  4. INMBSPAN016O000 / 064O000 / 128O000 Panasonic VRF (P-Link) to Modbus gateway

VRF / split AC gateway · Modbus register map

Intesis (HMS Networks) INMBSPAN016O000 / 064O000 / 128O000 Panasonic VRF (P-Link) to Modbus gateway Modbus register map

Updated 19 November 2026

Short answer

Modbus server for Panasonic VRF systems on P-Link. Each configured indoor unit gets a 100-register block with control, temperatures, limits, error, occupancy and energy values; outdoor units get pressure and demand-limit registers; low addresses carry occupancy setpoints and all-unit commands. Up to two P-Link lines.

This page lists 62 Modbus registers for the Intesis (HMS Networks) INMBSPAN016O000 / 064O000 / 128O000 Panasonic VRF (P-Link) to Modbus gateway — 40 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Intesis (HMS Networks)’s own free documentation (linked below) and checked against it.

Manufacturer
Intesis (HMS Networks)
Model
INMBSPAN016O000 / 064O000 / 128O000 Panasonic VRF (P-Link) to Modbus gateway
Equipment type
VRF / split AC gateway
Registers
62 (40 writable)
Transport
Modbus RTU, Modbus TCP
Default unit ID
Not stated
TCP port
502
Documented addressing
0-based (the number printed is the address on the wire)
Also known as
INMBSPAN016O000, INMBSPAN064O000, INMBSPAN128O000, PA-AC-MBS-16, PA-AC-MBS-64, PA-AC-MBS-128, Intesis Modbus Server Panasonic VRF
Source document
Intesis Modbus Server - Panasonic User Manual · User Manual r1.1 EN · rev. 2020-11
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Intesis (HMS Networks) INMBSPAN016O000 / 064O000 / 128O000 Panasonic VRF (P-Link) to Modbus gateway

Integration in brief

Configure lines and units in Intesis MAPS, send the project, then poll each IU x 100 block. Write on/off, mode, fan, vane and setpoint (tenths) per unit, or use the occupancy and all-unit registers 0..24.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 100IU on/offINT16On/offRead/write
HR 101IU operation modeINT16ModeRead/write
HR 102IU fan speedINT16Fan speedRead/write
HR 104IU temperature setpointINT16Setpoint (x10)Read/write
HR 105IU ambient temperatureINT16Room temperature (x10)Read
HR 119IU unit error codeINT16Error codeRead
HR 122IU communication errorINT16Communication errorRead
HR 7025OU communication errorINT16Outdoor unit communication errorRead

Enable Modbus control & writes

Indoor and outdoor units must be configured in MAPS; P-Link goes to Port A (A3/A4, no polarity).

Byte order & addressing

Network setup

Watch out for

Intesis (HMS Networks) INMBSPAN016O000 / 064O000 / 128O000 Panasonic VRF (P-Link) to Modbus gateway Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

62 of 62 shown
Intesis (HMS Networks) INMBSPAN016O000 / 064O000 / 128O000 Panasonic VRF (P-Link) to Modbus gateway Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0Occupancy cool setpointTenths of a degree; -15..60 °C.INT16× 0.1°CRead/write
HR1Occupancy heat setpointTenths of a degree; -15..60 °C.INT16× 0.1°CRead/write
HR2Unoccupancy cool setpointTenths of a degree; -15..60 °C.INT16× 0.1°CRead/write
HR3Unoccupancy heat setpointTenths of a degree; -15..60 °C.INT16× 0.1°CRead/write
HR4Occupancy continuous checkINT16Read/write0 = Disabled; 1 = Enabled
HR5Unoccupancy deadband actionINT16Read/write0 = Off; 1 = Current mode
HR6On (all units)INT16Write1 = Switch all on
HR7Off (all units)INT16Write1 = Switch all off
HR8Mode Auto (all units)INT16Write1 = Set Auto
HR9Mode Heat (all units)INT16Write1 = Set Heat
HR10Mode Dry (all units)INT16Write1 = Set Dry
HR11Mode Fan (all units)INT16Write1 = Set Fan
HR12Mode Cool (all units)INT16Write1 = Set Cool
HR13Fan speed Auto (all units)INT16Write1 = Set fan Auto
HR14Fan speed Low (all units)INT16Write1 = Set fan Low
HR15Fan speed Mid (all units)INT16Write1 = Set fan Med
HR16Fan speed High (all units)INT16Write1 = Set fan High
HR17Vanes stop (all units)INT16Write1 = Set vanes stop
HR18Vanes position 1 (all units)INT16Write1 = Set vanes position 1
HR19Vanes position 2 (all units)INT16Write1 = Set vanes position 2
HR20Vanes position 3 (all units)INT16Write1 = Set vanes position 3
HR21Vanes position 4 (all units)INT16Write1 = Set vanes position 4
HR22Vanes position 5 (all units)INT16Write1 = Set vanes position 5
HR23Vanes swing (all units)INT16Write1 = Set vanes swing
HR24Temperature setpoint (all units)Tenths of a degree; 16..30 °C.INT16× 0.1°CWrite
HR100doc ([IU] * 100) + (([L] - 1) * 10000) + 0IU on/offLine 1, indoor unit 1 shown; see notes.INT16Read/write0 = Off; 1 = On
HR101doc ([IU] * 100) + (([L] - 1) * 10000) + 1IU operation modeINT16Read/write0 = Auto; 1 = Heat; 2 = Dry; 3 = Fan; 4 = Cool; 5 = Auto Heat; 6 = Auto Cool
HR102doc ([IU] * 100) + (([L] - 1) * 10000) + 2IU fan speedINT16Read/write0 = Auto; 1 = Low; 2 = Low+; 3 = Med; 4 = Med+; 5 = High
HR103doc ([IU] * 100) + (([L] - 1) * 10000) + 3IU vane positionINT16Read/write0 = Stop; 1 = Pos 1; 2 = Pos 2; 3 = Pos 3; 4 = Pos 4; 5 = Pos 5; 10 = Swing
HR104doc ([IU] * 100) + (([L] - 1) * 10000) + 4IU temperature setpointTenths of a degree °C; 16..30.INT16× 0.1°CRead/write
HR105doc ([IU] * 100) + (([L] - 1) * 10000) + 5IU ambient temperatureTenths of a degree °C; -35..92.5.INT16× 0.1°CRead
HR106doc ([IU] * 100) + (([L] - 1) * 10000) + 6IU wired remote controller sensorSelects which sensor the unit uses.INT16Write0 = Body sensor; 1 = Remote controller sensor
HR107doc ([IU] * 100) + (([L] - 1) * 10000) + 7IU discharge setpoint coolTenths of a degree °C; range printed -10..10 °C.INT16× 0.1°CRead/write
HR108doc ([IU] * 100) + (([L] - 1) * 10000) + 8IU discharge setpoint heatTenths of a degree °C; range printed -10..10 °C.INT16× 0.1°CRead/write
HR109doc ([IU] * 100) + (([L] - 1) * 10000) + 9IU discharge current temperatureTenths of a degree °C.INT16× 0.1°CRead
HR110doc ([IU] * 100) + (([L] - 1) * 10000) + 10IU heat exchanger temperatureTenths of a degree °C; -1..26 °C.INT16× 0.1°CRead
HR111doc ([IU] * 100) + (([L] - 1) * 10000) + 11IU heat setpoint upper limitTenths of a degree °C.INT16× 0.1°CRead
HR112doc ([IU] * 100) + (([L] - 1) * 10000) + 12IU heat setpoint lower limitTenths of a degree °C.INT16× 0.1°CRead
HR113doc ([IU] * 100) + (([L] - 1) * 10000) + 13IU cool setpoint upper limitTenths of a degree °C.INT16× 0.1°CRead
HR114doc ([IU] * 100) + (([L] - 1) * 10000) + 14IU cool setpoint lower limitTenths of a degree °C.INT16× 0.1°CRead
HR115doc ([IU] * 100) + (([L] - 1) * 10000) + 15IU dry setpoint upper limitTenths of a degree °C.INT16× 0.1°CRead
HR116doc ([IU] * 100) + (([L] - 1) * 10000) + 16IU dry setpoint lower limitTenths of a degree °C.INT16× 0.1°CRead
HR117doc ([IU] * 100) + (([L] - 1) * 10000) + 17IU auto setpoint upper limitTenths of a degree °C.INT16× 0.1°CRead
HR118doc ([IU] * 100) + (([L] - 1) * 10000) + 18IU auto setpoint lower limitTenths of a degree °C.INT16× 0.1°CRead
HR119doc ([IU] * 100) + (([L] - 1) * 10000) + 19IU unit error code0 = no error, other = error code (0..255).INT16Read0 = No error
HR120doc ([IU] * 100) + (([L] - 1) * 10000) + 20IU filter alarmINT16Read0 = Normal; 1 = Alarm
HR121doc ([IU] * 100) + (([L] - 1) * 10000) + 21IU filter alarm resetINT16Write1 = Reset
HR122doc ([IU] * 100) + (([L] - 1) * 10000) + 22IU communication errorINT16Read0 = No error; 1 = Error
HR123doc ([IU] * 100) + (([L] - 1) * 10000) + 23IU allow on/off from remote controllerINT16Read/write0 = Allow; 1 = Not allow
HR124doc ([IU] * 100) + (([L] - 1) * 10000) + 24IU allow mode from remote controllerINT16Read/write0 = Allow; 1 = Not allow
HR125doc ([IU] * 100) + (([L] - 1) * 10000) + 25IU allow setpoint from remote controllerINT16Read/write0 = Allow; 1 = Not allow
HR126doc ([IU] * 100) + (([L] - 1) * 10000) + 26IU unit typeINT16Read0 = Not defined; 1 = TBD; 2 = GHP; 3 = PAC; 4 = VRF
HR127doc ([IU] * 100) + (([L] - 1) * 10000) + 27IU occupancyINT16Read/write1 = Occupied; 2 = Unoccupied; 3 = Disable
HR128doc ([IU] * 100) + (([L] - 1) * 10000) + 28IU Modbus ambient temperatureRoom temperature written from Modbus; tenths.INT16× 0.1°CRead/write
HR129doc ([IU] * 100) + (([L] - 1) * 10000) + 29IU AC real temperature setpointSetpoint the unit is actually using; tenths.INT16× 0.1°CRead
HR130doc ([IU] * 100) + (([L] - 1) * 10000) + 30IU consumption yesterdayINT16kWhRead
HR131doc ([IU] * 100) + (([L] - 1) * 10000) + 31IU consumption todayINT16kWhRead
HR132doc ([IU] * 100) + (([L] - 1) * 10000) + 32IU consumption totalINT16kWhRead
HR7025doc ([OU] * 25) + (([L] - 1) * 10000) + 7000) + 0OU communication errorLine 1, outdoor unit 1 shown; see notes.INT16Read0 = No error; 1 = Error
HR7026doc ([OU] * 25) + (([L] - 1) * 10000) + 7000) + 1OU demand limit ratio0..200 %; 255 = no limit.INT16%Read/write255 = No limit
HR7027doc ([OU] * 25) + (([L] - 1) * 10000) + 7000) + 2OU high pressure sensorTenths of bar.INT16× 0.1barRead
HR7028doc ([OU] * 25) + (([L] - 1) * 10000) + 7000) + 3OU low pressure sensorTenths of bar.INT16× 0.1barRead

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Intesis (HMS Networks) INMBSPAN016O000 / 064O000 / 128O000 Panasonic VRF (P-Link) to Modbus gateway

What Modbus registers does the Intesis (HMS Networks) INMBSPAN016O000 / 064O000 / 128O000 Panasonic VRF (P-Link) to Modbus gateway have?

This map lists 62 registers: 62 holding registers. 40 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Intesis (HMS Networks) INMBSPAN016O000 / 064O000 / 128O000 Panasonic VRF (P-Link) to Modbus gateway Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual states formula results are link-layer addresses with the first register at 0. Indoor unit IU (1..64) on line L (1 or 2) uses IU x 100 + (L-1) x 10000 + offset; outdoor unit OU (1..30) uses OU x 25 + (L-1) x 10000 + 7000 + offset. This file lists line 1, IU 1 (100..132) and OU 1 (7025..7028).

What are the minimum Modbus registers to integrate the Intesis (HMS Networks) INMBSPAN016O000 / 064O000 / 128O000 Panasonic VRF (P-Link) to Modbus gateway?

Start with HR 100 IU on/off (On/off); HR 101 IU operation mode (Mode); HR 102 IU fan speed (Fan speed); HR 104 IU temperature setpoint (Setpoint (x10)); HR 105 IU ambient temperature (Room temperature (x10)); HR 119 IU unit error code (Error code); HR 122 IU communication error (Communication error); HR 7025 OU communication error (Outdoor unit communication error).

How do I enable Modbus control of the Intesis (HMS Networks) INMBSPAN016O000 / 064O000 / 128O000 Panasonic VRF (P-Link) to Modbus gateway?

Indoor and outdoor units must be configured in MAPS; P-Link goes to Port A (A3/A4, no polarity).

Where is the official Intesis (HMS Networks) INMBSPAN016O000 / 064O000 / 128O000 Panasonic VRF (P-Link) to Modbus gateway Modbus documentation?

The source is Intesis Modbus Server - Panasonic User Manual (User Manual r1.1 EN), revision 2020-11, published free by Intesis (HMS Networks) at https://www.hms-networks.com/docs/default-source/products/intesis/manuals-and-guides---manuals/user-manual-inmbspanxxxo000.pdf.