Easy Modbus
  1. Home
  2. Modbus register maps
  3. Intesis (HMS Networks)
  4. INMBSHIT016O000 Hitachi VRF to Modbus RTU / TCP gateway (16 / 64 indoor units)

VRF / split AC gateway · Modbus register map

Intesis (HMS Networks) INMBSHIT016O000 Hitachi VRF to Modbus RTU / TCP gateway (16 / 64 indoor units) Modbus register map

Updated 19 November 2026

Short answer

Multi-unit Modbus server for Hitachi VRF systems (H-Link bus). Every configured indoor unit gets a 100-register block with control, temperatures and status, each outdoor unit gets a 25-register block, and low addresses hold 'all units' commands. Modbus RTU and Modbus TCP work together.

This page lists 55 Modbus registers for the Intesis (HMS Networks) INMBSHIT016O000 Hitachi VRF to Modbus RTU / TCP gateway (16 / 64 indoor units) — 32 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Intesis (HMS Networks)’s own free documentation (linked below) and checked against it.

Manufacturer
Intesis (HMS Networks)
Model
INMBSHIT016O000 Hitachi VRF to Modbus RTU / TCP gateway (16 / 64 indoor units)
Equipment type
VRF / split AC gateway
Registers
55 (32 writable)
Transport
Modbus RTU, Modbus TCP
Default unit ID
Not stated
TCP port
502
Documented addressing
0-based (the number printed is the address on the wire)
Also known as
INMBSHIT016O000, INMBSHIT064O000, HI-AC-MBS-16, HI-AC-MBS-64, Intesis Modbus Server Hitachi VRF
Source document
Intesis Modbus Server - Hitachi VRF User Manual · User Manual r1.2 EN · rev. 2022-02
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Intesis (HMS Networks) INMBSHIT016O000 Hitachi VRF to Modbus RTU / TCP gateway (16 / 64 indoor units)

Integration in brief

Add the indoor units in Intesis MAPS, send the configuration, then poll each unit block from Ui x 100. Write on/off, mode, fan and setpoint (tenths of °C) in the same block.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 100IU on/offINT16Indoor unit on/offRead/write
HR 101IU operation modeINT16Operation modeRead/write
HR 104IU temperature setpointINT16Setpoint (x10)Read/write
HR 106IU inlet (return) temperatureINT16Return air temperature (x10)Read
HR 110IU unit error codeINT16Error codeRead
HR 113IU communication statusINT16Unit present / communicatingRead
HR 125IU operation conditionINT16Thermo on/off / alarm stateRead
HR 10025OU communication errorINT16Outdoor unit communication errorRead

Enable Modbus control & writes

Indoor units must be configured in MAPS; their index there decides the register block.

Byte order & addressing

Network setup

Watch out for

Intesis (HMS Networks) INMBSHIT016O000 Hitachi VRF to Modbus RTU / TCP gateway (16 / 64 indoor units) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

55 of 55 shown
Intesis (HMS Networks) INMBSHIT016O000 Hitachi VRF to Modbus RTU / TCP gateway (16 / 64 indoor units) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0On (all units)INT16Write1 = Switch all units on
HR1Off (all units)INT16Write1 = Switch all units off
HR2Mode Auto (all units)INT16Write1 = Set Auto
HR3Mode Heat (all units)INT16Write1 = Set Heat
HR4Mode Dry (all units)INT16Write1 = Set Dry
HR5Mode Fan (all units)INT16Write1 = Set Fan
HR6Mode Cool (all units)INT16Write1 = Set Cool
HR7Fan speed Auto (all units)INT16Write1 = Set fan Auto
HR8Fan speed Low (all units)INT16Write1 = Set fan Low
HR9Fan speed Mid (all units)INT16Write1 = Set fan Mid
HR10Fan speed High (all units)INT16Write1 = Set fan High
HR11Fan speed High+ (all units)INT16Write1 = Set fan High+
HR12Vane position Auto (all units)INT16Write1 = Set vane Auto
HR13Vane position 1 (all units)INT16Write1 = Set vane position 1
HR14Vane position 2 (all units)INT16Write1 = Set vane position 2
HR15Vane position 3 (all units)INT16Write1 = Set vane position 3
HR16Vane position 4 (all units)INT16Write1 = Set vane position 4
HR17Vane position 5 (all units)INT16Write1 = Set vane position 5
HR18Vane position 6 (all units)INT16Write1 = Set vane position 6
HR19Vane position 7 (all units)INT16Write1 = Set vane position 7
HR20Temperature setpoint (all units)Tenths of °C. Cool 19..30, Heat 17..30.INT16× 0.1°CWrite
HR100doc (Ui*100)+0IU on/offUnit index 1 shown; see notes.INT16Read/write0 = Off; 1 = On
HR101doc (Ui*100)+1IU operation modeINT16Read/write0 = Auto; 1 = Heat; 2 = Dry; 3 = Fan; 4 = Cool
HR102doc (Ui*100)+2IU fan speedCode 3 = High; the manual also prints High+ as 3 (see notes).INT16Read/write0 = Auto; 1 = Low; 2 = Mid
HR103doc (Ui*100)+3IU vane position0 = Auto, 1..7 = position 1..7.INT16Read/write0 = Auto; 1 = Pos 1; 2 = Pos 2; 3 = Pos 3; 4 = Pos 4; 5 = Pos 5; 6 = Pos 6; 7 = Pos 7
HR104doc (Ui*100)+4IU temperature setpointTenths of °C. Cool 19..30, Heat 17..30.INT16× 0.1°CRead/write
HR105doc (Ui*100)+5IU remote sensor temperatureTenths of °C, -63..63.INT16× 0.1°CRead
HR106doc (Ui*100)+6IU inlet (return) temperatureTenths of °C, -63..63.INT16× 0.1°CRead
HR107doc (Ui*100)+7IU outlet (supply) temperatureTenths of °C, -63..63.INT16× 0.1°CRead
HR108doc (Ui*100)+8IU gas pipe temperatureTenths of °C, -63..63.INT16× 0.1°CRead
HR109doc (Ui*100)+9IU liquid pipe temperatureTenths of °C, -63..63.INT16× 0.1°CRead
HR110doc (Ui*100)+10IU unit error codeManufacturer error code.INT16Read
HR111doc (Ui*100)+11IU filter alarmINT16Read0 = Normal; 1 = Alarm
HR112doc (Ui*100)+12IU filter alarm resetINT16Write1 = Reset
HR113doc (Ui*100)+13IU communication statusINT16Read0 = Not existing; 1 = Exists
HR114doc (Ui*100)+14IU allow on/off from RCINT16Read/write0 = Allow; 1 = Not allow
HR115doc (Ui*100)+15IU allow mode from RCINT16Read/write0 = Allow; 1 = Not allow
HR116doc (Ui*100)+16IU allow setpoint from RCINT16Read/write0 = Allow; 1 = Not allow
HR117doc (Ui*100)+17IU allow fan from RCINT16Read/write0 = Allow; 1 = Not allow
HR118doc (Ui*100)+18IU unit typeINT16Read0 = Not defined; 1 = SS; 2 = FC; 3 = VRF; 4 = IU; 5 = ES
HR119doc (Ui*100)+19IU unit address1..64.INT16Read
HR120doc (Ui*100)+20IU system address1..64.INT16Read
HR121doc (Ui*100)+21IU dehumidificationINT16Read0 = Disabled; 1 = Enabled
HR122doc (Ui*100)+22IU dehumidification correctionINT16Read/write0 = 0; 1 = -1; 2 = -2
HR123doc (Ui*100)+23IU compressor stop cause255 = operation off; other codes per the manufacturer.INT16Read255 = Operation off
HR124doc (Ui*100)+24IU expansion valve opening0..100 %.INT16%Read
HR125doc (Ui*100)+25IU operation conditionINT16Read0 = Off; 1 = Thermo off; 2 = Thermo on; 3 = Alarm
HR126doc (Ui*100)+26IU remote controller sensor temperatureTenths of °C, -63..63.INT16× 0.1°CRead
HR127doc (Ui*100)+27IU RC sensor configurationRCS as printed (remote controller sensor).INT16Read0 = Without RCS; 1 = With RCS
HR10025doc (OU*25)+10000+0OU communication errorOutdoor unit address 1 shown; see notes.INT16Read0 = No error; 1 = Error
HR10026doc (OU*25)+10000+1OU outdoor air temperatureRange -50..99 °C; no x10 marker printed.INT16°CRead
HR10027doc (OU*25)+10000+2OU compressor top temperatureRange 0..200 °C.INT16°CRead
HR10028doc (OU*25)+10000+3OU compressor frequencyRange 0..255 Hz.INT16HzRead
HR10029doc (OU*25)+10000+4OU total compressor currentRange 0..255 A.INT16ARead
HR10030doc (OU*25)+10000+5OU expansion valve 1 opening0..100 %.INT16%Read

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Intesis (HMS Networks) INMBSHIT016O000 Hitachi VRF to Modbus RTU / TCP gateway (16 / 64 indoor units)

What Modbus registers does the Intesis (HMS Networks) INMBSHIT016O000 Hitachi VRF to Modbus RTU / TCP gateway (16 / 64 indoor units) have?

This map lists 55 registers: 55 holding registers. 32 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Intesis (HMS Networks) INMBSHIT016O000 Hitachi VRF to Modbus RTU / TCP gateway (16 / 64 indoor units) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual states formula results are link-layer addresses with the first register at 0, so they are wire addresses. Indoor unit index Ui (1..64, from the MAPS Units Configuration tab) uses Ui x 100 + offset; outdoor unit address OU (1..64) uses OU x 25 + 10000 + offset. This file lists Ui = 1 (100..127) and OU = 1 (10025..10030).

What are the minimum Modbus registers to integrate the Intesis (HMS Networks) INMBSHIT016O000 Hitachi VRF to Modbus RTU / TCP gateway (16 / 64 indoor units)?

Start with HR 100 IU on/off (Indoor unit on/off); HR 101 IU operation mode (Operation mode); HR 104 IU temperature setpoint (Setpoint (x10)); HR 106 IU inlet (return) temperature (Return air temperature (x10)); HR 110 IU unit error code (Error code); HR 113 IU communication status (Unit present / communicating); HR 125 IU operation condition (Thermo on/off / alarm state); HR 10025 OU communication error (Outdoor unit communication error).

How do I enable Modbus control of the Intesis (HMS Networks) INMBSHIT016O000 Hitachi VRF to Modbus RTU / TCP gateway (16 / 64 indoor units)?

Indoor units must be configured in MAPS; their index there decides the register block.

Where is the official Intesis (HMS Networks) INMBSHIT016O000 Hitachi VRF to Modbus RTU / TCP gateway (16 / 64 indoor units) Modbus documentation?

The source is Intesis Modbus Server - Hitachi VRF User Manual (User Manual r1.2 EN), revision 2022-02, published free by Intesis (HMS Networks) at https://www.hms-networks.com/docs/default-source/products/intesis/manuals-and-guides---manuals/user-manual-inmbshitxxxo000.pdf.

More Intesis (HMS Networks) Modbus register maps

Other ac & vrf gateways register maps

All ac & vrf gateways Modbus register maps →

Source: Intesis Modbus Server - Hitachi VRF User Manual · User Manual r1.2 EN · rev. 2022-02. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.