- INMBSPAN001I100 Panasonic Etherea (domestic) AC to Modbus RTU gateway
VRF / split AC gateway · Modbus register map
Intesis (HMS Networks) INMBSPAN001I100 Panasonic Etherea (domestic) AC to Modbus RTU gateway Modbus register map
Updated 17 November 2026
Modbus RTU server that connects to a Panasonic Etherea domestic split unit. Holding registers cover on/off, mode, fan, both vanes, setpoint, powerful/quiet/ECO modes, compressor state, demand response, outdoor and return temperatures, power, current and daily/total energy counters.
This page lists 45 Modbus registers for the Intesis (HMS Networks) INMBSPAN001I100 Panasonic Etherea (domestic) AC to Modbus RTU gateway — 24 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Intesis (HMS Networks)’s own free documentation (linked below) and checked against it.
- Manufacturer
- Intesis (HMS Networks)
- Model
- INMBSPAN001I100 Panasonic Etherea (domestic) AC to Modbus RTU gateway
- Equipment type
- VRF / split AC gateway
- Registers
- 45 (24 writable)
- Transport
- Modbus RTU
- Default unit ID
- 1
- Default serial
- 9600 baud, 8N2
- Documented addressing
- 0-based (the number printed is the address on the wire)
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- INMBSPAN001I100, Intesis Panasonic Etherea Modbus, Intesis Panasonic domestic Modbus
Integration notes: Intesis (HMS Networks) INMBSPAN001I100 Panasonic Etherea (domestic) AC to Modbus RTU gateway
Write 0-4 for on/off, mode, fan, vane and setpoint; poll 5, 10, 11, 66 and the energy pairs 72-77. Set the date registers 78-80 if you want daily energy to roll over correctly.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 0 | AC unit On/Off | UINT16 | On/off | Read/write |
| HR 1 | AC unit mode | UINT16 | Mode | Read/write |
| HR 4 | AC unit temperature setpoint | UINT16 | Setpoint | Read/write |
| HR 5 | AC unit temperature reference | UINT16 | Control temperature | Read |
| HR 11 | Error code | UINT16 | Error code | Read |
| HR 61 | Power consumption | UINT16 | Power | Read |
| HR 76 | Total energy | UINT32 ABCD | Total energy | Read/write |
Enable Modbus control & writes
No enable step; register 7 = 1 disables the gateway.
Byte order & addressing
- Temperature scale depends on SW4.
- Energy pairs are high word first.
- Writing an external temperature to 22 hands the setpoint to the gateway's virtual-temperature logic and the Panasonic remote can no longer change it.
Network setup
- 9600 baud 8N2 by default (8N1 auto-detected); baud on SW3/SW4.
- Slave address 1..63 on SW3 (default 1).
- 120 ohm terminator on SW4.
Watch out for
- Power, current and energy reflect the whole AC system.
- Several registers exist only on 2013 (PKE) and later models.
Intesis (HMS Networks) INMBSPAN001I100 Panasonic Etherea (domestic) AC to Modbus RTU gateway Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0 | AC unit On/Off | UINT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 1 | AC unit mode | Available modes depend on the indoor unit. | UINT16 | Read/write | 0 = Auto; 1 = Heat; 2 = Dry; 3 = Fan; 4 = Cool | |||
| HR | 2 | AC unit fan speed | Available speeds depend on the indoor unit. | UINT16 | Read/write | 0 = Auto; 1 = Low; 2 = Mid-1; 3 = Mid-2; 4 = Mid-3; 5 = High | |||
| HR | 3 | AC unit vertical vane position | UINT16 | Read/write | 0 = Auto; 1 = Horizontal; 2 = Position-2; 3 = Position-3; 4 = Position-4; 5 = Vertical; 6 = Swing | ||||
| HR | 4 | AC unit temperature setpoint | 16..30 °C (61..88 °F). SW4 x1 °C assumed (x10: 0.1, or °F). | UINT16 | °C | Read/write | 32768 = Initialisation value / no value (0x8000; manual writes -32768) | ||
| HR | 5 | AC unit temperature reference | 10..42 °C. SW4 x1 °C assumed (x10: 0.1, or °F). | UINT16 | °C | Read | 32768 = Initialisation value / no value (0x8000; manual writes -32768) | ||
| HR | 6 | Window contact | Virtual window contact written from Modbus. | UINT16 | Read/write | 0 = Closed; 1 = Open | |||
| HR | 7 | Gateway disablement | Non-volatile. | UINT16 | Read/write | 0 = Gateway enabled; 1 = Gateway disabled | |||
| HR | 8 | AC remote control disablement | Non-volatile. | UINT16 | Read/write | 0 = Remote control enabled; 1 = Remote control disabled | |||
| HR | 9 | AC unit operation time | Hours in On state, 0..65535. Non-volatile. | UINT16 | h | Read/write | |||
| HR | 10 | AC unit alarm status | UINT16 | Read | 0 = No alarm; 1 = Alarm | ||||
| HR | 11 | Error code | Panasonic error code; see manual section 7. | UINT16 | Read | 0 = No error; 65535 = Gateway cannot talk to the AC unit (-1) | |||
| HR | 13 | Open Window switch-off timeout | Minutes from window open to unit off, 0..30 (default 30). | UINT16 | min | Read/write | |||
| HR | 14 | Modbus RTU baud rate | Rate set on SW3/SW4 (2400..115200, default 9600). | UINT16 | Read | ||||
| HR | 15 | Modbus slave address | Address set on SW3, 1..63. | UINT16 | Read | ||||
| HR | 21 | Max number of fan speeds | UINT16 | Read | |||||
| HR | 22 | External ambient temperature (from Modbus) | Modbus-side room temperature; 0x8000 = none. SW4 x1 °C assumed (x10: 0.1, or °F). | UINT16 | °C | Read/write | 32768 = Initialisation value / no value (0x8000; manual writes -32768) | ||
| HR | 23 | AC real temperature setpoint | Setpoint actually applied to the unit. SW4 x1 °C assumed (x10: 0.1, or °F). | UINT16 | °C | Read | |||
| HR | 24 | Current AC max setpoint | 30 °C / 86 °F. SW4 x1 °C assumed (x10: 0.1, or °F). | UINT16 | °C | Read | 32768 = Initialisation value / no value (0x8000; manual writes -32768) | ||
| HR | 25 | Current AC min setpoint | 16 °C / 61 °F. SW4 x1 °C assumed (x10: 0.1, or °F). | UINT16 | °C | Read | 32768 = Initialisation value / no value (0x8000; manual writes -32768) | ||
| HR | 26 | AC unit horizontal vane position | UINT16 | Read/write | 0 = Auto; 1 = Horizontal; 2 = Position-2; 3 = Position-3; 4 = Position-4; 5 = Vertical | ||||
| HR | 37 | Auto mode | Mode chosen while in Auto. | UINT16 | Read | 0 = Auto; 1 = Heat; 2 = Dry; 3 = Fan; 4 = Cool | |||
| HR | 38 | Powerful | UINT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 39 | Quiet | UINT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 53 | Compressor status | UINT16 | Read | 0 = Off; 1 = To off; 2 = To on; 3 = On | ||||
| HR | 54 | Compressor on time | Hours, non-volatile. | UINT16 | h | Read/write | |||
| HR | 55 | Under voltage count | 0..300. | UINT16 | Read/write | ||||
| HR | 56 | Heat 8/10 °C mode | Frost-protection heating mode. | UINT16 | Read/write | 0 = Off; 1 = On | |||
| HR | 57 | ECO mode | 2013 (PKE) models onward. A third option, Auto Comfort, has no printed code. | UINT16 | Read/write | 0 = Off; 1 = ECONAVI | |||
| HR | 58 | Demand response (DRM level) | 2013 models onward. | UINT16 | Read | 0 = Normal; 1 = Comp OFF (DRM1); 2 = 50% (DRM2); 3 = 75% (DRM3) | |||
| HR | 59 | Human activity | 2013 models onward. | UINT16 | Read | 0 = Exist; 1 = Not exist | |||
| HR | 60 | Outdoor intake temperature | 2013 models onward. SW4 x1 °C assumed (x10: 0.1, or °F). | UINT16 | °C | Read | 32768 = Initialisation value / no value (0x8000; manual writes -32768) | ||
| HR | 61 | Power consumption | Whole AC system, not one unit. 2013 models onward. | UINT16 | W | Read | |||
| HR | 62 | Operation current | Whole AC system. 2013 models onward. | UINT16 | mA | Read | |||
| HR | 63 | Power consumption (slow) | Same as 61 with slower updates. | UINT16 | W | Read | |||
| HR | 65 | Input reference temperature | 2013 models onward. SW4 x1 °C assumed (x10: 0.1, or °F). | UINT16 | °C | Read | 32768 = Initialisation value / no value (0x8000; manual writes -32768) | ||
| HR | 66 | Return path temperature | SW4 x1 °C assumed (x10: 0.1, or °F). | UINT16 | °C | Read | |||
| HR | 72doc 72 (MSW) / 73 (LSW) | Today energy | Energy used so far today. | UINT32 | ABCD | Wh | Read | ||
| HR | 74doc 74 (MSW) / 75 (LSW) | Yesterday energy | Energy used the previous day. | UINT32 | ABCD | Wh | Read | ||
| HR | 76doc 76 (MSW) / 77 (LSW) | Total energy | Cumulative energy. | UINT32 | ABCD | Wh | Read/write | ||
| HR | 78 | Today: year | Date the gateway uses for daily energy; default 2000. | UINT16 | Read/write | ||||
| HR | 79 | Today: month | Default 1. | UINT16 | Read/write | ||||
| HR | 80 | Today: day | Default 0. | UINT16 | Read/write | ||||
| HR | 97 | Block periodic sendings | Blocked = only changed values are forwarded. Firmware 2.3+. | UINT16 | Read/write | 0 = Non-blocked; 1 = Blocked | |||
| HR | 1150 | Machine mode | UINT16 | Read/write | 0 = Normal; 1 = Autochangeover; 2 = Limited setpoint |
Notes on this map
- All registers are 16-bit unsigned holding registers; the 'no value' marker printed -32768 is raw 0x8000 (32768).
- Energy counters are given as MSW/LSW register pairs with the most significant word at the lower address (72/73, 74/75, 76/77), so they are mapped as UINT32 high word first (ABCD). The manual's text '0..65535 (hours)' on those rows is a copy slip; the unit is stated as watt-hours.
- Temperatures follow SW4: x1 °C, x10 °C or °F. The register footnote calls x10 the default but the DIP-switch table marks x1 and Celsius as factory setting, so scale 1 / °C is used; with x10 set use 0.1.
- FC16 is accepted only with a length of 1, so the two words of Total energy (76/77) must be written one at a time.
- Left out: machine threshold and custom setpoint-limit registers 1151-1156, because the manual does not say whether they follow the SW4 x1/x10 setting.
- Error code list not reproduced; see manual section 7.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Intesis (HMS Networks) INMBSPAN001I100 Panasonic Etherea (domestic) AC to Modbus RTU gateway
What Modbus registers does the Intesis (HMS Networks) INMBSPAN001I100 Panasonic Etherea (domestic) AC to Modbus RTU gateway have?
This map lists 45 registers: 45 holding registers. 24 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Intesis (HMS Networks) INMBSPAN001I100 Panasonic Etherea (domestic) AC to Modbus RTU gateway Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Tables give a 'protocol address' (base 0) and a 'PLC address' (base 1); the protocol address is the wire address and is used for 'documented'.
What byte order does the Intesis (HMS Networks) INMBSPAN001I100 Panasonic Etherea (domestic) AC to Modbus RTU gateway use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Intesis (HMS Networks) INMBSPAN001I100 Panasonic Etherea (domestic) AC to Modbus RTU gateway?
Start with HR 0 AC unit On/Off (On/off); HR 1 AC unit mode (Mode); HR 4 AC unit temperature setpoint (Setpoint); HR 5 AC unit temperature reference (Control temperature); HR 11 Error code (Error code); HR 61 Power consumption (Power); HR 76 Total energy (Total energy).
How do I enable Modbus control of the Intesis (HMS Networks) INMBSPAN001I100 Panasonic Etherea (domestic) AC to Modbus RTU gateway?
No enable step; register 7 = 1 disables the gateway.
Where is the official Intesis (HMS Networks) INMBSPAN001I100 Panasonic Etherea (domestic) AC to Modbus RTU gateway Modbus documentation?
The source is Intesis INMBSPAN001I100 User's Manual - Modbus RTU interface for Panasonic Etherea air conditioners (User's Manual r1.5 EN), revision 2025-09, published free by Intesis (HMS Networks) at https://www.hms-networks.com/docs/default-source/products/intesis/manuals-and-guides---manuals/user-manual-inmbspan001i100.pdf.
More Intesis (HMS Networks) Modbus register maps
- Heat pump gateway (VRF / split AC gateway)
Intesis (HMS Networks) IN485DAI001A000 Daikin Altherma 3 air-to-water to Modbus RTU / BACnet MS/TP gateway
Intesis (HMS Networks) IN485DAI001A000 gateway for Daikin Altherma 3 air-to-water heat pumps, set to Modbus RTU, per user manual version 1.0.2 (2025-07-18).
Also known as: IN485DAI001A000, Daikin Altherma 3 Modbus, Intesis Altherma 3, HMS Daikin Altherma gateway - Heat pump gateway (VRF / split AC gateway)
Intesis (HMS Networks) IN485MIT001A000 Mitsubishi Electric Ecodan air-to-water to Modbus RTU / BACnet MS/TP gateway
Intesis (HMS Networks) IN485MIT001A000 gateway on the CN105 socket of Mitsubishi Electric Ecodan air-to-water heat pumps, set to Modbus RTU, per user manual version 1.0.3 (2025-12-02).
Also known as: IN485MIT001A000, Ecodan Modbus, Mitsubishi Ecodan Modbus RTU, Intesis Ecodan, HMS Ecodan gateway - VRF / split AC gateway
Intesis (HMS Networks) IN485SAM001R000 Samsung AC to Modbus RTU / BACnet MS/TP gateway
Samsung indoor units on the F3F4 remote-controller bus, gateway set to Modbus RTU (SW1-5 ON); user manual version 1.0.0.
Also known as: IN485SAM001R000, Intesis Samsung BACnet MS/TP Modbus - VRF / split AC gateway
Intesis (HMS Networks) IN770AIR***O000 700 Series Air Gateway, Bosch application (Modbus)
Intesis 700 Series Air Gateway IN770AIR***O000 with the Bosch application (XYE bus), Modbus RTU / TCP server, user manual version 1.0.13 (2025-12-09).
Also known as: IN770AIR00MO000, IN770AIR00SO000, IN770AIRXXSO000 - VRF / split AC gateway
Intesis (HMS Networks) IN770AIR***O000 700 Series Air Gateway, Midea application (Modbus)
Intesis 700 Series Air Gateway IN770AIR***O000 with the Midea application (XYE bus), Modbus RTU / TCP server, user manual version 1.0.22 (2025-12-09).
Also known as: IN770AIR00MO000, IN770AIR00SO000, IN770AIRXXSO000 - VRF / split AC gateway
Intesis (HMS Networks) IN770AIR***O000 700 Series Air Gateway, Mitsubishi Electric City Multi application (Modbus)
Intesis 700 Series Air Gateway IN770AIR***O000 with the Mitsubishi Electric City Multi application (M-NET centralised controllers (AE-200, EW-50, G-50 and others)), Modbus RTU / TCP server, user manual version 1.0.19 (2026-03-16).
Also known as: IN770AIR00MO000, IN770AIR00SO000, IN770AIRXXSO000 - VRF / split AC gateway
Intesis (HMS Networks) IN770AIR***O000 700 Series Air Gateway, Panasonic application (Modbus)
Intesis 700 Series Air Gateway IN770AIR***O000 with the Panasonic application (U1U2 P-Link / S-Link), Modbus RTU / TCP server, user manual version 1.1.7 (2025-12-09).
Also known as: IN770AIR00MO000, IN770AIR00SO000, IN770AIRXXSO000 - VRF / split AC gateway
Intesis (HMS Networks) INMBSACA001I000 XYE-bus air conditioner to Modbus RTU interface (1 unit)
INMBSACA001I000, user manual v1.8 EN; one indoor unit at unit address 0 on its own XYE bus.
Also known as: INMBSACA001I000 - VRF / split AC gateway
Intesis (HMS Networks) INMBSACA004I000 / 008I000 / 032I000 XYE-bus air conditioner to Modbus RTU interface (4 to 32 units)
INMBSACA004I000 / INMBSACA008I000 / INMBSACA032I000, user manual v1.8 EN; up to 4, 8 or 32 indoor units on one XYE bus.
Also known as: INMBSACA004I000, INMBSACA008I000, INMBSACA032I000 - VRF / split AC gateway
Intesis (HMS Networks) INMBSDAI001I000 Daikin domestic AC to Modbus RTU gateway
Single Daikin domestic (S21-connector) indoor unit via INMBSDAI001I000, user manual v1.0.2.
Also known as: INMBSDAI001I000, Intesis Daikin domestic Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSDAI001R000 Daikin VRV / Sky Air to Modbus RTU gateway
One Daikin VRV or Sky Air indoor unit (or group) on the P1P2 bus via INMBSDAI001R000, user manual v1.0.1.
Also known as: INMBSDAI001R000, Intesis Daikin VRV Modbus - Lighting gateway (DALI-2 to Modbus)
Intesis (HMS Networks) INMBSDAL0640000 / INMBSDAL1280000 DALI-2 to Modbus RTU / TCP server
Intesis Modbus Server - DALI with one (0640000, RTU + TCP) or two (1280000, TCP only) DALI channels, Modbus Addresses parameter set to Fixed; user manual r1.2 (09/2021).
Also known as: INMBSDAL0640000, INMBSDAL1280000, Intesis Modbus Server - DALI, Intesis DALI-2 Modbus gateway - VRF / split AC gateway
Intesis (HMS Networks) INMBSFGL001I000 Fujitsu domestic AC to Modbus RTU gateway
One Fujitsu domestic (RAC) or compatible VRF indoor unit, connected to the CN65/CN12/CN6 socket on the indoor board via INMBSFGL001I000, user manual v1.5 (01/2024).
Also known as: INMBSFGL001I000, FJ-AC-MBS-1, Intesis Fujitsu domestic Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSFGL001R000 Fujitsu AC to Modbus RTU gateway
One Fujitsu indoor unit, or a group of up to 16 controlled together as one, on the 3-wire BWR remote-controller bus via INMBSFGL001R000, user manual v2.4 (02/2025).
Also known as: INMBSFGL001R000, Intesis Fujitsu Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSFGL016O000 Fujitsu VRF to Modbus RTU / TCP gateway (up to 16 indoor units)
Intesis Modbus Server - Fujitsu VRF, order code INMBSFGL016O000 (legacy FJ-AC-MBS-16), user manual r1.0 (02/2020); up to 16 indoor units configured in MAPS.
Also known as: INMBSFGL016O000, FJ-AC-MBS-16, Intesis Modbus Server Fujitsu VRF - VRF / split AC gateway
Intesis (HMS Networks) INMBSHIS001R000 Hisense AC to Modbus RTU gateway
Hisense commercial-line indoor units on the AB remote-controller bus, user manual v1.6 (01/2024).
Also known as: INMBSHIS001R000, HS-RC-MBS-1, Intesis Hisense Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSHIS016O000 Hisense VRF to Modbus RTU / TCP gateway (16 / 64 indoor units)
Intesis Modbus Server - Hisense VRF, order codes INMBSHIS016O000 / INMBSHIS064O000 (legacy HS-AC-MBS-16 / HS-AC-MBS-64), user manual User Manual r1.0 EN.
Also known as: INMBSHIS016O000, INMBSHIS064O000, HS-AC-MBS-16, HS-AC-MBS-64, Intesis Modbus Server Hisense VRF - VRF / split AC gateway
Intesis (HMS Networks) INMBSHIT001R000 Hitachi AC to Modbus RTU gateway
Intesis (HMS Networks) INMBSHIT001R000 interface on the AB bus of one Hitachi commercial-line indoor unit (or group), per user manual v1.6 (01/2024).
Also known as: INMBSHIT001R000, Hitachi Modbus gateway, Intesis Hitachi - VRF / split AC gateway
Intesis (HMS Networks) INMBSHIT016O000 Hitachi VRF to Modbus RTU / TCP gateway (16 / 64 indoor units)
Intesis Modbus Server - Hitachi VRF, order codes INMBSHIT016O000 / INMBSHIT064O000 (legacy HI-AC-MBS-16 / HI-AC-MBS-64), user manual User Manual r1.2 EN.
Also known as: INMBSHIT016O000, INMBSHIT064O000, HI-AC-MBS-16, HI-AC-MBS-64, Intesis Modbus Server Hitachi VRF - VRF / split AC gateway
Intesis (HMS Networks) INMBSLGE001R000 LG AC to Modbus RTU gateway
One LG indoor unit on the BYR (wired remote) bus via INMBSLGE001R000 (legacy code LG-RC-MBS-1), user manual v1.9 (01/2024).
Also known as: INMBSLGE001R000, LG-RC-MBS-1, Intesis LG Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSLGE016O000 LG VRF to Modbus RTU / TCP gateway (16 / 64 indoor units)
Intesis Modbus - LG VRF, order codes INMBSLGE016O000 / INMBSLGE064O000 (legacy LG-AC-MBS-16 / -64), user manual r1.0 (04/2020); LG PI485 bus.
Also known as: INMBSLGE016O000, INMBSLGE064O000, LG-AC-MBS-16, LG-AC-MBS-64, Intesis Modbus LG VRF - VRF / split AC gateway
Intesis (HMS Networks) INMBSMHI001R000 Mitsubishi Heavy Industries AC to Modbus RTU gateway
Mitsubishi Heavy Industries indoor units (one, or up to 16 controlled together as one) on the XY remote-controller bus, user manual r6.4 (01/2024).
Also known as: INMBSMHI001R000, MH-RC-MBS-1, Intesis Mitsubishi Heavy Industries Modbus, Intesis MHI Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSMHI128O000 / INMBSMHI048O000 Mitsubishi Heavy Industries Superlink to Modbus gateway
Intesis Modbus Server - Mitsubishi Heavy Industries AC, order codes INMBSMHI128O000 (128 units, Superlink-II) and INMBSMHI048O000 (48 units, Superlink-I or II), user's manual r1.0 (05/2012).
Also known as: INMBSMHI128O000, INMBSMHI048O000, MH-AC-MBS-128, MH-AC-MBS-48, Intesis Modbus Server MHI Superlink - VRF / split AC gateway
Intesis (HMS Networks) INMBSMID001I000 Midea AC to Modbus RTU gateway
One Midea commercial / VRF indoor unit on the XYE bus, user manual v1.11.
Also known as: INMBSMID001I000, Intesis Midea Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSMID004I000 / 008I000 / 032I000 Midea AC to Modbus RTU interface (4 to 32 units)
INMBSMID004I000 / INMBSMID008I000 / INMBSMID032I000 / MD-AC-MBS-4 / MD-AC-MBS-8 / MD-AC-MBS-32, user manual v1.7 EN; up to 4, 8 or 32 indoor units on one XYE bus.
Also known as: INMBSMID004I000, INMBSMID008I000, INMBSMID032I000, MD-AC-MBS-4, MD-AC-MBS-8, MD-AC-MBS-32 - VRF / split AC gateway
Intesis (HMS Networks) INMBSMIT001I000 Mitsubishi Electric AC to Modbus RTU gateway
One Mitsubishi Electric Domestic, Mr. Slim or City Multi indoor unit via INMBSMIT001I000, user manual r2.8 (11/2024).
Also known as: INMBSMIT001I000, Intesis Mitsubishi Electric Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSMIT050C000 / INMBSMIT100C000 Mitsubishi Electric City Multi centralised controller to Modbus gateway
Intesis Modbus Server - Mitsubishi Electric CC, order codes INMBSMIT050C000 / INMBSMIT100C000 (legacy ME-AC-MBS-50 / -100), user manual r1.4 (05/2021); talks to City Multi centralised controllers (G-50A, GB-50A, AG-150A, EB-50, EW-50, AE-200 and newer) through their XML interface over Ethernet.
Also known as: INMBSMIT050C000, INMBSMIT100C000, ME-AC-MBS-50, ME-AC-MBS-100, Intesis Modbus Server Mitsubishi Electric CC - Heat pump gateway (VRF / split AC gateway)
Intesis (HMS Networks) INMBSPAN001A100 Panasonic Aquarea H/J/K/L/M air-to-water to Modbus RTU gateway
Intesis (HMS Networks) INMBSPAN001A100 gateway connected to Panasonic Aquarea H, J, K, L and M series air-to-water heat pumps, per user manual version 1.0.2 (2026-02-04).
Also known as: INMBSPAN001A100, Aquarea Modbus, Panasonic Aquarea Modbus RTU, Intesis Aquarea, INMBSPAN001A000 (legacy order code) - VRF / split AC gateway
Intesis (HMS Networks) INMBSPAN001R000 Panasonic AC to Modbus RTU gateway
Panasonic / Sanyo ECOi and PACi indoor units (one, or up to 16 controlled together as one) on the R1R2 remote-controller bus, user manual v2.8 (09/2025).
Also known as: INMBSPAN001R000, PA-RC2-MBS-1, Intesis Panasonic Modbus, Intesis Sanyo Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSPAN016O000 / 064O000 / 128O000 Panasonic VRF (P-Link) to Modbus gateway
Intesis Modbus Server - Panasonic, order codes INMBSPAN016O000 / 064O000 / 128O000 (legacy PA-AC-MBS-16 / -64 / -128), user manual r1.1 (11/2020); Panasonic P-Link systems.
Also known as: INMBSPAN016O000, INMBSPAN064O000, INMBSPAN128O000, PA-AC-MBS-16, PA-AC-MBS-64, PA-AC-MBS-128, Intesis Modbus Server Panasonic VRF - VRF / split AC gateway
Intesis (HMS Networks) INMBSSAM001R000 Samsung AC to Modbus RTU gateway
Samsung commercial indoor units on the F3F4/V1V2 remote-controller bus, user's manual v1.5 (01/2024).
Also known as: INMBSSAM001R000, Intesis Samsung Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSSAM001R100 Samsung NASA AC to Modbus RTU gateway
Samsung NASA-protocol commercial indoor units on the remote-controller bus, user's manual r1.4 (01/2024).
Also known as: INMBSSAM001R100, Intesis Samsung NASA Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSSAM016O000 Samsung NASA (R1/R2) VRF to Modbus gateway (4 to 64 units)
Intesis Modbus Server - Samsung NASA, order codes INMBSSAM004O000 / 008O000 / 016O000 / 064O000 (legacy SM-ACN-MBS-4/8/16/64), user manual r1.4 (12/2020); Samsung NASA R1/R2 bus.
Also known as: INMBSSAM004O000, INMBSSAM008O000, INMBSSAM016O000, INMBSSAM064O000, SM-ACN-MBS-4, SM-ACN-MBS-8, SM-ACN-MBS-16, SM-ACN-MBS-64 - VRF / split AC gateway
Intesis (HMS Networks) INMBSTOS001R000 Toshiba AC to Modbus RTU gateway
Toshiba Digital Inverter (RAV) and VRF indoor units on the AB remote bus via INMBSTOS001R0xx, user manual r2.9 (01/2024).
Also known as: INMBSTOS001R000, INMBSTOS001R0xx, Intesis Toshiba Modbus
Other ac & vrf gateways register maps
- Air handler DX kit (VRF / split AC gateway built in)
LG PAHCMR000 AHU Communication Kit (Multi V DX kit, Modbus to DDC)
LG PAHCMR000 AHU Communication Kit (R32 and R410A Multi V / single split outdoor units with a PRLK EEV kit), installation manual IM_AHU_Comm_Kit_PAHCMR000_R32_06_26.
Also known as: PAHCMR000, LG AHU Communication Kit R32, LG AHU comm kit Modbus - VRF / split AC gateway (retail controller)
Mitsubishi Electric Procon MelcoRETAIL MINI controller for Air-To-Air split units
Procon MelcoRETAIL MINI on the CN105/CN92 connector of Mitsubishi Electric M, S and P series Air-To-Air indoor units, installation manual v1.0.6, firmware 1.0.3.
Also known as: MelcoRETAIL MINI, Procon MelcoRETAIL MINI - VRF / split AC gateway (built-in indoor-unit Modbus)
Sinclair UNI SPLIT DC inverter indoor units (integrated Modbus RTU)
Sinclair All DC Inverter UNI SPLIT indoor units with the built-in Modbus RTU interface, per the UNI SPLIT Modbus user's manual.
Also known as: Sinclair UNI SPLIT, UNI SPLIT Modbus, All DC Inverter UNI SPLIT - Split AC unit (VRF / split AC gateway built in)
Aermec LPG series DC inverter air conditioners (built-in Modbus)
Aermec LPG series DC inverter units whose indoor-unit controller has the built-in Modbus RTU interface; ModBus Protocol LPG series 5385759_02 (EN 25.05).
Also known as: LPG - Sensor / controller (CO2 condensing unit gateway)
Danfoss Optyma iCO2 gateway (OP-MPAM015 / OP-MPAM005)
Danfoss Optyma iCO2 CO2 condensing units (4.6 kW MT and 20 kW MT / 10 kW LT) through their Modbus gateway, software 1.0x.
Also known as: OP-MPAM015, OP-MPAM005, Optyma iCO2 4.6 kW MT, Optyma iCO2 20 kW MT / 10 kW LT - VRF / split AC gateway
Mitsubishi Electric MelcoBEMS MINI (A1M) gateway for Air-To-Air split units
Procon MelcoBEMS MINI (A1M) on the CN105/CN92 connector of a Mitsubishi Electric Air-To-Air indoor unit, installation manual v1.1.11 (firmware 3.0.28 for revision 2-4 hardware, 3.1.1 for revision 5).
Also known as: MelcoBEMS MINI (A1M), A1M, Procon A1M, MelcoBEMS MINI
All ac & vrf gateways Modbus register maps →
Source: Intesis INMBSPAN001I100 User's Manual - Modbus RTU interface for Panasonic Etherea air conditioners · User's Manual r1.5 EN · rev. 2025-09. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.