VRF / split AC gateway · Modbus register map

Intesis (HMS Networks) INMBSPAN001I100 Panasonic Etherea (domestic) AC to Modbus RTU gateway Modbus register map

Updated 17 November 2026

Short answer

Modbus RTU server that connects to a Panasonic Etherea domestic split unit. Holding registers cover on/off, mode, fan, both vanes, setpoint, powerful/quiet/ECO modes, compressor state, demand response, outdoor and return temperatures, power, current and daily/total energy counters.

This page lists 45 Modbus registers for the Intesis (HMS Networks) INMBSPAN001I100 Panasonic Etherea (domestic) AC to Modbus RTU gateway — 24 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Intesis (HMS Networks)’s own free documentation (linked below) and checked against it.

Manufacturer
Intesis (HMS Networks)
Model
INMBSPAN001I100 Panasonic Etherea (domestic) AC to Modbus RTU gateway
Equipment type
VRF / split AC gateway
Registers
45 (24 writable)
Transport
Modbus RTU
Default unit ID
1
Default serial
9600 baud, 8N2
Documented addressing
0-based (the number printed is the address on the wire)
32-bit word order
ABCD high word first (big-endian)
Also known as
INMBSPAN001I100, Intesis Panasonic Etherea Modbus, Intesis Panasonic domestic Modbus
Source document
Intesis INMBSPAN001I100 User's Manual - Modbus RTU interface for Panasonic Etherea air conditioners · User's Manual r1.5 EN · rev. 2025-09
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Intesis (HMS Networks) INMBSPAN001I100 Panasonic Etherea (domestic) AC to Modbus RTU gateway

Integration in brief

Write 0-4 for on/off, mode, fan, vane and setpoint; poll 5, 10, 11, 66 and the energy pairs 72-77. Set the date registers 78-80 if you want daily energy to roll over correctly.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 0AC unit On/OffUINT16On/offRead/write
HR 1AC unit modeUINT16ModeRead/write
HR 4AC unit temperature setpointUINT16SetpointRead/write
HR 5AC unit temperature referenceUINT16Control temperatureRead
HR 11Error codeUINT16Error codeRead
HR 61Power consumptionUINT16PowerRead
HR 76Total energyUINT32 ABCDTotal energyRead/write

Enable Modbus control & writes

No enable step; register 7 = 1 disables the gateway.

Byte order & addressing

Network setup

Watch out for

Intesis (HMS Networks) INMBSPAN001I100 Panasonic Etherea (domestic) AC to Modbus RTU gateway Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

45 of 45 shown
Intesis (HMS Networks) INMBSPAN001I100 Panasonic Etherea (domestic) AC to Modbus RTU gateway Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0AC unit On/OffUINT16Read/write0 = Off; 1 = On
HR1AC unit modeAvailable modes depend on the indoor unit.UINT16Read/write0 = Auto; 1 = Heat; 2 = Dry; 3 = Fan; 4 = Cool
HR2AC unit fan speedAvailable speeds depend on the indoor unit.UINT16Read/write0 = Auto; 1 = Low; 2 = Mid-1; 3 = Mid-2; 4 = Mid-3; 5 = High
HR3AC unit vertical vane positionUINT16Read/write0 = Auto; 1 = Horizontal; 2 = Position-2; 3 = Position-3; 4 = Position-4; 5 = Vertical; 6 = Swing
HR4AC unit temperature setpoint16..30 °C (61..88 °F). SW4 x1 °C assumed (x10: 0.1, or °F).UINT16°CRead/write32768 = Initialisation value / no value (0x8000; manual writes -32768)
HR5AC unit temperature reference10..42 °C. SW4 x1 °C assumed (x10: 0.1, or °F).UINT16°CRead32768 = Initialisation value / no value (0x8000; manual writes -32768)
HR6Window contactVirtual window contact written from Modbus.UINT16Read/write0 = Closed; 1 = Open
HR7Gateway disablementNon-volatile.UINT16Read/write0 = Gateway enabled; 1 = Gateway disabled
HR8AC remote control disablementNon-volatile.UINT16Read/write0 = Remote control enabled; 1 = Remote control disabled
HR9AC unit operation timeHours in On state, 0..65535. Non-volatile.UINT16hRead/write
HR10AC unit alarm statusUINT16Read0 = No alarm; 1 = Alarm
HR11Error codePanasonic error code; see manual section 7.UINT16Read0 = No error; 65535 = Gateway cannot talk to the AC unit (-1)
HR13Open Window switch-off timeoutMinutes from window open to unit off, 0..30 (default 30).UINT16minRead/write
HR14Modbus RTU baud rateRate set on SW3/SW4 (2400..115200, default 9600).UINT16Read
HR15Modbus slave addressAddress set on SW3, 1..63.UINT16Read
HR21Max number of fan speedsUINT16Read
HR22External ambient temperature (from Modbus)Modbus-side room temperature; 0x8000 = none. SW4 x1 °C assumed (x10: 0.1, or °F).UINT16°CRead/write32768 = Initialisation value / no value (0x8000; manual writes -32768)
HR23AC real temperature setpointSetpoint actually applied to the unit. SW4 x1 °C assumed (x10: 0.1, or °F).UINT16°CRead
HR24Current AC max setpoint30 °C / 86 °F. SW4 x1 °C assumed (x10: 0.1, or °F).UINT16°CRead32768 = Initialisation value / no value (0x8000; manual writes -32768)
HR25Current AC min setpoint16 °C / 61 °F. SW4 x1 °C assumed (x10: 0.1, or °F).UINT16°CRead32768 = Initialisation value / no value (0x8000; manual writes -32768)
HR26AC unit horizontal vane positionUINT16Read/write0 = Auto; 1 = Horizontal; 2 = Position-2; 3 = Position-3; 4 = Position-4; 5 = Vertical
HR37Auto modeMode chosen while in Auto.UINT16Read0 = Auto; 1 = Heat; 2 = Dry; 3 = Fan; 4 = Cool
HR38PowerfulUINT16Read/write0 = Off; 1 = On
HR39QuietUINT16Read/write0 = Off; 1 = On
HR53Compressor statusUINT16Read0 = Off; 1 = To off; 2 = To on; 3 = On
HR54Compressor on timeHours, non-volatile.UINT16hRead/write
HR55Under voltage count0..300.UINT16Read/write
HR56Heat 8/10 °C modeFrost-protection heating mode.UINT16Read/write0 = Off; 1 = On
HR57ECO mode2013 (PKE) models onward. A third option, Auto Comfort, has no printed code.UINT16Read/write0 = Off; 1 = ECONAVI
HR58Demand response (DRM level)2013 models onward.UINT16Read0 = Normal; 1 = Comp OFF (DRM1); 2 = 50% (DRM2); 3 = 75% (DRM3)
HR59Human activity2013 models onward.UINT16Read0 = Exist; 1 = Not exist
HR60Outdoor intake temperature2013 models onward. SW4 x1 °C assumed (x10: 0.1, or °F).UINT16°CRead32768 = Initialisation value / no value (0x8000; manual writes -32768)
HR61Power consumptionWhole AC system, not one unit. 2013 models onward.UINT16WRead
HR62Operation currentWhole AC system. 2013 models onward.UINT16mARead
HR63Power consumption (slow)Same as 61 with slower updates.UINT16WRead
HR65Input reference temperature2013 models onward. SW4 x1 °C assumed (x10: 0.1, or °F).UINT16°CRead32768 = Initialisation value / no value (0x8000; manual writes -32768)
HR66Return path temperatureSW4 x1 °C assumed (x10: 0.1, or °F).UINT16°CRead
HR72doc 72 (MSW) / 73 (LSW)Today energyEnergy used so far today.UINT32ABCDWhRead
HR74doc 74 (MSW) / 75 (LSW)Yesterday energyEnergy used the previous day.UINT32ABCDWhRead
HR76doc 76 (MSW) / 77 (LSW)Total energyCumulative energy.UINT32ABCDWhRead/write
HR78Today: yearDate the gateway uses for daily energy; default 2000.UINT16Read/write
HR79Today: monthDefault 1.UINT16Read/write
HR80Today: dayDefault 0.UINT16Read/write
HR97Block periodic sendingsBlocked = only changed values are forwarded. Firmware 2.3+.UINT16Read/write0 = Non-blocked; 1 = Blocked
HR1150Machine modeUINT16Read/write0 = Normal; 1 = Autochangeover; 2 = Limited setpoint

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Intesis (HMS Networks) INMBSPAN001I100 Panasonic Etherea (domestic) AC to Modbus RTU gateway

What Modbus registers does the Intesis (HMS Networks) INMBSPAN001I100 Panasonic Etherea (domestic) AC to Modbus RTU gateway have?

This map lists 45 registers: 45 holding registers. 24 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Intesis (HMS Networks) INMBSPAN001I100 Panasonic Etherea (domestic) AC to Modbus RTU gateway Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Tables give a 'protocol address' (base 0) and a 'PLC address' (base 1); the protocol address is the wire address and is used for 'documented'.

What byte order does the Intesis (HMS Networks) INMBSPAN001I100 Panasonic Etherea (domestic) AC to Modbus RTU gateway use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Intesis (HMS Networks) INMBSPAN001I100 Panasonic Etherea (domestic) AC to Modbus RTU gateway?

Start with HR 0 AC unit On/Off (On/off); HR 1 AC unit mode (Mode); HR 4 AC unit temperature setpoint (Setpoint); HR 5 AC unit temperature reference (Control temperature); HR 11 Error code (Error code); HR 61 Power consumption (Power); HR 76 Total energy (Total energy).

How do I enable Modbus control of the Intesis (HMS Networks) INMBSPAN001I100 Panasonic Etherea (domestic) AC to Modbus RTU gateway?

No enable step; register 7 = 1 disables the gateway.

Where is the official Intesis (HMS Networks) INMBSPAN001I100 Panasonic Etherea (domestic) AC to Modbus RTU gateway Modbus documentation?

The source is Intesis INMBSPAN001I100 User's Manual - Modbus RTU interface for Panasonic Etherea air conditioners (User's Manual r1.5 EN), revision 2025-09, published free by Intesis (HMS Networks) at https://www.hms-networks.com/docs/default-source/products/intesis/manuals-and-guides---manuals/user-manual-inmbspan001i100.pdf.

More Intesis (HMS Networks) Modbus register maps

Other ac & vrf gateways register maps

All ac & vrf gateways Modbus register maps →

Source: Intesis INMBSPAN001I100 User's Manual - Modbus RTU interface for Panasonic Etherea air conditioners · User's Manual r1.5 EN · rev. 2025-09. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.