  4. INMBSACA001I000 XYE-bus air conditioner to Modbus RTU interface (1 unit)

VRF / split AC gateway · Modbus register map

Intesis (HMS Networks) INMBSACA001I000 XYE-bus air conditioner to Modbus RTU interface (1 unit) Modbus register map

Updated 19 November 2026

Short answer

Small Modbus RTU slave that connects to the XYE bus of one VRF / commercial-line indoor unit. Holding registers give on/off, mode, fan, vane, setpoint and room temperature, alarms and error code, window-contact and remote-lock features, a Modbus-fed ambient temperature and run hours.

This page lists 23 Modbus registers for the Intesis (HMS Networks) INMBSACA001I000 XYE-bus air conditioner to Modbus RTU interface (1 unit) — 13 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Intesis (HMS Networks)’s own free documentation (linked below) and checked against it.

Manufacturer
Intesis (HMS Networks)
Model
INMBSACA001I000 XYE-bus air conditioner to Modbus RTU interface (1 unit)
Equipment type
VRF / split AC gateway
Registers
23 (13 writable)
Transport
Modbus RTU
Default unit ID
1
Default serial
9600 baud, 8N2
Documented addressing
0-based (the number printed is the address on the wire)
Also known as
INMBSACA001I000
Source document
Intesis INMBSACA***I000 Modbus RTU (EIA-485) Interface for air conditioners - User Manual · User Manual v1.8 EN · rev. 2026-04
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Intesis (HMS Networks) INMBSACA001I000 XYE-bus air conditioner to Modbus RTU interface (1 unit)

Integration in brief

Set the slave address and baud on SW3/SW4, set the indoor unit address to 0, then read and write holding registers 0..11. Check SW4 for the temperature format before scaling.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 0AC unit on/offUINT16On/offRead/write
HR 1AC unit modeUINT16ModeRead/write
HR 2AC unit fan speedUINT16Fan speedRead/write
HR 4AC unit temperature setpointUINT16SetpointRead/write
HR 5AC unit temperature referenceUINT16Room temperatureRead
HR 10AC unit alarm statusUINT16AlarmRead
HR 11Error codeUINT16Error code / communication errorRead

Enable Modbus control & writes

No enable step; register 7 must stay 0 (interface enabled).

Byte order & addressing

Network setup

Watch out for

Intesis (HMS Networks) INMBSACA001I000 XYE-bus air conditioner to Modbus RTU interface (1 unit) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

23 of 23 shown
Intesis (HMS Networks) INMBSACA001I000 XYE-bus air conditioner to Modbus RTU interface (1 unit) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0AC unit on/offUINT16Read/write0 = Off; 1 = On
HR1AC unit modeAvailable modes depend on the indoor unit.UINT16Read/write0 = Auto; 1 = Heat; 2 = Dry; 3 = Fan; 4 = Cool
HR2AC unit fan speedAvailable speeds depend on the indoor unit.UINT16Read/write0 = Auto; 1 = SP1; 2 = SP2; 3 = SP3
HR3AC unit up/down vane positionUINT16Read/write0 = Off; 10 = Swing
HR4AC unit temperature setpoint17..30 °C (63..86 °F). SW4 x1 °C assumed (x10: 0.1, or °F).UINT16°CRead/write
HR5AC unit temperature referenceTemperature the unit controls on. SW4 x1 °C assumed (x10: 0.1, or °F).UINT16°CRead
HR6Window contactVirtual window contact written from Modbus.UINT16Read/write0 = Closed; 1 = Open
HR7Interface disablementNon-volatile.UINT16Read/write0 = Interface enabled; 1 = Interface disabled
HR8Remote control disablementBlocks the wired remote on the MD-RC bus. Non-volatile.UINT16Read/write0 = Remote enabled; 1 = Remote disabled
HR9AC unit operation timeHours the unit has been on, 0..65535. Non-volatile.UINT16hRead/write
HR10AC unit alarm statusUINT16Read0 = No alarm; 1 = Alarm
HR11Error code0 = no error, 65535 = interface-to-unit communication error, other = unit error code.UINT16Read0 = No error active; 65535 = Interface to AC unit communication error
HR13Open-window switch-off timeout0..30 min, factory 30.UINT16minRead/write
HR15Modbus slave address1..63.UINT16Read
HR21Max number of fan speedsUINT16Read
HR22Ambient temperature from external sensorRoom temperature written from Modbus. SW4 x1 °C assumed (x10: 0.1, or °F).UINT16°CRead/write32768 = Initialisation value / no value (0x8000)
HR23AC real temperature setpointSetpoint in use by the unit. SW4 x1 °C assumed (x10: 0.1, or °F).UINT16°CRead
HR49Device IDReads 0x2200.UINT16Read
HR50Software versionUINT16Read
HR66Return path temperatureSW4 x1 °C assumed (x10: 0.1, or °F).UINT16°CRead32768 = Initialisation value / no value (0x8000)
HR97Block periodic sendingsBlocked = commands only sent when the value changes.UINT16Read/write0 = Non-blocked; 1 = Blocked
HR99Reset / reboot deviceUINT16Write1 = Reset
HR2031CapacityUINT16Read1 = 1 indoor unit

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Intesis (HMS Networks) INMBSACA001I000 XYE-bus air conditioner to Modbus RTU interface (1 unit)

What Modbus registers does the Intesis (HMS Networks) INMBSACA001I000 XYE-bus air conditioner to Modbus RTU interface (1 unit) have?

This map lists 23 registers: 23 holding registers. 13 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Intesis (HMS Networks) INMBSACA001I000 XYE-bus air conditioner to Modbus RTU interface (1 unit) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Tables give a 'protocol address' and a 'PLC address' (protocol + 1); the protocol address is the wire address and is used for 'documented'.

What are the minimum Modbus registers to integrate the Intesis (HMS Networks) INMBSACA001I000 XYE-bus air conditioner to Modbus RTU interface (1 unit)?

Start with HR 0 AC unit on/off (On/off); HR 1 AC unit mode (Mode); HR 2 AC unit fan speed (Fan speed); HR 4 AC unit temperature setpoint (Setpoint); HR 5 AC unit temperature reference (Room temperature); HR 10 AC unit alarm status (Alarm); HR 11 Error code (Error code / communication error).

How do I enable Modbus control of the Intesis (HMS Networks) INMBSACA001I000 XYE-bus air conditioner to Modbus RTU interface (1 unit)?

No enable step; register 7 must stay 0 (interface enabled).

Where is the official Intesis (HMS Networks) INMBSACA001I000 XYE-bus air conditioner to Modbus RTU interface (1 unit) Modbus documentation?

The source is Intesis INMBSACA***I000 Modbus RTU (EIA-485) Interface for air conditioners - User Manual (User Manual v1.8 EN), revision 2026-04, published free by Intesis (HMS Networks) at https://www.hms-networks.com/docs/default-source/products/intesis/manuals-and-guides---manuals/user-manual-inmbsacaxxxi000.pdf.