | Read |
| HR 105 | Tank Water Temperature (signed) | INT16 | Tank water temperature | Read |
| HR 93 | Room Temperature - Zone 1 (signed) | INT16 | Zone 1 room temperature | Read |
| HR 99 | Outdoor Ambient Temperature (signed) | INT16 | Outdoor ambient temperature | Read |
| HR 80 | Heat Source Status | UINT16 | Heat source in use | Read |
Enable Modbus control & writes
No enable step is described in the register tables; the gateway answers once it is powered from the unit and its Modbus address, baud rate and parity (40005-40007) match the master. See the separate MelcoBEMS MINI installation instructions.
Byte order & addressing
- Temperatures are x100 for most points but x10 for outdoor ambient (40100) and DHW temperature drop (40092).
- Each signed temperature has an unsigned twin one address higher for masters that cannot handle negative values.
- Baud-rate code 0 and code 4 both mean 9600 in the table.
- Holding registers support FC 03, FC 06 and FC 16; registers marked READ ONLY cannot be written.
Network setup
- Set the Modbus address (1-247), baud rate and parity in 40005-40007 to match the BMS.
- Energy values (40283-40299) are reported as a kWh part plus a Wh part (x10 Wh); add them for the full reading.
Watch out for
- Value 0x6999 (hex register) or 6999 (decimal register) means the gateway cannot talk to the heat pump controller, not a heat pump fault.
- Operating mode register 40027 is not marked for FTC units; use the zone A/C mode registers 40029/40030 and DHW mode 40028 instead.
Mitsubishi Electric MelcoBEMS MINI (A1M+) gateway for Ecodan FTC4/FTC5/FTC6 air-to-water systems Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 4doc 40005 | Modbus Slave ID | Gateway Modbus address, 1-247. | UINT16 | Read/write | ||||
| HR | 5doc 40006 | Modbus RS-485 Baud Rate | UINT16 | Read/write | 0 = 9600; 1 = 1200; 2 = 2400; 3 = 4800; 4 = 9600; 5 = 14400; 6 = 19200; 7 = 28800; 8 = 38400; 9 = 56000; 10 = 57600; 11 = 115200 | ||||
| HR | 6doc 40007 | RS-485 Parity Type | UINT16 | Read/write | 0 = None; 1 = Even; 2 = Odd | ||||
| HR | 9doc 40010 | Fault/Error Code (hex) | 0x8000 = no error, 0x6999 = no communication with the unit. | UINT16 | Read | ||||
| HR | 10doc 40011 | A1M+ Firmware Version | Gateway firmware version. | UINT16 | Read | ||||
| HR | 11doc 40012 | Modbus Comms Counter | Counts valid Modbus commands; wraps after 65535. | UINT16 | Read | ||||
| HR | 12doc 40013 | Fault Code (decimal) | 8000 = no error, 6999 = no communication with the unit. | UINT16 | Read | ||||
| HR | 13doc 40014 | System Type Detected | UINT16 | Read | 0 = ATA unit connected; 1 = ATW system connected; 2 = Lossnay system connected; 255 = Undetermined (no unit detected yet) | ||||
| HR | 25doc 40026 | System On/Off | Values 2 and 3 are reported only, not writable. | UINT16 | Read/write | 0 = System OFF; 1 = System ON; 2 = Emergency Run (read only); 3 = Test Run (read only) | |||
| HR | 27doc 40028 | Operating Mode (DHW) | FTC5 and FTC6 only. | UINT16 | Read/write | 0 = Normal; 1 = Eco | |||
| HR | 28doc 40029 | A/C Mode - Zone 1 | UINT16 | Read/write | 0 = Heating Room Temp; 1 = Heating Flow Temp; 2 = Heating Heat Curve; 3 = Cooling Room Temp (not on 13K model); 4 = Cooling Flow Temp; 5 = Floor Dryup | ||||
| HR | 29doc 40030 | A/C Mode - Zone 2 | UINT16 | Read/write | 0 = Heating Room Temp; 1 = Heating Flow Temp; 2 = Heating Heat Curve; 3 = Cooling Room Temp (not on 13K model); 4 = Cooling Flow Temp; 5 = Floor Dryup | ||||
| HR | 30doc 40031 | Set Tank Water Temperature (signed) | DHW tank setpoint, x100. Read-only on FTC4. | INT16 | × 0.01 | °C | Read/write | ||
| HR | 32doc 40033 | H/C Thermostat Target Temperature - Zone 1 (signed) | x100. | INT16 | × 0.01 | °C | Read/write | ||
| HR | 34doc 40035 | H/C Thermostat Target Temperature - Zone 2 (signed) | x100. | INT16 | × 0.01 | °C | Read/write | ||
| HR | 36doc 40037 | MRC Prohibit | Locks functions on the main remote controller. | BITMAP16 | Read/write | bit 0 = System On/Off (0 = on, 1 = prohibit); bit 1 = Running mode (0 = on, 1 = prohibit); bit 2 = Setting temperature (0 = on, 1 = prohibit); bit 4 = Function setting (0 = normal, 1 = function setting) | |||
| HR | 37doc 40038 | Force DHW | UINT16 | Read/write | 0 = Normal; 1 = Force DHW | ||||
| HR | 38doc 40039 | Holiday | UINT16 | Read/write | 0 = Normal; 1 = Holiday | ||||
| HR | 39doc 40040 | DHW On Prohibit | UINT16 | Read | 0 = On; 1 = Prohibit | ||||
| HR | 40doc 40041 | Heating On Prohibit - Zone 1 | UINT16 | Read | 0 = On; 1 = Prohibit | ||||
| HR | 41doc 40042 | Cooling On Prohibit - Zone 1 | Read-only on FTC4. | UINT16 | Read/write | 0 = On; 1 = Prohibit | |||
| HR | 42doc 40043 | Heating On Prohibit - Zone 2 | UINT16 | Read | 0 = On; 1 = Prohibit | ||||
| HR | 43doc 40044 | Cooling On Prohibit - Zone 2 | FTC5 and FTC6 only. | UINT16 | Read/write | 0 = On; 1 = Prohibit | |||
| HR | 54doc 40055 | Thermostat Target Temperature - Zone 1 (signed) | x100. | INT16 | × 0.01 | °C | Read/write | ||
| HR | 56doc 40057 | Thermostat Target Temperature - Zone 2 (signed) | x100. | INT16 | × 0.01 | °C | Read/write | ||
| HR | 58doc 40059 | HC Control Type | UINT16 | Read/write | 0 = Heating; 1 = Cooling | ||||
| HR | 66doc 40067 | Own Refrigerant Address | 0-32. | UINT16 | Read | ||||
| HR | 67doc 40068 | Defrost | UINT16 | Read | 0 = Normal; 1 = Standby; 2 = Defrost; 3 = Waiting Restart | ||||
| HR | 68doc 40069 | Residual Heat Removal | UINT16 | Read | 0 = Normal; 1 = Prepared; 2 = Residual Heat Removal | ||||
| HR | 69doc 40070 | Refrigerant Error Info | UINT16 | Read | 0 = Normal; 1 = Error (System); 2 = Error (Startup); 3 = Maintenance Error | ||||
| HR | 70doc 40071 | 7-Segment Error Code Digit 1 | First character of the displayed error code. | UINT16 | Read | 0 = A; 1 = b; 2 = E; 3 = F; 4 = J; 5 = L; 6 = P; 7 = U | |||
| HR | 71doc 40072 | 7-Segment Error Code Digit 2 | Second character; 1-15 = 1-F. | UINT16 | Read | 16 = O; 17 = H; 18 = J; 19 = L; 20 = P; 21 = U | |||
| HR | 73doc 40074 | Heat Pump Frequency - Master | Compressor frequency, 0-255 Hz. | UINT16 | Hz | Read | |||
| HR | 80doc 40081 | Heat Source Status | UINT16 | Read | 0 = H/P; 1 = IH; 2 = BH; 3 = IH + BH; 4 = Boiler | ||||
| HR | 81doc 40082 | Temperature Setpoint - Zone 1 (signed) | x100. | INT16 | × 0.01 | °C | Read | ||
| HR | 83doc 40084 | Temperature Setpoint - Zone 2 (signed) | x100. | INT16 | × 0.01 | °C | Read | ||
| HR | 85doc 40086 | Flow Temperature Setpoint - Zone 1 (signed) | x100. | INT16 | × 0.01 | °C | Read | ||
| HR | 87doc 40088 | Flow Temperature Setpoint - Zone 2 (signed) | x100. | INT16 | × 0.01 | °C | Read | ||
| HR | 89doc 40090 | Legionella Temperature Setpoint (signed) | x100. | INT16 | × 0.01 | °C | Read | ||
| HR | 91doc 40092 | DHW Temperature Drop (signed) | x10. | INT16 | × 0.1 | °C | Read | ||
| HR | 93doc 40094 | Room Temperature - Zone 1 (signed) | x100. | INT16 | × 0.01 | °C | Read | ||
| HR | 95doc 40096 | Room Temperature - Zone 2 (signed) | x100. | INT16 | × 0.01 | °C | Read | ||
| HR | 97doc 40098 | Refrigerant Liquid Temperature (signed) | x100. | INT16 | × 0.01 | °C | Read | ||
| HR | 99doc 40100 | Outdoor Ambient Temperature (signed) | x10. | INT16 | × 0.1 | °C | Read | ||
| HR | 101doc 40102 | Flow Temperature (signed) | x100. | INT16 | × 0.01 | °C | Read | ||
| HR | 103doc 40104 | Return Temperature (signed) | x100. | INT16 | × 0.01 | °C | Read | ||
| HR | 105doc 40106 | Tank Water Temperature (signed) | x100. | INT16 | × 0.01 | °C | Read | ||
| HR | 107doc 40108 | Flow Temperature - Zone 1 (signed) | x100. | INT16 | × 0.01 | °C | Read | ||
| HR | 109doc 40110 | Return Temperature - Zone 1 (signed) | x100. | INT16 | × 0.01 | °C | Read | ||
| HR | 111doc 40112 | Flow Temperature - Zone 2 (signed) | x100. | INT16 | × 0.01 | °C | Read | ||
| HR | 113doc 40114 | Return Temperature - Zone 2 (signed) | x100. | INT16 | × 0.01 | °C | Read | ||
| HR | 115doc 40116 | Boiler Flow Temperature (signed) | x100. | INT16 | × 0.01 | °C | Read | ||
| HR | 117doc 40118 | Boiler Return Temperature (signed) | x100. | INT16 | × 0.01 | °C | Read | ||
| HR | 119doc 40120 | Room Thermo 1 (IN1) | UINT16 | Read | 0 = OFF; 1 = ON | ||||
| HR | 120doc 40121 | Room Thermo 2 (IN6) | UINT16 | Read | 0 = OFF; 1 = ON | ||||
| HR | 121doc 40122 | Flow SW1 (IN2) | UINT16 | Read | 0 = OFF; 1 = ON | ||||
| HR | 122doc 40123 | Flow SW2 (IN3) | UINT16 | Read | 0 = OFF; 1 = ON | ||||
| HR | 123doc 40124 | Flow SW3 (IN7) | UINT16 | Read | 0 = OFF; 1 = ON | ||||
| HR | 124doc 40125 | Demand (IN4) | UINT16 | Read | 0 = OFF; 1 = ON | ||||
| HR | 125doc 40126 | Outdoor Thermo (IN5) | UINT16 | Read | 0 = OFF; 1 = ON | ||||
| HR | 127doc 40128 | Heat Pump Master ON/OFF | UINT16 | Read | 0 = Stop; 1 = Run | ||||
| HR | 136doc 40137 | Heat Pump Run Time (hours) | Hours part, 0-99. | UINT16 | h | Read | |||
| HR | 137doc 40138 | Heat Pump Run Time (hours x100) | Hundreds-of-hours part. | UINT16 | × 100 | h | Read | ||
| HR | 144doc 40145 | Boiler ON/OFF | UINT16 | Read | 0 = Stop; 1 = Run | ||||
| HR | 145doc 40146 | Booster Heater 1 ON/OFF | UINT16 | Read | 0 = Stop; 1 = Run | ||||
| HR | 146doc 40147 | Booster Heater 2 ON/OFF | UINT16 | Read | 0 = Stop; 1 = Run | ||||
| HR | 147doc 40148 | Booster Heater 2+ ON/OFF | UINT16 | Read | 0 = Stop; 1 = Run | ||||
| HR | 148doc 40149 | Immersion Heater ON/OFF | UINT16 | Read | 0 = Stop; 1 = Run | ||||
| HR | 149doc 40150 | Water Pump 1 ON/OFF | UINT16 | Read | 0 = Stop; 1 = Run | ||||
| HR | 150doc 40151 | Water Pump 2 ON/OFF | UINT16 | Read | 0 = Stop; 1 = Run | ||||
| HR | 151doc 40152 | Water Pump 3 ON/OFF | UINT16 | Read | 0 = Stop; 1 = Run | ||||
| HR | 152doc 40153 | 3-Way Valve ON/OFF | UINT16 | Read | 0 = Stop; 1 = Run | ||||
| HR | 153doc 40154 | 2-Way Valve 2 ON/OFF | UINT16 | Read | 0 = Stop; 1 = Run | ||||
| HR | 154doc 40155 | Mixing Valve Step | Step 0-10. | UINT16 | Read | ||||
| HR | 282doc 40283 | Last Heating Energy Consumed - kWh part | FTC5/FTC6 only. | UINT16 | kWh | Read | |||
| HR | 283doc 40284 | Last Heating Energy Consumed - Wh part | x10 Wh (0-99 = 0-990 Wh). FTC5/FTC6 only. | UINT16 | × 10 | Wh | Read | ||
| HR | 286doc 40287 | Last DHW Energy Consumed - kWh part | FTC5/FTC6 only. | UINT16 | kWh | Read | |||
| HR | 287doc 40288 | Last DHW Energy Consumed - Wh part | x10 Wh. FTC5/FTC6 only. | UINT16 | × 10 | Wh | Read | ||
| HR | 288doc 40289 | Last Total Energy Consumed | FTC5/FTC6 only. | UINT16 | kWh | Read | |||
| HR | 292doc 40293 | Last Heating Energy Produced - kWh part | FTC5/FTC6 only. | UINT16 | kWh | Read | |||
| HR | 293doc 40294 | Last Heating Energy Produced - Wh part | x10 Wh. FTC5/FTC6 only. | UINT16 | × 10 | Wh | Read | ||
| HR | 296doc 40297 | Last DHW Energy Produced - kWh part | FTC5/FTC6 only. | UINT16 | kWh | Read | |||
| HR | 297doc 40298 | Last DHW Energy Produced - Wh part | x10 Wh. FTC5/FTC6 only. | UINT16 | × 10 | Wh | Read | ||
| HR | 298doc 40299 | Last Total Energy Produced | FTC5/FTC6 only. | UINT16 | kWh | Read | |||
| HR | 299doc 40300 | Flow Rate | FTC5/FTC6 only. | UINT16 | l/min | Read |
Notes on this map
- Only holding registers ticked for FTC4, FTC5 or FTC6 are listed. Registers marked FTC5/FTC6 only (or read-only on FTC4) say so in their description. CAHV/CRHV/QAHV/EAHV-only registers (operating mode 40027, capacity control, outdoor temperature by BMS, setting water temperature, brine and condensing temperatures, electric energy 1-16) are left out.
- Most temperatures exist twice: a signed version (x100, 0x8000 = -327.68 °C) and an unsigned version at the next address that never returns a negative. Only the signed versions are listed; the unsigned twin is at address + 1.
- The gateway also exposes the same data as input registers, coils and discrete inputs; their read-only holding-register copies are what is listed here.
- Left out: 40073 Status Of Heating, 40270-40272 model profile/capacity rows and the slave heat-pump frequency/run-time rows, because the extracted table text for those rows runs together and could not be matched to a single register with certainty; also the FTC6-only block 40343-40430 (date/time, software version, hybrid boiler settings, error status 1-39).
- The register tables do not state the gateway's factory slave ID, baud rate or parity, so the defaults are left empty; they are set via registers 40005-40007 or the installation instructions.
- Note in the source: the MRC Prohibit command must not be written to Shizuoka-designed models.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Mitsubishi Electric MelcoBEMS MINI (A1M+) gateway for Ecodan FTC4/FTC5/FTC6 air-to-water systems
What Modbus registers does the Mitsubishi Electric MelcoBEMS MINI (A1M+) gateway for Ecodan FTC4/FTC5/FTC6 air-to-water systems have?
This map lists 85 registers: 85 holding registers. 18 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Mitsubishi Electric MelcoBEMS MINI (A1M+) gateway for Ecodan FTC4/FTC5/FTC6 air-to-water systems Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Every row gives both a protocol 'Addr' and a Modicon address (e.g. Addr 4 = 40005). The Addr value is what goes on the wire, so Modicon 40005 is wire address 4.
What are the minimum Modbus registers to integrate the Mitsubishi Electric MelcoBEMS MINI (A1M+) gateway for Ecodan FTC4/FTC5/FTC6 air-to-water systems?
Start with HR 13 System Type Detected (System type detected (1 = ATW)); HR 9 Fault/Error Code (hex) (Fault code, 0x8000 = no error); HR 25 System On/Off (System on/off); HR 30 Set Tank Water Temperature (signed) (DHW tank setpoint); HR 54 Thermostat Target Temperature - Zone 1 (signed) (Zone 1 thermostat target); HR 101 Flow Temperature (signed) (Flow temperature); HR 105 Tank Water Temperature (signed) (Tank water temperature); HR 93 Room Temperature - Zone 1 (signed) (Zone 1 room temperature); HR 99 Outdoor Ambient Temperature (signed) (Outdoor ambient temperature); HR 80 Heat Source Status (Heat source in use).
How do I enable Modbus control of the Mitsubishi Electric MelcoBEMS MINI (A1M+) gateway for Ecodan FTC4/FTC5/FTC6 air-to-water systems?
No enable step is described in the register tables; the gateway answers once it is powered from the unit and its Modbus address, baud rate and parity (40005-40007) match the master. See the separate MelcoBEMS MINI installation instructions.
Where is the official Mitsubishi Electric MelcoBEMS MINI (A1M+) gateway for Ecodan FTC4/FTC5/FTC6 air-to-water systems Modbus documentation?
The source is MelcoBEMS MINI (A1M+) ATW Modbus Register Tables (Document version 1.0.1), revision 2025-10-07, published free by Mitsubishi Electric at https://library.mitsubishielectric.co.uk/pdf/download_full/5537.
More Mitsubishi Electric Modbus register maps
- Variable frequency drive
Mitsubishi Electric FR-A700 inverter (RS-485 terminals, Modbus RTU)
FR-A700 series inverters (FR-A720-0.4K to 90K, FR-A740-0.4K to 500K) using the RS-485 terminals with Pr.549 = 1 (Modbus-RTU); Instruction Manual (Applied) revision E.
Also known as: FR-A720, FR-A740, FR-A700 series - Variable frequency drive
Mitsubishi Electric FR-A800 inverter (RS-485 terminals, Modbus RTU)
FR-A800 series inverters (FR-A820/A840/A842/A846, incl. -GF) using the built-in RS-485 terminals with Pr.549 = 1 (MODBUS RTU); Instruction Manual (Detailed) revision P.
Also known as: FR-A820, FR-A840, FR-A842, FR-A846, FR-A800-GF, FR-A800 series - Variable frequency drive
Mitsubishi Electric FR-D700 compact inverter (PU connector, Modbus RTU)
FR-D700 series (FR-D720/D740/D720S/D710W) using the PU connector with Pr.549 = 1; Instruction Manual (Applied) revision H.
Also known as: FR-D720, FR-D740, FR-D720S, FR-D710W - Variable frequency drive
Mitsubishi Electric FR-E700 compact inverter (PU connector, Modbus RTU)
FR-E700 series (FR-E720/E740/E720S/E710W, incl. SC safety-stop models) using the PU connector with Pr.549 = 1; Instruction Manual (Applied) revision G.
Also known as: FR-E720, FR-E740, FR-E720S, FR-E710W, FR-E700-SC - Variable frequency drive
Mitsubishi Electric FR-F800 fan and pump inverter (RS-485 terminals, Modbus RTU)
FR-F800 series inverters (FR-F820/F840/F842/F846) using the built-in RS-485 terminals with Pr.549 = 1 (MODBUS RTU); Instruction Manual (Detailed) revision G.
Also known as: FR-F820, FR-F840, FR-F842, FR-F846, FR-F800 series - VRF / split AC gateway
Mitsubishi Electric MelcoBEMS MINI (A1M) gateway for Air-To-Air split units
Procon MelcoBEMS MINI (A1M) on the CN105/CN92 connector of a Mitsubishi Electric Air-To-Air indoor unit, installation manual v1.1.11 (firmware 3.0.28 for revision 2-4 hardware, 3.1.1 for revision 5).
Also known as: MelcoBEMS MINI (A1M), A1M, Procon A1M, MelcoBEMS MINI - Air handler (heat recovery ventilation unit)
Mitsubishi Electric MelcoBEMS MINI (A1M+ / A1M) gateway for Lossnay heat recovery ventilators (LGH and VL series)
Procon MelcoBEMS MINI A1M+ (manual v1.0.3, firmware 4.1.1) on Lossnay LGH-15..200RVX-E1, LGH-150..250RVXT-E1 and VL-250..500CZPVU-R/L-E; the older A1M (manual v1.1.11) prints the identical Lossnay table.
Also known as: A1M+ Lossnay, MelcoBEMS MINI Lossnay, Procon A1M+, Procon A1M, A1M, Lossnay LGH-RVX Modbus, LGH-15RVX-E1, LGH-200RVX-E1, LGH-150RVXT-E1, LGH-250RVXT-E1, VL-250CZPVU-R-E, VL-500CZPVU-L-E, Lossnay VL Vertical - VRF / split AC gateway
Mitsubishi Electric MelcoBEMS MINI (A1M+) gateway for Air-To-Air split units (M, S and P series)
MelcoBEMS MINI (A1M+) on the CN105 connector of a Mitsubishi Electric Air-To-Air indoor unit (M series MSZ/MFZ/MLZ, S series SEZ/SLZ, P series per Appendix A), installation manual v1.0.3, firmware 4.1.1.
Also known as: A1M+, MelcoBEMS MINI, Procon A1M+, MelcoBEMS MINI A1M PLUS, A1M+ ATA - Chiller / heat pump gateway (VRF / split AC gateway)
Mitsubishi Electric MelcoBEMS MINI (A1M+) gateway for CAHV / CRHV / QAHV heat pumps and EAHV / EACV e-series chillers
Procon MelcoBEMS MINI (A1M+) firmware 4.1.0 on Mitsubishi Electric CAHV and CRHV heat pumps, QAHV CO2 heat pumps and EAHV / EACV e-series chillers (master and slave units); holding-register table only.
Also known as: A1M+, MelcoBEMS MINI, Procon A1M+, CAHV, CRHV, QAHV, EAHV, EACV, e-series chiller - Air handler DX interface (VRF / split AC gateway)
Mitsubishi Electric PAC-IF013B-E / PAC-SIF013B-E air handling unit interface (Modbus RTU)
PAC-IF013B-E and PAC-SIF013B-E interface controllers linking a Mitsubishi Electric outdoor unit to an AHU coil, Modbus manual dated September 2015 (RG79F084H01).
Also known as: PAC-IF013B-E, PAC-SIF013B-E, PAC-(S)IF013B-E - VRF / split AC gateway (retail controller)
Mitsubishi Electric Procon MelcoRETAIL MINI controller for Air-To-Air split units
Procon MelcoRETAIL MINI on the CN105/CN92 connector of Mitsubishi Electric M, S and P series Air-To-Air indoor units, installation manual v1.0.6, firmware 1.0.3.
Also known as: MelcoRETAIL MINI, Procon MelcoRETAIL MINI - Air handler (computer room air conditioner)
Mitsubishi Electric s-MEXT-G00 computer room air conditioner (ME28 relC)
Mitsubishi Electric (Hydronics & IT Cooling) s-MEXT-G00 006-044 close-control units with ME28-relC software and the Modbus serial board.
Also known as: s-MEXT, s-MEXT-G00 006-044, s-MEXT G00, ME28 relC
Other ac & vrf gateways register maps
- VRF / split AC gateway
Samsung MIM-B19N Modbus interface module (DVM / EHS / indoor units)
Samsung MIM-B19N Modbus interface module on the R1/R2 bus of one outdoor system with up to 48 indoor units (installation manual DB68-07538A-00).
Also known as: MIM-B19N, Samsung Modbus interface module - Sensor (1-Wire temperature gateway)
Unipi Technology Unipi Extension xG18 1-Wire temperature gateway
Unipi Extension xG18 RS-485 module per the Unipi Extension xG18 Modbus map v1.1.
Also known as: Unipi Extension xG18, xG18 - VRF / split AC gateway
Daikin EKMBDXB Modbus Interface DIII
EKMBDXB7V1 Modbus RTU interface on the DIII-net of Daikin VRV, Sky Air, split (via KRP928), VAM/VKM ventilation, VRV hydrobox, air curtains, ERQ control box, heating and applied units; design guide 4P642495-1A (2022.02).
Also known as: EKMBDXB7V1, Modbus Interface DIII - Heat pump gateway (VRF / split AC gateway)
Intesis (HMS Networks) IN485DAI001A000 Daikin Altherma 3 air-to-water to Modbus RTU / BACnet MS/TP gateway
Intesis (HMS Networks) IN485DAI001A000 gateway for Daikin Altherma 3 air-to-water heat pumps, set to Modbus RTU, per user manual version 1.0.2 (2025-07-18).
Also known as: IN485DAI001A000, Daikin Altherma 3 Modbus, Intesis Altherma 3, HMS Daikin Altherma gateway - VRF / split AC gateway
Intesis (HMS Networks) INMBSACA001I000 XYE-bus air conditioner to Modbus RTU interface (1 unit)
INMBSACA001I000, user manual v1.8 EN; one indoor unit at unit address 0 on its own XYE bus.
Also known as: INMBSACA001I000 - VRF / split AC gateway
Intesis (HMS Networks) INMBSFGL016O000 Fujitsu VRF to Modbus RTU / TCP gateway (up to 16 indoor units)
Intesis Modbus Server - Fujitsu VRF, order code INMBSFGL016O000 (legacy FJ-AC-MBS-16), user manual r1.0 (02/2020); up to 16 indoor units configured in MAPS.
Also known as: INMBSFGL016O000, FJ-AC-MBS-16, Intesis Modbus Server Fujitsu VRF
All ac & vrf gateways Modbus register maps →
Source: MelcoBEMS MINI (A1M+) ATW Modbus Register Tables · Document version 1.0.1 · rev. 2025-10-07. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.