- INMBSPAN016O000 / 064O000 / 128O000 Panasonic VRF (P-Link) to Modbus gateway
VRF / split AC gateway · Modbus register map
Intesis (HMS Networks) INMBSPAN016O000 / 064O000 / 128O000 Panasonic VRF (P-Link) to Modbus gateway Modbus register map
Updated 19 November 2026
Modbus server for Panasonic VRF systems on P-Link. Each configured indoor unit gets a 100-register block with control, temperatures, limits, error, occupancy and energy values; outdoor units get pressure and demand-limit registers; low addresses carry occupancy setpoints and all-unit commands. Up to two P-Link lines.
This page lists 62 Modbus registers for the Intesis (HMS Networks) INMBSPAN016O000 / 064O000 / 128O000 Panasonic VRF (P-Link) to Modbus gateway — 40 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Intesis (HMS Networks)’s own free documentation (linked below) and checked against it.
- Manufacturer
- Intesis (HMS Networks)
- Model
- INMBSPAN016O000 / 064O000 / 128O000 Panasonic VRF (P-Link) to Modbus gateway
- Equipment type
- VRF / split AC gateway
- Registers
- 62 (40 writable)
- Transport
- Modbus RTU, Modbus TCP
- Default unit ID
- Not stated
- TCP port
- 502
- Documented addressing
- 0-based (the number printed is the address on the wire)
- Also known as
- INMBSPAN016O000, INMBSPAN064O000, INMBSPAN128O000, PA-AC-MBS-16, PA-AC-MBS-64, PA-AC-MBS-128, Intesis Modbus Server Panasonic VRF
Integration notes: Intesis (HMS Networks) INMBSPAN016O000 / 064O000 / 128O000 Panasonic VRF (P-Link) to Modbus gateway
Configure lines and units in Intesis MAPS, send the project, then poll each IU x 100 block. Write on/off, mode, fan, vane and setpoint (tenths) per unit, or use the occupancy and all-unit registers 0..24.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 100 | IU on/off | INT16 | On/off | Read/write |
| HR 101 | IU operation mode | INT16 | Mode | Read/write |
| HR 102 | IU fan speed | INT16 | Fan speed | Read/write |
| HR 104 | IU temperature setpoint | INT16 | Setpoint (x10) | Read/write |
| HR 105 | IU ambient temperature | INT16 | Room temperature (x10) | Read |
| HR 119 | IU unit error code | INT16 | Error code | Read |
| HR 122 | IU communication error | INT16 | Communication error | Read |
| HR 7025 | OU communication error | INT16 | Outdoor unit communication error | Read |
Enable Modbus control & writes
Indoor and outdoor units must be configured in MAPS; P-Link goes to Port A (A3/A4, no polarity).
Byte order & addressing
- Every register is a 16-bit signed integer; there are no 32-bit values (unless stated in this file).
- Read with FC03 or FC04; write with FC06 or FC16.
- Undefined addresses in the 0..20000 poll range read back 0; the manual also says invalid addresses return a Modbus exception code.
Network setup
- All Modbus settings (RTU slave number, baud 1200..115200, parity, stop bits, RS-485 or RS-232, TCP port, IP) are set with the Intesis MAPS tool over the USB console port or Ethernet.
- Factory IP is 192.168.100.246 with DHCP enabled.
- Modbus RTU and Modbus TCP can be used at the same time on the 16 and 64 versions; on the 128 version Port B carries the second P-Link line, so Modbus RTU is not available.
- Port B carries Modbus RTU on B1, B2 and B3 (SGND). The manual prints the B1/B2 polarity both ways in two sections, so check the terminal label. A DIP switch enables 120 ohm termination and bias.
Watch out for
- The line number (1 or 2) moves the whole map by 10000.
Intesis (HMS Networks) INMBSPAN016O000 / 064O000 / 128O000 Panasonic VRF (P-Link) to Modbus gateway Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0 | Occupancy cool setpoint | Tenths of a degree; -15..60 °C. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 1 | Occupancy heat setpoint | Tenths of a degree; -15..60 °C. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 2 | Unoccupancy cool setpoint | Tenths of a degree; -15..60 °C. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 3 | Unoccupancy heat setpoint | Tenths of a degree; -15..60 °C. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 4 | Occupancy continuous check | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 5 | Unoccupancy deadband action | INT16 | Read/write | 0 = Off; 1 = Current mode | ||||
| HR | 6 | On (all units) | INT16 | Write | 1 = Switch all on | ||||
| HR | 7 | Off (all units) | INT16 | Write | 1 = Switch all off | ||||
| HR | 8 | Mode Auto (all units) | INT16 | Write | 1 = Set Auto | ||||
| HR | 9 | Mode Heat (all units) | INT16 | Write | 1 = Set Heat | ||||
| HR | 10 | Mode Dry (all units) | INT16 | Write | 1 = Set Dry | ||||
| HR | 11 | Mode Fan (all units) | INT16 | Write | 1 = Set Fan | ||||
| HR | 12 | Mode Cool (all units) | INT16 | Write | 1 = Set Cool | ||||
| HR | 13 | Fan speed Auto (all units) | INT16 | Write | 1 = Set fan Auto | ||||
| HR | 14 | Fan speed Low (all units) | INT16 | Write | 1 = Set fan Low | ||||
| HR | 15 | Fan speed Mid (all units) | INT16 | Write | 1 = Set fan Med | ||||
| HR | 16 | Fan speed High (all units) | INT16 | Write | 1 = Set fan High | ||||
| HR | 17 | Vanes stop (all units) | INT16 | Write | 1 = Set vanes stop | ||||
| HR | 18 | Vanes position 1 (all units) | INT16 | Write | 1 = Set vanes position 1 | ||||
| HR | 19 | Vanes position 2 (all units) | INT16 | Write | 1 = Set vanes position 2 | ||||
| HR | 20 | Vanes position 3 (all units) | INT16 | Write | 1 = Set vanes position 3 | ||||
| HR | 21 | Vanes position 4 (all units) | INT16 | Write | 1 = Set vanes position 4 | ||||
| HR | 22 | Vanes position 5 (all units) | INT16 | Write | 1 = Set vanes position 5 | ||||
| HR | 23 | Vanes swing (all units) | INT16 | Write | 1 = Set vanes swing | ||||
| HR | 24 | Temperature setpoint (all units) | Tenths of a degree; 16..30 °C. | INT16 | × 0.1 | °C | Write | ||
| HR | 100doc ([IU] * 100) + (([L] - 1) * 10000) + 0 | IU on/off | Line 1, indoor unit 1 shown; see notes. | INT16 | Read/write | 0 = Off; 1 = On | |||
| HR | 101doc ([IU] * 100) + (([L] - 1) * 10000) + 1 | IU operation mode | INT16 | Read/write | 0 = Auto; 1 = Heat; 2 = Dry; 3 = Fan; 4 = Cool; 5 = Auto Heat; 6 = Auto Cool | ||||
| HR | 102doc ([IU] * 100) + (([L] - 1) * 10000) + 2 | IU fan speed | INT16 | Read/write | 0 = Auto; 1 = Low; 2 = Low+; 3 = Med; 4 = Med+; 5 = High | ||||
| HR | 103doc ([IU] * 100) + (([L] - 1) * 10000) + 3 | IU vane position | INT16 | Read/write | 0 = Stop; 1 = Pos 1; 2 = Pos 2; 3 = Pos 3; 4 = Pos 4; 5 = Pos 5; 10 = Swing | ||||
| HR | 104doc ([IU] * 100) + (([L] - 1) * 10000) + 4 | IU temperature setpoint | Tenths of a degree °C; 16..30. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 105doc ([IU] * 100) + (([L] - 1) * 10000) + 5 | IU ambient temperature | Tenths of a degree °C; -35..92.5. | INT16 | × 0.1 | °C | Read | ||
| HR | 106doc ([IU] * 100) + (([L] - 1) * 10000) + 6 | IU wired remote controller sensor | Selects which sensor the unit uses. | INT16 | Write | 0 = Body sensor; 1 = Remote controller sensor | |||
| HR | 107doc ([IU] * 100) + (([L] - 1) * 10000) + 7 | IU discharge setpoint cool | Tenths of a degree °C; range printed -10..10 °C. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 108doc ([IU] * 100) + (([L] - 1) * 10000) + 8 | IU discharge setpoint heat | Tenths of a degree °C; range printed -10..10 °C. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 109doc ([IU] * 100) + (([L] - 1) * 10000) + 9 | IU discharge current temperature | Tenths of a degree °C. | INT16 | × 0.1 | °C | Read | ||
| HR | 110doc ([IU] * 100) + (([L] - 1) * 10000) + 10 | IU heat exchanger temperature | Tenths of a degree °C; -1..26 °C. | INT16 | × 0.1 | °C | Read | ||
| HR | 111doc ([IU] * 100) + (([L] - 1) * 10000) + 11 | IU heat setpoint upper limit | Tenths of a degree °C. | INT16 | × 0.1 | °C | Read | ||
| HR | 112doc ([IU] * 100) + (([L] - 1) * 10000) + 12 | IU heat setpoint lower limit | Tenths of a degree °C. | INT16 | × 0.1 | °C | Read | ||
| HR | 113doc ([IU] * 100) + (([L] - 1) * 10000) + 13 | IU cool setpoint upper limit | Tenths of a degree °C. | INT16 | × 0.1 | °C | Read | ||
| HR | 114doc ([IU] * 100) + (([L] - 1) * 10000) + 14 | IU cool setpoint lower limit | Tenths of a degree °C. | INT16 | × 0.1 | °C | Read | ||
| HR | 115doc ([IU] * 100) + (([L] - 1) * 10000) + 15 | IU dry setpoint upper limit | Tenths of a degree °C. | INT16 | × 0.1 | °C | Read | ||
| HR | 116doc ([IU] * 100) + (([L] - 1) * 10000) + 16 | IU dry setpoint lower limit | Tenths of a degree °C. | INT16 | × 0.1 | °C | Read | ||
| HR | 117doc ([IU] * 100) + (([L] - 1) * 10000) + 17 | IU auto setpoint upper limit | Tenths of a degree °C. | INT16 | × 0.1 | °C | Read | ||
| HR | 118doc ([IU] * 100) + (([L] - 1) * 10000) + 18 | IU auto setpoint lower limit | Tenths of a degree °C. | INT16 | × 0.1 | °C | Read | ||
| HR | 119doc ([IU] * 100) + (([L] - 1) * 10000) + 19 | IU unit error code | 0 = no error, other = error code (0..255). | INT16 | Read | 0 = No error | |||
| HR | 120doc ([IU] * 100) + (([L] - 1) * 10000) + 20 | IU filter alarm | INT16 | Read | 0 = Normal; 1 = Alarm | ||||
| HR | 121doc ([IU] * 100) + (([L] - 1) * 10000) + 21 | IU filter alarm reset | INT16 | Write | 1 = Reset | ||||
| HR | 122doc ([IU] * 100) + (([L] - 1) * 10000) + 22 | IU communication error | INT16 | Read | 0 = No error; 1 = Error | ||||
| HR | 123doc ([IU] * 100) + (([L] - 1) * 10000) + 23 | IU allow on/off from remote controller | INT16 | Read/write | 0 = Allow; 1 = Not allow | ||||
| HR | 124doc ([IU] * 100) + (([L] - 1) * 10000) + 24 | IU allow mode from remote controller | INT16 | Read/write | 0 = Allow; 1 = Not allow | ||||
| HR | 125doc ([IU] * 100) + (([L] - 1) * 10000) + 25 | IU allow setpoint from remote controller | INT16 | Read/write | 0 = Allow; 1 = Not allow | ||||
| HR | 126doc ([IU] * 100) + (([L] - 1) * 10000) + 26 | IU unit type | INT16 | Read | 0 = Not defined; 1 = TBD; 2 = GHP; 3 = PAC; 4 = VRF | ||||
| HR | 127doc ([IU] * 100) + (([L] - 1) * 10000) + 27 | IU occupancy | INT16 | Read/write | 1 = Occupied; 2 = Unoccupied; 3 = Disable | ||||
| HR | 128doc ([IU] * 100) + (([L] - 1) * 10000) + 28 | IU Modbus ambient temperature | Room temperature written from Modbus; tenths. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 129doc ([IU] * 100) + (([L] - 1) * 10000) + 29 | IU AC real temperature setpoint | Setpoint the unit is actually using; tenths. | INT16 | × 0.1 | °C | Read | ||
| HR | 130doc ([IU] * 100) + (([L] - 1) * 10000) + 30 | IU consumption yesterday | INT16 | kWh | Read | ||||
| HR | 131doc ([IU] * 100) + (([L] - 1) * 10000) + 31 | IU consumption today | INT16 | kWh | Read | ||||
| HR | 132doc ([IU] * 100) + (([L] - 1) * 10000) + 32 | IU consumption total | INT16 | kWh | Read | ||||
| HR | 7025doc ([OU] * 25) + (([L] - 1) * 10000) + 7000) + 0 | OU communication error | Line 1, outdoor unit 1 shown; see notes. | INT16 | Read | 0 = No error; 1 = Error | |||
| HR | 7026doc ([OU] * 25) + (([L] - 1) * 10000) + 7000) + 1 | OU demand limit ratio | 0..200 %; 255 = no limit. | INT16 | % | Read/write | 255 = No limit | ||
| HR | 7027doc ([OU] * 25) + (([L] - 1) * 10000) + 7000) + 2 | OU high pressure sensor | Tenths of bar. | INT16 | × 0.1 | bar | Read | ||
| HR | 7028doc ([OU] * 25) + (([L] - 1) * 10000) + 7000) + 3 | OU low pressure sensor | Tenths of bar. | INT16 | × 0.1 | bar | Read |
Notes on this map
- Only line 1, indoor unit 1 and outdoor unit 1 are listed. Indoor unit IU: add (IU-1) x 100; outdoor unit OU: add (OU-1) x 25; line 2: add 10000.
- Compressor 1..3 operation time (OU block +4..+6) are left out: the manual gives a 0..16777215 h range, which does not fit the single 16-bit register it lists.
- Consumption registers (+30..+32) are printed in kWh with no scale factor; listed at scale 1.
- The manual says Modbus RTU and TCP work at the same time on the 16 and 64 versions; the 128 version has different connections (manual section 3.2).
- Temperatures are tenths of °C or °F per the MAPS temperature setting; °C shown.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Intesis (HMS Networks) INMBSPAN016O000 / 064O000 / 128O000 Panasonic VRF (P-Link) to Modbus gateway
What Modbus registers does the Intesis (HMS Networks) INMBSPAN016O000 / 064O000 / 128O000 Panasonic VRF (P-Link) to Modbus gateway have?
This map lists 62 registers: 62 holding registers. 40 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Intesis (HMS Networks) INMBSPAN016O000 / 064O000 / 128O000 Panasonic VRF (P-Link) to Modbus gateway Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual states formula results are link-layer addresses with the first register at 0. Indoor unit IU (1..64) on line L (1 or 2) uses IU x 100 + (L-1) x 10000 + offset; outdoor unit OU (1..30) uses OU x 25 + (L-1) x 10000 + 7000 + offset. This file lists line 1, IU 1 (100..132) and OU 1 (7025..7028).
What are the minimum Modbus registers to integrate the Intesis (HMS Networks) INMBSPAN016O000 / 064O000 / 128O000 Panasonic VRF (P-Link) to Modbus gateway?
Start with HR 100 IU on/off (On/off); HR 101 IU operation mode (Mode); HR 102 IU fan speed (Fan speed); HR 104 IU temperature setpoint (Setpoint (x10)); HR 105 IU ambient temperature (Room temperature (x10)); HR 119 IU unit error code (Error code); HR 122 IU communication error (Communication error); HR 7025 OU communication error (Outdoor unit communication error).
How do I enable Modbus control of the Intesis (HMS Networks) INMBSPAN016O000 / 064O000 / 128O000 Panasonic VRF (P-Link) to Modbus gateway?
Indoor and outdoor units must be configured in MAPS; P-Link goes to Port A (A3/A4, no polarity).
Where is the official Intesis (HMS Networks) INMBSPAN016O000 / 064O000 / 128O000 Panasonic VRF (P-Link) to Modbus gateway Modbus documentation?
The source is Intesis Modbus Server - Panasonic User Manual (User Manual r1.1 EN), revision 2020-11, published free by Intesis (HMS Networks) at https://www.hms-networks.com/docs/default-source/products/intesis/manuals-and-guides---manuals/user-manual-inmbspanxxxo000.pdf.
More Intesis (HMS Networks) Modbus register maps
- Heat pump gateway (VRF / split AC gateway)
Intesis (HMS Networks) IN485DAI001A000 Daikin Altherma 3 air-to-water to Modbus RTU / BACnet MS/TP gateway
Intesis (HMS Networks) IN485DAI001A000 gateway for Daikin Altherma 3 air-to-water heat pumps, set to Modbus RTU, per user manual version 1.0.2 (2025-07-18).
Also known as: IN485DAI001A000, Daikin Altherma 3 Modbus, Intesis Altherma 3, HMS Daikin Altherma gateway - Heat pump gateway (VRF / split AC gateway)
Intesis (HMS Networks) IN485MIT001A000 Mitsubishi Electric Ecodan air-to-water to Modbus RTU / BACnet MS/TP gateway
Intesis (HMS Networks) IN485MIT001A000 gateway on the CN105 socket of Mitsubishi Electric Ecodan air-to-water heat pumps, set to Modbus RTU, per user manual version 1.0.3 (2025-12-02).
Also known as: IN485MIT001A000, Ecodan Modbus, Mitsubishi Ecodan Modbus RTU, Intesis Ecodan, HMS Ecodan gateway - VRF / split AC gateway
Intesis (HMS Networks) IN485SAM001R000 Samsung AC to Modbus RTU / BACnet MS/TP gateway
Samsung indoor units on the F3F4 remote-controller bus, gateway set to Modbus RTU (SW1-5 ON); user manual version 1.0.0.
Also known as: IN485SAM001R000, Intesis Samsung BACnet MS/TP Modbus - VRF / split AC gateway
Intesis (HMS Networks) IN770AIR***O000 700 Series Air Gateway, Bosch application (Modbus)
Intesis 700 Series Air Gateway IN770AIR***O000 with the Bosch application (XYE bus), Modbus RTU / TCP server, user manual version 1.0.13 (2025-12-09).
Also known as: IN770AIR00MO000, IN770AIR00SO000, IN770AIRXXSO000 - VRF / split AC gateway
Intesis (HMS Networks) IN770AIR***O000 700 Series Air Gateway, Midea application (Modbus)
Intesis 700 Series Air Gateway IN770AIR***O000 with the Midea application (XYE bus), Modbus RTU / TCP server, user manual version 1.0.22 (2025-12-09).
Also known as: IN770AIR00MO000, IN770AIR00SO000, IN770AIRXXSO000 - VRF / split AC gateway
Intesis (HMS Networks) IN770AIR***O000 700 Series Air Gateway, Mitsubishi Electric City Multi application (Modbus)
Intesis 700 Series Air Gateway IN770AIR***O000 with the Mitsubishi Electric City Multi application (M-NET centralised controllers (AE-200, EW-50, G-50 and others)), Modbus RTU / TCP server, user manual version 1.0.19 (2026-03-16).
Also known as: IN770AIR00MO000, IN770AIR00SO000, IN770AIRXXSO000 - VRF / split AC gateway
Intesis (HMS Networks) IN770AIR***O000 700 Series Air Gateway, Panasonic application (Modbus)
Intesis 700 Series Air Gateway IN770AIR***O000 with the Panasonic application (U1U2 P-Link / S-Link), Modbus RTU / TCP server, user manual version 1.1.7 (2025-12-09).
Also known as: IN770AIR00MO000, IN770AIR00SO000, IN770AIRXXSO000 - VRF / split AC gateway
Intesis (HMS Networks) INMBSACA001I000 XYE-bus air conditioner to Modbus RTU interface (1 unit)
INMBSACA001I000, user manual v1.8 EN; one indoor unit at unit address 0 on its own XYE bus.
Also known as: INMBSACA001I000 - VRF / split AC gateway
Intesis (HMS Networks) INMBSACA004I000 / 008I000 / 032I000 XYE-bus air conditioner to Modbus RTU interface (4 to 32 units)
INMBSACA004I000 / INMBSACA008I000 / INMBSACA032I000, user manual v1.8 EN; up to 4, 8 or 32 indoor units on one XYE bus.
Also known as: INMBSACA004I000, INMBSACA008I000, INMBSACA032I000 - VRF / split AC gateway
Intesis (HMS Networks) INMBSDAI001I000 Daikin domestic AC to Modbus RTU gateway
Single Daikin domestic (S21-connector) indoor unit via INMBSDAI001I000, user manual v1.0.2.
Also known as: INMBSDAI001I000, Intesis Daikin domestic Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSDAI001R000 Daikin VRV / Sky Air to Modbus RTU gateway
One Daikin VRV or Sky Air indoor unit (or group) on the P1P2 bus via INMBSDAI001R000, user manual v1.0.1.
Also known as: INMBSDAI001R000, Intesis Daikin VRV Modbus - Lighting gateway (DALI-2 to Modbus)
Intesis (HMS Networks) INMBSDAL0640000 / INMBSDAL1280000 DALI-2 to Modbus RTU / TCP server
Intesis Modbus Server - DALI with one (0640000, RTU + TCP) or two (1280000, TCP only) DALI channels, Modbus Addresses parameter set to Fixed; user manual r1.2 (09/2021).
Also known as: INMBSDAL0640000, INMBSDAL1280000, Intesis Modbus Server - DALI, Intesis DALI-2 Modbus gateway - VRF / split AC gateway
Intesis (HMS Networks) INMBSFGL001I000 Fujitsu domestic AC to Modbus RTU gateway
One Fujitsu domestic (RAC) or compatible VRF indoor unit, connected to the CN65/CN12/CN6 socket on the indoor board via INMBSFGL001I000, user manual v1.5 (01/2024).
Also known as: INMBSFGL001I000, FJ-AC-MBS-1, Intesis Fujitsu domestic Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSFGL001R000 Fujitsu AC to Modbus RTU gateway
One Fujitsu indoor unit, or a group of up to 16 controlled together as one, on the 3-wire BWR remote-controller bus via INMBSFGL001R000, user manual v2.4 (02/2025).
Also known as: INMBSFGL001R000, Intesis Fujitsu Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSFGL016O000 Fujitsu VRF to Modbus RTU / TCP gateway (up to 16 indoor units)
Intesis Modbus Server - Fujitsu VRF, order code INMBSFGL016O000 (legacy FJ-AC-MBS-16), user manual r1.0 (02/2020); up to 16 indoor units configured in MAPS.
Also known as: INMBSFGL016O000, FJ-AC-MBS-16, Intesis Modbus Server Fujitsu VRF - VRF / split AC gateway
Intesis (HMS Networks) INMBSHIS001R000 Hisense AC to Modbus RTU gateway
Hisense commercial-line indoor units on the AB remote-controller bus, user manual v1.6 (01/2024).
Also known as: INMBSHIS001R000, HS-RC-MBS-1, Intesis Hisense Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSHIS016O000 Hisense VRF to Modbus RTU / TCP gateway (16 / 64 indoor units)
Intesis Modbus Server - Hisense VRF, order codes INMBSHIS016O000 / INMBSHIS064O000 (legacy HS-AC-MBS-16 / HS-AC-MBS-64), user manual User Manual r1.0 EN.
Also known as: INMBSHIS016O000, INMBSHIS064O000, HS-AC-MBS-16, HS-AC-MBS-64, Intesis Modbus Server Hisense VRF - VRF / split AC gateway
Intesis (HMS Networks) INMBSHIT001R000 Hitachi AC to Modbus RTU gateway
Intesis (HMS Networks) INMBSHIT001R000 interface on the AB bus of one Hitachi commercial-line indoor unit (or group), per user manual v1.6 (01/2024).
Also known as: INMBSHIT001R000, Hitachi Modbus gateway, Intesis Hitachi - VRF / split AC gateway
Intesis (HMS Networks) INMBSHIT016O000 Hitachi VRF to Modbus RTU / TCP gateway (16 / 64 indoor units)
Intesis Modbus Server - Hitachi VRF, order codes INMBSHIT016O000 / INMBSHIT064O000 (legacy HI-AC-MBS-16 / HI-AC-MBS-64), user manual User Manual r1.2 EN.
Also known as: INMBSHIT016O000, INMBSHIT064O000, HI-AC-MBS-16, HI-AC-MBS-64, Intesis Modbus Server Hitachi VRF - VRF / split AC gateway
Intesis (HMS Networks) INMBSLGE001R000 LG AC to Modbus RTU gateway
One LG indoor unit on the BYR (wired remote) bus via INMBSLGE001R000 (legacy code LG-RC-MBS-1), user manual v1.9 (01/2024).
Also known as: INMBSLGE001R000, LG-RC-MBS-1, Intesis LG Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSLGE016O000 LG VRF to Modbus RTU / TCP gateway (16 / 64 indoor units)
Intesis Modbus - LG VRF, order codes INMBSLGE016O000 / INMBSLGE064O000 (legacy LG-AC-MBS-16 / -64), user manual r1.0 (04/2020); LG PI485 bus.
Also known as: INMBSLGE016O000, INMBSLGE064O000, LG-AC-MBS-16, LG-AC-MBS-64, Intesis Modbus LG VRF - VRF / split AC gateway
Intesis (HMS Networks) INMBSMHI001R000 Mitsubishi Heavy Industries AC to Modbus RTU gateway
Mitsubishi Heavy Industries indoor units (one, or up to 16 controlled together as one) on the XY remote-controller bus, user manual r6.4 (01/2024).
Also known as: INMBSMHI001R000, MH-RC-MBS-1, Intesis Mitsubishi Heavy Industries Modbus, Intesis MHI Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSMHI128O000 / INMBSMHI048O000 Mitsubishi Heavy Industries Superlink to Modbus gateway
Intesis Modbus Server - Mitsubishi Heavy Industries AC, order codes INMBSMHI128O000 (128 units, Superlink-II) and INMBSMHI048O000 (48 units, Superlink-I or II), user's manual r1.0 (05/2012).
Also known as: INMBSMHI128O000, INMBSMHI048O000, MH-AC-MBS-128, MH-AC-MBS-48, Intesis Modbus Server MHI Superlink - VRF / split AC gateway
Intesis (HMS Networks) INMBSMID001I000 Midea AC to Modbus RTU gateway
One Midea commercial / VRF indoor unit on the XYE bus, user manual v1.11.
Also known as: INMBSMID001I000, Intesis Midea Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSMID004I000 / 008I000 / 032I000 Midea AC to Modbus RTU interface (4 to 32 units)
INMBSMID004I000 / INMBSMID008I000 / INMBSMID032I000 / MD-AC-MBS-4 / MD-AC-MBS-8 / MD-AC-MBS-32, user manual v1.7 EN; up to 4, 8 or 32 indoor units on one XYE bus.
Also known as: INMBSMID004I000, INMBSMID008I000, INMBSMID032I000, MD-AC-MBS-4, MD-AC-MBS-8, MD-AC-MBS-32 - VRF / split AC gateway
Intesis (HMS Networks) INMBSMIT001I000 Mitsubishi Electric AC to Modbus RTU gateway
One Mitsubishi Electric Domestic, Mr. Slim or City Multi indoor unit via INMBSMIT001I000, user manual r2.8 (11/2024).
Also known as: INMBSMIT001I000, Intesis Mitsubishi Electric Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSMIT050C000 / INMBSMIT100C000 Mitsubishi Electric City Multi centralised controller to Modbus gateway
Intesis Modbus Server - Mitsubishi Electric CC, order codes INMBSMIT050C000 / INMBSMIT100C000 (legacy ME-AC-MBS-50 / -100), user manual r1.4 (05/2021); talks to City Multi centralised controllers (G-50A, GB-50A, AG-150A, EB-50, EW-50, AE-200 and newer) through their XML interface over Ethernet.
Also known as: INMBSMIT050C000, INMBSMIT100C000, ME-AC-MBS-50, ME-AC-MBS-100, Intesis Modbus Server Mitsubishi Electric CC - Heat pump gateway (VRF / split AC gateway)
Intesis (HMS Networks) INMBSPAN001A100 Panasonic Aquarea H/J/K/L/M air-to-water to Modbus RTU gateway
Intesis (HMS Networks) INMBSPAN001A100 gateway connected to Panasonic Aquarea H, J, K, L and M series air-to-water heat pumps, per user manual version 1.0.2 (2026-02-04).
Also known as: INMBSPAN001A100, Aquarea Modbus, Panasonic Aquarea Modbus RTU, Intesis Aquarea, INMBSPAN001A000 (legacy order code) - VRF / split AC gateway
Intesis (HMS Networks) INMBSPAN001I100 Panasonic Etherea (domestic) AC to Modbus RTU gateway
Panasonic Etherea-line domestic split units, user's manual r1.5 (09/2025). Some registers only on 2013 (PKE series) and later models.
Also known as: INMBSPAN001I100, Intesis Panasonic Etherea Modbus, Intesis Panasonic domestic Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSPAN001R000 Panasonic AC to Modbus RTU gateway
Panasonic / Sanyo ECOi and PACi indoor units (one, or up to 16 controlled together as one) on the R1R2 remote-controller bus, user manual v2.8 (09/2025).
Also known as: INMBSPAN001R000, PA-RC2-MBS-1, Intesis Panasonic Modbus, Intesis Sanyo Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSSAM001R000 Samsung AC to Modbus RTU gateway
Samsung commercial indoor units on the F3F4/V1V2 remote-controller bus, user's manual v1.5 (01/2024).
Also known as: INMBSSAM001R000, Intesis Samsung Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSSAM001R100 Samsung NASA AC to Modbus RTU gateway
Samsung NASA-protocol commercial indoor units on the remote-controller bus, user's manual r1.4 (01/2024).
Also known as: INMBSSAM001R100, Intesis Samsung NASA Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSSAM016O000 Samsung NASA (R1/R2) VRF to Modbus gateway (4 to 64 units)
Intesis Modbus Server - Samsung NASA, order codes INMBSSAM004O000 / 008O000 / 016O000 / 064O000 (legacy SM-ACN-MBS-4/8/16/64), user manual r1.4 (12/2020); Samsung NASA R1/R2 bus.
Also known as: INMBSSAM004O000, INMBSSAM008O000, INMBSSAM016O000, INMBSSAM064O000, SM-ACN-MBS-4, SM-ACN-MBS-8, SM-ACN-MBS-16, SM-ACN-MBS-64 - VRF / split AC gateway
Intesis (HMS Networks) INMBSTOS001R000 Toshiba AC to Modbus RTU gateway
Toshiba Digital Inverter (RAV) and VRF indoor units on the AB remote bus via INMBSTOS001R0xx, user manual r2.9 (01/2024).
Also known as: INMBSTOS001R000, INMBSTOS001R0xx, Intesis Toshiba Modbus
Other ac & vrf gateways register maps
- VRF / split AC gateway
Mitsubishi Electric MelcoBEMS MINI (A1M) gateway for Air-To-Air split units
Procon MelcoBEMS MINI (A1M) on the CN105/CN92 connector of a Mitsubishi Electric Air-To-Air indoor unit, installation manual v1.1.11 (firmware 3.0.28 for revision 2-4 hardware, 3.1.1 for revision 5).
Also known as: MelcoBEMS MINI (A1M), A1M, Procon A1M, MelcoBEMS MINI - VRF / split AC gateway
Realtime Control Systems RTD-RA Modbus interface for Daikin room air conditioners
RTD-RA plugged into the S21 port of a Daikin room air conditioner (split) indoor unit, installation instructions 21070-1.07.04.
Also known as: RTD-RA, Daikin RTD-RA - Heat pump (integral ventilation unit, via ISG Modbus TCP gateway)
Stiebel Eltron Integral ventilation units LWZ / LWA via ISG Modbus TCP/IP
Stiebel Eltron LWZ / LWA integral ventilation and heat pump units reached through an ISG web or ISG plus with the Modbus TCP/IP software extension.
Also known as: LWZ 303 Integral, LWZ 403 SOL, LWA 403, LWZ 304 Trend, LWZ 404 Trend, LWZ 304 SOL, LWZ 404 SOL, LWZ 504, LWZ Smart, LWZ 604 Air, LWZ 5 S Plus, LWZ 5 S Trend, LWZ 8 S Trend, LWZ 5 S Smart, LWZ 5 CS Premium, LWZ 8 CS Premium - Gateway for Bender BMS-bus devices (insulation monitors, RCMs, changeover modules) - sensor/alarm data
Bender COM461MT BMS-to-Modbus/TCP gateway
COM461MT software D402 V1.0x; the map is the gateway's process image, shown here for BMS device address 1 plus the built-in test record.
Also known as: COM461MT, B95061021 - Split AC unit (VRF / split AC gateway built in)
Gree Export residential split air conditioners (built-in Modbus on indoor unit / wired controller)
Gree export residential air conditioners whose indoor-unit controller or wired controller has the integrated Modbus RTU interface; protocol PDF dated 2023-05.
Also known as: Gree residential split Modbus, Gree wall split Modbus, Gree wired controller Modbus - Chiller / heat pump gateway (VRF / split AC gateway)
Mitsubishi Electric MelcoBEMS MINI (A1M+) gateway for CAHV / CRHV / QAHV heat pumps and EAHV / EACV e-series chillers
Procon MelcoBEMS MINI (A1M+) firmware 4.1.0 on Mitsubishi Electric CAHV and CRHV heat pumps, QAHV CO2 heat pumps and EAHV / EACV e-series chillers (master and slave units); holding-register table only.
Also known as: A1M+, MelcoBEMS MINI, Procon A1M+, CAHV, CRHV, QAHV, EAHV, EACV, e-series chiller
All ac & vrf gateways Modbus register maps →
Source: Intesis Modbus Server - Panasonic User Manual · User Manual r1.1 EN · rev. 2020-11. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.