  4. MelcoBEMS MINI (A1M+) gateway for Ecodan FTC4/FTC5/FTC6 air-to-water systems

Heat pump (VRF / split AC gateway) · Modbus register map

Mitsubishi Electric MelcoBEMS MINI (A1M+) gateway for Ecodan FTC4/FTC5/FTC6 air-to-water systems Modbus register map

Updated 17 November 2026

Short answer

The MelcoBEMS MINI (A1M+) is a Procon-built RS-485 Modbus RTU gateway for Mitsubishi Electric units, documented by Mitsubishi Electric UK. With an Ecodan FTC controller it exposes on/off, zone modes, tank and zone setpoints, temperatures, heater and pump states and energy totals. This map lists the holding registers that the register tables mark as applicable to FTC4, FTC5 or FTC6.

This page lists 85 Modbus registers for the Mitsubishi Electric MelcoBEMS MINI (A1M+) gateway for Ecodan FTC4/FTC5/FTC6 air-to-water systems — 18 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Mitsubishi Electric’s own free documentation (linked below) and checked against it.

Manufacturer
Mitsubishi Electric
Model
MelcoBEMS MINI (A1M+) gateway for Ecodan FTC4/FTC5/FTC6 air-to-water systems
Equipment type
Heat pump (VRF / split AC gateway)
Registers
85 (18 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
Firmware
A1M+ firmware 4.1.0
Also known as
A1M+, MelcoBEMS MINI, Procon A1M+, Ecodan FTC4, Ecodan FTC5, Ecodan FTC6
Source document
MelcoBEMS MINI (A1M+) ATW Modbus Register Tables · Document version 1.0.1 · rev. 2025-10-07
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Mitsubishi Electric MelcoBEMS MINI (A1M+) gateway for Ecodan FTC4/FTC5/FTC6 air-to-water systems

Integration in brief

Connect the A1M+ to the FTC controller as described in its installation instructions and to the BMS RS-485 line, then read 40014 to confirm an ATW system is detected and 40010 for faults. Switch the system with 40026, set the tank and zone targets at 40031/40055/40057, and poll flow, return, tank and room temperatures from 40094-40118.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 13System Type DetectedUINT16System type detected (1 = ATW)Read
HR 9Fault/Error Code (hex)UINT16Fault code, 0x8000 = no errorRead
HR 25System On/OffUINT16System on/offRead/write
HR 30Set Tank Water Temperature (signed)INT16DHW tank setpointRead/write
HR 54Thermostat Target Temperature - Zone 1 (signed)INT16Zone 1 thermostat targetRead/write
HR 101Flow Temperature (signed)INT16Flow temperatureRead
HR 105Tank Water Temperature (signed)INT16Tank water temperatureRead
HR 93Room Temperature - Zone 1 (signed)INT16Zone 1 room temperatureRead
HR 99Outdoor Ambient Temperature (signed)INT16Outdoor ambient temperatureRead
HR 80Heat Source StatusUINT16Heat source in useRead

Enable Modbus control & writes

No enable step is described in the register tables; the gateway answers once it is powered from the unit and its Modbus address, baud rate and parity (40005-40007) match the master. See the separate MelcoBEMS MINI installation instructions.

Byte order & addressing

Network setup

Watch out for

Mitsubishi Electric MelcoBEMS MINI (A1M+) gateway for Ecodan FTC4/FTC5/FTC6 air-to-water systems Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

85 of 85 shown
Mitsubishi Electric MelcoBEMS MINI (A1M+) gateway for Ecodan FTC4/FTC5/FTC6 air-to-water systems Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR4doc 40005Modbus Slave IDGateway Modbus address, 1-247.UINT16Read/write
HR5doc 40006Modbus RS-485 Baud RateUINT16Read/write0 = 9600; 1 = 1200; 2 = 2400; 3 = 4800; 4 = 9600; 5 = 14400; 6 = 19200; 7 = 28800; 8 = 38400; 9 = 56000; 10 = 57600; 11 = 115200
HR6doc 40007RS-485 Parity TypeUINT16Read/write0 = None; 1 = Even; 2 = Odd
HR9doc 40010Fault/Error Code (hex)0x8000 = no error, 0x6999 = no communication with the unit.UINT16Read
HR10doc 40011A1M+ Firmware VersionGateway firmware version.UINT16Read
HR11doc 40012Modbus Comms CounterCounts valid Modbus commands; wraps after 65535.UINT16Read
HR12doc 40013Fault Code (decimal)8000 = no error, 6999 = no communication with the unit.UINT16Read
HR13doc 40014System Type DetectedUINT16Read0 = ATA unit connected; 1 = ATW system connected; 2 = Lossnay system connected; 255 = Undetermined (no unit detected yet)
HR25doc 40026System On/OffValues 2 and 3 are reported only, not writable.UINT16Read/write0 = System OFF; 1 = System ON; 2 = Emergency Run (read only); 3 = Test Run (read only)
HR27doc 40028Operating Mode (DHW)FTC5 and FTC6 only.UINT16Read/write0 = Normal; 1 = Eco
HR28doc 40029A/C Mode - Zone 1UINT16Read/write0 = Heating Room Temp; 1 = Heating Flow Temp; 2 = Heating Heat Curve; 3 = Cooling Room Temp (not on 13K model); 4 = Cooling Flow Temp; 5 = Floor Dryup
HR29doc 40030A/C Mode - Zone 2UINT16Read/write0 = Heating Room Temp; 1 = Heating Flow Temp; 2 = Heating Heat Curve; 3 = Cooling Room Temp (not on 13K model); 4 = Cooling Flow Temp; 5 = Floor Dryup
HR30doc 40031Set Tank Water Temperature (signed)DHW tank setpoint, x100. Read-only on FTC4.INT16× 0.01°CRead/write
HR32doc 40033H/C Thermostat Target Temperature - Zone 1 (signed)x100.INT16× 0.01°CRead/write
HR34doc 40035H/C Thermostat Target Temperature - Zone 2 (signed)x100.INT16× 0.01°CRead/write
HR36doc 40037MRC ProhibitLocks functions on the main remote controller.BITMAP16Read/writebit 0 = System On/Off (0 = on, 1 = prohibit); bit 1 = Running mode (0 = on, 1 = prohibit); bit 2 = Setting temperature (0 = on, 1 = prohibit); bit 4 = Function setting (0 = normal, 1 = function setting)
HR37doc 40038Force DHWUINT16Read/write0 = Normal; 1 = Force DHW
HR38doc 40039HolidayUINT16Read/write0 = Normal; 1 = Holiday
HR39doc 40040DHW On ProhibitUINT16Read0 = On; 1 = Prohibit
HR40doc 40041Heating On Prohibit - Zone 1UINT16Read0 = On; 1 = Prohibit
HR41doc 40042Cooling On Prohibit - Zone 1Read-only on FTC4.UINT16Read/write0 = On; 1 = Prohibit
HR42doc 40043Heating On Prohibit - Zone 2UINT16Read0 = On; 1 = Prohibit
HR43doc 40044Cooling On Prohibit - Zone 2FTC5 and FTC6 only.UINT16Read/write0 = On; 1 = Prohibit
HR54doc 40055Thermostat Target Temperature - Zone 1 (signed)x100.INT16× 0.01°CRead/write
HR56doc 40057Thermostat Target Temperature - Zone 2 (signed)x100.INT16× 0.01°CRead/write
HR58doc 40059HC Control TypeUINT16Read/write0 = Heating; 1 = Cooling
HR66doc 40067Own Refrigerant Address0-32.UINT16Read
HR67doc 40068DefrostUINT16Read0 = Normal; 1 = Standby; 2 = Defrost; 3 = Waiting Restart
HR68doc 40069Residual Heat RemovalUINT16Read0 = Normal; 1 = Prepared; 2 = Residual Heat Removal
HR69doc 40070Refrigerant Error InfoUINT16Read0 = Normal; 1 = Error (System); 2 = Error (Startup); 3 = Maintenance Error
HR70doc 400717-Segment Error Code Digit 1First character of the displayed error code.UINT16Read0 = A; 1 = b; 2 = E; 3 = F; 4 = J; 5 = L; 6 = P; 7 = U
HR71doc 400727-Segment Error Code Digit 2Second character; 1-15 = 1-F.UINT16Read16 = O; 17 = H; 18 = J; 19 = L; 20 = P; 21 = U
HR73doc 40074Heat Pump Frequency - MasterCompressor frequency, 0-255 Hz.UINT16HzRead
HR80doc 40081Heat Source StatusUINT16Read0 = H/P; 1 = IH; 2 = BH; 3 = IH + BH; 4 = Boiler
HR81doc 40082Temperature Setpoint - Zone 1 (signed)x100.INT16× 0.01°CRead
HR83doc 40084Temperature Setpoint - Zone 2 (signed)x100.INT16× 0.01°CRead
HR85doc 40086Flow Temperature Setpoint - Zone 1 (signed)x100.INT16× 0.01°CRead
HR87doc 40088Flow Temperature Setpoint - Zone 2 (signed)x100.INT16× 0.01°CRead
HR89doc 40090Legionella Temperature Setpoint (signed)x100.INT16× 0.01°CRead
HR91doc 40092DHW Temperature Drop (signed)x10.INT16× 0.1°CRead
HR93doc 40094Room Temperature - Zone 1 (signed)x100.INT16× 0.01°CRead
HR95doc 40096Room Temperature - Zone 2 (signed)x100.INT16× 0.01°CRead
HR97doc 40098Refrigerant Liquid Temperature (signed)x100.INT16× 0.01°CRead
HR99doc 40100Outdoor Ambient Temperature (signed)x10.INT16× 0.1°CRead
HR101doc 40102Flow Temperature (signed)x100.INT16× 0.01°CRead
HR103doc 40104Return Temperature (signed)x100.INT16× 0.01°CRead
HR105doc 40106Tank Water Temperature (signed)x100.INT16× 0.01°CRead
HR107doc 40108Flow Temperature - Zone 1 (signed)x100.INT16× 0.01°CRead
HR109doc 40110Return Temperature - Zone 1 (signed)x100.INT16× 0.01°CRead
HR111doc 40112Flow Temperature - Zone 2 (signed)x100.INT16× 0.01°CRead
HR113doc 40114Return Temperature - Zone 2 (signed)x100.INT16× 0.01°CRead
HR115doc 40116Boiler Flow Temperature (signed)x100.INT16× 0.01°CRead
HR117doc 40118Boiler Return Temperature (signed)x100.INT16× 0.01°CRead
HR119doc 40120Room Thermo 1 (IN1)UINT16Read0 = OFF; 1 = ON
HR120doc 40121Room Thermo 2 (IN6)UINT16Read0 = OFF; 1 = ON
HR121doc 40122Flow SW1 (IN2)UINT16Read0 = OFF; 1 = ON
HR122doc 40123Flow SW2 (IN3)UINT16Read0 = OFF; 1 = ON
HR123doc 40124Flow SW3 (IN7)UINT16Read0 = OFF; 1 = ON
HR124doc 40125Demand (IN4)UINT16Read0 = OFF; 1 = ON
HR125doc 40126Outdoor Thermo (IN5)UINT16Read0 = OFF; 1 = ON
HR127doc 40128Heat Pump Master ON/OFFUINT16Read0 = Stop; 1 = Run
HR136doc 40137Heat Pump Run Time (hours)Hours part, 0-99.UINT16hRead
HR137doc 40138Heat Pump Run Time (hours x100)Hundreds-of-hours part.UINT16× 100hRead
HR144doc 40145Boiler ON/OFFUINT16Read0 = Stop; 1 = Run
HR145doc 40146Booster Heater 1 ON/OFFUINT16Read0 = Stop; 1 = Run
HR146doc 40147Booster Heater 2 ON/OFFUINT16Read0 = Stop; 1 = Run
HR147doc 40148Booster Heater 2+ ON/OFFUINT16Read0 = Stop; 1 = Run
HR148doc 40149Immersion Heater ON/OFFUINT16Read0 = Stop; 1 = Run
HR149doc 40150Water Pump 1 ON/OFFUINT16Read0 = Stop; 1 = Run
HR150doc 40151Water Pump 2 ON/OFFUINT16Read0 = Stop; 1 = Run
HR151doc 40152Water Pump 3 ON/OFFUINT16Read0 = Stop; 1 = Run
HR152doc 401533-Way Valve ON/OFFUINT16Read0 = Stop; 1 = Run
HR153doc 401542-Way Valve 2 ON/OFFUINT16Read0 = Stop; 1 = Run
HR154doc 40155Mixing Valve StepStep 0-10.UINT16Read
HR282doc 40283Last Heating Energy Consumed - kWh partFTC5/FTC6 only.UINT16kWhRead
HR283doc 40284Last Heating Energy Consumed - Wh partx10 Wh (0-99 = 0-990 Wh). FTC5/FTC6 only.UINT16× 10WhRead
HR286doc 40287Last DHW Energy Consumed - kWh partFTC5/FTC6 only.UINT16kWhRead
HR287doc 40288Last DHW Energy Consumed - Wh partx10 Wh. FTC5/FTC6 only.UINT16× 10WhRead
HR288doc 40289Last Total Energy ConsumedFTC5/FTC6 only.UINT16kWhRead
HR292doc 40293Last Heating Energy Produced - kWh partFTC5/FTC6 only.UINT16kWhRead
HR293doc 40294Last Heating Energy Produced - Wh partx10 Wh. FTC5/FTC6 only.UINT16× 10WhRead
HR296doc 40297Last DHW Energy Produced - kWh partFTC5/FTC6 only.UINT16kWhRead
HR297doc 40298Last DHW Energy Produced - Wh partx10 Wh. FTC5/FTC6 only.UINT16× 10WhRead
HR298doc 40299Last Total Energy ProducedFTC5/FTC6 only.UINT16kWhRead
HR299doc 40300Flow RateFTC5/FTC6 only.UINT16l/minRead

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Mitsubishi Electric MelcoBEMS MINI (A1M+) gateway for Ecodan FTC4/FTC5/FTC6 air-to-water systems

What Modbus registers does the Mitsubishi Electric MelcoBEMS MINI (A1M+) gateway for Ecodan FTC4/FTC5/FTC6 air-to-water systems have?

This map lists 85 registers: 85 holding registers. 18 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Mitsubishi Electric MelcoBEMS MINI (A1M+) gateway for Ecodan FTC4/FTC5/FTC6 air-to-water systems Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Every row gives both a protocol 'Addr' and a Modicon address (e.g. Addr 4 = 40005). The Addr value is what goes on the wire, so Modicon 40005 is wire address 4.

What are the minimum Modbus registers to integrate the Mitsubishi Electric MelcoBEMS MINI (A1M+) gateway for Ecodan FTC4/FTC5/FTC6 air-to-water systems?

Start with HR 13 System Type Detected (System type detected (1 = ATW)); HR 9 Fault/Error Code (hex) (Fault code, 0x8000 = no error); HR 25 System On/Off (System on/off); HR 30 Set Tank Water Temperature (signed) (DHW tank setpoint); HR 54 Thermostat Target Temperature - Zone 1 (signed) (Zone 1 thermostat target); HR 101 Flow Temperature (signed) (Flow temperature); HR 105 Tank Water Temperature (signed) (Tank water temperature); HR 93 Room Temperature - Zone 1 (signed) (Zone 1 room temperature); HR 99 Outdoor Ambient Temperature (signed) (Outdoor ambient temperature); HR 80 Heat Source Status (Heat source in use).

How do I enable Modbus control of the Mitsubishi Electric MelcoBEMS MINI (A1M+) gateway for Ecodan FTC4/FTC5/FTC6 air-to-water systems?

No enable step is described in the register tables; the gateway answers once it is powered from the unit and its Modbus address, baud rate and parity (40005-40007) match the master. See the separate MelcoBEMS MINI installation instructions.

Where is the official Mitsubishi Electric MelcoBEMS MINI (A1M+) gateway for Ecodan FTC4/FTC5/FTC6 air-to-water systems Modbus documentation?

The source is MelcoBEMS MINI (A1M+) ATW Modbus Register Tables (Document version 1.0.1), revision 2025-10-07, published free by Mitsubishi Electric at https://library.mitsubishielectric.co.uk/pdf/download_full/5537.

More Mitsubishi Electric Modbus register maps

Other ac & vrf gateways register maps

All ac & vrf gateways Modbus register maps →

Source: MelcoBEMS MINI (A1M+) ATW Modbus Register Tables · Document version 1.0.1 · rev. 2025-10-07. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.