VRF / split AC gateway · Modbus register map
Daikin EKMBDXB Modbus Interface DIII Modbus register map
Updated 17 November 2026
The EKMBDXB connects to the Daikin DIII-net and presents up to 64 indoor groups (DIII addresses 1-00 to 4-15) to a BMS as Modbus RTU registers. Each group has capability, status, setpoint, room temperature, water setpoint, error and lock registers. This map lists the gateway status words and the full register set of group 1-00 plus the formula for the other groups.
This page lists 34 Modbus registers for the Daikin EKMBDXB Modbus Interface DIII — 9 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Daikin’s own free documentation (linked below) and checked against it.
- Manufacturer
- Daikin
- Model
- EKMBDXB Modbus Interface DIII
- Equipment type
- VRF / split AC gateway
- Registers
- 34 (9 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- Also known as
- EKMBDXB7V1, Modbus Interface DIII
Integration notes: Daikin EKMBDXB Modbus Interface DIII
Wait for 30001 bit 0 = ready, read 30002-30005 to find connected groups, then poll each group's 32001-32005 status block. To command, copy the current status bits into 42001/42002 first, change only what you need, and write setpoints to 42003 in 0.1 °C.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| IR 0 | Interface status | BITMAP16 | Interface ready | Read |
| IR 1 | DIII units 1-00..1-15 connected | BITMAP16 | Groups 1-00..1-15 connected | Read |
| IR 2000 | 1-00 status 1 | BITMAP16 | 1-00 on/off, fan, thermo | Read |
| IR 2001 | 1-00 status 2 | BITMAP16 | 1-00 mode, filter, defrost | Read |
| IR 2004 | 1-00 room temperature | INT16 | 1-00 room temperature | Read |
| IR 3600 | 1-00 error code | UINT16 | 1-00 error code | Read |
| HR 2000 | 1-00 control 1 | UINT16 | 1-00 on/off and fan command | Read/write |
| HR 2002 | 1-00 room setpoint command | INT16 | 1-00 setpoint command | Read/write |
Enable Modbus control & writes
Set baud rate, parity/stop bits and the Modbus address (1-15) on dip switches DS1/DS2 of the interface; the DIII units are discovered automatically after power-up.
Byte order & addressing
- Holding registers only take the unit's values at discovery; the BMS must copy the related input-register bits into a holding register before changing one field, or it will overwrite the others.
- Write the fan control flag (42001 bits 4-7) as 6 when commanding fan speed or direction, 0 if the unit has no fan control.
- Do not write the same register more often than every 0.5 s. Each indoor unit accepts at most 7000 control commands per year.
Network setup
- Modbus address 1-15 on DS2; baud 9600 or 19200 and Even/Odd/None parity on DS1.
- Set termination with the SS switches at the end of the RS485 line.
Watch out for
- Central forced off (41001) and the button locks (42801+) only work when no other DIII central controller (e.g. iTM) is on the same DIII-net.
- After a power cut of the interface, forced off and locks must be written again once the units are rediscovered.
Daikin EKMBDXB Modbus Interface DIII Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| IR | 0doc 30001 | Interface status | Bit 0: 0 = busy, 1 = ready. Bit 1: another DIII device exists. | BITMAP16 | Read | bit 0 = Modbus Interface DIII ready (0 = busy); bit 1 = Other DIII device exists | |||
| IR | 1doc 30002 | DIII units 1-00..1-15 connected | 1 = connected. | BITMAP16 | Read | bit 0 = DIII 1-00 connected; bit 1 = DIII 1-01 connected; bit 2 = DIII 1-02 connected; bit 3 = DIII 1-03 connected; bit 4 = DIII 1-04 connected; bit 5 = DIII 1-05 connected; bit 6 = DIII 1-06 connected; bit 7 = DIII 1-07 connected; bit 8 = DIII 1-08 connected; bit 9 = DIII 1-09 connected; bit 10 = DIII 1-10 connected; bit 11 = DIII 1-11 connected; bit 12 = DIII 1-12 connected; bit 13 = DIII 1-13 connected; bit 14 = DIII 1-14 connected; bit 15 = DIII 1-15 connected | |||
| IR | 2doc 30003 | DIII units 2-00..2-15 connected | 1 = connected. | BITMAP16 | Read | bit 0 = DIII 2-00 connected; bit 1 = DIII 2-01 connected; bit 2 = DIII 2-02 connected; bit 3 = DIII 2-03 connected; bit 4 = DIII 2-04 connected; bit 5 = DIII 2-05 connected; bit 6 = DIII 2-06 connected; bit 7 = DIII 2-07 connected; bit 8 = DIII 2-08 connected; bit 9 = DIII 2-09 connected; bit 10 = DIII 2-10 connected; bit 11 = DIII 2-11 connected; bit 12 = DIII 2-12 connected; bit 13 = DIII 2-13 connected; bit 14 = DIII 2-14 connected; bit 15 = DIII 2-15 connected | |||
| IR | 3doc 30004 | DIII units 3-00..3-15 connected | 1 = connected. | BITMAP16 | Read | bit 0 = DIII 3-00 connected; bit 1 = DIII 3-01 connected; bit 2 = DIII 3-02 connected; bit 3 = DIII 3-03 connected; bit 4 = DIII 3-04 connected; bit 5 = DIII 3-05 connected; bit 6 = DIII 3-06 connected; bit 7 = DIII 3-07 connected; bit 8 = DIII 3-08 connected; bit 9 = DIII 3-09 connected; bit 10 = DIII 3-10 connected; bit 11 = DIII 3-11 connected; bit 12 = DIII 3-12 connected; bit 13 = DIII 3-13 connected; bit 14 = DIII 3-14 connected; bit 15 = DIII 3-15 connected | |||
| IR | 4doc 30005 | DIII units 4-00..4-15 connected | 1 = connected. | BITMAP16 | Read | bit 0 = DIII 4-00 connected; bit 1 = DIII 4-01 connected; bit 2 = DIII 4-02 connected; bit 3 = DIII 4-03 connected; bit 4 = DIII 4-04 connected; bit 5 = DIII 4-05 connected; bit 6 = DIII 4-06 connected; bit 7 = DIII 4-07 connected; bit 8 = DIII 4-08 connected; bit 9 = DIII 4-09 connected; bit 10 = DIII 4-10 connected; bit 11 = DIII 4-11 connected; bit 12 = DIII 4-12 connected; bit 13 = DIII 4-13 connected; bit 14 = DIII 4-14 connected; bit 15 = DIII 4-15 connected | |||
| IR | 5doc 30006 | DIII units 1-00..1-15 communication | 1 = communication error. | BITMAP16 | Read | bit 0 = DIII 1-00 communication error; bit 1 = DIII 1-01 communication error; bit 2 = DIII 1-02 communication error; bit 3 = DIII 1-03 communication error; bit 4 = DIII 1-04 communication error; bit 5 = DIII 1-05 communication error; bit 6 = DIII 1-06 communication error; bit 7 = DIII 1-07 communication error; bit 8 = DIII 1-08 communication error; bit 9 = DIII 1-09 communication error; bit 10 = DIII 1-10 communication error; bit 11 = DIII 1-11 communication error; bit 12 = DIII 1-12 communication error; bit 13 = DIII 1-13 communication error; bit 14 = DIII 1-14 communication error; bit 15 = DIII 1-15 communication error | |||
| IR | 6doc 30007 | DIII units 2-00..2-15 communication | 1 = communication error. | BITMAP16 | Read | bit 0 = DIII 2-00 communication error; bit 1 = DIII 2-01 communication error; bit 2 = DIII 2-02 communication error; bit 3 = DIII 2-03 communication error; bit 4 = DIII 2-04 communication error; bit 5 = DIII 2-05 communication error; bit 6 = DIII 2-06 communication error; bit 7 = DIII 2-07 communication error; bit 8 = DIII 2-08 communication error; bit 9 = DIII 2-09 communication error; bit 10 = DIII 2-10 communication error; bit 11 = DIII 2-11 communication error; bit 12 = DIII 2-12 communication error; bit 13 = DIII 2-13 communication error; bit 14 = DIII 2-14 communication error; bit 15 = DIII 2-15 communication error | |||
| IR | 7doc 30008 | DIII units 3-00..3-15 communication | 1 = communication error. | BITMAP16 | Read | bit 0 = DIII 3-00 communication error; bit 1 = DIII 3-01 communication error; bit 2 = DIII 3-02 communication error; bit 3 = DIII 3-03 communication error; bit 4 = DIII 3-04 communication error; bit 5 = DIII 3-05 communication error; bit 6 = DIII 3-06 communication error; bit 7 = DIII 3-07 communication error; bit 8 = DIII 3-08 communication error; bit 9 = DIII 3-09 communication error; bit 10 = DIII 3-10 communication error; bit 11 = DIII 3-11 communication error; bit 12 = DIII 3-12 communication error; bit 13 = DIII 3-13 communication error; bit 14 = DIII 3-14 communication error; bit 15 = DIII 3-15 communication error | |||
| IR | 8doc 30009 | DIII units 4-00..4-15 communication | 1 = communication error. | BITMAP16 | Read | bit 0 = DIII 4-00 communication error; bit 1 = DIII 4-01 communication error; bit 2 = DIII 4-02 communication error; bit 3 = DIII 4-03 communication error; bit 4 = DIII 4-04 communication error; bit 5 = DIII 4-05 communication error; bit 6 = DIII 4-06 communication error; bit 7 = DIII 4-07 communication error; bit 8 = DIII 4-08 communication error; bit 9 = DIII 4-09 communication error; bit 10 = DIII 4-10 communication error; bit 11 = DIII 4-11 communication error; bit 12 = DIII 4-12 communication error; bit 13 = DIII 4-13 communication error; bit 14 = DIII 4-14 communication error; bit 15 = DIII 4-15 communication error | |||
| IR | 1000doc 31001 | 1-00 capability | Bits 8-10 fan direction steps, bits 12-14 fan speed steps (0-7). | BITMAP16 | Read | bit 0 = Fan mode capability; bit 1 = Cooling mode capability; bit 2 = Heating mode capability; bit 3 = Auto mode capability; bit 4 = Dry mode capability; bit 11 = Fan direction capability; bit 15 = Fan speed capability | |||
| IR | 1001doc 31002 | 1-00 cooling setpoint range | High byte lower limit, low byte upper limit; each signed 8-bit, 1 °C. | UINT16 | Read | ||||
| IR | 1002doc 31003 | 1-00 heating setpoint range | High byte lower limit, low byte upper limit; each signed 8-bit, 1 °C. | UINT16 | Read | ||||
| IR | 1400doc 31401 | 1-00 water capability | Leaving water, low noise, space heating and reheat capability flags. | BITMAP16 | Read | bit 1 = Leaving water set point exists; bit 2 = Low noise capability; bit 4 = Space heating capability; bit 5 = Reheat capability | |||
| IR | 1401doc 31402 | 1-00 cooling water setpoint range | High byte upper limit, low byte lower limit; each signed 8-bit, 1 °C. | UINT16 | Read | ||||
| IR | 1402doc 31403 | 1-00 heating water setpoint range | High byte upper limit, low byte lower limit; each signed 8-bit, 1 °C. | UINT16 | Read | ||||
| IR | 2000doc 32001 | 1-00 status 1 | Bits 12-14 fan speed, bits 8-10 fan direction (0-4 P0-P4, 6 stop, 7 swing). | BITMAP16 | Read | bit 0 = On; bit 2 = Forced off (T1-T2 input or central forced off); bit 3 = Normal operation (1 = running normally; 0 = off, or on with an error); bit 5 = Indoor fan on; bit 6 = Heater on; bit 7 = Thermostat on | |||
| IR | 2001doc 32002 | 1-00 status 2 | Bits 0-3 mode, 4-7 filter sign, 8-11 actual run, 14-15 cool/heat master (see notes). | BITMAP16 | Read | bit 13 = Defrost / hot start | |||
| IR | 2002doc 32003 | 1-00 room setpoint | INT16 | × 0.1 | °C | Read | |||
| IR | 2004doc 32005 | 1-00 room temperature | Suction temperature, or user-interface sensor if set up. | INT16 | × 0.1 | °C | Read | ||
| IR | 2800doc 32801 | 1-00 heating water setpoint | INT16 | × 0.1 | °C | Read | |||
| IR | 2801doc 32802 | 1-00 cooling water setpoint | INT16 | × 0.1 | °C | Read | |||
| IR | 2802doc 32803 | 1-00 hot water / quiet status | High byte: storage setpoint (signed 8-bit; scale stated inconsistently, see notes). | BITMAP16 | Read | bit 0 = Reheat on; bit 1 = Storage start requested; bit 2 = Low noise on | |||
| IR | 2803doc 32804 | 1-00 ventilation mode | Bits 6-7: 1 auto, 2 energy reclaim, 3 bypass (VAM only). | UINT16 | Read | ||||
| IR | 3600doc 33601 | 1-00 error code | Two ASCII characters, high byte first; "00" = no error. | UINT16 | Read | ||||
| IR | 3601doc 33602 | 1-00 error detail | Bits 12-15 unit number, bits 0-5 sub-code. | BITMAP16 | Read | bit 8 = Error (unit stopped); bit 9 = Alarm; bit 10 = Warning | |||
| HR | 1000doc 41001 | Central forced off | 1 = force off all DIII units (only without other DIII devices). | UINT16 | Read/write | 0 = None; 1 = Forced off | |||
| HR | 2000doc 42001 | 1-00 control 1 | Bit 0 on/off, bits 4-7 = 6 for fan control, fan direction, fan speed. | UINT16 | Read/write | ||||
| HR | 2001doc 42002 | 1-00 control 2 | Bits 0-3 operation mode, bits 4-7 filter sign reset (15). | UINT16 | Read/write | ||||
| HR | 2002doc 42003 | 1-00 room setpoint command | INT16 | × 0.1 | °C | Read/write | |||
| HR | 2400doc 42401 | 1-00 heating water setpoint command | INT16 | × 0.1 | °C | Read/write | |||
| HR | 2401doc 42402 | 1-00 cooling water setpoint command | INT16 | × 0.1 | °C | Read/write | |||
| HR | 2402doc 42403 | 1-00 hot water / quiet command | High byte storage setpoint (signed 8-bit, scale unclear); bit 2 quiet, bit 0 reheat. | UINT16 | Read/write | ||||
| HR | 2403doc 42404 | 1-00 ventilation mode command | Bits 6-7: 1 auto, 2 energy reclaim, 3 bypass (VAM only). | UINT16 | Read/write | ||||
| HR | 2800doc 42801 | 1-00 user interface lock | 1 = button disabled on the remote controller. | BITMAP16 | Read/write | bit 0 = On button lock; bit 1 = Off button lock; bit 2 = Setpoint up/down lock; bit 3 = Operation mode lock; bit 4 = Fan direction lock; bit 5 = Fan speed lock |
Notes on this map
- Only DIII group 1-00 is listed. Register of another group = base register + ((upper address - 1) x 16 + lower address) x step. Steps: 31001/42001 blocks step 3, 31401/32801/42401 step 4, 32001 step 6, 33601 step 2, 42801 step 1. Example: 4-15 capability = 31190.
- Status 1 (32001): bits 12-14 fan speed 0-7 (meaning depends on the fan-speed step capability; 3-step: 0 auto, 1 L, 3 M, 5 H), bits 8-10 fan direction (0-4 P0-P4, 6 stop, 7 swing). Status 2 (32002): bits 0-3 operation mode (0 fan, 1 heat, 2 cool, 3 auto, 4 ventilation, 7 dry), bits 4-7 filter sign (0 off, 1-15 on), bits 8-11 actual operation (0 fan, 1 heat, 2 cool), bits 14-15 cool/heat master (0 undecided, 1 slave, 2 master).
- Control 1 (42001): bit 0 on/off, bits 4-7 fan control flag (6 = fan control, 0 = none), bits 8-10 fan direction, bits 12-14 fan speed. Control 2 (42002): bits 0-3 mode (0 fan, 1 heat, 2 cool, 3 auto, 4 ventilation, 6 setpoint/dependent, 7 dry), bits 4-7 filter sign reset (15 = reset, then write 0 again).
- Setpoint range fields are signed 8-bit values in 1 °C packed into a 16-bit word; they are listed as UINT16 because the schema has no 8-bit type. The storage (hot water) setpoint byte in 32803/42403 is described both as 'unity 1 °C' and as 'value multiplied by 10', so its scale is not given here.
- Error code 33601: high byte and low byte are the two ASCII characters of the Daikin code (e.g. 'C7'); '00' means no error. 33602 holds unit number (bits 12-15), warning/alarm/error flags (bits 10/9/8) and sub-code (bits 0-5).
- Room setpoint, water setpoints and temperatures are signed 16-bit in 0.1 °C. Out-of-range setpoints are clamped by the unit; read the input register for the result.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Daikin EKMBDXB Modbus Interface DIII
What Modbus registers does the Daikin EKMBDXB Modbus Interface DIII have?
This map lists 34 registers: 25 input registers, 9 holding registers. 9 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Daikin EKMBDXB Modbus Interface DIII Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The guide prints 30001/40001-style registers and says the request address starts at zero: 30001 is sent as 0 and 40001 as 0. Its example frames agree (31001 is requested as 0x03E8, 42002 as 0x07D1).
What are the minimum Modbus registers to integrate the Daikin EKMBDXB Modbus Interface DIII?
Start with IR 0 Interface status (Interface ready); IR 1 DIII units 1-00..1-15 connected (Groups 1-00..1-15 connected); IR 2000 1-00 status 1 (1-00 on/off, fan, thermo); IR 2001 1-00 status 2 (1-00 mode, filter, defrost); IR 2004 1-00 room temperature (1-00 room temperature); IR 3600 1-00 error code (1-00 error code); HR 2000 1-00 control 1 (1-00 on/off and fan command); HR 2002 1-00 room setpoint command (1-00 setpoint command).
How do I enable Modbus control of the Daikin EKMBDXB Modbus Interface DIII?
Set baud rate, parity/stop bits and the Modbus address (1-15) on dip switches DS1/DS2 of the interface; the DIII units are discovered automatically after power-up.
Where is the official Daikin EKMBDXB Modbus Interface DIII Modbus documentation?
The source is Design guide Modbus Interface DIII EKMBDXB7V1 (4P642495-1A), revision 2022-02, published free by Daikin at https://www.daikin.eu/content/dam/document-library/Installer-reference-guide/ac/vrv/ekmbdxb/EKMBDXB_Design%20guide_4PEN642495-1A_English.pdf.
More Daikin Modbus register maps
- Heat pump
Daikin DCOM-LT/MB Modbus interface for Daikin Altherma LT heat pumps
Daikin Altherma low-temperature (LT) air-to-water heat pumps fitted with the DCOM-LT/MB (model number 534-001) P1P2-to-Modbus RTU interface, standard operating mode, per reference manual 534-252-A3.
Also known as: DCOM-LT-MB, 534-001, Altherma LT Modbus interface - VRF / split AC gateway
Daikin DTA116A51 D-NET / Modbus communication adaptor (VRV)
DTA116A51 adaptor with up to 16 VRV indoor units (D-NET 1-00 to 1-15), per functional specification CB13A033 first edition.
Also known as: DTA116A51, DIII-NET Modbus adaptor, D3NET Modbus adapter - VRF / split AC gateway
Daikin EKMBPP1 / EKMBPP1A Modbus adapter (Sky Air / VRV P1P2)
EKMBPP1 and EKMBPP1A adapters on the P1P2 bus of Sky Air / VRV indoor units (up to 16), installation manual 4P720139-1C (2024.11).
Also known as: EKMBPP1, EKMBPP1A - Heat pump (air-to-water) Modbus interface
Daikin EKRHH Daikin HomeHub (Modbus TCP/RTU for Daikin Altherma and air-to-air heat pumps)
Daikin HomeHub EKRHH in use case 3 (Modbus for Daikin Altherma air-to-water heat pumps) and use case 4 (Modbus smart-grid control of air-to-air heat pumps), installer reference guide 4P744838-1E (2026.01).
Also known as: EKRHH, Daikin HomeHub, 4P744838-1E, Daikin Altherma 3 Modbus, Altherma Smart Grid Modbus
Other ac & vrf gateways register maps
- Heat pump gateway (VRF / split AC gateway)
Intesis (HMS Networks) IN485DAI001A000 Daikin Altherma 3 air-to-water to Modbus RTU / BACnet MS/TP gateway
Intesis (HMS Networks) IN485DAI001A000 gateway for Daikin Altherma 3 air-to-water heat pumps, set to Modbus RTU, per user manual version 1.0.2 (2025-07-18).
Also known as: IN485DAI001A000, Daikin Altherma 3 Modbus, Intesis Altherma 3, HMS Daikin Altherma gateway - VRF / split AC gateway
Intesis (HMS Networks) INMBSACA001I000 XYE-bus air conditioner to Modbus RTU interface (1 unit)
INMBSACA001I000, user manual v1.8 EN; one indoor unit at unit address 0 on its own XYE bus.
Also known as: INMBSACA001I000 - VRF / split AC gateway
Intesis (HMS Networks) INMBSFGL016O000 Fujitsu VRF to Modbus RTU / TCP gateway (up to 16 indoor units)
Intesis Modbus Server - Fujitsu VRF, order code INMBSFGL016O000 (legacy FJ-AC-MBS-16), user manual r1.0 (02/2020); up to 16 indoor units configured in MAPS.
Also known as: INMBSFGL016O000, FJ-AC-MBS-16, Intesis Modbus Server Fujitsu VRF - VRF / split AC gateway
Intesis (HMS Networks) INMBSMHI001R000 Mitsubishi Heavy Industries AC to Modbus RTU gateway
Mitsubishi Heavy Industries indoor units (one, or up to 16 controlled together as one) on the XY remote-controller bus, user manual r6.4 (01/2024).
Also known as: INMBSMHI001R000, MH-RC-MBS-1, Intesis Mitsubishi Heavy Industries Modbus, Intesis MHI Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSPAN001I100 Panasonic Etherea (domestic) AC to Modbus RTU gateway
Panasonic Etherea-line domestic split units, user's manual r1.5 (09/2025). Some registers only on 2013 (PKE series) and later models.
Also known as: INMBSPAN001I100, Intesis Panasonic Etherea Modbus, Intesis Panasonic domestic Modbus - Air handler DX kit (VRF / split AC gateway built in)
LG PAHCMR000 AHU Communication Kit (Multi V DX kit, Modbus to DDC)
LG PAHCMR000 AHU Communication Kit (R32 and R410A Multi V / single split outdoor units with a PRLK EEV kit), installation manual IM_AHU_Comm_Kit_PAHCMR000_R32_06_26.
Also known as: PAHCMR000, LG AHU Communication Kit R32, LG AHU comm kit Modbus
All ac & vrf gateways Modbus register maps →
Source: Design guide Modbus Interface DIII EKMBDXB7V1 · 4P642495-1A · rev. 2022-02. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.