Chiller / heat pump gateway (VRF / split AC gateway) · Modbus register map

Mitsubishi Electric MelcoBEMS MINI (A1M+) gateway for CAHV / CRHV / QAHV heat pumps and EAHV / EACV e-series chillers Modbus register map

Updated 19 November 2026

Short answer

The Procon MelcoBEMS MINI (A1M+) is an RS-485 Modbus gateway; its air-to-water (ATW) register tables carry separate applicability columns for the commercial units: CAHV and CRHV heat pumps, QAHV CO2 heat pumps and EAHV / EACV e-series chillers. This map lists the holding registers ticked for those units: on/off, operating mode, water setpoint, capacity mode and ratio, outdoor temperature from the BMS, water inlet/outlet, evaporating, condensing and brine temperatures, compressor frequencies, run states of up to 32 modules, pumps, energy counters and model information.

This page lists 131 Modbus registers for the Mitsubishi Electric MelcoBEMS MINI (A1M+) gateway for CAHV / CRHV / QAHV heat pumps and EAHV / EACV e-series chillers — 14 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Mitsubishi Electric’s own free documentation (linked below) and checked against it.

Manufacturer
Mitsubishi Electric
Model
MelcoBEMS MINI (A1M+) gateway for CAHV / CRHV / QAHV heat pumps and EAHV / EACV e-series chillers
Equipment type
Chiller / heat pump gateway (VRF / split AC gateway)
Registers
131 (14 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
Firmware
A1M+ firmware 4.1.0
Also known as
A1M+, MelcoBEMS MINI, Procon A1M+, CAHV, CRHV, QAHV, EAHV, EACV, e-series chiller
Source document
MelcoBEMS MINI (A1M+) ATW Modbus Register Tables · Document version 1.0.1 · rev. 2025-10-07
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Mitsubishi Electric MelcoBEMS MINI (A1M+) gateway for CAHV / CRHV / QAHV heat pumps and EAHV / EACV e-series chillers

Integration in brief

Read 40014 to confirm an ATW system and 40010 / 40013 for faults. Switch with 40026 and choose the mode with 40027 on the master unit; write the water setpoint at 40053 (x100) and read water outlet / inlet temperatures at 40102 / 40104.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 13System type detectedUINT16System type (1 = ATW)Read
HR 12Fault code (decimal)UINT16Fault code (8000 = none)Read
HR 25System on/offUINT16System on/offRead/write
HR 26Operating modeUINT16Operating modeRead/write
HR 52Setting water temperature (signed)INT16Water setpoint (x100)Read/write
HR 101Water outlet temperature (signed)INT16Water outlet temperatureRead
HR 103Water inlet temperature (signed)INT16Water inlet temperatureRead
HR 73Heat pump frequency - masterUINT16Master compressor frequencyRead

Enable Modbus control & writes

No enable step is described in the register tables; set the gateway's address, baud rate and parity (40005-40007) to match the BMS. See the MelcoBEMS MINI (A1M+) installation instructions.

Byte order & addressing

Network setup

Watch out for

Mitsubishi Electric MelcoBEMS MINI (A1M+) gateway for CAHV / CRHV / QAHV heat pumps and EAHV / EACV e-series chillers Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

131 of 131 shown
Mitsubishi Electric MelcoBEMS MINI (A1M+) gateway for CAHV / CRHV / QAHV heat pumps and EAHV / EACV e-series chillers Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR4doc 40005Modbus slave ID1-247. For: CAHV m/s, CRHV m/s, QAHV, EAHV/EACV m/s.UINT16Read/write
HR5doc 40006Modbus RS-485 baud rateFor: CAHV m/s, CRHV m/s, QAHV, EAHV/EACV m/s.UINT16Read/write0 = 9600; 1 = 1200; 2 = 2400; 3 = 4800; 4 = 9600; 5 = 14400; 6 = 19200; 7 = 28800; 8 = 38400; 9 = 56000; 10 = 57600; 11 = 115200
HR6doc 40007RS-485 parityFor: CAHV m/s, CRHV m/s, QAHV, EAHV/EACV m/s.UINT16Read/write0 = None; 1 = Even; 2 = Odd
HR9doc 40010Fault code (hex)For: CAHV, CRHV, QAHV, EAHV/EACV.UINT16Read27033 = Bad communication with unit; 32768 = No error
HR10doc 40011A1M+ firmware versionFor: CAHV m/s, CRHV m/s, QAHV, EAHV/EACV m/s.UINT16Read
HR11doc 40012Modbus comms counterWraps after 65535. For: CAHV m/s, CRHV m/s, QAHV, EAHV/EACV m/s.UINT16Read
HR12doc 40013Fault code (decimal)For: CAHV, CRHV, QAHV, EAHV/EACV.UINT16Read6999 = Bad communication with unit; 8000 = No error
HR13doc 40014System type detectedFor: CAHV m/s, CRHV m/s, QAHV, EAHV/EACV m/s.UINT16Read0 = ATA unit; 1 = ATW system; 2 = Lossnay system; 255 = Undetermined
HR25doc 40026System on/offFor: CAHV m/s, CRHV m/s, QAHV, EAHV/EACV m/s; read only on slaves.UINT16Read/write0 = System off; 1 = System on; 2 = Emergency run (read only); 3 = Test run (read only)
HR26doc 40027Operating modeFor: CAHV m/s, CRHV m/s, QAHV, EAHV/EACV m/s; read only on slaves.UINT16Read/write0 = Stop; 1 = Hot water; 2 = Heating; 3 = Cooling; 4 = No-voltage contact input (hot water storage); 5 = Freeze stat; 6 = Legionella; 7 = Heating-Eco; 8 = Mode 1; 9 = Mode 2; 10 = Mode 3; 11 = No-voltage contact input (heating up)
HR30doc 40031Thermo-off temperature (signed)Same address as the FTC tank setpoint. For: QAHV.INT16× 0.01°CRead/write
HR36doc 40037MRC prohibitDo not write to Shizuoka-designed models. For: CAHV, CRHV, QAHV, EAHV/EACV.BITMAP16Read/writebit 0 = System on/off (1 = prohibit); bit 1 = Running mode (1 = prohibit); bit 2 = Setting temperature (1 = prohibit); bit 4 = Function setting (1 = function setting)
HR45doc 40046Capacity modeFor: CAHV, CRHV, QAHV, EAHV/EACV.UINT16Read/write0 = COP priority; 1 = Capacity priority
HR46doc 40047Capacity control ratio0-100 %. For: CAHV, CRHV, QAHV, EAHV/EACV.UINT16%Read/write
HR47doc 40048Fan modeFor: CRHV, QAHV, EAHV/EACV.UINT16Read/write0 = Ordinary; 1 = Coercion
HR48doc 40049Current hour0-23. For: CAHV m/s, CRHV m/s, QAHV, EAHV/EACV m/s; read only on slaves.UINT16hRead/write
HR49doc 40050Current minute0-59. For: CAHV m/s, CRHV m/s, QAHV, EAHV/EACV m/s; read only on slaves.UINT16minRead/write
HR50doc 40051Outdoor temperature by BMS (signed)x10; -30 to +50 °C on CAHV/CRHV/EAHV. For: CAHV, CRHV, EAHV/EACV.INT16× 0.1°CRead/write
HR52doc 40053Setting water temperature (signed)Water setpoint x100; range depends on model (see notes). For: CAHV, CRHV, QAHV, EAHV/EACV m/s.INT16× 0.01°CRead/write
HR66doc 40067Own refrigerant address0-32. For: CAHV m/s, CRHV m/s, QAHV, EAHV/EACV m/s.UINT16Read
HR67doc 40068DefrostFor: CAHV m/s, QAHV, EAHV/EACV m/s.UINT16Read0 = Normal; 1 = Standby; 2 = Defrost; 3 = Waiting restart
HR69doc 40070Refrigerant error infoFor: CAHV, CRHV, QAHV, EAHV/EACV.UINT16Read0 = Normal; 1 = Error (system); 2 = Error (startup); 3 = Maintenance error
HR73doc 40074Heat pump frequency - master0-255 Hz. For: CAHV, CRHV, QAHV, EAHV/EACV.UINT16HzRead
HR74doc 40075Heat pump frequency - slave 10-255 Hz. For: CAHV, CRHV, QAHV, EAHV/EACV.UINT16HzRead
HR75doc 40076Heat pump frequency - slave 20-255 Hz. For: CAHV, CRHV, QAHV, EAHV/EACV.UINT16HzRead
HR76doc 40077Heat pump frequency - slave 30-255 Hz. For: CAHV, CRHV, QAHV, EAHV/EACV.UINT16HzRead
HR77doc 40078Heat pump frequency - slave 40-255 Hz. For: CAHV, CRHV, QAHV, EAHV/EACV.UINT16HzRead
HR78doc 40079Heat pump frequency - slave 50-255 Hz. For: CAHV, CRHV, QAHV, EAHV/EACV.UINT16HzRead
HR79doc 40080Heat pump frequency - slave 60-255 Hz. For: CAHV, CRHV, QAHV.UINT16HzRead
HR85doc 40086Flow temperature setpoint - zone 1 (signed)For: CAHV m/s, CRHV m/s, EAHV/EACV m/s.INT16× 0.01°CRead
HR99doc 40100Outdoor ambient temperature (signed)x10. For: CAHV, CRHV m/s, QAHV, EAHV/EACV m/s.INT16× 0.1°CRead
HR101doc 40102Water outlet temperature (signed)For: CAHV m/s, CRHV m/s, QAHV, EAHV/EACV m/s.INT16× 0.01°CRead
HR103doc 40104Water inlet temperature (signed)For: CAHV m/s, CRHV m/s, QAHV, EAHV/EACV m/s.INT16× 0.01°CRead
HR107doc 40108External water temperature 1 (signed)For: CAHV, CRHV, QAHV, EAHV/EACV.INT16× 0.01°CRead
HR109doc 40110External water temperature 3 (signed)For: QAHV.INT16× 0.01°CRead
HR111doc 40112External water temperature 2 / 4 (signed)Ext. water temp 2 on CAHV/CRHV, 4 on QAHV. For: CAHV, CRHV, QAHV.INT16× 0.01°CRead
HR127doc 40128Heat pump master on/offFor: CAHV, CRHV, QAHV, EAHV/EACV.UINT16Read0 = Stop; 1 = Run
HR128doc 40129Heat pump slave 1 on/offAddress 2 on CAHV/CRHV. For: CAHV, CRHV, QAHV, EAHV/EACV.UINT16Read0 = Stop; 1 = Run
HR129doc 40130Heat pump slave 2 on/offAddress 3 on CAHV/CRHV. For: CAHV, CRHV.UINT16Read0 = Stop; 1 = Run
HR130doc 40131Heat pump slave 3 on/offAddress 4 on CAHV/CRHV. For: CAHV, CRHV.UINT16Read0 = Stop; 1 = Run
HR131doc 40132Heat pump slave 4 on/offAddress 5 on CAHV/CRHV. For: CAHV, CRHV.UINT16Read0 = Stop; 1 = Run
HR132doc 40133Heat pump slave 5 on/offAddress 6 on CAHV/CRHV. For: CAHV, CRHV.UINT16Read0 = Stop; 1 = Run
HR133doc 40134Heat pump slave 6 on/offAddress 7 on CAHV/CRHV. For: CAHV, CRHV.UINT16Read0 = Stop; 1 = Run
HR134doc 40135Heat pump slave 7 on/offAddress 8 on CAHV/CRHV. For: CAHV, CRHV.UINT16Read0 = Stop; 1 = Run
HR135doc 40136Heat pump slave 8 on/offAddress 9 on CAHV/CRHV. For: CAHV, CRHV.UINT16Read0 = Stop; 1 = Run
HR136doc 40137Heat pump run time (hours)Units part, 0-99 h. For: CAHV, CRHV.UINT16hRead
HR137doc 40138Heat pump run time (hours x100)Hundreds part; add to 40137. For: CAHV, CRHV.UINT16× 100hRead
HR144doc 40145Boiler / external heater operation 1Boiler on EAHV/EACV; external heater 1 on CAHV/CRHV. For: CAHV, CRHV, EAHV/EACV m/s.UINT16Read0 = Stop; 1 = Run
HR149doc 40150Water pump 1 on/offFor: CAHV, CRHV m/s, QAHV, EAHV/EACV m/s.UINT16Read0 = Stop; 1 = Run
HR150doc 40151Water pump 2 on/offFor: CAHV.UINT16Read0 = Stop; 1 = Run
HR151doc 40152Water pump 3 on/offFor: CAHV.UINT16Read0 = Stop; 1 = Run
HR167doc 40168Heat pump frequency - slave 70-255 Hz. For: CAHV, CRHV, QAHV.UINT16HzRead
HR168doc 40169Heat pump frequency - slave 80-255 Hz. For: CAHV, CRHV, QAHV.UINT16HzRead
HR169doc 40170Heat pump frequency - slave 90-255 Hz. For: CAHV, CRHV, QAHV.UINT16HzRead
HR170doc 40171Heat pump frequency - slave 100-255 Hz. For: CAHV, CRHV, QAHV.UINT16HzRead
HR171doc 40172Heat pump frequency - slave 110-255 Hz. For: CAHV, CRHV, QAHV.UINT16HzRead
HR172doc 40173Heat pump frequency - slave 120-255 Hz. For: CAHV, CRHV, QAHV.UINT16HzRead
HR173doc 40174Heat pump frequency - slave 130-255 Hz. For: CAHV, CRHV, QAHV.UINT16HzRead
HR174doc 40175Heat pump frequency - slave 140-255 Hz. For: CAHV, CRHV, QAHV.UINT16HzRead
HR175doc 40176Heat pump frequency - slave 150-255 Hz. For: CAHV, CRHV, QAHV.UINT16HzRead
HR176doc 40177Heat pump 10 on/offFor: CAHV, CRHV, QAHV.UINT16Read0 = Stop; 1 = Run
HR177doc 40178Heat pump 11 on/offFor: CAHV, CRHV, QAHV.UINT16Read0 = Stop; 1 = Run
HR178doc 40179Heat pump 12 on/offFor: CAHV, CRHV, QAHV.UINT16Read0 = Stop; 1 = Run
HR179doc 40180Heat pump 13 on/offFor: CAHV, CRHV, QAHV.UINT16Read0 = Stop; 1 = Run
HR180doc 40181Heat pump 14 on/offFor: CAHV, CRHV, QAHV.UINT16Read0 = Stop; 1 = Run
HR181doc 40182Heat pump 15 on/offFor: CAHV, CRHV, QAHV.UINT16Read0 = Stop; 1 = Run
HR182doc 40183Heat pump 16 on/offFor: CAHV, CRHV, QAHV.UINT16Read0 = Stop; 1 = Run
HR183doc 40184Heat pump 17 on/offFor: CAHV, CRHV, QAHV.UINT16Read0 = Stop; 1 = Run
HR184doc 40185Heat pump 18 on/offFor: CAHV, CRHV.UINT16Read0 = Stop; 1 = Run
HR185doc 40186Heat pump 19 on/offFor: CAHV, CRHV.UINT16Read0 = Stop; 1 = Run
HR186doc 40187Heat pump 20 on/offFor: CAHV, CRHV.UINT16Read0 = Stop; 1 = Run
HR187doc 40188Heat pump 21 on/offFor: CAHV, CRHV.UINT16Read0 = Stop; 1 = Run
HR188doc 40189Heat pump 22 on/offFor: CAHV, CRHV.UINT16Read0 = Stop; 1 = Run
HR189doc 40190Heat pump 23 on/offFor: CAHV, CRHV.UINT16Read0 = Stop; 1 = Run
HR190doc 40191Heat pump 24 on/offFor: CAHV, CRHV.UINT16Read0 = Stop; 1 = Run
HR191doc 40192Heat pump 25 on/offFor: CAHV, CRHV.UINT16Read0 = Stop; 1 = Run
HR192doc 40193Heat pump 26 on/offFor: CAHV, CRHV.UINT16Read0 = Stop; 1 = Run
HR193doc 40194Heat pump 27 on/offFor: CAHV, CRHV.UINT16Read0 = Stop; 1 = Run
HR194doc 40195Heat pump 28 on/offFor: CAHV, CRHV.UINT16Read0 = Stop; 1 = Run
HR195doc 40196Heat pump 29 on/offFor: CAHV, CRHV.UINT16Read0 = Stop; 1 = Run
HR196doc 40197Heat pump 30 on/offFor: CAHV, CRHV.UINT16Read0 = Stop; 1 = Run
HR197doc 40198Heat pump 31 on/offFor: CAHV, CRHV.UINT16Read0 = Stop; 1 = Run
HR198doc 40199Heat pump 32 on/offFor: CAHV, CRHV.UINT16Read0 = Stop; 1 = Run
HR215doc 40216External heater on/offFor: CRHV.UINT16Read0 = Stop; 1 = Run
HR216doc 40217Water pump 4 on/offFor: CAHV.UINT16Read0 = Stop; 1 = Run
HR217doc 40218Water pump 5 on/offFor: CAHV.UINT16Read0 = Stop; 1 = Run
HR218doc 40219Water pump 6 on/offFor: CAHV.UINT16Read0 = Stop; 1 = Run
HR219doc 40220Water pump 7 on/offFor: CAHV.UINT16Read0 = Stop; 1 = Run
HR220doc 40221Water pump 8 on/offFor: CAHV.UINT16Read0 = Stop; 1 = Run
HR221doc 40222Water pump 9 on/offFor: CAHV.UINT16Read0 = Stop; 1 = Run
HR222doc 40223Water pump 10 on/offFor: CAHV.UINT16Read0 = Stop; 1 = Run
HR223doc 40224Water pump 11 on/offFor: CAHV.UINT16Read0 = Stop; 1 = Run
HR224doc 40225Water pump 12 on/offFor: CAHV.UINT16Read0 = Stop; 1 = Run
HR225doc 40226Water pump 13 on/offFor: CAHV.UINT16Read0 = Stop; 1 = Run
HR226doc 40227Water pump 14 on/offFor: CAHV.UINT16Read0 = Stop; 1 = Run
HR227doc 40228Water pump 15 on/offFor: CAHV.UINT16Read0 = Stop; 1 = Run
HR228doc 40229Water pump 16 on/offFor: CAHV.UINT16Read0 = Stop; 1 = Run
HR229doc 40230Drain pan heater / antifreeze piping heaterDrain pan heater on CRHV/EAHV; antifreeze piping heater on QAHV. For: CRHV m/s, QAHV, EAHV/EACV m/s.UINT16Read0 = Stop; 1 = Run
HR230doc 40231Evaporating temperature (signed)For: CAHV m/s, CRHV m/s, QAHV, EAHV/EACV m/s.INT16× 0.01°CRead
HR232doc 40233Condensing temperature (signed)For: CAHV m/s, CRHV m/s, QAHV, EAHV/EACV m/s.INT16× 0.01°CRead
HR234doc 40235Electric energy 10-655.35 kWh. Reads 0 on CAHV/CRHV 2013 models. For: CAHV m/s, CRHV m/s, EAHV/EACV m/s.UINT16× 0.01kWhRead
HR235doc 40236Electric energy 20-655.35 kWh. Reads 0 on CAHV/CRHV 2013 models. For: CAHV m/s, CRHV m/s, EAHV/EACV m/s.UINT16× 0.01kWhRead
HR236doc 40237Electric energy 30-655.35 kWh. Reads 0 on CAHV/CRHV 2013 models. For: CAHV m/s, CRHV m/s, EAHV/EACV m/s.UINT16× 0.01kWhRead
HR237doc 40238Electric energy 40-655.35 kWh. Reads 0 on CAHV/CRHV 2013 models. For: CAHV m/s, CRHV m/s, EAHV/EACV m/s.UINT16× 0.01kWhRead
HR238doc 40239Electric energy 50-655.35 kWh. Reads 0 on CAHV/CRHV 2013 models. For: CAHV m/s, CRHV m/s, EAHV/EACV m/s.UINT16× 0.01kWhRead
HR239doc 40240Electric energy 60-655.35 kWh. Reads 0 on CAHV/CRHV 2013 models. For: CAHV m/s, CRHV m/s, EAHV/EACV m/s.UINT16× 0.01kWhRead
HR240doc 40241Electric energy 70-655.35 kWh. Reads 0 on CAHV/CRHV 2013 models. For: CAHV m/s, CRHV m/s, EAHV/EACV m/s.UINT16× 0.01kWhRead
HR241doc 40242Electric energy 80-655.35 kWh. Reads 0 on CAHV/CRHV 2013 models. For: CAHV m/s, CRHV m/s, EAHV/EACV m/s.UINT16× 0.01kWhRead
HR242doc 40243Electric energy 90-655.35 kWh. Reads 0 on CAHV/CRHV 2013 models. For: CAHV m/s, CRHV m/s, EAHV/EACV m/s.UINT16× 0.01kWhRead
HR243doc 40244Electric energy 100-655.35 kWh. Reads 0 on CAHV/CRHV 2013 models. For: CAHV m/s, CRHV m/s, EAHV/EACV m/s.UINT16× 0.01kWhRead
HR244doc 40245Electric energy 110-655.35 kWh. Reads 0 on CAHV/CRHV 2013 models. For: CAHV m/s, CRHV m/s, EAHV/EACV m/s.UINT16× 0.01kWhRead
HR245doc 40246Electric energy 120-655.35 kWh. Reads 0 on CAHV/CRHV 2013 models. For: CAHV m/s, CRHV m/s, EAHV/EACV m/s.UINT16× 0.01kWhRead
HR246doc 40247Electric energy 130-655.35 kWh. Reads 0 on CAHV/CRHV 2013 models. For: CAHV m/s, CRHV m/s, EAHV/EACV m/s.UINT16× 0.01kWhRead
HR247doc 40248Electric energy 140-655.35 kWh. Reads 0 on CAHV/CRHV 2013 models. For: CAHV m/s, CRHV m/s, EAHV/EACV m/s.UINT16× 0.01kWhRead
HR248doc 40249Electric energy 150-655.35 kWh. Reads 0 on CAHV/CRHV 2013 models. For: CAHV m/s, CRHV m/s, EAHV/EACV m/s.UINT16× 0.01kWhRead
HR249doc 40250Electric energy 160-655.35 kWh. Reads 0 on CAHV/CRHV 2013 models. For: CAHV m/s, CRHV m/s, EAHV/EACV m/s.UINT16× 0.01kWhRead
HR250doc 40251Brine inlet temperature (signed)For: CRHV m/s.INT16× 0.01°CRead
HR252doc 40253Brine outlet temperature 1 (signed)For: CRHV m/s.INT16× 0.01°CRead
HR254doc 40255Brine outlet temperature 2 (signed)For: CRHV m/s.INT16× 0.01°CRead
HR256doc 40257Condensing temperature 2 (signed)For: CAHV m/s, CRHV m/s, EAHV/EACV m/s.INT16× 0.01°CRead
HR258doc 40259Water outlet temperature 2 (signed)For: CAHV m/s, CRHV m/s, EAHV/EACV m/s.INT16× 0.01°CRead
HR260doc 40261Evaporating temperature 2 (signed)For: CAHV m/s, CRHV m/s, EAHV/EACV m/s.INT16× 0.01°CRead
HR262doc 40263Water pump 1 PWM duty0-100 %. For: QAHV.UINT16%Read
HR264doc 402653-way valve 1For: CAHV, QAHV.UINT16Read0 = Off (stop); 1 = On (run)
HR265doc 40266Protocol version (upper)BCD; V3.01 = 3 upper, 1 lower. For: CAHV m/s, CRHV m/s, QAHV, EAHV/EACV m/s.UINT16Read
HR266doc 40267Protocol version (lower)BCD. For: CAHV m/s, CRHV m/s, QAHV, EAHV/EACV m/s.UINT16Read
HR267doc 40268Model version (upper)BCD; V2.00 = 2 upper, 0 lower. For: CAHV m/s, CRHV m/s, QAHV, EAHV/EACV m/s.UINT16Read
HR268doc 40269Model version (lower)BCD. For: CAHV m/s, CRHV m/s, QAHV, EAHV/EACV m/s.UINT16Read
HR269doc 40270Capacity of supplying electricity0-25.5 W. For: CAHV m/s, CRHV m/s, QAHV, EAHV/EACV m/s.UINT16× 0.1WRead
HR270doc 40271Model profile 1For: CAHV m/s, CRHV m/s, QAHV, EAHV/EACV m/s.UINT16Read0 = FTC2B; 1 = FTC4; 2 = FTC5; 3 = FTC6; 128 = CAHV1A; 129 = CAHV1B; 130 = CRHV1A; 131 = CRHV1B; 132 = EAHV1A; 133 = EAHV1B; 134 = QAHV1A; 135 = QAHV1B; 144 = PWFY1
HR271doc 40272Model profile 2 (refrigerant address)0-255. For: CAHV m/s, CRHV m/s, QAHV, EAHV/EACV m/s.UINT16Read

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Mitsubishi Electric MelcoBEMS MINI (A1M+) gateway for CAHV / CRHV / QAHV heat pumps and EAHV / EACV e-series chillers

What Modbus registers does the Mitsubishi Electric MelcoBEMS MINI (A1M+) gateway for CAHV / CRHV / QAHV heat pumps and EAHV / EACV e-series chillers have?

This map lists 131 registers: 131 holding registers. 14 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Mitsubishi Electric MelcoBEMS MINI (A1M+) gateway for CAHV / CRHV / QAHV heat pumps and EAHV / EACV e-series chillers Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Every row gives a protocol 'Addr' and a Modicon address (Addr 25 = 40026). The Addr value is the wire address.

What are the minimum Modbus registers to integrate the Mitsubishi Electric MelcoBEMS MINI (A1M+) gateway for CAHV / CRHV / QAHV heat pumps and EAHV / EACV e-series chillers?

Start with HR 13 System type detected (System type (1 = ATW)); HR 12 Fault code (decimal) (Fault code (8000 = none)); HR 25 System on/off (System on/off); HR 26 Operating mode (Operating mode); HR 52 Setting water temperature (signed) (Water setpoint (x100)); HR 101 Water outlet temperature (signed) (Water outlet temperature); HR 103 Water inlet temperature (signed) (Water inlet temperature); HR 73 Heat pump frequency - master (Master compressor frequency).

How do I enable Modbus control of the Mitsubishi Electric MelcoBEMS MINI (A1M+) gateway for CAHV / CRHV / QAHV heat pumps and EAHV / EACV e-series chillers?

No enable step is described in the register tables; set the gateway's address, baud rate and parity (40005-40007) to match the BMS. See the MelcoBEMS MINI (A1M+) installation instructions.

Where is the official Mitsubishi Electric MelcoBEMS MINI (A1M+) gateway for CAHV / CRHV / QAHV heat pumps and EAHV / EACV e-series chillers Modbus documentation?

The source is MelcoBEMS MINI (A1M+) ATW Modbus Register Tables (Document version 1.0.1), revision 2025-10-07, published free by Mitsubishi Electric at https://library.mitsubishielectric.co.uk/pdf/download_full/5537.

More Mitsubishi Electric Modbus register maps

Other ac & vrf gateways register maps

All ac & vrf gateways Modbus register maps →

Source: MelcoBEMS MINI (A1M+) ATW Modbus Register Tables · Document version 1.0.1 · rev. 2025-10-07. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.