- MelcoBEMS MINI (A1M+) gateway for CAHV / CRHV / QAHV heat pumps and EAHV / EACV e-series chillers
Chiller / heat pump gateway (VRF / split AC gateway) · Modbus register map
Mitsubishi Electric MelcoBEMS MINI (A1M+) gateway for CAHV / CRHV / QAHV heat pumps and EAHV / EACV e-series chillers Modbus register map
Updated 19 November 2026
The Procon MelcoBEMS MINI (A1M+) is an RS-485 Modbus gateway; its air-to-water (ATW) register tables carry separate applicability columns for the commercial units: CAHV and CRHV heat pumps, QAHV CO2 heat pumps and EAHV / EACV e-series chillers. This map lists the holding registers ticked for those units: on/off, operating mode, water setpoint, capacity mode and ratio, outdoor temperature from the BMS, water inlet/outlet, evaporating, condensing and brine temperatures, compressor frequencies, run states of up to 32 modules, pumps, energy counters and model information.
This page lists 131 Modbus registers for the Mitsubishi Electric MelcoBEMS MINI (A1M+) gateway for CAHV / CRHV / QAHV heat pumps and EAHV / EACV e-series chillers — 14 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Mitsubishi Electric’s own free documentation (linked below) and checked against it.
- Manufacturer
- Mitsubishi Electric
- Model
- MelcoBEMS MINI (A1M+) gateway for CAHV / CRHV / QAHV heat pumps and EAHV / EACV e-series chillers
- Equipment type
- Chiller / heat pump gateway (VRF / split AC gateway)
- Registers
- 131 (14 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- Firmware
- A1M+ firmware 4.1.0
- Also known as
- A1M+, MelcoBEMS MINI, Procon A1M+, CAHV, CRHV, QAHV, EAHV, EACV, e-series chiller
Integration notes: Mitsubishi Electric MelcoBEMS MINI (A1M+) gateway for CAHV / CRHV / QAHV heat pumps and EAHV / EACV e-series chillers
Read 40014 to confirm an ATW system and 40010 / 40013 for faults. Switch with 40026 and choose the mode with 40027 on the master unit; write the water setpoint at 40053 (x100) and read water outlet / inlet temperatures at 40102 / 40104.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 13 | System type detected | UINT16 | System type (1 = ATW) | Read |
| HR 12 | Fault code (decimal) | UINT16 | Fault code (8000 = none) | Read |
| HR 25 | System on/off | UINT16 | System on/off | Read/write |
| HR 26 | Operating mode | UINT16 | Operating mode | Read/write |
| HR 52 | Setting water temperature (signed) | INT16 | Water setpoint (x100) | Read/write |
| HR 101 | Water outlet temperature (signed) | INT16 | Water outlet temperature | Read |
| HR 103 | Water inlet temperature (signed) | INT16 | Water inlet temperature | Read |
| HR 73 | Heat pump frequency - master | UINT16 | Master compressor frequency | Read |
Enable Modbus control & writes
No enable step is described in the register tables; set the gateway's address, baud rate and parity (40005-40007) to match the BMS. See the MelcoBEMS MINI (A1M+) installation instructions.
Byte order & addressing
- Holding registers are read with FC 03 and written with FC 06 or 16; rows marked READ ONLY cannot be written.
- Baud codes 0 and 4 both mean 9600.
Network setup
- Each A1M+ reads the unit it is connected to; the slave columns show what a gateway on a slave unit can read. Wiring and DIP settings are in the separate A1M+ installation instructions.
Watch out for
- Run-time hours are split: 40137 holds 0-99 h and 40138 the hundreds (x100 h); total = 40138 x 100 + 40137.
- Energy counters 40235-40250 are 0.01 kWh in one register, so they top out at 655.35 kWh; the tables do not say what happens after that.
Mitsubishi Electric MelcoBEMS MINI (A1M+) gateway for CAHV / CRHV / QAHV heat pumps and EAHV / EACV e-series chillers Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 4doc 40005 | Modbus slave ID | 1-247. For: CAHV m/s, CRHV m/s, QAHV, EAHV/EACV m/s. | UINT16 | Read/write | ||||
| HR | 5doc 40006 | Modbus RS-485 baud rate | For: CAHV m/s, CRHV m/s, QAHV, EAHV/EACV m/s. | UINT16 | Read/write | 0 = 9600; 1 = 1200; 2 = 2400; 3 = 4800; 4 = 9600; 5 = 14400; 6 = 19200; 7 = 28800; 8 = 38400; 9 = 56000; 10 = 57600; 11 = 115200 | |||
| HR | 6doc 40007 | RS-485 parity | For: CAHV m/s, CRHV m/s, QAHV, EAHV/EACV m/s. | UINT16 | Read/write | 0 = None; 1 = Even; 2 = Odd | |||
| HR | 9doc 40010 | Fault code (hex) | For: CAHV, CRHV, QAHV, EAHV/EACV. | UINT16 | Read | 27033 = Bad communication with unit; 32768 = No error | |||
| HR | 10doc 40011 | A1M+ firmware version | For: CAHV m/s, CRHV m/s, QAHV, EAHV/EACV m/s. | UINT16 | Read | ||||
| HR | 11doc 40012 | Modbus comms counter | Wraps after 65535. For: CAHV m/s, CRHV m/s, QAHV, EAHV/EACV m/s. | UINT16 | Read | ||||
| HR | 12doc 40013 | Fault code (decimal) | For: CAHV, CRHV, QAHV, EAHV/EACV. | UINT16 | Read | 6999 = Bad communication with unit; 8000 = No error | |||
| HR | 13doc 40014 | System type detected | For: CAHV m/s, CRHV m/s, QAHV, EAHV/EACV m/s. | UINT16 | Read | 0 = ATA unit; 1 = ATW system; 2 = Lossnay system; 255 = Undetermined | |||
| HR | 25doc 40026 | System on/off | For: CAHV m/s, CRHV m/s, QAHV, EAHV/EACV m/s; read only on slaves. | UINT16 | Read/write | 0 = System off; 1 = System on; 2 = Emergency run (read only); 3 = Test run (read only) | |||
| HR | 26doc 40027 | Operating mode | For: CAHV m/s, CRHV m/s, QAHV, EAHV/EACV m/s; read only on slaves. | UINT16 | Read/write | 0 = Stop; 1 = Hot water; 2 = Heating; 3 = Cooling; 4 = No-voltage contact input (hot water storage); 5 = Freeze stat; 6 = Legionella; 7 = Heating-Eco; 8 = Mode 1; 9 = Mode 2; 10 = Mode 3; 11 = No-voltage contact input (heating up) | |||
| HR | 30doc 40031 | Thermo-off temperature (signed) | Same address as the FTC tank setpoint. For: QAHV. | INT16 | × 0.01 | °C | Read/write | ||
| HR | 36doc 40037 | MRC prohibit | Do not write to Shizuoka-designed models. For: CAHV, CRHV, QAHV, EAHV/EACV. | BITMAP16 | Read/write | bit 0 = System on/off (1 = prohibit); bit 1 = Running mode (1 = prohibit); bit 2 = Setting temperature (1 = prohibit); bit 4 = Function setting (1 = function setting) | |||
| HR | 45doc 40046 | Capacity mode | For: CAHV, CRHV, QAHV, EAHV/EACV. | UINT16 | Read/write | 0 = COP priority; 1 = Capacity priority | |||
| HR | 46doc 40047 | Capacity control ratio | 0-100 %. For: CAHV, CRHV, QAHV, EAHV/EACV. | UINT16 | % | Read/write | |||
| HR | 47doc 40048 | Fan mode | For: CRHV, QAHV, EAHV/EACV. | UINT16 | Read/write | 0 = Ordinary; 1 = Coercion | |||
| HR | 48doc 40049 | Current hour | 0-23. For: CAHV m/s, CRHV m/s, QAHV, EAHV/EACV m/s; read only on slaves. | UINT16 | h | Read/write | |||
| HR | 49doc 40050 | Current minute | 0-59. For: CAHV m/s, CRHV m/s, QAHV, EAHV/EACV m/s; read only on slaves. | UINT16 | min | Read/write | |||
| HR | 50doc 40051 | Outdoor temperature by BMS (signed) | x10; -30 to +50 °C on CAHV/CRHV/EAHV. For: CAHV, CRHV, EAHV/EACV. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 52doc 40053 | Setting water temperature (signed) | Water setpoint x100; range depends on model (see notes). For: CAHV, CRHV, QAHV, EAHV/EACV m/s. | INT16 | × 0.01 | °C | Read/write | ||
| HR | 66doc 40067 | Own refrigerant address | 0-32. For: CAHV m/s, CRHV m/s, QAHV, EAHV/EACV m/s. | UINT16 | Read | ||||
| HR | 67doc 40068 | Defrost | For: CAHV m/s, QAHV, EAHV/EACV m/s. | UINT16 | Read | 0 = Normal; 1 = Standby; 2 = Defrost; 3 = Waiting restart | |||
| HR | 69doc 40070 | Refrigerant error info | For: CAHV, CRHV, QAHV, EAHV/EACV. | UINT16 | Read | 0 = Normal; 1 = Error (system); 2 = Error (startup); 3 = Maintenance error | |||
| HR | 73doc 40074 | Heat pump frequency - master | 0-255 Hz. For: CAHV, CRHV, QAHV, EAHV/EACV. | UINT16 | Hz | Read | |||
| HR | 74doc 40075 | Heat pump frequency - slave 1 | 0-255 Hz. For: CAHV, CRHV, QAHV, EAHV/EACV. | UINT16 | Hz | Read | |||
| HR | 75doc 40076 | Heat pump frequency - slave 2 | 0-255 Hz. For: CAHV, CRHV, QAHV, EAHV/EACV. | UINT16 | Hz | Read | |||
| HR | 76doc 40077 | Heat pump frequency - slave 3 | 0-255 Hz. For: CAHV, CRHV, QAHV, EAHV/EACV. | UINT16 | Hz | Read | |||
| HR | 77doc 40078 | Heat pump frequency - slave 4 | 0-255 Hz. For: CAHV, CRHV, QAHV, EAHV/EACV. | UINT16 | Hz | Read | |||
| HR | 78doc 40079 | Heat pump frequency - slave 5 | 0-255 Hz. For: CAHV, CRHV, QAHV, EAHV/EACV. | UINT16 | Hz | Read | |||
| HR | 79doc 40080 | Heat pump frequency - slave 6 | 0-255 Hz. For: CAHV, CRHV, QAHV. | UINT16 | Hz | Read | |||
| HR | 85doc 40086 | Flow temperature setpoint - zone 1 (signed) | For: CAHV m/s, CRHV m/s, EAHV/EACV m/s. | INT16 | × 0.01 | °C | Read | ||
| HR | 99doc 40100 | Outdoor ambient temperature (signed) | x10. For: CAHV, CRHV m/s, QAHV, EAHV/EACV m/s. | INT16 | × 0.1 | °C | Read | ||
| HR | 101doc 40102 | Water outlet temperature (signed) | For: CAHV m/s, CRHV m/s, QAHV, EAHV/EACV m/s. | INT16 | × 0.01 | °C | Read | ||
| HR | 103doc 40104 | Water inlet temperature (signed) | For: CAHV m/s, CRHV m/s, QAHV, EAHV/EACV m/s. | INT16 | × 0.01 | °C | Read | ||
| HR | 107doc 40108 | External water temperature 1 (signed) | For: CAHV, CRHV, QAHV, EAHV/EACV. | INT16 | × 0.01 | °C | Read | ||
| HR | 109doc 40110 | External water temperature 3 (signed) | For: QAHV. | INT16 | × 0.01 | °C | Read | ||
| HR | 111doc 40112 | External water temperature 2 / 4 (signed) | Ext. water temp 2 on CAHV/CRHV, 4 on QAHV. For: CAHV, CRHV, QAHV. | INT16 | × 0.01 | °C | Read | ||
| HR | 127doc 40128 | Heat pump master on/off | For: CAHV, CRHV, QAHV, EAHV/EACV. | UINT16 | Read | 0 = Stop; 1 = Run | |||
| HR | 128doc 40129 | Heat pump slave 1 on/off | Address 2 on CAHV/CRHV. For: CAHV, CRHV, QAHV, EAHV/EACV. | UINT16 | Read | 0 = Stop; 1 = Run | |||
| HR | 129doc 40130 | Heat pump slave 2 on/off | Address 3 on CAHV/CRHV. For: CAHV, CRHV. | UINT16 | Read | 0 = Stop; 1 = Run | |||
| HR | 130doc 40131 | Heat pump slave 3 on/off | Address 4 on CAHV/CRHV. For: CAHV, CRHV. | UINT16 | Read | 0 = Stop; 1 = Run | |||
| HR | 131doc 40132 | Heat pump slave 4 on/off | Address 5 on CAHV/CRHV. For: CAHV, CRHV. | UINT16 | Read | 0 = Stop; 1 = Run | |||
| HR | 132doc 40133 | Heat pump slave 5 on/off | Address 6 on CAHV/CRHV. For: CAHV, CRHV. | UINT16 | Read | 0 = Stop; 1 = Run | |||
| HR | 133doc 40134 | Heat pump slave 6 on/off | Address 7 on CAHV/CRHV. For: CAHV, CRHV. | UINT16 | Read | 0 = Stop; 1 = Run | |||
| HR | 134doc 40135 | Heat pump slave 7 on/off | Address 8 on CAHV/CRHV. For: CAHV, CRHV. | UINT16 | Read | 0 = Stop; 1 = Run | |||
| HR | 135doc 40136 | Heat pump slave 8 on/off | Address 9 on CAHV/CRHV. For: CAHV, CRHV. | UINT16 | Read | 0 = Stop; 1 = Run | |||
| HR | 136doc 40137 | Heat pump run time (hours) | Units part, 0-99 h. For: CAHV, CRHV. | UINT16 | h | Read | |||
| HR | 137doc 40138 | Heat pump run time (hours x100) | Hundreds part; add to 40137. For: CAHV, CRHV. | UINT16 | × 100 | h | Read | ||
| HR | 144doc 40145 | Boiler / external heater operation 1 | Boiler on EAHV/EACV; external heater 1 on CAHV/CRHV. For: CAHV, CRHV, EAHV/EACV m/s. | UINT16 | Read | 0 = Stop; 1 = Run | |||
| HR | 149doc 40150 | Water pump 1 on/off | For: CAHV, CRHV m/s, QAHV, EAHV/EACV m/s. | UINT16 | Read | 0 = Stop; 1 = Run | |||
| HR | 150doc 40151 | Water pump 2 on/off | For: CAHV. | UINT16 | Read | 0 = Stop; 1 = Run | |||
| HR | 151doc 40152 | Water pump 3 on/off | For: CAHV. | UINT16 | Read | 0 = Stop; 1 = Run | |||
| HR | 167doc 40168 | Heat pump frequency - slave 7 | 0-255 Hz. For: CAHV, CRHV, QAHV. | UINT16 | Hz | Read | |||
| HR | 168doc 40169 | Heat pump frequency - slave 8 | 0-255 Hz. For: CAHV, CRHV, QAHV. | UINT16 | Hz | Read | |||
| HR | 169doc 40170 | Heat pump frequency - slave 9 | 0-255 Hz. For: CAHV, CRHV, QAHV. | UINT16 | Hz | Read | |||
| HR | 170doc 40171 | Heat pump frequency - slave 10 | 0-255 Hz. For: CAHV, CRHV, QAHV. | UINT16 | Hz | Read | |||
| HR | 171doc 40172 | Heat pump frequency - slave 11 | 0-255 Hz. For: CAHV, CRHV, QAHV. | UINT16 | Hz | Read | |||
| HR | 172doc 40173 | Heat pump frequency - slave 12 | 0-255 Hz. For: CAHV, CRHV, QAHV. | UINT16 | Hz | Read | |||
| HR | 173doc 40174 | Heat pump frequency - slave 13 | 0-255 Hz. For: CAHV, CRHV, QAHV. | UINT16 | Hz | Read | |||
| HR | 174doc 40175 | Heat pump frequency - slave 14 | 0-255 Hz. For: CAHV, CRHV, QAHV. | UINT16 | Hz | Read | |||
| HR | 175doc 40176 | Heat pump frequency - slave 15 | 0-255 Hz. For: CAHV, CRHV, QAHV. | UINT16 | Hz | Read | |||
| HR | 176doc 40177 | Heat pump 10 on/off | For: CAHV, CRHV, QAHV. | UINT16 | Read | 0 = Stop; 1 = Run | |||
| HR | 177doc 40178 | Heat pump 11 on/off | For: CAHV, CRHV, QAHV. | UINT16 | Read | 0 = Stop; 1 = Run | |||
| HR | 178doc 40179 | Heat pump 12 on/off | For: CAHV, CRHV, QAHV. | UINT16 | Read | 0 = Stop; 1 = Run | |||
| HR | 179doc 40180 | Heat pump 13 on/off | For: CAHV, CRHV, QAHV. | UINT16 | Read | 0 = Stop; 1 = Run | |||
| HR | 180doc 40181 | Heat pump 14 on/off | For: CAHV, CRHV, QAHV. | UINT16 | Read | 0 = Stop; 1 = Run | |||
| HR | 181doc 40182 | Heat pump 15 on/off | For: CAHV, CRHV, QAHV. | UINT16 | Read | 0 = Stop; 1 = Run | |||
| HR | 182doc 40183 | Heat pump 16 on/off | For: CAHV, CRHV, QAHV. | UINT16 | Read | 0 = Stop; 1 = Run | |||
| HR | 183doc 40184 | Heat pump 17 on/off | For: CAHV, CRHV, QAHV. | UINT16 | Read | 0 = Stop; 1 = Run | |||
| HR | 184doc 40185 | Heat pump 18 on/off | For: CAHV, CRHV. | UINT16 | Read | 0 = Stop; 1 = Run | |||
| HR | 185doc 40186 | Heat pump 19 on/off | For: CAHV, CRHV. | UINT16 | Read | 0 = Stop; 1 = Run | |||
| HR | 186doc 40187 | Heat pump 20 on/off | For: CAHV, CRHV. | UINT16 | Read | 0 = Stop; 1 = Run | |||
| HR | 187doc 40188 | Heat pump 21 on/off | For: CAHV, CRHV. | UINT16 | Read | 0 = Stop; 1 = Run | |||
| HR | 188doc 40189 | Heat pump 22 on/off | For: CAHV, CRHV. | UINT16 | Read | 0 = Stop; 1 = Run | |||
| HR | 189doc 40190 | Heat pump 23 on/off | For: CAHV, CRHV. | UINT16 | Read | 0 = Stop; 1 = Run | |||
| HR | 190doc 40191 | Heat pump 24 on/off | For: CAHV, CRHV. | UINT16 | Read | 0 = Stop; 1 = Run | |||
| HR | 191doc 40192 | Heat pump 25 on/off | For: CAHV, CRHV. | UINT16 | Read | 0 = Stop; 1 = Run | |||
| HR | 192doc 40193 | Heat pump 26 on/off | For: CAHV, CRHV. | UINT16 | Read | 0 = Stop; 1 = Run | |||
| HR | 193doc 40194 | Heat pump 27 on/off | For: CAHV, CRHV. | UINT16 | Read | 0 = Stop; 1 = Run | |||
| HR | 194doc 40195 | Heat pump 28 on/off | For: CAHV, CRHV. | UINT16 | Read | 0 = Stop; 1 = Run | |||
| HR | 195doc 40196 | Heat pump 29 on/off | For: CAHV, CRHV. | UINT16 | Read | 0 = Stop; 1 = Run | |||
| HR | 196doc 40197 | Heat pump 30 on/off | For: CAHV, CRHV. | UINT16 | Read | 0 = Stop; 1 = Run | |||
| HR | 197doc 40198 | Heat pump 31 on/off | For: CAHV, CRHV. | UINT16 | Read | 0 = Stop; 1 = Run | |||
| HR | 198doc 40199 | Heat pump 32 on/off | For: CAHV, CRHV. | UINT16 | Read | 0 = Stop; 1 = Run | |||
| HR | 215doc 40216 | External heater on/off | For: CRHV. | UINT16 | Read | 0 = Stop; 1 = Run | |||
| HR | 216doc 40217 | Water pump 4 on/off | For: CAHV. | UINT16 | Read | 0 = Stop; 1 = Run | |||
| HR | 217doc 40218 | Water pump 5 on/off | For: CAHV. | UINT16 | Read | 0 = Stop; 1 = Run | |||
| HR | 218doc 40219 | Water pump 6 on/off | For: CAHV. | UINT16 | Read | 0 = Stop; 1 = Run | |||
| HR | 219doc 40220 | Water pump 7 on/off | For: CAHV. | UINT16 | Read | 0 = Stop; 1 = Run | |||
| HR | 220doc 40221 | Water pump 8 on/off | For: CAHV. | UINT16 | Read | 0 = Stop; 1 = Run | |||
| HR | 221doc 40222 | Water pump 9 on/off | For: CAHV. | UINT16 | Read | 0 = Stop; 1 = Run | |||
| HR | 222doc 40223 | Water pump 10 on/off | For: CAHV. | UINT16 | Read | 0 = Stop; 1 = Run | |||
| HR | 223doc 40224 | Water pump 11 on/off | For: CAHV. | UINT16 | Read | 0 = Stop; 1 = Run | |||
| HR | 224doc 40225 | Water pump 12 on/off | For: CAHV. | UINT16 | Read | 0 = Stop; 1 = Run | |||
| HR | 225doc 40226 | Water pump 13 on/off | For: CAHV. | UINT16 | Read | 0 = Stop; 1 = Run | |||
| HR | 226doc 40227 | Water pump 14 on/off | For: CAHV. | UINT16 | Read | 0 = Stop; 1 = Run | |||
| HR | 227doc 40228 | Water pump 15 on/off | For: CAHV. | UINT16 | Read | 0 = Stop; 1 = Run | |||
| HR | 228doc 40229 | Water pump 16 on/off | For: CAHV. | UINT16 | Read | 0 = Stop; 1 = Run | |||
| HR | 229doc 40230 | Drain pan heater / antifreeze piping heater | Drain pan heater on CRHV/EAHV; antifreeze piping heater on QAHV. For: CRHV m/s, QAHV, EAHV/EACV m/s. | UINT16 | Read | 0 = Stop; 1 = Run | |||
| HR | 230doc 40231 | Evaporating temperature (signed) | For: CAHV m/s, CRHV m/s, QAHV, EAHV/EACV m/s. | INT16 | × 0.01 | °C | Read | ||
| HR | 232doc 40233 | Condensing temperature (signed) | For: CAHV m/s, CRHV m/s, QAHV, EAHV/EACV m/s. | INT16 | × 0.01 | °C | Read | ||
| HR | 234doc 40235 | Electric energy 1 | 0-655.35 kWh. Reads 0 on CAHV/CRHV 2013 models. For: CAHV m/s, CRHV m/s, EAHV/EACV m/s. | UINT16 | × 0.01 | kWh | Read | ||
| HR | 235doc 40236 | Electric energy 2 | 0-655.35 kWh. Reads 0 on CAHV/CRHV 2013 models. For: CAHV m/s, CRHV m/s, EAHV/EACV m/s. | UINT16 | × 0.01 | kWh | Read | ||
| HR | 236doc 40237 | Electric energy 3 | 0-655.35 kWh. Reads 0 on CAHV/CRHV 2013 models. For: CAHV m/s, CRHV m/s, EAHV/EACV m/s. | UINT16 | × 0.01 | kWh | Read | ||
| HR | 237doc 40238 | Electric energy 4 | 0-655.35 kWh. Reads 0 on CAHV/CRHV 2013 models. For: CAHV m/s, CRHV m/s, EAHV/EACV m/s. | UINT16 | × 0.01 | kWh | Read | ||
| HR | 238doc 40239 | Electric energy 5 | 0-655.35 kWh. Reads 0 on CAHV/CRHV 2013 models. For: CAHV m/s, CRHV m/s, EAHV/EACV m/s. | UINT16 | × 0.01 | kWh | Read | ||
| HR | 239doc 40240 | Electric energy 6 | 0-655.35 kWh. Reads 0 on CAHV/CRHV 2013 models. For: CAHV m/s, CRHV m/s, EAHV/EACV m/s. | UINT16 | × 0.01 | kWh | Read | ||
| HR | 240doc 40241 | Electric energy 7 | 0-655.35 kWh. Reads 0 on CAHV/CRHV 2013 models. For: CAHV m/s, CRHV m/s, EAHV/EACV m/s. | UINT16 | × 0.01 | kWh | Read | ||
| HR | 241doc 40242 | Electric energy 8 | 0-655.35 kWh. Reads 0 on CAHV/CRHV 2013 models. For: CAHV m/s, CRHV m/s, EAHV/EACV m/s. | UINT16 | × 0.01 | kWh | Read | ||
| HR | 242doc 40243 | Electric energy 9 | 0-655.35 kWh. Reads 0 on CAHV/CRHV 2013 models. For: CAHV m/s, CRHV m/s, EAHV/EACV m/s. | UINT16 | × 0.01 | kWh | Read | ||
| HR | 243doc 40244 | Electric energy 10 | 0-655.35 kWh. Reads 0 on CAHV/CRHV 2013 models. For: CAHV m/s, CRHV m/s, EAHV/EACV m/s. | UINT16 | × 0.01 | kWh | Read | ||
| HR | 244doc 40245 | Electric energy 11 | 0-655.35 kWh. Reads 0 on CAHV/CRHV 2013 models. For: CAHV m/s, CRHV m/s, EAHV/EACV m/s. | UINT16 | × 0.01 | kWh | Read | ||
| HR | 245doc 40246 | Electric energy 12 | 0-655.35 kWh. Reads 0 on CAHV/CRHV 2013 models. For: CAHV m/s, CRHV m/s, EAHV/EACV m/s. | UINT16 | × 0.01 | kWh | Read | ||
| HR | 246doc 40247 | Electric energy 13 | 0-655.35 kWh. Reads 0 on CAHV/CRHV 2013 models. For: CAHV m/s, CRHV m/s, EAHV/EACV m/s. | UINT16 | × 0.01 | kWh | Read | ||
| HR | 247doc 40248 | Electric energy 14 | 0-655.35 kWh. Reads 0 on CAHV/CRHV 2013 models. For: CAHV m/s, CRHV m/s, EAHV/EACV m/s. | UINT16 | × 0.01 | kWh | Read | ||
| HR | 248doc 40249 | Electric energy 15 | 0-655.35 kWh. Reads 0 on CAHV/CRHV 2013 models. For: CAHV m/s, CRHV m/s, EAHV/EACV m/s. | UINT16 | × 0.01 | kWh | Read | ||
| HR | 249doc 40250 | Electric energy 16 | 0-655.35 kWh. Reads 0 on CAHV/CRHV 2013 models. For: CAHV m/s, CRHV m/s, EAHV/EACV m/s. | UINT16 | × 0.01 | kWh | Read | ||
| HR | 250doc 40251 | Brine inlet temperature (signed) | For: CRHV m/s. | INT16 | × 0.01 | °C | Read | ||
| HR | 252doc 40253 | Brine outlet temperature 1 (signed) | For: CRHV m/s. | INT16 | × 0.01 | °C | Read | ||
| HR | 254doc 40255 | Brine outlet temperature 2 (signed) | For: CRHV m/s. | INT16 | × 0.01 | °C | Read | ||
| HR | 256doc 40257 | Condensing temperature 2 (signed) | For: CAHV m/s, CRHV m/s, EAHV/EACV m/s. | INT16 | × 0.01 | °C | Read | ||
| HR | 258doc 40259 | Water outlet temperature 2 (signed) | For: CAHV m/s, CRHV m/s, EAHV/EACV m/s. | INT16 | × 0.01 | °C | Read | ||
| HR | 260doc 40261 | Evaporating temperature 2 (signed) | For: CAHV m/s, CRHV m/s, EAHV/EACV m/s. | INT16 | × 0.01 | °C | Read | ||
| HR | 262doc 40263 | Water pump 1 PWM duty | 0-100 %. For: QAHV. | UINT16 | % | Read | |||
| HR | 264doc 40265 | 3-way valve 1 | For: CAHV, QAHV. | UINT16 | Read | 0 = Off (stop); 1 = On (run) | |||
| HR | 265doc 40266 | Protocol version (upper) | BCD; V3.01 = 3 upper, 1 lower. For: CAHV m/s, CRHV m/s, QAHV, EAHV/EACV m/s. | UINT16 | Read | ||||
| HR | 266doc 40267 | Protocol version (lower) | BCD. For: CAHV m/s, CRHV m/s, QAHV, EAHV/EACV m/s. | UINT16 | Read | ||||
| HR | 267doc 40268 | Model version (upper) | BCD; V2.00 = 2 upper, 0 lower. For: CAHV m/s, CRHV m/s, QAHV, EAHV/EACV m/s. | UINT16 | Read | ||||
| HR | 268doc 40269 | Model version (lower) | BCD. For: CAHV m/s, CRHV m/s, QAHV, EAHV/EACV m/s. | UINT16 | Read | ||||
| HR | 269doc 40270 | Capacity of supplying electricity | 0-25.5 W. For: CAHV m/s, CRHV m/s, QAHV, EAHV/EACV m/s. | UINT16 | × 0.1 | W | Read | ||
| HR | 270doc 40271 | Model profile 1 | For: CAHV m/s, CRHV m/s, QAHV, EAHV/EACV m/s. | UINT16 | Read | 0 = FTC2B; 1 = FTC4; 2 = FTC5; 3 = FTC6; 128 = CAHV1A; 129 = CAHV1B; 130 = CRHV1A; 131 = CRHV1B; 132 = EAHV1A; 133 = EAHV1B; 134 = QAHV1A; 135 = QAHV1B; 144 = PWFY1 | |||
| HR | 271doc 40272 | Model profile 2 (refrigerant address) | 0-255. For: CAHV m/s, CRHV m/s, QAHV, EAHV/EACV m/s. | UINT16 | Read |
Notes on this map
- Only holding registers ticked for at least one of CAHV master/slave, CRHV master/slave, QAHV master or EAHV/EACV master/slave are listed; each description names the units it applies to (m/s = master and slave). The FTC (Ecodan) part of the same tables is a separate file in this library.
- Several addresses carry a different name for the commercial units than for FTC (e.g. 40102 'Water Outlet Temperature' instead of 'Flow Temperature', 40031 'Thermo-off Temperature' on QAHV); the commercial name is used here.
- Temperatures are x100 (0.01 °C) except outdoor temperatures 40051 and 40100 (x10). Every signed temperature has an unsigned twin at the next address; only the signed versions are listed.
- Ticks shown in brackets with note #18 (slave units on 40026, 40027, 40049, 40050) are read-only values.
- Setting water temperature (40053) range per the notes: CAHV +30 to +65 °C, CRHV +25 to +65 °C, QAHV +40 to +90 °C, EAHV +30 to +55 °C heating and +5 to +25 °C cooling. Outdoor temperature by BMS (40051): -30 to +50 °C.
- Model notes: on CAHV 2013 models Stop and Cooling modes are not supported (CRHV 2013: also Legionella); EAHV 2015 models do not support Stop, Hot Water, No-Voltage Contact and Legionella modes; Emergency/Test Run are not supported on CAHV/CRHV 2013 and EAHV 2015; MRC prohibit bit 4 is not supported on those models; capacity mode is not supported on CAHV 2013; values marked #1 read 0 on CAHV/CRHV 2013 models.
- Left out: 40114 (printed '(signed)' but with the unsigned note **), and the input register, coil and discrete input tables, which repeat the same data.
- The MRC Prohibit register must not be written to Shizuoka-designed models (note ††).
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Mitsubishi Electric MelcoBEMS MINI (A1M+) gateway for CAHV / CRHV / QAHV heat pumps and EAHV / EACV e-series chillers
What Modbus registers does the Mitsubishi Electric MelcoBEMS MINI (A1M+) gateway for CAHV / CRHV / QAHV heat pumps and EAHV / EACV e-series chillers have?
This map lists 131 registers: 131 holding registers. 14 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Mitsubishi Electric MelcoBEMS MINI (A1M+) gateway for CAHV / CRHV / QAHV heat pumps and EAHV / EACV e-series chillers Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Every row gives a protocol 'Addr' and a Modicon address (Addr 25 = 40026). The Addr value is the wire address.
What are the minimum Modbus registers to integrate the Mitsubishi Electric MelcoBEMS MINI (A1M+) gateway for CAHV / CRHV / QAHV heat pumps and EAHV / EACV e-series chillers?
Start with HR 13 System type detected (System type (1 = ATW)); HR 12 Fault code (decimal) (Fault code (8000 = none)); HR 25 System on/off (System on/off); HR 26 Operating mode (Operating mode); HR 52 Setting water temperature (signed) (Water setpoint (x100)); HR 101 Water outlet temperature (signed) (Water outlet temperature); HR 103 Water inlet temperature (signed) (Water inlet temperature); HR 73 Heat pump frequency - master (Master compressor frequency).
How do I enable Modbus control of the Mitsubishi Electric MelcoBEMS MINI (A1M+) gateway for CAHV / CRHV / QAHV heat pumps and EAHV / EACV e-series chillers?
No enable step is described in the register tables; set the gateway's address, baud rate and parity (40005-40007) to match the BMS. See the MelcoBEMS MINI (A1M+) installation instructions.
Where is the official Mitsubishi Electric MelcoBEMS MINI (A1M+) gateway for CAHV / CRHV / QAHV heat pumps and EAHV / EACV e-series chillers Modbus documentation?
The source is MelcoBEMS MINI (A1M+) ATW Modbus Register Tables (Document version 1.0.1), revision 2025-10-07, published free by Mitsubishi Electric at https://library.mitsubishielectric.co.uk/pdf/download_full/5537.
More Mitsubishi Electric Modbus register maps
- Variable frequency drive
Mitsubishi Electric FR-A700 inverter (RS-485 terminals, Modbus RTU)
FR-A700 series inverters (FR-A720-0.4K to 90K, FR-A740-0.4K to 500K) using the RS-485 terminals with Pr.549 = 1 (Modbus-RTU); Instruction Manual (Applied) revision E.
Also known as: FR-A720, FR-A740, FR-A700 series - Variable frequency drive
Mitsubishi Electric FR-A800 inverter (RS-485 terminals, Modbus RTU)
FR-A800 series inverters (FR-A820/A840/A842/A846, incl. -GF) using the built-in RS-485 terminals with Pr.549 = 1 (MODBUS RTU); Instruction Manual (Detailed) revision P.
Also known as: FR-A820, FR-A840, FR-A842, FR-A846, FR-A800-GF, FR-A800 series - Variable frequency drive
Mitsubishi Electric FR-D700 compact inverter (PU connector, Modbus RTU)
FR-D700 series (FR-D720/D740/D720S/D710W) using the PU connector with Pr.549 = 1; Instruction Manual (Applied) revision H.
Also known as: FR-D720, FR-D740, FR-D720S, FR-D710W - Variable frequency drive
Mitsubishi Electric FR-E700 compact inverter (PU connector, Modbus RTU)
FR-E700 series (FR-E720/E740/E720S/E710W, incl. SC safety-stop models) using the PU connector with Pr.549 = 1; Instruction Manual (Applied) revision G.
Also known as: FR-E720, FR-E740, FR-E720S, FR-E710W, FR-E700-SC - Variable frequency drive
Mitsubishi Electric FR-F800 fan and pump inverter (RS-485 terminals, Modbus RTU)
FR-F800 series inverters (FR-F820/F840/F842/F846) using the built-in RS-485 terminals with Pr.549 = 1 (MODBUS RTU); Instruction Manual (Detailed) revision G.
Also known as: FR-F820, FR-F840, FR-F842, FR-F846, FR-F800 series - VRF / split AC gateway
Mitsubishi Electric MelcoBEMS MINI (A1M) gateway for Air-To-Air split units
Procon MelcoBEMS MINI (A1M) on the CN105/CN92 connector of a Mitsubishi Electric Air-To-Air indoor unit, installation manual v1.1.11 (firmware 3.0.28 for revision 2-4 hardware, 3.1.1 for revision 5).
Also known as: MelcoBEMS MINI (A1M), A1M, Procon A1M, MelcoBEMS MINI - Air handler (heat recovery ventilation unit)
Mitsubishi Electric MelcoBEMS MINI (A1M+ / A1M) gateway for Lossnay heat recovery ventilators (LGH and VL series)
Procon MelcoBEMS MINI A1M+ (manual v1.0.3, firmware 4.1.1) on Lossnay LGH-15..200RVX-E1, LGH-150..250RVXT-E1 and VL-250..500CZPVU-R/L-E; the older A1M (manual v1.1.11) prints the identical Lossnay table.
Also known as: A1M+ Lossnay, MelcoBEMS MINI Lossnay, Procon A1M+, Procon A1M, A1M, Lossnay LGH-RVX Modbus, LGH-15RVX-E1, LGH-200RVX-E1, LGH-150RVXT-E1, LGH-250RVXT-E1, VL-250CZPVU-R-E, VL-500CZPVU-L-E, Lossnay VL Vertical - VRF / split AC gateway
Mitsubishi Electric MelcoBEMS MINI (A1M+) gateway for Air-To-Air split units (M, S and P series)
MelcoBEMS MINI (A1M+) on the CN105 connector of a Mitsubishi Electric Air-To-Air indoor unit (M series MSZ/MFZ/MLZ, S series SEZ/SLZ, P series per Appendix A), installation manual v1.0.3, firmware 4.1.1.
Also known as: A1M+, MelcoBEMS MINI, Procon A1M+, MelcoBEMS MINI A1M PLUS, A1M+ ATA - Heat pump (VRF / split AC gateway)
Mitsubishi Electric MelcoBEMS MINI (A1M+) gateway for Ecodan FTC4/FTC5/FTC6 air-to-water systems
Procon MelcoBEMS MINI (A1M+) firmware 4.1.0 connected to an Ecodan FTC4, FTC5 or FTC6 air-to-water controller; holding-register table only.
Also known as: A1M+, MelcoBEMS MINI, Procon A1M+, Ecodan FTC4, Ecodan FTC5, Ecodan FTC6 - Air handler DX interface (VRF / split AC gateway)
Mitsubishi Electric PAC-IF013B-E / PAC-SIF013B-E air handling unit interface (Modbus RTU)
PAC-IF013B-E and PAC-SIF013B-E interface controllers linking a Mitsubishi Electric outdoor unit to an AHU coil, Modbus manual dated September 2015 (RG79F084H01).
Also known as: PAC-IF013B-E, PAC-SIF013B-E, PAC-(S)IF013B-E - VRF / split AC gateway (retail controller)
Mitsubishi Electric Procon MelcoRETAIL MINI controller for Air-To-Air split units
Procon MelcoRETAIL MINI on the CN105/CN92 connector of Mitsubishi Electric M, S and P series Air-To-Air indoor units, installation manual v1.0.6, firmware 1.0.3.
Also known as: MelcoRETAIL MINI, Procon MelcoRETAIL MINI - Air handler (computer room air conditioner)
Mitsubishi Electric s-MEXT-G00 computer room air conditioner (ME28 relC)
Mitsubishi Electric (Hydronics & IT Cooling) s-MEXT-G00 006-044 close-control units with ME28-relC software and the Modbus serial board.
Also known as: s-MEXT, s-MEXT-G00 006-044, s-MEXT G00, ME28 relC
Other ac & vrf gateways register maps
- VRF / split AC gateway
Samsung CycloGic CL-MC03 Modbus interface module (Samsung DVM / CAC / RAC)
CycloGic CL-MC03*** series Modbus interface modules (1 to 64 indoor units) for Samsung DVM, CAC, FJM and RAC units, instruction manual Rev. 2 (Oct. 2017).
Also known as: CL-MC0301C, CL-MC0308C, CL-MC0316C, CL-MC0332C, CL-MC0364C, CycloGic Modbus Interface Module - Boiler gateway (OpenTherm to Modbus RTU)
Unipi Technology MM-OT101 Modbus / OpenTherm gateway
Unipi MM-OT101 DIN-rail gateway between Modbus RTU (RS-485) and OpenTherm/Plus boilers and thermostats, per its technical documentation.
Also known as: MM-OT101, MM-OT1010, Unipi OpenTherm gateway - VRF / split AC gateway
Daikin DTA116A51 D-NET / Modbus communication adaptor (VRV)
DTA116A51 adaptor with up to 16 VRV indoor units (D-NET 1-00 to 1-15), per functional specification CB13A033 first edition.
Also known as: DTA116A51, DIII-NET Modbus adaptor, D3NET Modbus adapter - Split AC unit (VRF / split AC gateway built in)
Gree U-Match all-DC-inverter duct / cassette / floor-ceiling units (built-in Modbus)
Gree U-Match fourth-generation all-DC-inverter light-commercial units whose controller has the integrated Modbus RTU interface; Chinese-English protocol dated 2018-03-07.
Also known as: U-Match, Gree U-Match 4th generation DC inverter, U-Match BMS Modbus - VRF / split AC gateway
Intesis (HMS Networks) IN770AIR***O000 700 Series Air Gateway, Panasonic application (Modbus)
Intesis 700 Series Air Gateway IN770AIR***O000 with the Panasonic application (U1U2 P-Link / S-Link), Modbus RTU / TCP server, user manual version 1.1.7 (2025-12-09).
Also known as: IN770AIR00MO000, IN770AIR00SO000, IN770AIRXXSO000 - VRF / split AC gateway
Intesis (HMS Networks) INMBSFGL001R000 Fujitsu AC to Modbus RTU gateway
One Fujitsu indoor unit, or a group of up to 16 controlled together as one, on the 3-wire BWR remote-controller bus via INMBSFGL001R000, user manual v2.4 (02/2025).
Also known as: INMBSFGL001R000, Intesis Fujitsu Modbus
All ac & vrf gateways Modbus register maps →
Source: MelcoBEMS MINI (A1M+) ATW Modbus Register Tables · Document version 1.0.1 · rev. 2025-10-07. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.