Daikin DTA116A51 D-NET / Modbus communication adaptor (VRV) Modbus register map

Updated 17 November 2026

Short answer

The DTA116A51 connects a Daikin VRV system's D-III NET bus to a Modbus RTU master. Input registers report adaptor readiness, which indoor units are connected, each unit's capabilities, on/off, mode, setpoint, room temperature and error state; holding registers send on/off, mode, fan and setpoint commands. Most per-unit registers pack several small fields into one word, so this map gives the single-bit flags directly and describes the multi-bit fields.

This page lists 196 Modbus registers for the Daikin DTA116A51 D-NET / Modbus communication adaptor (VRV) — 49 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Daikin’s own free documentation (linked below) and checked against it.

Manufacturer
Daikin
Model
DTA116A51 D-NET / Modbus communication adaptor (VRV)
Equipment type
VRF / split AC gateway
Registers
196 (49 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
Also known as
DTA116A51, DIII-NET Modbus adaptor, D3NET Modbus adapter
Source document
Functional Specifications D-NET/Modbus Communication adaptor DTA116A51 · CB13A033 · rev. 2013-08-09 · unofficial copy
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Daikin DTA116A51 D-NET / Modbus communication adaptor (VRV)

Integration in brief

Wait for 30001 = 1, read 30002 to see which indoor units exist, then poll each unit's six status registers from 32001 with function 04 (up to 32 registers per read). Before commanding a unit, copy its current state into its three holding registers; the adaptor sends a command whenever a holding register value changes.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
IR 0Adaptor statusUINT16Adaptor readyRead
IR 1Indoor unit connection statusBITMAP16Which indoor units are connectedRead
IR 5Indoor unit communication statusBITMAP16Indoor unit communication errorsRead
IR 2000IU 1-00 status 1BITMAP16Unit 1-00 on/off and fanRead
IR 2002IU 1-00 setpointINT16Unit 1-00 setpointRead
IR 2004IU 1-00 room temperatureINT16Unit 1-00 room temperatureRead
HR 2000IU 1-00 control 1UINT16Unit 1-00 on/off and fan commandRead/write
HR 2002IU 1-00 setpoint commandINT16Unit 1-00 setpoint commandRead/write

Enable Modbus control & writes

Set the Modbus slave address (1-15, 0 = Modbus off) on DIP switch DS2 and baud, stop bits and parity on DS1. Holding register 40001 sets whether the adaptor is D-NET master; set it to slave (bit 8 = 0) when another central controller is on the VRV system.

Byte order & addressing

Network setup

Watch out for

Daikin DTA116A51 D-NET / Modbus communication adaptor (VRV) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

196 of 196 shown
Daikin DTA116A51 D-NET / Modbus communication adaptor (VRV) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
IR0doc 30001Adaptor statusUINT16Read0 = Not ready; 1 = Ready
IR1doc 30002Indoor unit connection status1 = connected.BITMAP16Readbit 0 = Indoor unit 1-00 connected; bit 1 = Indoor unit 1-01 connected; bit 2 = Indoor unit 1-02 connected; bit 3 = Indoor unit 1-03 connected; bit 4 = Indoor unit 1-04 connected; bit 5 = Indoor unit 1-05 connected; bit 6 = Indoor unit 1-06 connected; bit 7 = Indoor unit 1-07 connected; bit 8 = Indoor unit 1-08 connected; bit 9 = Indoor unit 1-09 connected; bit 10 = Indoor unit 1-10 connected; bit 11 = Indoor unit 1-11 connected; bit 12 = Indoor unit 1-12 connected; bit 13 = Indoor unit 1-13 connected; bit 14 = Indoor unit 1-14 connected; bit 15 = Indoor unit 1-15 connected
IR5doc 30006Indoor unit communication status1 = communication error.BITMAP16Readbit 0 = Indoor unit 1-00 communication error; bit 1 = Indoor unit 1-01 communication error; bit 2 = Indoor unit 1-02 communication error; bit 3 = Indoor unit 1-03 communication error; bit 4 = Indoor unit 1-04 communication error; bit 5 = Indoor unit 1-05 communication error; bit 6 = Indoor unit 1-06 communication error; bit 7 = Indoor unit 1-07 communication error; bit 8 = Indoor unit 1-08 communication error; bit 9 = Indoor unit 1-09 communication error; bit 10 = Indoor unit 1-10 communication error; bit 11 = Indoor unit 1-11 communication error; bit 12 = Indoor unit 1-12 communication error; bit 13 = Indoor unit 1-13 communication error; bit 14 = Indoor unit 1-14 communication error; bit 15 = Indoor unit 1-15 communication error
IR1000doc 31001IU 1-00 capabilitiesBits 8-10 fan direction steps, bits 12-14 fan volume steps (see notes).BITMAP16Readbit 0 = Fan mode available; bit 1 = Cooling mode available; bit 2 = Heating mode available; bit 3 = Auto mode available; bit 4 = Dry mode available; bit 11 = Fan direction available; bit 15 = Fan volume available
IR1001doc 31002IU 1-00 cooling setpoint limitsLow byte = upper limit, high byte = lower limit, each signed 8-bit °C.UINT16Read
IR1002doc 31003IU 1-00 heating setpoint limitsLow byte = upper limit, high byte = lower limit, each signed 8-bit °C.UINT16Read
IR1003doc 31004IU 1-01 capabilitiesBits 8-10 fan direction steps, bits 12-14 fan volume steps (see notes).BITMAP16Readbit 0 = Fan mode available; bit 1 = Cooling mode available; bit 2 = Heating mode available; bit 3 = Auto mode available; bit 4 = Dry mode available; bit 11 = Fan direction available; bit 15 = Fan volume available
IR1004doc 31005IU 1-01 cooling setpoint limitsLow byte = upper limit, high byte = lower limit, each signed 8-bit °C.UINT16Read
IR1005doc 31006IU 1-01 heating setpoint limitsLow byte = upper limit, high byte = lower limit, each signed 8-bit °C.UINT16Read
IR1006doc 31007IU 1-02 capabilitiesBits 8-10 fan direction steps, bits 12-14 fan volume steps (see notes).BITMAP16Readbit 0 = Fan mode available; bit 1 = Cooling mode available; bit 2 = Heating mode available; bit 3 = Auto mode available; bit 4 = Dry mode available; bit 11 = Fan direction available; bit 15 = Fan volume available
IR1007doc 31008IU 1-02 cooling setpoint limitsLow byte = upper limit, high byte = lower limit, each signed 8-bit °C.UINT16Read
IR1008doc 31009IU 1-02 heating setpoint limitsLow byte = upper limit, high byte = lower limit, each signed 8-bit °C.UINT16Read
IR1009doc 31010IU 1-03 capabilitiesBits 8-10 fan direction steps, bits 12-14 fan volume steps (see notes).BITMAP16Readbit 0 = Fan mode available; bit 1 = Cooling mode available; bit 2 = Heating mode available; bit 3 = Auto mode available; bit 4 = Dry mode available; bit 11 = Fan direction available; bit 15 = Fan volume available
IR1010doc 31011IU 1-03 cooling setpoint limitsLow byte = upper limit, high byte = lower limit, each signed 8-bit °C.UINT16Read
IR1011doc 31012IU 1-03 heating setpoint limitsLow byte = upper limit, high byte = lower limit, each signed 8-bit °C.UINT16Read
IR1012doc 31013IU 1-04 capabilitiesBits 8-10 fan direction steps, bits 12-14 fan volume steps (see notes).BITMAP16Readbit 0 = Fan mode available; bit 1 = Cooling mode available; bit 2 = Heating mode available; bit 3 = Auto mode available; bit 4 = Dry mode available; bit 11 = Fan direction available; bit 15 = Fan volume available
IR1013doc 31014IU 1-04 cooling setpoint limitsLow byte = upper limit, high byte = lower limit, each signed 8-bit °C.UINT16Read
IR1014doc 31015IU 1-04 heating setpoint limitsLow byte = upper limit, high byte = lower limit, each signed 8-bit °C.UINT16Read
IR1015doc 31016IU 1-05 capabilitiesBits 8-10 fan direction steps, bits 12-14 fan volume steps (see notes).BITMAP16Readbit 0 = Fan mode available; bit 1 = Cooling mode available; bit 2 = Heating mode available; bit 3 = Auto mode available; bit 4 = Dry mode available; bit 11 = Fan direction available; bit 15 = Fan volume available
IR1016doc 31017IU 1-05 cooling setpoint limitsLow byte = upper limit, high byte = lower limit, each signed 8-bit °C.UINT16Read
IR1017doc 31018IU 1-05 heating setpoint limitsLow byte = upper limit, high byte = lower limit, each signed 8-bit °C.UINT16Read
IR1018doc 31019IU 1-06 capabilitiesBits 8-10 fan direction steps, bits 12-14 fan volume steps (see notes).BITMAP16Readbit 0 = Fan mode available; bit 1 = Cooling mode available; bit 2 = Heating mode available; bit 3 = Auto mode available; bit 4 = Dry mode available; bit 11 = Fan direction available; bit 15 = Fan volume available
IR1019doc 31020IU 1-06 cooling setpoint limitsLow byte = upper limit, high byte = lower limit, each signed 8-bit °C.UINT16Read
IR1020doc 31021IU 1-06 heating setpoint limitsLow byte = upper limit, high byte = lower limit, each signed 8-bit °C.UINT16Read
IR1021doc 31022IU 1-07 capabilitiesBits 8-10 fan direction steps, bits 12-14 fan volume steps (see notes).BITMAP16Readbit 0 = Fan mode available; bit 1 = Cooling mode available; bit 2 = Heating mode available; bit 3 = Auto mode available; bit 4 = Dry mode available; bit 11 = Fan direction available; bit 15 = Fan volume available
IR1022doc 31023IU 1-07 cooling setpoint limitsLow byte = upper limit, high byte = lower limit, each signed 8-bit °C.UINT16Read
IR1023doc 31024IU 1-07 heating setpoint limitsLow byte = upper limit, high byte = lower limit, each signed 8-bit °C.UINT16Read
IR1024doc 31025IU 1-08 capabilitiesBits 8-10 fan direction steps, bits 12-14 fan volume steps (see notes).BITMAP16Readbit 0 = Fan mode available; bit 1 = Cooling mode available; bit 2 = Heating mode available; bit 3 = Auto mode available; bit 4 = Dry mode available; bit 11 = Fan direction available; bit 15 = Fan volume available
IR1025doc 31026IU 1-08 cooling setpoint limitsLow byte = upper limit, high byte = lower limit, each signed 8-bit °C.UINT16Read
IR1026doc 31027IU 1-08 heating setpoint limitsLow byte = upper limit, high byte = lower limit, each signed 8-bit °C.UINT16Read
IR1027doc 31028IU 1-09 capabilitiesBits 8-10 fan direction steps, bits 12-14 fan volume steps (see notes).BITMAP16Readbit 0 = Fan mode available; bit 1 = Cooling mode available; bit 2 = Heating mode available; bit 3 = Auto mode available; bit 4 = Dry mode available; bit 11 = Fan direction available; bit 15 = Fan volume available
IR1028doc 31029IU 1-09 cooling setpoint limitsLow byte = upper limit, high byte = lower limit, each signed 8-bit °C.UINT16Read
IR1029doc 31030IU 1-09 heating setpoint limitsLow byte = upper limit, high byte = lower limit, each signed 8-bit °C.UINT16Read
IR1030doc 31031IU 1-10 capabilitiesBits 8-10 fan direction steps, bits 12-14 fan volume steps (see notes).BITMAP16Readbit 0 = Fan mode available; bit 1 = Cooling mode available; bit 2 = Heating mode available; bit 3 = Auto mode available; bit 4 = Dry mode available; bit 11 = Fan direction available; bit 15 = Fan volume available
IR1031doc 31032IU 1-10 cooling setpoint limitsLow byte = upper limit, high byte = lower limit, each signed 8-bit °C.UINT16Read
IR1032doc 31033IU 1-10 heating setpoint limitsLow byte = upper limit, high byte = lower limit, each signed 8-bit °C.UINT16Read
IR1033doc 31034IU 1-11 capabilitiesBits 8-10 fan direction steps, bits 12-14 fan volume steps (see notes).BITMAP16Readbit 0 = Fan mode available; bit 1 = Cooling mode available; bit 2 = Heating mode available; bit 3 = Auto mode available; bit 4 = Dry mode available; bit 11 = Fan direction available; bit 15 = Fan volume available
IR1034doc 31035IU 1-11 cooling setpoint limitsLow byte = upper limit, high byte = lower limit, each signed 8-bit °C.UINT16Read
IR1035doc 31036IU 1-11 heating setpoint limitsLow byte = upper limit, high byte = lower limit, each signed 8-bit °C.UINT16Read
IR1036doc 31037IU 1-12 capabilitiesBits 8-10 fan direction steps, bits 12-14 fan volume steps (see notes).BITMAP16Readbit 0 = Fan mode available; bit 1 = Cooling mode available; bit 2 = Heating mode available; bit 3 = Auto mode available; bit 4 = Dry mode available; bit 11 = Fan direction available; bit 15 = Fan volume available
IR1037doc 31038IU 1-12 cooling setpoint limitsLow byte = upper limit, high byte = lower limit, each signed 8-bit °C.UINT16Read
IR1038doc 31039IU 1-12 heating setpoint limitsLow byte = upper limit, high byte = lower limit, each signed 8-bit °C.UINT16Read
IR1039doc 31040IU 1-13 capabilitiesBits 8-10 fan direction steps, bits 12-14 fan volume steps (see notes).BITMAP16Readbit 0 = Fan mode available; bit 1 = Cooling mode available; bit 2 = Heating mode available; bit 3 = Auto mode available; bit 4 = Dry mode available; bit 11 = Fan direction available; bit 15 = Fan volume available
IR1040doc 31041IU 1-13 cooling setpoint limitsLow byte = upper limit, high byte = lower limit, each signed 8-bit °C.UINT16Read
IR1041doc 31042IU 1-13 heating setpoint limitsLow byte = upper limit, high byte = lower limit, each signed 8-bit °C.UINT16Read
IR1042doc 31043IU 1-14 capabilitiesBits 8-10 fan direction steps, bits 12-14 fan volume steps (see notes).BITMAP16Readbit 0 = Fan mode available; bit 1 = Cooling mode available; bit 2 = Heating mode available; bit 3 = Auto mode available; bit 4 = Dry mode available; bit 11 = Fan direction available; bit 15 = Fan volume available
IR1043doc 31044IU 1-14 cooling setpoint limitsLow byte = upper limit, high byte = lower limit, each signed 8-bit °C.UINT16Read
IR1044doc 31045IU 1-14 heating setpoint limitsLow byte = upper limit, high byte = lower limit, each signed 8-bit °C.UINT16Read
IR1045doc 31046IU 1-15 capabilitiesBits 8-10 fan direction steps, bits 12-14 fan volume steps (see notes).BITMAP16Readbit 0 = Fan mode available; bit 1 = Cooling mode available; bit 2 = Heating mode available; bit 3 = Auto mode available; bit 4 = Dry mode available; bit 11 = Fan direction available; bit 15 = Fan volume available
IR1046doc 31047IU 1-15 cooling setpoint limitsLow byte = upper limit, high byte = lower limit, each signed 8-bit °C.UINT16Read
IR1047doc 31048IU 1-15 heating setpoint limitsLow byte = upper limit, high byte = lower limit, each signed 8-bit °C.UINT16Read
IR2000doc 32001IU 1-00 status 1Bits 8-10 fan direction (7 = swing), bits 12-14 fan volume.BITMAP16Readbit 0 = On; bit 2 = Forced off
IR2001doc 32002IU 1-00 status 2Packed: mode, filter sign, actual operation, cool/heat master (see notes).UINT16Read
IR2002doc 32003IU 1-00 setpointINT16× 0.1°CRead
IR2003doc 32004IU 1-00 errorBits 0-3 and 4-8: error code mapping values (see section 6 of the spec).BITMAP16Readbit 9 = Malfunction; bit 10 = Warning
IR2004doc 32005IU 1-00 room temperatureINT16× 0.1°CRead
IR2005doc 32006IU 1-00 temperature sensor statusBITMAP16Readbit 8 = Temperature sensor error; bit 15 = Sensor data received
IR2006doc 32007IU 1-01 status 1Bits 8-10 fan direction (7 = swing), bits 12-14 fan volume.BITMAP16Readbit 0 = On; bit 2 = Forced off
IR2007doc 32008IU 1-01 status 2Packed: mode, filter sign, actual operation, cool/heat master (see notes).UINT16Read
IR2008doc 32009IU 1-01 setpointINT16× 0.1°CRead
IR2009doc 32010IU 1-01 errorBits 0-3 and 4-8: error code mapping values (see section 6 of the spec).BITMAP16Readbit 9 = Malfunction; bit 10 = Warning
IR2010doc 32011IU 1-01 room temperatureINT16× 0.1°CRead
IR2011doc 32012IU 1-01 temperature sensor statusBITMAP16Readbit 8 = Temperature sensor error; bit 15 = Sensor data received
IR2012doc 32013IU 1-02 status 1Bits 8-10 fan direction (7 = swing), bits 12-14 fan volume.BITMAP16Readbit 0 = On; bit 2 = Forced off
IR2013doc 32014IU 1-02 status 2Packed: mode, filter sign, actual operation, cool/heat master (see notes).UINT16Read
IR2014doc 32015IU 1-02 setpointINT16× 0.1°CRead
IR2015doc 32016IU 1-02 errorBits 0-3 and 4-8: error code mapping values (see section 6 of the spec).BITMAP16Readbit 9 = Malfunction; bit 10 = Warning
IR2016doc 32017IU 1-02 room temperatureINT16× 0.1°CRead
IR2017doc 32018IU 1-02 temperature sensor statusBITMAP16Readbit 8 = Temperature sensor error; bit 15 = Sensor data received
IR2018doc 32019IU 1-03 status 1Bits 8-10 fan direction (7 = swing), bits 12-14 fan volume.BITMAP16Readbit 0 = On; bit 2 = Forced off
IR2019doc 32020IU 1-03 status 2Packed: mode, filter sign, actual operation, cool/heat master (see notes).UINT16Read
IR2020doc 32021IU 1-03 setpointINT16× 0.1°CRead
IR2021doc 32022IU 1-03 errorBits 0-3 and 4-8: error code mapping values (see section 6 of the spec).BITMAP16Readbit 9 = Malfunction; bit 10 = Warning
IR2022doc 32023IU 1-03 room temperatureINT16× 0.1°CRead
IR2023doc 32024IU 1-03 temperature sensor statusBITMAP16Readbit 8 = Temperature sensor error; bit 15 = Sensor data received
IR2024doc 32025IU 1-04 status 1Bits 8-10 fan direction (7 = swing), bits 12-14 fan volume.BITMAP16Readbit 0 = On; bit 2 = Forced off
IR2025doc 32026IU 1-04 status 2Packed: mode, filter sign, actual operation, cool/heat master (see notes).UINT16Read
IR2026doc 32027IU 1-04 setpointINT16× 0.1°CRead
IR2027doc 32028IU 1-04 errorBits 0-3 and 4-8: error code mapping values (see section 6 of the spec).BITMAP16Readbit 9 = Malfunction; bit 10 = Warning
IR2028doc 32029IU 1-04 room temperatureINT16× 0.1°CRead
IR2029doc 32030IU 1-04 temperature sensor statusBITMAP16Readbit 8 = Temperature sensor error; bit 15 = Sensor data received
IR2030doc 32031IU 1-05 status 1Bits 8-10 fan direction (7 = swing), bits 12-14 fan volume.BITMAP16Readbit 0 = On; bit 2 = Forced off
IR2031doc 32032IU 1-05 status 2Packed: mode, filter sign, actual operation, cool/heat master (see notes).UINT16Read
IR2032doc 32033IU 1-05 setpointINT16× 0.1°CRead
IR2033doc 32034IU 1-05 errorBits 0-3 and 4-8: error code mapping values (see section 6 of the spec).BITMAP16Readbit 9 = Malfunction; bit 10 = Warning
IR2034doc 32035IU 1-05 room temperatureINT16× 0.1°CRead
IR2035doc 32036IU 1-05 temperature sensor statusBITMAP16Readbit 8 = Temperature sensor error; bit 15 = Sensor data received
IR2036doc 32037IU 1-06 status 1Bits 8-10 fan direction (7 = swing), bits 12-14 fan volume.BITMAP16Readbit 0 = On; bit 2 = Forced off
IR2037doc 32038IU 1-06 status 2Packed: mode, filter sign, actual operation, cool/heat master (see notes).UINT16Read
IR2038doc 32039IU 1-06 setpointINT16× 0.1°CRead
IR2039doc 32040IU 1-06 errorBits 0-3 and 4-8: error code mapping values (see section 6 of the spec).BITMAP16Readbit 9 = Malfunction; bit 10 = Warning
IR2040doc 32041IU 1-06 room temperatureINT16× 0.1°CRead
IR2041doc 32042IU 1-06 temperature sensor statusBITMAP16Readbit 8 = Temperature sensor error; bit 15 = Sensor data received
IR2042doc 32043IU 1-07 status 1Bits 8-10 fan direction (7 = swing), bits 12-14 fan volume.BITMAP16Readbit 0 = On; bit 2 = Forced off
IR2043doc 32044IU 1-07 status 2Packed: mode, filter sign, actual operation, cool/heat master (see notes).UINT16Read
IR2044doc 32045IU 1-07 setpointINT16× 0.1°CRead
IR2045doc 32046IU 1-07 errorBits 0-3 and 4-8: error code mapping values (see section 6 of the spec).BITMAP16Readbit 9 = Malfunction; bit 10 = Warning
IR2046doc 32047IU 1-07 room temperatureINT16× 0.1°CRead
IR2047doc 32048IU 1-07 temperature sensor statusBITMAP16Readbit 8 = Temperature sensor error; bit 15 = Sensor data received
IR2048doc 32049IU 1-08 status 1Bits 8-10 fan direction (7 = swing), bits 12-14 fan volume.BITMAP16Readbit 0 = On; bit 2 = Forced off
IR2049doc 32050IU 1-08 status 2Packed: mode, filter sign, actual operation, cool/heat master (see notes).UINT16Read
IR2050doc 32051IU 1-08 setpointINT16× 0.1°CRead
IR2051doc 32052IU 1-08 errorBits 0-3 and 4-8: error code mapping values (see section 6 of the spec).BITMAP16Readbit 9 = Malfunction; bit 10 = Warning
IR2052doc 32053IU 1-08 room temperatureINT16× 0.1°CRead
IR2053doc 32054IU 1-08 temperature sensor statusBITMAP16Readbit 8 = Temperature sensor error; bit 15 = Sensor data received
IR2054doc 32055IU 1-09 status 1Bits 8-10 fan direction (7 = swing), bits 12-14 fan volume.BITMAP16Readbit 0 = On; bit 2 = Forced off
IR2055doc 32056IU 1-09 status 2Packed: mode, filter sign, actual operation, cool/heat master (see notes).UINT16Read
IR2056doc 32057IU 1-09 setpointINT16× 0.1°CRead
IR2057doc 32058IU 1-09 errorBits 0-3 and 4-8: error code mapping values (see section 6 of the spec).BITMAP16Readbit 9 = Malfunction; bit 10 = Warning
IR2058doc 32059IU 1-09 room temperatureINT16× 0.1°CRead
IR2059doc 32060IU 1-09 temperature sensor statusBITMAP16Readbit 8 = Temperature sensor error; bit 15 = Sensor data received
IR2060doc 32061IU 1-10 status 1Bits 8-10 fan direction (7 = swing), bits 12-14 fan volume.BITMAP16Readbit 0 = On; bit 2 = Forced off
IR2061doc 32062IU 1-10 status 2Packed: mode, filter sign, actual operation, cool/heat master (see notes).UINT16Read
IR2062doc 32063IU 1-10 setpointINT16× 0.1°CRead
IR2063doc 32064IU 1-10 errorBits 0-3 and 4-8: error code mapping values (see section 6 of the spec).BITMAP16Readbit 9 = Malfunction; bit 10 = Warning
IR2064doc 32065IU 1-10 room temperatureINT16× 0.1°CRead
IR2065doc 32066IU 1-10 temperature sensor statusBITMAP16Readbit 8 = Temperature sensor error; bit 15 = Sensor data received
IR2066doc 32067IU 1-11 status 1Bits 8-10 fan direction (7 = swing), bits 12-14 fan volume.BITMAP16Readbit 0 = On; bit 2 = Forced off
IR2067doc 32068IU 1-11 status 2Packed: mode, filter sign, actual operation, cool/heat master (see notes).UINT16Read
IR2068doc 32069IU 1-11 setpointINT16× 0.1°CRead
IR2069doc 32070IU 1-11 errorBits 0-3 and 4-8: error code mapping values (see section 6 of the spec).BITMAP16Readbit 9 = Malfunction; bit 10 = Warning
IR2070doc 32071IU 1-11 room temperatureINT16× 0.1°CRead
IR2071doc 32072IU 1-11 temperature sensor statusBITMAP16Readbit 8 = Temperature sensor error; bit 15 = Sensor data received
IR2072doc 32073IU 1-12 status 1Bits 8-10 fan direction (7 = swing), bits 12-14 fan volume.BITMAP16Readbit 0 = On; bit 2 = Forced off
IR2073doc 32074IU 1-12 status 2Packed: mode, filter sign, actual operation, cool/heat master (see notes).UINT16Read
IR2074doc 32075IU 1-12 setpointINT16× 0.1°CRead
IR2075doc 32076IU 1-12 errorBits 0-3 and 4-8: error code mapping values (see section 6 of the spec).BITMAP16Readbit 9 = Malfunction; bit 10 = Warning
IR2076doc 32077IU 1-12 room temperatureINT16× 0.1°CRead
IR2077doc 32078IU 1-12 temperature sensor statusBITMAP16Readbit 8 = Temperature sensor error; bit 15 = Sensor data received
IR2078doc 32079IU 1-13 status 1Bits 8-10 fan direction (7 = swing), bits 12-14 fan volume.BITMAP16Readbit 0 = On; bit 2 = Forced off
IR2079doc 32080IU 1-13 status 2Packed: mode, filter sign, actual operation, cool/heat master (see notes).UINT16Read
IR2080doc 32081IU 1-13 setpointINT16× 0.1°CRead
IR2081doc 32082IU 1-13 errorBits 0-3 and 4-8: error code mapping values (see section 6 of the spec).BITMAP16Readbit 9 = Malfunction; bit 10 = Warning
IR2082doc 32083IU 1-13 room temperatureINT16× 0.1°CRead
IR2083doc 32084IU 1-13 temperature sensor statusBITMAP16Readbit 8 = Temperature sensor error; bit 15 = Sensor data received
IR2084doc 32085IU 1-14 status 1Bits 8-10 fan direction (7 = swing), bits 12-14 fan volume.BITMAP16Readbit 0 = On; bit 2 = Forced off
IR2085doc 32086IU 1-14 status 2Packed: mode, filter sign, actual operation, cool/heat master (see notes).UINT16Read
IR2086doc 32087IU 1-14 setpointINT16× 0.1°CRead
IR2087doc 32088IU 1-14 errorBits 0-3 and 4-8: error code mapping values (see section 6 of the spec).BITMAP16Readbit 9 = Malfunction; bit 10 = Warning
IR2088doc 32089IU 1-14 room temperatureINT16× 0.1°CRead
IR2089doc 32090IU 1-14 temperature sensor statusBITMAP16Readbit 8 = Temperature sensor error; bit 15 = Sensor data received
IR2090doc 32091IU 1-15 status 1Bits 8-10 fan direction (7 = swing), bits 12-14 fan volume.BITMAP16Readbit 0 = On; bit 2 = Forced off
IR2091doc 32092IU 1-15 status 2Packed: mode, filter sign, actual operation, cool/heat master (see notes).UINT16Read
IR2092doc 32093IU 1-15 setpointINT16× 0.1°CRead
IR2093doc 32094IU 1-15 errorBits 0-3 and 4-8: error code mapping values (see section 6 of the spec).BITMAP16Readbit 9 = Malfunction; bit 10 = Warning
IR2094doc 32095IU 1-15 room temperatureINT16× 0.1°CRead
IR2095doc 32096IU 1-15 temperature sensor statusBITMAP16Readbit 8 = Temperature sensor error; bit 15 = Sensor data received
HR0doc 40001Adaptor initial settingStored in EEPROM; takes effect after a power cycle. Each bit defaults to 1.BITMAP16Read/writebit 0 = Manage D-NET addresses 1-00 to 1-15; bit 8 = Adaptor is D-NET master (0 = slave); bit 15 = D-NET communication start (0 = stop)
HR2000doc 42001IU 1-00 control 1Packed: bit 0 on/off, bits 4-7 = 6, fan direction, fan volume (see notes).UINT16Read/write
HR2001doc 42002IU 1-00 control 2Packed: operation mode, filter sign reset, auto heat/cool select (see notes).UINT16Read/write
HR2002doc 42003IU 1-00 setpoint commandINT16× 0.1°CRead/write
HR2003doc 42004IU 1-01 control 1Packed: bit 0 on/off, bits 4-7 = 6, fan direction, fan volume (see notes).UINT16Read/write
HR2004doc 42005IU 1-01 control 2Packed: operation mode, filter sign reset, auto heat/cool select (see notes).UINT16Read/write
HR2005doc 42006IU 1-01 setpoint commandINT16× 0.1°CRead/write
HR2006doc 42007IU 1-02 control 1Packed: bit 0 on/off, bits 4-7 = 6, fan direction, fan volume (see notes).UINT16Read/write
HR2007doc 42008IU 1-02 control 2Packed: operation mode, filter sign reset, auto heat/cool select (see notes).UINT16Read/write
HR2008doc 42009IU 1-02 setpoint commandINT16× 0.1°CRead/write
HR2009doc 42010IU 1-03 control 1Packed: bit 0 on/off, bits 4-7 = 6, fan direction, fan volume (see notes).UINT16Read/write
HR2010doc 42011IU 1-03 control 2Packed: operation mode, filter sign reset, auto heat/cool select (see notes).UINT16Read/write
HR2011doc 42012IU 1-03 setpoint commandINT16× 0.1°CRead/write
HR2012doc 42013IU 1-04 control 1Packed: bit 0 on/off, bits 4-7 = 6, fan direction, fan volume (see notes).UINT16Read/write
HR2013doc 42014IU 1-04 control 2Packed: operation mode, filter sign reset, auto heat/cool select (see notes).UINT16Read/write
HR2014doc 42015IU 1-04 setpoint commandINT16× 0.1°CRead/write
HR2015doc 42016IU 1-05 control 1Packed: bit 0 on/off, bits 4-7 = 6, fan direction, fan volume (see notes).UINT16Read/write
HR2016doc 42017IU 1-05 control 2Packed: operation mode, filter sign reset, auto heat/cool select (see notes).UINT16Read/write
HR2017doc 42018IU 1-05 setpoint commandINT16× 0.1°CRead/write
HR2018doc 42019IU 1-06 control 1Packed: bit 0 on/off, bits 4-7 = 6, fan direction, fan volume (see notes).UINT16Read/write
HR2019doc 42020IU 1-06 control 2Packed: operation mode, filter sign reset, auto heat/cool select (see notes).UINT16Read/write
HR2020doc 42021IU 1-06 setpoint commandINT16× 0.1°CRead/write
HR2021doc 42022IU 1-07 control 1Packed: bit 0 on/off, bits 4-7 = 6, fan direction, fan volume (see notes).UINT16Read/write
HR2022doc 42023IU 1-07 control 2Packed: operation mode, filter sign reset, auto heat/cool select (see notes).UINT16Read/write
HR2023doc 42024IU 1-07 setpoint commandINT16× 0.1°CRead/write
HR2024doc 42025IU 1-08 control 1Packed: bit 0 on/off, bits 4-7 = 6, fan direction, fan volume (see notes).UINT16Read/write
HR2025doc 42026IU 1-08 control 2Packed: operation mode, filter sign reset, auto heat/cool select (see notes).UINT16Read/write
HR2026doc 42027IU 1-08 setpoint commandINT16× 0.1°CRead/write
HR2027doc 42028IU 1-09 control 1Packed: bit 0 on/off, bits 4-7 = 6, fan direction, fan volume (see notes).UINT16Read/write
HR2028doc 42029IU 1-09 control 2Packed: operation mode, filter sign reset, auto heat/cool select (see notes).UINT16Read/write
HR2029doc 42030IU 1-09 setpoint commandINT16× 0.1°CRead/write
HR2030doc 42031IU 1-10 control 1Packed: bit 0 on/off, bits 4-7 = 6, fan direction, fan volume (see notes).UINT16Read/write
HR2031doc 42032IU 1-10 control 2Packed: operation mode, filter sign reset, auto heat/cool select (see notes).UINT16Read/write
HR2032doc 42033IU 1-10 setpoint commandINT16× 0.1°CRead/write
HR2033doc 42034IU 1-11 control 1Packed: bit 0 on/off, bits 4-7 = 6, fan direction, fan volume (see notes).UINT16Read/write
HR2034doc 42035IU 1-11 control 2Packed: operation mode, filter sign reset, auto heat/cool select (see notes).UINT16Read/write
HR2035doc 42036IU 1-11 setpoint commandINT16× 0.1°CRead/write
HR2036doc 42037IU 1-12 control 1Packed: bit 0 on/off, bits 4-7 = 6, fan direction, fan volume (see notes).UINT16Read/write
HR2037doc 42038IU 1-12 control 2Packed: operation mode, filter sign reset, auto heat/cool select (see notes).UINT16Read/write
HR2038doc 42039IU 1-12 setpoint commandINT16× 0.1°CRead/write
HR2039doc 42040IU 1-13 control 1Packed: bit 0 on/off, bits 4-7 = 6, fan direction, fan volume (see notes).UINT16Read/write
HR2040doc 42041IU 1-13 control 2Packed: operation mode, filter sign reset, auto heat/cool select (see notes).UINT16Read/write
HR2041doc 42042IU 1-13 setpoint commandINT16× 0.1°CRead/write
HR2042doc 42043IU 1-14 control 1Packed: bit 0 on/off, bits 4-7 = 6, fan direction, fan volume (see notes).UINT16Read/write
HR2043doc 42044IU 1-14 control 2Packed: operation mode, filter sign reset, auto heat/cool select (see notes).UINT16Read/write
HR2044doc 42045IU 1-14 setpoint commandINT16× 0.1°CRead/write
HR2045doc 42046IU 1-15 control 1Packed: bit 0 on/off, bits 4-7 = 6, fan direction, fan volume (see notes).UINT16Read/write
HR2046doc 42047IU 1-15 control 2Packed: operation mode, filter sign reset, auto heat/cool select (see notes).UINT16Read/write
HR2047doc 42048IU 1-15 setpoint commandINT16× 0.1°CRead/write

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Daikin DTA116A51 D-NET / Modbus communication adaptor (VRV)

What Modbus registers does the Daikin DTA116A51 D-NET / Modbus communication adaptor (VRV) have?

This map lists 196 registers: 147 input registers, 49 holding registers. 49 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Daikin DTA116A51 D-NET / Modbus communication adaptor (VRV) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The spec lists 30001/40001-style registers and states that the request addresses them from zero (30001 is sent as 0, 40001 as 0). Its example frames confirm it: register 31001 is requested as 0x03E8 and 42002 as 0x07D1.

What are the minimum Modbus registers to integrate the Daikin DTA116A51 D-NET / Modbus communication adaptor (VRV)?

Start with IR 0 Adaptor status (Adaptor ready); IR 1 Indoor unit connection status (Which indoor units are connected); IR 5 Indoor unit communication status (Indoor unit communication errors); IR 2000 IU 1-00 status 1 (Unit 1-00 on/off and fan); IR 2002 IU 1-00 setpoint (Unit 1-00 setpoint); IR 2004 IU 1-00 room temperature (Unit 1-00 room temperature); HR 2000 IU 1-00 control 1 (Unit 1-00 on/off and fan command); HR 2002 IU 1-00 setpoint command (Unit 1-00 setpoint command).

How do I enable Modbus control of the Daikin DTA116A51 D-NET / Modbus communication adaptor (VRV)?

Set the Modbus slave address (1-15, 0 = Modbus off) on DIP switch DS2 and baud, stop bits and parity on DS1. Holding register 40001 sets whether the adaptor is D-NET master; set it to slave (bit 8 = 0) when another central controller is on the VRV system.

Where is the official Daikin DTA116A51 D-NET / Modbus communication adaptor (VRV) Modbus documentation?

The source is Functional Specifications D-NET/Modbus Communication adaptor DTA116A51 (CB13A033), revision 2013-08-09. Daikin doesn't publish it on its own website, so this map was re-typed from a free copy at https://taphome.com/compatibility/devices/daikin-dta116a51-vrv/manufacturer/functional-specifications.pdf. It may be an older revision, so check it against the live unit.

More Daikin Modbus register maps

Other ac & vrf gateways register maps

All ac & vrf gateways Modbus register maps →

Source: Functional Specifications D-NET/Modbus Communication adaptor DTA116A51 · CB13A033 · rev. 2013-08-09 · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.