- LPG series DC inverter air conditioners (built-in Modbus)
Split AC unit (VRF / split AC gateway built in) · Modbus register map
Aermec LPG series DC inverter air conditioners (built-in Modbus) Modbus register map
Updated 17 November 2026
The indoor-unit controller of Aermec LPG units answers Modbus RTU directly, so no extra gateway is needed. Holding registers carry on/off, mode, fan speed, setpoint, louvre position and temperatures; coils carry feature flags (turbo, silent, locks, energy saving) and a long list of indoor, outdoor and inverter-drive fault bits. Up to 255 units can share a BMS line.
This page lists 114 Modbus registers for the Aermec LPG series DC inverter air conditioners (built-in Modbus) — 30 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Aermec’s own free documentation (linked below) and checked against it.
- Manufacturer
- Aermec
- Model
- LPG series DC inverter air conditioners (built-in Modbus)
- Equipment type
- Split AC unit (VRF / split AC gateway built in)
- Registers
- 114 (30 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Default serial
- 9600 baud, 8N1
- Documented addressing
- 0-based (the number printed is the address on the wire)
- Also known as
- LPG
- Source document
- ModBus Protocol LPG series · 5385759_02 · rev. 2025-05
Integration notes: Aermec LPG series DC inverter air conditioners (built-in Modbus)
Read words 2-25 for on/off, mode, fan, setpoint and louvres and word 4/49 for indoor and outdoor temperature; read coils 0-215 for status and fault bits. Write word 2 (0xAA/0x55), 17, 19 and 20 to control the unit.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 2 | Unit On/Off | UINT16 | On/off | Read/write |
| HR 17 | Set mode | UINT16 | Mode | Read/write |
| HR 19 | Set fan speed | UINT16 | Fan speed | Read/write |
| HR 20 | Set temp | UINT16 | Setpoint | Read/write |
| HR 4 | Ambient temp | INT16 | Indoor temperature | Read |
| HR 49 | Outdoor ambient temp | INT16 | Outdoor temperature | Read |
| CO 151 | Compressor status | BIT | Compressor running | Read |
| CO 95 | Error output status | BIT | Error output | Read |
Enable Modbus control & writes
The Modbus interface is built into the indoor-unit controller; the unit address and BMS mode are set from the wired controller (see the unit's service manual).
Byte order & addressing
- Writes are refused while an energy-saving limit blocks the requested setpoint; the BMS should check the result.
- Energy saving bits 32 and 33 must be written together.
- Fault code 0x04 in an exception reply means the interface lost contact with the unit; it is also returned after power-up until valid data arrives.
Network setup
- RS485, 9600 baud, 8 data bits, no parity, 1 stop bit.
- Twisted pair, kept at least 15 cm from power cables; use repeaters for long lines.
Watch out for
- In fan or auto mode the sleep setting is ignored; in auto mode the remote temperature shield is ignored.
- Heating commands to cooling-only units (bit 177 = 1) have no effect.
Aermec LPG series DC inverter air conditioners (built-in Modbus) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| CO | 8doc Bit8 | ODU flag present | 1 = yes. | BIT | Read | ||||
| CO | 9doc Bit9 | Master wired controller flag | 1 = yes. | BIT | Read | ||||
| CO | 13doc Bit13 | Slave wired controller flag | 1 = yes. | BIT | Read | ||||
| CO | 17doc Bit17 | Remote lock | 1 = locked by remote monitoring or the charging system. | BIT | Read/write | ||||
| CO | 19doc Bit19 | Remote mode shield | 1 = mode changes from the unit are blocked. | BIT | Read/write | ||||
| CO | 20doc Bit20 | Remote On/Off shield | 1 = on/off from the unit is blocked. | BIT | Read/write | ||||
| CO | 21doc Bit21 | Remote energy saving shield | 1 = shield on. | BIT | Read/write | ||||
| CO | 24doc Bit24 | Absence mode | 1 = on. | BIT | Read/write | ||||
| CO | 25doc Bit25 | Healthy function | 1 = on. | BIT | Read/write | ||||
| CO | 26doc Bit26 | I-Demand comfort/energy saving | 1 = on. | BIT | Read/write | ||||
| CO | 27doc Bit27 | Turbo | 1 = on. | BIT | Read/write | ||||
| CO | 28doc Bit28 | E-heating permission | 0 = electric heater allowed, 1 = not allowed. | BIT | Read/write | ||||
| CO | 29doc Bit29 | X-fan | 1 = on. | BIT | Read/write | ||||
| CO | 30doc Bit30 | Silent | 1 = on. | BIT | Read/write | ||||
| CO | 31doc Bit31 | Low temp drying mode | 1 = on. | BIT | Read/write | ||||
| CO | 32doc Bit32 | Energy saving under cooling | 1 = on. Write together with bit 33. | BIT | Read/write | ||||
| CO | 33doc Bit33 | Energy saving under heating | 1 = on. Write together with bit 32. | BIT | Read/write | ||||
| CO | 34doc Bit34 | Buttons lock (child lock) | 1 = on. | BIT | Read/write | ||||
| CO | 35doc Bit35 | On/Off memory | 0 = memorize, 1 = do not memorize. | BIT | Read/write | ||||
| CO | 36doc Bit36 | °C/°F flag | 1 = °F, 0 = °C. | BIT | Read/write | ||||
| CO | 40doc Bit40 | Timer status | 1 = timer set. | BIT | Read | ||||
| CO | 46doc Bit46 | Gate control system present | 1 = yes. | BIT | Read | ||||
| CO | 47doc Bit47 | Human body sensing module present | 1 = yes. | BIT | Read | ||||
| CO | 49doc Bit49 | Timer On flag | 1 = active. | BIT | Read | ||||
| CO | 50doc Bit50 | Timer Off flag | 1 = active. | BIT | Read | ||||
| CO | 51doc Bit51 | Indoor ambient source | 0 = return-air sensor, 1 = wired controller sensor. | BIT | Read | ||||
| CO | 55doc Bit55 | Low standby power control | 1 = mode 2, 0 = mode 1. | BIT | Read | ||||
| CO | 65doc Bit65 | Wired controller temp sensor error | 1 = error. | BIT | Read | ||||
| CO | 70doc Bit70 | Wired controller memory chip error | 1 = error. | BIT | Read | ||||
| CO | 72doc Bit72 | Cancel timer | 1 = cancel. | BIT | Read/write | ||||
| CO | 74doc Bit74 | Up & down swing mode | 0 = simple swing, 1 = fixed angle and small-area swing. | BIT | Read/write | ||||
| CO | 91doc Bit91 | Electric heating | 1 = yes. | BIT | Read | ||||
| CO | 92doc Bit92 | Water pump | 1 = on. | BIT | Read | ||||
| CO | 93doc Bit93 | Fresh air valve switch | 1 = on. | BIT | Read | ||||
| CO | 95doc Bit95 | Error output status | 1 = yes. | BIT | Read | ||||
| CO | 97doc Bit97 | Indoor evaporator temp sensor error | 1 = error. | BIT | Read | ||||
| CO | 98doc Bit98 | Indoor return air temp sensor error | 1 = error. | BIT | Read | ||||
| CO | 99doc Bit99 | Light board ambient temp sensor error | 1 = error. | BIT | Read | ||||
| CO | 101doc Bit101 | Water overflow protection | 1 = active. | BIT | Read | ||||
| CO | 102doc Bit102 | IDU memory chip error | 1 = error. | BIT | Read | ||||
| CO | 104doc Bit104 | Jumper cap error | 1 = error. | BIT | Read | ||||
| CO | 105doc Bit105 | Indoor fan error | 1 = error. | BIT | Read | ||||
| CO | 112doc Bit112 | Card in/out status | 1 = card in. | BIT | Read | ||||
| CO | 113doc Bit113 | People in room | 1 = yes. | BIT | Read | ||||
| CO | 114doc Bit114 | Static pressure type | 0 = low static, 1 = high static. | BIT | Read | ||||
| CO | 120doc Bit120 | Comm failure with master wired controller | 1 = failure. | BIT | Read | ||||
| CO | 121doc Bit121 | Comm failure with slave wired controller | 1 = failure. | BIT | Read | ||||
| CO | 122doc Bit122 | Comm failure with ODU | 1 = failure. | BIT | Read | ||||
| CO | 147doc Bit147 | Outdoor fan status | 1 = on. | BIT | Read | ||||
| CO | 150doc Bit150 | 4-way valve status | 1 = on. | BIT | Read | ||||
| CO | 151doc Bit151 | Compressor status | 1 = on. | BIT | Read | ||||
| CO | 152doc Bit152 | Discharge temperature protection | 1 = active. | BIT | Read | ||||
| CO | 153doc Bit153 | Refrigerant shortage protection | 1 = active. | BIT | Read | ||||
| CO | 154doc Bit154 | DC fan motor protection | 1 = active. | BIT | Read | ||||
| CO | 156doc Bit156 | Over power protection | 1 = active. | BIT | Read | ||||
| CO | 157doc Bit157 | Overload protection | 1 = active. | BIT | Read | ||||
| CO | 158doc Bit158 | Low pressure protection | 1 = active. | BIT | Read | ||||
| CO | 159doc Bit159 | High pressure protection | 1 = active. | BIT | Read | ||||
| CO | 160doc Bit160 | Evaporator anti-freezing protection | 1 = active. | BIT | Read | ||||
| CO | 161doc Bit161 | Outdoor ambient temp sensor error | 1 = error. | BIT | Read | ||||
| CO | 162doc Bit162 | Discharge temp sensor error | 1 = error. | BIT | Read | ||||
| CO | 163doc Bit163 | Condenser temp sensor error | 1 = error. | BIT | Read | ||||
| CO | 164doc Bit164 | Outdoor coil pipe temp sensor error | 1 = error. | BIT | Read | ||||
| CO | 166doc Bit166 | ODU memory chip error | 1 = error. | BIT | Read | ||||
| CO | 174doc Bit174 | Drive communication failure | 1 = failure. | BIT | Read | ||||
| CO | 176doc Bit176 | SAVE status | 1 = yes. | BIT | Read | ||||
| CO | 177doc Bit177 | Cooling only flag | 0 = heat pump, 1 = cooling only. | BIT | Read | ||||
| CO | 179doc Bit179 | System defrosting | 1 = defrosting. | BIT | Read | ||||
| CO | 182doc Bit182 | Low power consumption status | 1 = ready. | BIT | Read | ||||
| CO | 183doc Bit183 | AC input phase sequence protection | 1 = active. | BIT | Read | ||||
| CO | 184doc Bit184 | Drive DC bus undervoltage | 1 = failure. | BIT | Read | ||||
| CO | 185doc Bit185 | Drive DC bus overvoltage | 1 = failure. | BIT | Read | ||||
| CO | 186doc Bit186 | Drive AC input current protection | 1 = failure. | BIT | Read | ||||
| CO | 187doc Bit187 | Drive IPM protection | 1 = failure. | BIT | Read | ||||
| CO | 188doc Bit188 | Drive PFC protection | 1 = failure. | BIT | Read | ||||
| CO | 190doc Bit190 | Compressor phase loss protection | 1 = failure. | BIT | Read | ||||
| CO | 191doc Bit191 | Drive module reset | 1 = failure. | BIT | Read | ||||
| CO | 192doc Bit192 | Compressor over-current protection | 1 = failure. | BIT | Read | ||||
| CO | 193doc Bit193 | Compressor power protection | 1 = failure. | BIT | Read | ||||
| CO | 194doc Bit194 | Drive current check circuit failure | 1 = failure. | BIT | Read | ||||
| CO | 195doc Bit195 | Compressor out-of-step protection | 1 = failure. | BIT | Read | ||||
| CO | 198doc Bit198 | Drive module high temperature | 1 = failure. | BIT | Read | ||||
| CO | 199doc Bit199 | Drive module temp sensor failure | 1 = failure. | BIT | Read | ||||
| CO | 201doc Bit201 | Compressor low field (flux weakening) | 1 = active. | BIT | Read | ||||
| CO | 202doc Bit202 | Drive frequency limit | 1 = active. | BIT | Read | ||||
| CO | 203doc Bit203 | Drive frequency reduction | 1 = active. | BIT | Read | ||||
| CO | 204doc Bit204 | Drive AC input low voltage | 1 = active. | BIT | Read | ||||
| CO | 205doc Bit205 | Drive under charge | 1 = under charge, 0 = charged. | BIT | Read | ||||
| CO | 207doc Bit207 | Drive AC input power type | Flag 1/0; meaning not given. | BIT | Read | ||||
| CO | 208doc Bit208 | Drive storage chip failure | 1 = failure. | BIT | Read | ||||
| CO | 210doc Bit210 | Drive charge circuit failure | 1 = failure. | BIT | Read | ||||
| CO | 211doc Bit211 | Drive AC input voltage abnormal | 1 = failure. | BIT | Read | ||||
| CO | 212doc Bit212 | Compressor temp sensor failure | 1 = failure. | BIT | Read | ||||
| CO | 213doc Bit213 | Drive AC zero-cross protection | 1 = failure. | BIT | Read | ||||
| CO | 214doc Bit214 | Temperature drift protection | 1 = failure. | BIT | Read | ||||
| CO | 215doc Bit215 | Current sensor connection protection | 1 = failure (sensor not on U or V phase). | BIT | Read | ||||
| HR | 2doc Word 2 | Unit On/Off | 0xAA (170) = on, 0x55 (85) = off. | UINT16 | Read/write | 85 = Off (0x55); 170 = On (0xAA) | |||
| HR | 4doc Word 4 | Ambient temp | Indoor ambient temperature. | INT16 | × 0.1 | °C | Read | ||
| HR | 5doc Word 5 | IDU Addr. | 1-16 with a central controller, 1-255 in PC address mode. | UINT16 | Read | ||||
| HR | 17doc Word 17 | Set mode | UINT16 | Read/write | 1 = Cooling; 2 = Heating; 3 = Drying; 4 = Fan only; 5 = Auto | ||||
| HR | 19doc Word 19 | Set fan speed | UINT16 | Read/write | 0 = Auto; 1 = Speed 1; 2 = Speed 2; 3 = Speed 3; 4 = Speed 4; 5 = Speed 5; 6 = Turbo | ||||
| HR | 20doc Word 20 | Set temp | 16-30 °C; reads 12 in low-temp drying and 8 in absence mode. | UINT16 | °C | Read/write | |||
| HR | 22doc Word 22 | Up & down swing | UINT16 | Read/write | 0 = Off; 1 = Swing 1-5; 2 = Position 1; 3 = Position 2; 4 = Position 3; 5 = Position 4; 6 = Position 5; 7 = Swing 3-5; 8 = Swing 2-5; 9 = Swing 2-4; 10 = Swing 1-4; 11 = Swing 1-3 | ||||
| HR | 23doc Word 23 | Left & right swing | UINT16 | Read/write | 0 = Off (default after power-on); 1 = Swing, same direction; 2 = Position 1; 3 = Position 2; 4 = Position 3; 5 = Position 4; 6 = Position 5; 12 = 15 position (as printed); 13 = Swing, opposite direction | ||||
| HR | 24doc Word 24 | Fresh air valve status | 0-10: fresh air valve mode. | UINT16 | Read/write | ||||
| HR | 25doc Word 25 | Sleep mode | UINT16 | Read/write | 0 = No sleep mode; 1 = Sleep mode 1; 2 = Sleep mode 2; 3 = Sleep mode 3 | ||||
| HR | 34doc Word 34 | Clean function | 0 = no clean function, 10-39 = contamination grade. | UINT16 | Read/write | ||||
| HR | 35doc Word 35 | Energy saving cooling lower limit | Lowest setpoint allowed when cooling energy saving is on (16-30). | UINT16 | °C | Read/write | |||
| HR | 36doc Word 36 | Energy saving heating upper limit | Highest setpoint allowed when heating energy saving is on (16-30). | UINT16 | °C | Read/write | |||
| HR | 39doc Word 39 | Selection of ambient temp sensor | UINT16 | Read | 1 = Return-air sensor; 2 = Wired controller sensor; 3 = Return air for cool/dry/fan, wired controller for heat/auto | ||||
| HR | 49doc Word 49 | Outdoor ambient temp | -100 to 155. | INT16 | °C | Read | |||
| HR | 77doc Word 77 | DRED function | UINT16 | Read | 0 = No DRED function; 1 = DRED1 mode; 2 = DRED2 mode; 3 = DRED3 mode | ||||
| HR | 82doc Word 82 | Return air temp | Ambient temperature at the return-air port. | INT16 | × 0.1 | °C | Read | ||
| HR | 83doc Word 83 | Light board temp | Ambient temperature at the display (light) board. | INT16 | × 0.1 | °C | Read |
Notes on this map
- Only named points are listed; reserved words and bits are left out.
- Left out because the table row is incomplete in the source: bit 18 (no name), bits 125, 155, 196 and 216-247 (blank names), plus bits 3, 48, 67, 94, 124, 189, 197, 200, 206 and 209 which fall on page breaks where the address and text do not line up reliably.
- Some fault bits are printed with the legend '1: yes 0: on'; the 0 state is read here as 'no fault'.
- Word 2 uses 0xAA for on and 0x55 for off, not 1/0.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Aermec LPG series DC inverter air conditioners (built-in Modbus)
What Modbus registers does the Aermec LPG series DC inverter air conditioners (built-in Modbus) have?
This map lists 114 registers: 96 coils, 18 holding registers. 30 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Aermec LPG series DC inverter air conditioners (built-in Modbus) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The protocol says registers are words numbered from 0 and coils are bits numbered from 0 (Byte0.0 = bit 0). Word n is wire address n and Bit n is coil n; the example frames agree (read starting at word 1 sends 0x0001, coil 5 sends 0x0005).
What are the minimum Modbus registers to integrate the Aermec LPG series DC inverter air conditioners (built-in Modbus)?
Start with HR 2 Unit On/Off (On/off); HR 17 Set mode (Mode); HR 19 Set fan speed (Fan speed); HR 20 Set temp (Setpoint); HR 4 Ambient temp (Indoor temperature); HR 49 Outdoor ambient temp (Outdoor temperature); CO 151 Compressor status (Compressor running); CO 95 Error output status (Error output).
How do I enable Modbus control of the Aermec LPG series DC inverter air conditioners (built-in Modbus)?
The Modbus interface is built into the indoor-unit controller; the unit address and BMS mode are set from the wired controller (see the unit's service manual).
Where is the official Aermec LPG series DC inverter air conditioners (built-in Modbus) Modbus documentation?
The source is ModBus Protocol LPG series (5385759_02), revision 2025-05, published free by Aermec at https://aermec.com/download?id=19782.
More Aermec Modbus register maps
- Split AC unit (VRF / split AC gateway built in)
Aermec LCG series DC inverter air conditioners (built-in Modbus)
Aermec LCG series DC inverter units whose indoor-unit controller has the built-in Modbus RTU interface; Modbus Protocol user manual LCG 5385758_02 (24.01).
Also known as: LCG - Chiller
Aermec WTX water-cooled chiller with Turbocor compressors (pCO5+ BMS)
Aermec WTX oil-free (Danfoss Turbocor) water-cooled chillers with the pCO5+ controller, via the AER485P1 RS485 card or AERNET; BMS manual for WTX 5009100_00 (1705).
Also known as: WTX, TBX
Other ac & vrf gateways register maps
- Sensor / controller (CO2 condensing unit gateway)
Danfoss Optyma iCO2 gateway (OP-MPAM015 / OP-MPAM005)
Danfoss Optyma iCO2 CO2 condensing units (4.6 kW MT and 20 kW MT / 10 kW LT) through their Modbus gateway, software 1.0x.
Also known as: OP-MPAM015, OP-MPAM005, Optyma iCO2 4.6 kW MT, Optyma iCO2 20 kW MT / 10 kW LT - VRF / split AC gateway
Intesis (HMS Networks) IN485SAM001R000 Samsung AC to Modbus RTU / BACnet MS/TP gateway
Samsung indoor units on the F3F4 remote-controller bus, gateway set to Modbus RTU (SW1-5 ON); user manual version 1.0.0.
Also known as: IN485SAM001R000, Intesis Samsung BACnet MS/TP Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSDAI001I000 Daikin domestic AC to Modbus RTU gateway
Single Daikin domestic (S21-connector) indoor unit via INMBSDAI001I000, user manual v1.0.2.
Also known as: INMBSDAI001I000, Intesis Daikin domestic Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSHIS016O000 Hisense VRF to Modbus RTU / TCP gateway (16 / 64 indoor units)
Intesis Modbus Server - Hisense VRF, order codes INMBSHIS016O000 / INMBSHIS064O000 (legacy HS-AC-MBS-16 / HS-AC-MBS-64), user manual User Manual r1.0 EN.
Also known as: INMBSHIS016O000, INMBSHIS064O000, HS-AC-MBS-16, HS-AC-MBS-64, Intesis Modbus Server Hisense VRF - VRF / split AC gateway
Intesis (HMS Networks) INMBSMID001I000 Midea AC to Modbus RTU gateway
One Midea commercial / VRF indoor unit on the XYE bus, user manual v1.11.
Also known as: INMBSMID001I000, Intesis Midea Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSPAN016O000 / 064O000 / 128O000 Panasonic VRF (P-Link) to Modbus gateway
Intesis Modbus Server - Panasonic, order codes INMBSPAN016O000 / 064O000 / 128O000 (legacy PA-AC-MBS-16 / -64 / -128), user manual r1.1 (11/2020); Panasonic P-Link systems.
Also known as: INMBSPAN016O000, INMBSPAN064O000, INMBSPAN128O000, PA-AC-MBS-16, PA-AC-MBS-64, PA-AC-MBS-128, Intesis Modbus Server Panasonic VRF
All ac & vrf gateways Modbus register maps →
Source: ModBus Protocol LPG series · 5385759_02 · rev. 2025-05. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.