- DTA116A51 D-NET / Modbus communication adaptor (VRV)
VRF / split AC gateway · Modbus register map
Daikin DTA116A51 D-NET / Modbus communication adaptor (VRV) Modbus register map
Updated 17 November 2026
The DTA116A51 connects a Daikin VRV system's D-III NET bus to a Modbus RTU master. Input registers report adaptor readiness, which indoor units are connected, each unit's capabilities, on/off, mode, setpoint, room temperature and error state; holding registers send on/off, mode, fan and setpoint commands. Most per-unit registers pack several small fields into one word, so this map gives the single-bit flags directly and describes the multi-bit fields.
This page lists 196 Modbus registers for the Daikin DTA116A51 D-NET / Modbus communication adaptor (VRV) — 49 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Daikin’s own free documentation (linked below) and checked against it.
- Manufacturer
- Daikin
- Model
- DTA116A51 D-NET / Modbus communication adaptor (VRV)
- Equipment type
- VRF / split AC gateway
- Registers
- 196 (49 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- Also known as
- DTA116A51, DIII-NET Modbus adaptor, D3NET Modbus adapter
Integration notes: Daikin DTA116A51 D-NET / Modbus communication adaptor (VRV)
Wait for 30001 = 1, read 30002 to see which indoor units exist, then poll each unit's six status registers from 32001 with function 04 (up to 32 registers per read). Before commanding a unit, copy its current state into its three holding registers; the adaptor sends a command whenever a holding register value changes.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| IR 0 | Adaptor status | UINT16 | Adaptor ready | Read |
| IR 1 | Indoor unit connection status | BITMAP16 | Which indoor units are connected | Read |
| IR 5 | Indoor unit communication status | BITMAP16 | Indoor unit communication errors | Read |
| IR 2000 | IU 1-00 status 1 | BITMAP16 | Unit 1-00 on/off and fan | Read |
| IR 2002 | IU 1-00 setpoint | INT16 | Unit 1-00 setpoint | Read |
| IR 2004 | IU 1-00 room temperature | INT16 | Unit 1-00 room temperature | Read |
| HR 2000 | IU 1-00 control 1 | UINT16 | Unit 1-00 on/off and fan command | Read/write |
| HR 2002 | IU 1-00 setpoint command | INT16 | Unit 1-00 setpoint command | Read/write |
Enable Modbus control & writes
Set the Modbus slave address (1-15, 0 = Modbus off) on DIP switch DS2 and baud, stop bits and parity on DS1. Holding register 40001 sets whether the adaptor is D-NET master; set it to slave (bit 8 = 0) when another central controller is on the VRV system.
Byte order & addressing
- Function 03 is not supported: read input registers with 04, write holding registers with 06 or 16 (up to 30 registers).
- Reads are limited to 32 registers per request.
- Holding registers are not refreshed from the units; if they are not kept in step with the input registers, a command can be skipped or undo a change made at a remote controller.
Network setup
- DS1-2: 9600 (off) or 19200 (on) baud. DS1-3 off = 1 stop bit with parity, on = 2 stop bits, no parity. DS1-4 parity even (off) or odd (on).
- Leave a silent interval (5 ms at 9600, 2.5 ms at 19200) plus 20 ms between a reply and the next query.
Watch out for
- Daikin limits commands to about 7,000 per indoor unit per year; avoid writing values that did not change.
- With an RQCEQ-PY1 outdoor unit, synchronise the operation mode register with the unit's actual mode before writing a setpoint.
Daikin DTA116A51 D-NET / Modbus communication adaptor (VRV) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| IR | 0doc 30001 | Adaptor status | UINT16 | Read | 0 = Not ready; 1 = Ready | ||||
| IR | 1doc 30002 | Indoor unit connection status | 1 = connected. | BITMAP16 | Read | bit 0 = Indoor unit 1-00 connected; bit 1 = Indoor unit 1-01 connected; bit 2 = Indoor unit 1-02 connected; bit 3 = Indoor unit 1-03 connected; bit 4 = Indoor unit 1-04 connected; bit 5 = Indoor unit 1-05 connected; bit 6 = Indoor unit 1-06 connected; bit 7 = Indoor unit 1-07 connected; bit 8 = Indoor unit 1-08 connected; bit 9 = Indoor unit 1-09 connected; bit 10 = Indoor unit 1-10 connected; bit 11 = Indoor unit 1-11 connected; bit 12 = Indoor unit 1-12 connected; bit 13 = Indoor unit 1-13 connected; bit 14 = Indoor unit 1-14 connected; bit 15 = Indoor unit 1-15 connected | |||
| IR | 5doc 30006 | Indoor unit communication status | 1 = communication error. | BITMAP16 | Read | bit 0 = Indoor unit 1-00 communication error; bit 1 = Indoor unit 1-01 communication error; bit 2 = Indoor unit 1-02 communication error; bit 3 = Indoor unit 1-03 communication error; bit 4 = Indoor unit 1-04 communication error; bit 5 = Indoor unit 1-05 communication error; bit 6 = Indoor unit 1-06 communication error; bit 7 = Indoor unit 1-07 communication error; bit 8 = Indoor unit 1-08 communication error; bit 9 = Indoor unit 1-09 communication error; bit 10 = Indoor unit 1-10 communication error; bit 11 = Indoor unit 1-11 communication error; bit 12 = Indoor unit 1-12 communication error; bit 13 = Indoor unit 1-13 communication error; bit 14 = Indoor unit 1-14 communication error; bit 15 = Indoor unit 1-15 communication error | |||
| IR | 1000doc 31001 | IU 1-00 capabilities | Bits 8-10 fan direction steps, bits 12-14 fan volume steps (see notes). | BITMAP16 | Read | bit 0 = Fan mode available; bit 1 = Cooling mode available; bit 2 = Heating mode available; bit 3 = Auto mode available; bit 4 = Dry mode available; bit 11 = Fan direction available; bit 15 = Fan volume available | |||
| IR | 1001doc 31002 | IU 1-00 cooling setpoint limits | Low byte = upper limit, high byte = lower limit, each signed 8-bit °C. | UINT16 | Read | ||||
| IR | 1002doc 31003 | IU 1-00 heating setpoint limits | Low byte = upper limit, high byte = lower limit, each signed 8-bit °C. | UINT16 | Read | ||||
| IR | 1003doc 31004 | IU 1-01 capabilities | Bits 8-10 fan direction steps, bits 12-14 fan volume steps (see notes). | BITMAP16 | Read | bit 0 = Fan mode available; bit 1 = Cooling mode available; bit 2 = Heating mode available; bit 3 = Auto mode available; bit 4 = Dry mode available; bit 11 = Fan direction available; bit 15 = Fan volume available | |||
| IR | 1004doc 31005 | IU 1-01 cooling setpoint limits | Low byte = upper limit, high byte = lower limit, each signed 8-bit °C. | UINT16 | Read | ||||
| IR | 1005doc 31006 | IU 1-01 heating setpoint limits | Low byte = upper limit, high byte = lower limit, each signed 8-bit °C. | UINT16 | Read | ||||
| IR | 1006doc 31007 | IU 1-02 capabilities | Bits 8-10 fan direction steps, bits 12-14 fan volume steps (see notes). | BITMAP16 | Read | bit 0 = Fan mode available; bit 1 = Cooling mode available; bit 2 = Heating mode available; bit 3 = Auto mode available; bit 4 = Dry mode available; bit 11 = Fan direction available; bit 15 = Fan volume available | |||
| IR | 1007doc 31008 | IU 1-02 cooling setpoint limits | Low byte = upper limit, high byte = lower limit, each signed 8-bit °C. | UINT16 | Read | ||||
| IR | 1008doc 31009 | IU 1-02 heating setpoint limits | Low byte = upper limit, high byte = lower limit, each signed 8-bit °C. | UINT16 | Read | ||||
| IR | 1009doc 31010 | IU 1-03 capabilities | Bits 8-10 fan direction steps, bits 12-14 fan volume steps (see notes). | BITMAP16 | Read | bit 0 = Fan mode available; bit 1 = Cooling mode available; bit 2 = Heating mode available; bit 3 = Auto mode available; bit 4 = Dry mode available; bit 11 = Fan direction available; bit 15 = Fan volume available | |||
| IR | 1010doc 31011 | IU 1-03 cooling setpoint limits | Low byte = upper limit, high byte = lower limit, each signed 8-bit °C. | UINT16 | Read | ||||
| IR | 1011doc 31012 | IU 1-03 heating setpoint limits | Low byte = upper limit, high byte = lower limit, each signed 8-bit °C. | UINT16 | Read | ||||
| IR | 1012doc 31013 | IU 1-04 capabilities | Bits 8-10 fan direction steps, bits 12-14 fan volume steps (see notes). | BITMAP16 | Read | bit 0 = Fan mode available; bit 1 = Cooling mode available; bit 2 = Heating mode available; bit 3 = Auto mode available; bit 4 = Dry mode available; bit 11 = Fan direction available; bit 15 = Fan volume available | |||
| IR | 1013doc 31014 | IU 1-04 cooling setpoint limits | Low byte = upper limit, high byte = lower limit, each signed 8-bit °C. | UINT16 | Read | ||||
| IR | 1014doc 31015 | IU 1-04 heating setpoint limits | Low byte = upper limit, high byte = lower limit, each signed 8-bit °C. | UINT16 | Read | ||||
| IR | 1015doc 31016 | IU 1-05 capabilities | Bits 8-10 fan direction steps, bits 12-14 fan volume steps (see notes). | BITMAP16 | Read | bit 0 = Fan mode available; bit 1 = Cooling mode available; bit 2 = Heating mode available; bit 3 = Auto mode available; bit 4 = Dry mode available; bit 11 = Fan direction available; bit 15 = Fan volume available | |||
| IR | 1016doc 31017 | IU 1-05 cooling setpoint limits | Low byte = upper limit, high byte = lower limit, each signed 8-bit °C. | UINT16 | Read | ||||
| IR | 1017doc 31018 | IU 1-05 heating setpoint limits | Low byte = upper limit, high byte = lower limit, each signed 8-bit °C. | UINT16 | Read | ||||
| IR | 1018doc 31019 | IU 1-06 capabilities | Bits 8-10 fan direction steps, bits 12-14 fan volume steps (see notes). | BITMAP16 | Read | bit 0 = Fan mode available; bit 1 = Cooling mode available; bit 2 = Heating mode available; bit 3 = Auto mode available; bit 4 = Dry mode available; bit 11 = Fan direction available; bit 15 = Fan volume available | |||
| IR | 1019doc 31020 | IU 1-06 cooling setpoint limits | Low byte = upper limit, high byte = lower limit, each signed 8-bit °C. | UINT16 | Read | ||||
| IR | 1020doc 31021 | IU 1-06 heating setpoint limits | Low byte = upper limit, high byte = lower limit, each signed 8-bit °C. | UINT16 | Read | ||||
| IR | 1021doc 31022 | IU 1-07 capabilities | Bits 8-10 fan direction steps, bits 12-14 fan volume steps (see notes). | BITMAP16 | Read | bit 0 = Fan mode available; bit 1 = Cooling mode available; bit 2 = Heating mode available; bit 3 = Auto mode available; bit 4 = Dry mode available; bit 11 = Fan direction available; bit 15 = Fan volume available | |||
| IR | 1022doc 31023 | IU 1-07 cooling setpoint limits | Low byte = upper limit, high byte = lower limit, each signed 8-bit °C. | UINT16 | Read | ||||
| IR | 1023doc 31024 | IU 1-07 heating setpoint limits | Low byte = upper limit, high byte = lower limit, each signed 8-bit °C. | UINT16 | Read | ||||
| IR | 1024doc 31025 | IU 1-08 capabilities | Bits 8-10 fan direction steps, bits 12-14 fan volume steps (see notes). | BITMAP16 | Read | bit 0 = Fan mode available; bit 1 = Cooling mode available; bit 2 = Heating mode available; bit 3 = Auto mode available; bit 4 = Dry mode available; bit 11 = Fan direction available; bit 15 = Fan volume available | |||
| IR | 1025doc 31026 | IU 1-08 cooling setpoint limits | Low byte = upper limit, high byte = lower limit, each signed 8-bit °C. | UINT16 | Read | ||||
| IR | 1026doc 31027 | IU 1-08 heating setpoint limits | Low byte = upper limit, high byte = lower limit, each signed 8-bit °C. | UINT16 | Read | ||||
| IR | 1027doc 31028 | IU 1-09 capabilities | Bits 8-10 fan direction steps, bits 12-14 fan volume steps (see notes). | BITMAP16 | Read | bit 0 = Fan mode available; bit 1 = Cooling mode available; bit 2 = Heating mode available; bit 3 = Auto mode available; bit 4 = Dry mode available; bit 11 = Fan direction available; bit 15 = Fan volume available | |||
| IR | 1028doc 31029 | IU 1-09 cooling setpoint limits | Low byte = upper limit, high byte = lower limit, each signed 8-bit °C. | UINT16 | Read | ||||
| IR | 1029doc 31030 | IU 1-09 heating setpoint limits | Low byte = upper limit, high byte = lower limit, each signed 8-bit °C. | UINT16 | Read | ||||
| IR | 1030doc 31031 | IU 1-10 capabilities | Bits 8-10 fan direction steps, bits 12-14 fan volume steps (see notes). | BITMAP16 | Read | bit 0 = Fan mode available; bit 1 = Cooling mode available; bit 2 = Heating mode available; bit 3 = Auto mode available; bit 4 = Dry mode available; bit 11 = Fan direction available; bit 15 = Fan volume available | |||
| IR | 1031doc 31032 | IU 1-10 cooling setpoint limits | Low byte = upper limit, high byte = lower limit, each signed 8-bit °C. | UINT16 | Read | ||||
| IR | 1032doc 31033 | IU 1-10 heating setpoint limits | Low byte = upper limit, high byte = lower limit, each signed 8-bit °C. | UINT16 | Read | ||||
| IR | 1033doc 31034 | IU 1-11 capabilities | Bits 8-10 fan direction steps, bits 12-14 fan volume steps (see notes). | BITMAP16 | Read | bit 0 = Fan mode available; bit 1 = Cooling mode available; bit 2 = Heating mode available; bit 3 = Auto mode available; bit 4 = Dry mode available; bit 11 = Fan direction available; bit 15 = Fan volume available | |||
| IR | 1034doc 31035 | IU 1-11 cooling setpoint limits | Low byte = upper limit, high byte = lower limit, each signed 8-bit °C. | UINT16 | Read | ||||
| IR | 1035doc 31036 | IU 1-11 heating setpoint limits | Low byte = upper limit, high byte = lower limit, each signed 8-bit °C. | UINT16 | Read | ||||
| IR | 1036doc 31037 | IU 1-12 capabilities | Bits 8-10 fan direction steps, bits 12-14 fan volume steps (see notes). | BITMAP16 | Read | bit 0 = Fan mode available; bit 1 = Cooling mode available; bit 2 = Heating mode available; bit 3 = Auto mode available; bit 4 = Dry mode available; bit 11 = Fan direction available; bit 15 = Fan volume available | |||
| IR | 1037doc 31038 | IU 1-12 cooling setpoint limits | Low byte = upper limit, high byte = lower limit, each signed 8-bit °C. | UINT16 | Read | ||||
| IR | 1038doc 31039 | IU 1-12 heating setpoint limits | Low byte = upper limit, high byte = lower limit, each signed 8-bit °C. | UINT16 | Read | ||||
| IR | 1039doc 31040 | IU 1-13 capabilities | Bits 8-10 fan direction steps, bits 12-14 fan volume steps (see notes). | BITMAP16 | Read | bit 0 = Fan mode available; bit 1 = Cooling mode available; bit 2 = Heating mode available; bit 3 = Auto mode available; bit 4 = Dry mode available; bit 11 = Fan direction available; bit 15 = Fan volume available | |||
| IR | 1040doc 31041 | IU 1-13 cooling setpoint limits | Low byte = upper limit, high byte = lower limit, each signed 8-bit °C. | UINT16 | Read | ||||
| IR | 1041doc 31042 | IU 1-13 heating setpoint limits | Low byte = upper limit, high byte = lower limit, each signed 8-bit °C. | UINT16 | Read | ||||
| IR | 1042doc 31043 | IU 1-14 capabilities | Bits 8-10 fan direction steps, bits 12-14 fan volume steps (see notes). | BITMAP16 | Read | bit 0 = Fan mode available; bit 1 = Cooling mode available; bit 2 = Heating mode available; bit 3 = Auto mode available; bit 4 = Dry mode available; bit 11 = Fan direction available; bit 15 = Fan volume available | |||
| IR | 1043doc 31044 | IU 1-14 cooling setpoint limits | Low byte = upper limit, high byte = lower limit, each signed 8-bit °C. | UINT16 | Read | ||||
| IR | 1044doc 31045 | IU 1-14 heating setpoint limits | Low byte = upper limit, high byte = lower limit, each signed 8-bit °C. | UINT16 | Read | ||||
| IR | 1045doc 31046 | IU 1-15 capabilities | Bits 8-10 fan direction steps, bits 12-14 fan volume steps (see notes). | BITMAP16 | Read | bit 0 = Fan mode available; bit 1 = Cooling mode available; bit 2 = Heating mode available; bit 3 = Auto mode available; bit 4 = Dry mode available; bit 11 = Fan direction available; bit 15 = Fan volume available | |||
| IR | 1046doc 31047 | IU 1-15 cooling setpoint limits | Low byte = upper limit, high byte = lower limit, each signed 8-bit °C. | UINT16 | Read | ||||
| IR | 1047doc 31048 | IU 1-15 heating setpoint limits | Low byte = upper limit, high byte = lower limit, each signed 8-bit °C. | UINT16 | Read | ||||
| IR | 2000doc 32001 | IU 1-00 status 1 | Bits 8-10 fan direction (7 = swing), bits 12-14 fan volume. | BITMAP16 | Read | bit 0 = On; bit 2 = Forced off | |||
| IR | 2001doc 32002 | IU 1-00 status 2 | Packed: mode, filter sign, actual operation, cool/heat master (see notes). | UINT16 | Read | ||||
| IR | 2002doc 32003 | IU 1-00 setpoint | INT16 | × 0.1 | °C | Read | |||
| IR | 2003doc 32004 | IU 1-00 error | Bits 0-3 and 4-8: error code mapping values (see section 6 of the spec). | BITMAP16 | Read | bit 9 = Malfunction; bit 10 = Warning | |||
| IR | 2004doc 32005 | IU 1-00 room temperature | INT16 | × 0.1 | °C | Read | |||
| IR | 2005doc 32006 | IU 1-00 temperature sensor status | BITMAP16 | Read | bit 8 = Temperature sensor error; bit 15 = Sensor data received | ||||
| IR | 2006doc 32007 | IU 1-01 status 1 | Bits 8-10 fan direction (7 = swing), bits 12-14 fan volume. | BITMAP16 | Read | bit 0 = On; bit 2 = Forced off | |||
| IR | 2007doc 32008 | IU 1-01 status 2 | Packed: mode, filter sign, actual operation, cool/heat master (see notes). | UINT16 | Read | ||||
| IR | 2008doc 32009 | IU 1-01 setpoint | INT16 | × 0.1 | °C | Read | |||
| IR | 2009doc 32010 | IU 1-01 error | Bits 0-3 and 4-8: error code mapping values (see section 6 of the spec). | BITMAP16 | Read | bit 9 = Malfunction; bit 10 = Warning | |||
| IR | 2010doc 32011 | IU 1-01 room temperature | INT16 | × 0.1 | °C | Read | |||
| IR | 2011doc 32012 | IU 1-01 temperature sensor status | BITMAP16 | Read | bit 8 = Temperature sensor error; bit 15 = Sensor data received | ||||
| IR | 2012doc 32013 | IU 1-02 status 1 | Bits 8-10 fan direction (7 = swing), bits 12-14 fan volume. | BITMAP16 | Read | bit 0 = On; bit 2 = Forced off | |||
| IR | 2013doc 32014 | IU 1-02 status 2 | Packed: mode, filter sign, actual operation, cool/heat master (see notes). | UINT16 | Read | ||||
| IR | 2014doc 32015 | IU 1-02 setpoint | INT16 | × 0.1 | °C | Read | |||
| IR | 2015doc 32016 | IU 1-02 error | Bits 0-3 and 4-8: error code mapping values (see section 6 of the spec). | BITMAP16 | Read | bit 9 = Malfunction; bit 10 = Warning | |||
| IR | 2016doc 32017 | IU 1-02 room temperature | INT16 | × 0.1 | °C | Read | |||
| IR | 2017doc 32018 | IU 1-02 temperature sensor status | BITMAP16 | Read | bit 8 = Temperature sensor error; bit 15 = Sensor data received | ||||
| IR | 2018doc 32019 | IU 1-03 status 1 | Bits 8-10 fan direction (7 = swing), bits 12-14 fan volume. | BITMAP16 | Read | bit 0 = On; bit 2 = Forced off | |||
| IR | 2019doc 32020 | IU 1-03 status 2 | Packed: mode, filter sign, actual operation, cool/heat master (see notes). | UINT16 | Read | ||||
| IR | 2020doc 32021 | IU 1-03 setpoint | INT16 | × 0.1 | °C | Read | |||
| IR | 2021doc 32022 | IU 1-03 error | Bits 0-3 and 4-8: error code mapping values (see section 6 of the spec). | BITMAP16 | Read | bit 9 = Malfunction; bit 10 = Warning | |||
| IR | 2022doc 32023 | IU 1-03 room temperature | INT16 | × 0.1 | °C | Read | |||
| IR | 2023doc 32024 | IU 1-03 temperature sensor status | BITMAP16 | Read | bit 8 = Temperature sensor error; bit 15 = Sensor data received | ||||
| IR | 2024doc 32025 | IU 1-04 status 1 | Bits 8-10 fan direction (7 = swing), bits 12-14 fan volume. | BITMAP16 | Read | bit 0 = On; bit 2 = Forced off | |||
| IR | 2025doc 32026 | IU 1-04 status 2 | Packed: mode, filter sign, actual operation, cool/heat master (see notes). | UINT16 | Read | ||||
| IR | 2026doc 32027 | IU 1-04 setpoint | INT16 | × 0.1 | °C | Read | |||
| IR | 2027doc 32028 | IU 1-04 error | Bits 0-3 and 4-8: error code mapping values (see section 6 of the spec). | BITMAP16 | Read | bit 9 = Malfunction; bit 10 = Warning | |||
| IR | 2028doc 32029 | IU 1-04 room temperature | INT16 | × 0.1 | °C | Read | |||
| IR | 2029doc 32030 | IU 1-04 temperature sensor status | BITMAP16 | Read | bit 8 = Temperature sensor error; bit 15 = Sensor data received | ||||
| IR | 2030doc 32031 | IU 1-05 status 1 | Bits 8-10 fan direction (7 = swing), bits 12-14 fan volume. | BITMAP16 | Read | bit 0 = On; bit 2 = Forced off | |||
| IR | 2031doc 32032 | IU 1-05 status 2 | Packed: mode, filter sign, actual operation, cool/heat master (see notes). | UINT16 | Read | ||||
| IR | 2032doc 32033 | IU 1-05 setpoint | INT16 | × 0.1 | °C | Read | |||
| IR | 2033doc 32034 | IU 1-05 error | Bits 0-3 and 4-8: error code mapping values (see section 6 of the spec). | BITMAP16 | Read | bit 9 = Malfunction; bit 10 = Warning | |||
| IR | 2034doc 32035 | IU 1-05 room temperature | INT16 | × 0.1 | °C | Read | |||
| IR | 2035doc 32036 | IU 1-05 temperature sensor status | BITMAP16 | Read | bit 8 = Temperature sensor error; bit 15 = Sensor data received | ||||
| IR | 2036doc 32037 | IU 1-06 status 1 | Bits 8-10 fan direction (7 = swing), bits 12-14 fan volume. | BITMAP16 | Read | bit 0 = On; bit 2 = Forced off | |||
| IR | 2037doc 32038 | IU 1-06 status 2 | Packed: mode, filter sign, actual operation, cool/heat master (see notes). | UINT16 | Read | ||||
| IR | 2038doc 32039 | IU 1-06 setpoint | INT16 | × 0.1 | °C | Read | |||
| IR | 2039doc 32040 | IU 1-06 error | Bits 0-3 and 4-8: error code mapping values (see section 6 of the spec). | BITMAP16 | Read | bit 9 = Malfunction; bit 10 = Warning | |||
| IR | 2040doc 32041 | IU 1-06 room temperature | INT16 | × 0.1 | °C | Read | |||
| IR | 2041doc 32042 | IU 1-06 temperature sensor status | BITMAP16 | Read | bit 8 = Temperature sensor error; bit 15 = Sensor data received | ||||
| IR | 2042doc 32043 | IU 1-07 status 1 | Bits 8-10 fan direction (7 = swing), bits 12-14 fan volume. | BITMAP16 | Read | bit 0 = On; bit 2 = Forced off | |||
| IR | 2043doc 32044 | IU 1-07 status 2 | Packed: mode, filter sign, actual operation, cool/heat master (see notes). | UINT16 | Read | ||||
| IR | 2044doc 32045 | IU 1-07 setpoint | INT16 | × 0.1 | °C | Read | |||
| IR | 2045doc 32046 | IU 1-07 error | Bits 0-3 and 4-8: error code mapping values (see section 6 of the spec). | BITMAP16 | Read | bit 9 = Malfunction; bit 10 = Warning | |||
| IR | 2046doc 32047 | IU 1-07 room temperature | INT16 | × 0.1 | °C | Read | |||
| IR | 2047doc 32048 | IU 1-07 temperature sensor status | BITMAP16 | Read | bit 8 = Temperature sensor error; bit 15 = Sensor data received | ||||
| IR | 2048doc 32049 | IU 1-08 status 1 | Bits 8-10 fan direction (7 = swing), bits 12-14 fan volume. | BITMAP16 | Read | bit 0 = On; bit 2 = Forced off | |||
| IR | 2049doc 32050 | IU 1-08 status 2 | Packed: mode, filter sign, actual operation, cool/heat master (see notes). | UINT16 | Read | ||||
| IR | 2050doc 32051 | IU 1-08 setpoint | INT16 | × 0.1 | °C | Read | |||
| IR | 2051doc 32052 | IU 1-08 error | Bits 0-3 and 4-8: error code mapping values (see section 6 of the spec). | BITMAP16 | Read | bit 9 = Malfunction; bit 10 = Warning | |||
| IR | 2052doc 32053 | IU 1-08 room temperature | INT16 | × 0.1 | °C | Read | |||
| IR | 2053doc 32054 | IU 1-08 temperature sensor status | BITMAP16 | Read | bit 8 = Temperature sensor error; bit 15 = Sensor data received | ||||
| IR | 2054doc 32055 | IU 1-09 status 1 | Bits 8-10 fan direction (7 = swing), bits 12-14 fan volume. | BITMAP16 | Read | bit 0 = On; bit 2 = Forced off | |||
| IR | 2055doc 32056 | IU 1-09 status 2 | Packed: mode, filter sign, actual operation, cool/heat master (see notes). | UINT16 | Read | ||||
| IR | 2056doc 32057 | IU 1-09 setpoint | INT16 | × 0.1 | °C | Read | |||
| IR | 2057doc 32058 | IU 1-09 error | Bits 0-3 and 4-8: error code mapping values (see section 6 of the spec). | BITMAP16 | Read | bit 9 = Malfunction; bit 10 = Warning | |||
| IR | 2058doc 32059 | IU 1-09 room temperature | INT16 | × 0.1 | °C | Read | |||
| IR | 2059doc 32060 | IU 1-09 temperature sensor status | BITMAP16 | Read | bit 8 = Temperature sensor error; bit 15 = Sensor data received | ||||
| IR | 2060doc 32061 | IU 1-10 status 1 | Bits 8-10 fan direction (7 = swing), bits 12-14 fan volume. | BITMAP16 | Read | bit 0 = On; bit 2 = Forced off | |||
| IR | 2061doc 32062 | IU 1-10 status 2 | Packed: mode, filter sign, actual operation, cool/heat master (see notes). | UINT16 | Read | ||||
| IR | 2062doc 32063 | IU 1-10 setpoint | INT16 | × 0.1 | °C | Read | |||
| IR | 2063doc 32064 | IU 1-10 error | Bits 0-3 and 4-8: error code mapping values (see section 6 of the spec). | BITMAP16 | Read | bit 9 = Malfunction; bit 10 = Warning | |||
| IR | 2064doc 32065 | IU 1-10 room temperature | INT16 | × 0.1 | °C | Read | |||
| IR | 2065doc 32066 | IU 1-10 temperature sensor status | BITMAP16 | Read | bit 8 = Temperature sensor error; bit 15 = Sensor data received | ||||
| IR | 2066doc 32067 | IU 1-11 status 1 | Bits 8-10 fan direction (7 = swing), bits 12-14 fan volume. | BITMAP16 | Read | bit 0 = On; bit 2 = Forced off | |||
| IR | 2067doc 32068 | IU 1-11 status 2 | Packed: mode, filter sign, actual operation, cool/heat master (see notes). | UINT16 | Read | ||||
| IR | 2068doc 32069 | IU 1-11 setpoint | INT16 | × 0.1 | °C | Read | |||
| IR | 2069doc 32070 | IU 1-11 error | Bits 0-3 and 4-8: error code mapping values (see section 6 of the spec). | BITMAP16 | Read | bit 9 = Malfunction; bit 10 = Warning | |||
| IR | 2070doc 32071 | IU 1-11 room temperature | INT16 | × 0.1 | °C | Read | |||
| IR | 2071doc 32072 | IU 1-11 temperature sensor status | BITMAP16 | Read | bit 8 = Temperature sensor error; bit 15 = Sensor data received | ||||
| IR | 2072doc 32073 | IU 1-12 status 1 | Bits 8-10 fan direction (7 = swing), bits 12-14 fan volume. | BITMAP16 | Read | bit 0 = On; bit 2 = Forced off | |||
| IR | 2073doc 32074 | IU 1-12 status 2 | Packed: mode, filter sign, actual operation, cool/heat master (see notes). | UINT16 | Read | ||||
| IR | 2074doc 32075 | IU 1-12 setpoint | INT16 | × 0.1 | °C | Read | |||
| IR | 2075doc 32076 | IU 1-12 error | Bits 0-3 and 4-8: error code mapping values (see section 6 of the spec). | BITMAP16 | Read | bit 9 = Malfunction; bit 10 = Warning | |||
| IR | 2076doc 32077 | IU 1-12 room temperature | INT16 | × 0.1 | °C | Read | |||
| IR | 2077doc 32078 | IU 1-12 temperature sensor status | BITMAP16 | Read | bit 8 = Temperature sensor error; bit 15 = Sensor data received | ||||
| IR | 2078doc 32079 | IU 1-13 status 1 | Bits 8-10 fan direction (7 = swing), bits 12-14 fan volume. | BITMAP16 | Read | bit 0 = On; bit 2 = Forced off | |||
| IR | 2079doc 32080 | IU 1-13 status 2 | Packed: mode, filter sign, actual operation, cool/heat master (see notes). | UINT16 | Read | ||||
| IR | 2080doc 32081 | IU 1-13 setpoint | INT16 | × 0.1 | °C | Read | |||
| IR | 2081doc 32082 | IU 1-13 error | Bits 0-3 and 4-8: error code mapping values (see section 6 of the spec). | BITMAP16 | Read | bit 9 = Malfunction; bit 10 = Warning | |||
| IR | 2082doc 32083 | IU 1-13 room temperature | INT16 | × 0.1 | °C | Read | |||
| IR | 2083doc 32084 | IU 1-13 temperature sensor status | BITMAP16 | Read | bit 8 = Temperature sensor error; bit 15 = Sensor data received | ||||
| IR | 2084doc 32085 | IU 1-14 status 1 | Bits 8-10 fan direction (7 = swing), bits 12-14 fan volume. | BITMAP16 | Read | bit 0 = On; bit 2 = Forced off | |||
| IR | 2085doc 32086 | IU 1-14 status 2 | Packed: mode, filter sign, actual operation, cool/heat master (see notes). | UINT16 | Read | ||||
| IR | 2086doc 32087 | IU 1-14 setpoint | INT16 | × 0.1 | °C | Read | |||
| IR | 2087doc 32088 | IU 1-14 error | Bits 0-3 and 4-8: error code mapping values (see section 6 of the spec). | BITMAP16 | Read | bit 9 = Malfunction; bit 10 = Warning | |||
| IR | 2088doc 32089 | IU 1-14 room temperature | INT16 | × 0.1 | °C | Read | |||
| IR | 2089doc 32090 | IU 1-14 temperature sensor status | BITMAP16 | Read | bit 8 = Temperature sensor error; bit 15 = Sensor data received | ||||
| IR | 2090doc 32091 | IU 1-15 status 1 | Bits 8-10 fan direction (7 = swing), bits 12-14 fan volume. | BITMAP16 | Read | bit 0 = On; bit 2 = Forced off | |||
| IR | 2091doc 32092 | IU 1-15 status 2 | Packed: mode, filter sign, actual operation, cool/heat master (see notes). | UINT16 | Read | ||||
| IR | 2092doc 32093 | IU 1-15 setpoint | INT16 | × 0.1 | °C | Read | |||
| IR | 2093doc 32094 | IU 1-15 error | Bits 0-3 and 4-8: error code mapping values (see section 6 of the spec). | BITMAP16 | Read | bit 9 = Malfunction; bit 10 = Warning | |||
| IR | 2094doc 32095 | IU 1-15 room temperature | INT16 | × 0.1 | °C | Read | |||
| IR | 2095doc 32096 | IU 1-15 temperature sensor status | BITMAP16 | Read | bit 8 = Temperature sensor error; bit 15 = Sensor data received | ||||
| HR | 0doc 40001 | Adaptor initial setting | Stored in EEPROM; takes effect after a power cycle. Each bit defaults to 1. | BITMAP16 | Read/write | bit 0 = Manage D-NET addresses 1-00 to 1-15; bit 8 = Adaptor is D-NET master (0 = slave); bit 15 = D-NET communication start (0 = stop) | |||
| HR | 2000doc 42001 | IU 1-00 control 1 | Packed: bit 0 on/off, bits 4-7 = 6, fan direction, fan volume (see notes). | UINT16 | Read/write | ||||
| HR | 2001doc 42002 | IU 1-00 control 2 | Packed: operation mode, filter sign reset, auto heat/cool select (see notes). | UINT16 | Read/write | ||||
| HR | 2002doc 42003 | IU 1-00 setpoint command | INT16 | × 0.1 | °C | Read/write | |||
| HR | 2003doc 42004 | IU 1-01 control 1 | Packed: bit 0 on/off, bits 4-7 = 6, fan direction, fan volume (see notes). | UINT16 | Read/write | ||||
| HR | 2004doc 42005 | IU 1-01 control 2 | Packed: operation mode, filter sign reset, auto heat/cool select (see notes). | UINT16 | Read/write | ||||
| HR | 2005doc 42006 | IU 1-01 setpoint command | INT16 | × 0.1 | °C | Read/write | |||
| HR | 2006doc 42007 | IU 1-02 control 1 | Packed: bit 0 on/off, bits 4-7 = 6, fan direction, fan volume (see notes). | UINT16 | Read/write | ||||
| HR | 2007doc 42008 | IU 1-02 control 2 | Packed: operation mode, filter sign reset, auto heat/cool select (see notes). | UINT16 | Read/write | ||||
| HR | 2008doc 42009 | IU 1-02 setpoint command | INT16 | × 0.1 | °C | Read/write | |||
| HR | 2009doc 42010 | IU 1-03 control 1 | Packed: bit 0 on/off, bits 4-7 = 6, fan direction, fan volume (see notes). | UINT16 | Read/write | ||||
| HR | 2010doc 42011 | IU 1-03 control 2 | Packed: operation mode, filter sign reset, auto heat/cool select (see notes). | UINT16 | Read/write | ||||
| HR | 2011doc 42012 | IU 1-03 setpoint command | INT16 | × 0.1 | °C | Read/write | |||
| HR | 2012doc 42013 | IU 1-04 control 1 | Packed: bit 0 on/off, bits 4-7 = 6, fan direction, fan volume (see notes). | UINT16 | Read/write | ||||
| HR | 2013doc 42014 | IU 1-04 control 2 | Packed: operation mode, filter sign reset, auto heat/cool select (see notes). | UINT16 | Read/write | ||||
| HR | 2014doc 42015 | IU 1-04 setpoint command | INT16 | × 0.1 | °C | Read/write | |||
| HR | 2015doc 42016 | IU 1-05 control 1 | Packed: bit 0 on/off, bits 4-7 = 6, fan direction, fan volume (see notes). | UINT16 | Read/write | ||||
| HR | 2016doc 42017 | IU 1-05 control 2 | Packed: operation mode, filter sign reset, auto heat/cool select (see notes). | UINT16 | Read/write | ||||
| HR | 2017doc 42018 | IU 1-05 setpoint command | INT16 | × 0.1 | °C | Read/write | |||
| HR | 2018doc 42019 | IU 1-06 control 1 | Packed: bit 0 on/off, bits 4-7 = 6, fan direction, fan volume (see notes). | UINT16 | Read/write | ||||
| HR | 2019doc 42020 | IU 1-06 control 2 | Packed: operation mode, filter sign reset, auto heat/cool select (see notes). | UINT16 | Read/write | ||||
| HR | 2020doc 42021 | IU 1-06 setpoint command | INT16 | × 0.1 | °C | Read/write | |||
| HR | 2021doc 42022 | IU 1-07 control 1 | Packed: bit 0 on/off, bits 4-7 = 6, fan direction, fan volume (see notes). | UINT16 | Read/write | ||||
| HR | 2022doc 42023 | IU 1-07 control 2 | Packed: operation mode, filter sign reset, auto heat/cool select (see notes). | UINT16 | Read/write | ||||
| HR | 2023doc 42024 | IU 1-07 setpoint command | INT16 | × 0.1 | °C | Read/write | |||
| HR | 2024doc 42025 | IU 1-08 control 1 | Packed: bit 0 on/off, bits 4-7 = 6, fan direction, fan volume (see notes). | UINT16 | Read/write | ||||
| HR | 2025doc 42026 | IU 1-08 control 2 | Packed: operation mode, filter sign reset, auto heat/cool select (see notes). | UINT16 | Read/write | ||||
| HR | 2026doc 42027 | IU 1-08 setpoint command | INT16 | × 0.1 | °C | Read/write | |||
| HR | 2027doc 42028 | IU 1-09 control 1 | Packed: bit 0 on/off, bits 4-7 = 6, fan direction, fan volume (see notes). | UINT16 | Read/write | ||||
| HR | 2028doc 42029 | IU 1-09 control 2 | Packed: operation mode, filter sign reset, auto heat/cool select (see notes). | UINT16 | Read/write | ||||
| HR | 2029doc 42030 | IU 1-09 setpoint command | INT16 | × 0.1 | °C | Read/write | |||
| HR | 2030doc 42031 | IU 1-10 control 1 | Packed: bit 0 on/off, bits 4-7 = 6, fan direction, fan volume (see notes). | UINT16 | Read/write | ||||
| HR | 2031doc 42032 | IU 1-10 control 2 | Packed: operation mode, filter sign reset, auto heat/cool select (see notes). | UINT16 | Read/write | ||||
| HR | 2032doc 42033 | IU 1-10 setpoint command | INT16 | × 0.1 | °C | Read/write | |||
| HR | 2033doc 42034 | IU 1-11 control 1 | Packed: bit 0 on/off, bits 4-7 = 6, fan direction, fan volume (see notes). | UINT16 | Read/write | ||||
| HR | 2034doc 42035 | IU 1-11 control 2 | Packed: operation mode, filter sign reset, auto heat/cool select (see notes). | UINT16 | Read/write | ||||
| HR | 2035doc 42036 | IU 1-11 setpoint command | INT16 | × 0.1 | °C | Read/write | |||
| HR | 2036doc 42037 | IU 1-12 control 1 | Packed: bit 0 on/off, bits 4-7 = 6, fan direction, fan volume (see notes). | UINT16 | Read/write | ||||
| HR | 2037doc 42038 | IU 1-12 control 2 | Packed: operation mode, filter sign reset, auto heat/cool select (see notes). | UINT16 | Read/write | ||||
| HR | 2038doc 42039 | IU 1-12 setpoint command | INT16 | × 0.1 | °C | Read/write | |||
| HR | 2039doc 42040 | IU 1-13 control 1 | Packed: bit 0 on/off, bits 4-7 = 6, fan direction, fan volume (see notes). | UINT16 | Read/write | ||||
| HR | 2040doc 42041 | IU 1-13 control 2 | Packed: operation mode, filter sign reset, auto heat/cool select (see notes). | UINT16 | Read/write | ||||
| HR | 2041doc 42042 | IU 1-13 setpoint command | INT16 | × 0.1 | °C | Read/write | |||
| HR | 2042doc 42043 | IU 1-14 control 1 | Packed: bit 0 on/off, bits 4-7 = 6, fan direction, fan volume (see notes). | UINT16 | Read/write | ||||
| HR | 2043doc 42044 | IU 1-14 control 2 | Packed: operation mode, filter sign reset, auto heat/cool select (see notes). | UINT16 | Read/write | ||||
| HR | 2044doc 42045 | IU 1-14 setpoint command | INT16 | × 0.1 | °C | Read/write | |||
| HR | 2045doc 42046 | IU 1-15 control 1 | Packed: bit 0 on/off, bits 4-7 = 6, fan direction, fan volume (see notes). | UINT16 | Read/write | ||||
| HR | 2046doc 42047 | IU 1-15 control 2 | Packed: operation mode, filter sign reset, auto heat/cool select (see notes). | UINT16 | Read/write | ||||
| HR | 2047doc 42048 | IU 1-15 setpoint command | INT16 | × 0.1 | °C | Read/write |
Notes on this map
- Daikin does not appear to host this specification publicly; the link is the unaltered Daikin Industries document as mirrored by the integrator TapHome.
- Per-unit blocks repeat: capabilities every 3 registers from 31001, status every 6 from 32001, control every 3 from 42001, for D-NET addresses 1-00 to 1-15.
- Packed fields (from the spec's bit diagrams): capability word bits 8-10 fan direction level (1 fix, 2-5 = 2-5 step), bit 11 fan direction available, bits 12-14 fan volume steps (1 fix, 2 two-step, 3 three-step), bit 15 fan volume available. Status 1 bits 8-10 fan direction (0-4 = P0-P4, 7 = swing), bits 12-14 fan volume (1 L, 3 M, 5 H). Status 2 bits 0-3 operation mode, 4-7 filter sign (0 off, 1-15 on), 8-11 actual operation (0 fan, 1 heat, 2 cool), 14-15 cool/heat master (0 undecided, 1 slave, 2 master).
- Control 1 (42001+3n): bit 0 on/off, bits 4-7 fan control flag that must be 6, bits 8-10 fan direction (0-4 P0-P4, 6 stop, 7 swing), bits 12-14 fan volume (1 L, 3 M, 5 H; 0 if the unit has no fan volume capability). Control 2: bits 0-3 mode (0 fan, 1 heat, 2 cool, 3 auto, 6 setpoint, 7 dry), bits 4-7 filter sign reset (15 = reset, then write 0 again), bits 8-11 heat/cool setpoint selection in auto (1 heat, 2 cool).
- Setpoint limit registers hold two signed 8-bit values (°C) in one word; they are listed as UINT16 because the schema has no 8-bit type.
- Left out: the error code mapping table (section 6), which converts the two mapping values into Daikin error codes.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Daikin DTA116A51 D-NET / Modbus communication adaptor (VRV)
What Modbus registers does the Daikin DTA116A51 D-NET / Modbus communication adaptor (VRV) have?
This map lists 196 registers: 147 input registers, 49 holding registers. 49 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Daikin DTA116A51 D-NET / Modbus communication adaptor (VRV) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The spec lists 30001/40001-style registers and states that the request addresses them from zero (30001 is sent as 0, 40001 as 0). Its example frames confirm it: register 31001 is requested as 0x03E8 and 42002 as 0x07D1.
What are the minimum Modbus registers to integrate the Daikin DTA116A51 D-NET / Modbus communication adaptor (VRV)?
Start with IR 0 Adaptor status (Adaptor ready); IR 1 Indoor unit connection status (Which indoor units are connected); IR 5 Indoor unit communication status (Indoor unit communication errors); IR 2000 IU 1-00 status 1 (Unit 1-00 on/off and fan); IR 2002 IU 1-00 setpoint (Unit 1-00 setpoint); IR 2004 IU 1-00 room temperature (Unit 1-00 room temperature); HR 2000 IU 1-00 control 1 (Unit 1-00 on/off and fan command); HR 2002 IU 1-00 setpoint command (Unit 1-00 setpoint command).
How do I enable Modbus control of the Daikin DTA116A51 D-NET / Modbus communication adaptor (VRV)?
Set the Modbus slave address (1-15, 0 = Modbus off) on DIP switch DS2 and baud, stop bits and parity on DS1. Holding register 40001 sets whether the adaptor is D-NET master; set it to slave (bit 8 = 0) when another central controller is on the VRV system.
Where is the official Daikin DTA116A51 D-NET / Modbus communication adaptor (VRV) Modbus documentation?
The source is Functional Specifications D-NET/Modbus Communication adaptor DTA116A51 (CB13A033), revision 2013-08-09. Daikin doesn't publish it on its own website, so this map was re-typed from a free copy at https://taphome.com/compatibility/devices/daikin-dta116a51-vrv/manufacturer/functional-specifications.pdf. It may be an older revision, so check it against the live unit.
More Daikin Modbus register maps
- Heat pump
Daikin DCOM-LT/MB Modbus interface for Daikin Altherma LT heat pumps
Daikin Altherma low-temperature (LT) air-to-water heat pumps fitted with the DCOM-LT/MB (model number 534-001) P1P2-to-Modbus RTU interface, standard operating mode, per reference manual 534-252-A3.
Also known as: DCOM-LT-MB, 534-001, Altherma LT Modbus interface - VRF / split AC gateway
Daikin EKMBDXB Modbus Interface DIII
EKMBDXB7V1 Modbus RTU interface on the DIII-net of Daikin VRV, Sky Air, split (via KRP928), VAM/VKM ventilation, VRV hydrobox, air curtains, ERQ control box, heating and applied units; design guide 4P642495-1A (2022.02).
Also known as: EKMBDXB7V1, Modbus Interface DIII - VRF / split AC gateway
Daikin EKMBPP1 / EKMBPP1A Modbus adapter (Sky Air / VRV P1P2)
EKMBPP1 and EKMBPP1A adapters on the P1P2 bus of Sky Air / VRV indoor units (up to 16), installation manual 4P720139-1C (2024.11).
Also known as: EKMBPP1, EKMBPP1A - Heat pump (air-to-water) Modbus interface
Daikin EKRHH Daikin HomeHub (Modbus TCP/RTU for Daikin Altherma and air-to-air heat pumps)
Daikin HomeHub EKRHH in use case 3 (Modbus for Daikin Altherma air-to-water heat pumps) and use case 4 (Modbus smart-grid control of air-to-air heat pumps), installer reference guide 4P744838-1E (2026.01).
Also known as: EKRHH, Daikin HomeHub, 4P744838-1E, Daikin Altherma 3 Modbus, Altherma Smart Grid Modbus
Other ac & vrf gateways register maps
- Split AC unit (VRF / split AC gateway built in)
Gree U-Match all-DC-inverter duct / cassette / floor-ceiling units (built-in Modbus)
Gree U-Match fourth-generation all-DC-inverter light-commercial units whose controller has the integrated Modbus RTU interface; Chinese-English protocol dated 2018-03-07.
Also known as: U-Match, Gree U-Match 4th generation DC inverter, U-Match BMS Modbus - VRF / split AC gateway
Intesis (HMS Networks) IN770AIR***O000 700 Series Air Gateway, Panasonic application (Modbus)
Intesis 700 Series Air Gateway IN770AIR***O000 with the Panasonic application (U1U2 P-Link / S-Link), Modbus RTU / TCP server, user manual version 1.1.7 (2025-12-09).
Also known as: IN770AIR00MO000, IN770AIR00SO000, IN770AIRXXSO000 - VRF / split AC gateway
Intesis (HMS Networks) INMBSFGL001R000 Fujitsu AC to Modbus RTU gateway
One Fujitsu indoor unit, or a group of up to 16 controlled together as one, on the 3-wire BWR remote-controller bus via INMBSFGL001R000, user manual v2.4 (02/2025).
Also known as: INMBSFGL001R000, Intesis Fujitsu Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSLGE016O000 LG VRF to Modbus RTU / TCP gateway (16 / 64 indoor units)
Intesis Modbus - LG VRF, order codes INMBSLGE016O000 / INMBSLGE064O000 (legacy LG-AC-MBS-16 / -64), user manual r1.0 (04/2020); LG PI485 bus.
Also known as: INMBSLGE016O000, INMBSLGE064O000, LG-AC-MBS-16, LG-AC-MBS-64, Intesis Modbus LG VRF - Heat pump gateway (VRF / split AC gateway)
Intesis (HMS Networks) INMBSPAN001A100 Panasonic Aquarea H/J/K/L/M air-to-water to Modbus RTU gateway
Intesis (HMS Networks) INMBSPAN001A100 gateway connected to Panasonic Aquarea H, J, K, L and M series air-to-water heat pumps, per user manual version 1.0.2 (2026-02-04).
Also known as: INMBSPAN001A100, Aquarea Modbus, Panasonic Aquarea Modbus RTU, Intesis Aquarea, INMBSPAN001A000 (legacy order code) - VRF / split AC gateway
Intesis (HMS Networks) INMBSTOS001R000 Toshiba AC to Modbus RTU gateway
Toshiba Digital Inverter (RAV) and VRF indoor units on the AB remote bus via INMBSTOS001R0xx, user manual r2.9 (01/2024).
Also known as: INMBSTOS001R000, INMBSTOS001R0xx, Intesis Toshiba Modbus
All ac & vrf gateways Modbus register maps →
Source: Functional Specifications D-NET/Modbus Communication adaptor DTA116A51 · CB13A033 · rev. 2013-08-09 · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.