  3. Intesis (HMS Networks)
  4. INMBSSAM001R100 Samsung NASA AC to Modbus RTU gateway

VRF / split AC gateway · Modbus register map

Intesis (HMS Networks) INMBSSAM001R100 Samsung NASA AC to Modbus RTU gateway Modbus register map

Updated 17 November 2026

Short answer

Newer Intesis Modbus RTU server for Samsung NASA commercial units. Holding registers cover on/off, mode, fan (incl. turbo), both vanes, setpoint, external temperature, window contact, filter status and reset, alarm and error code, return-air temperature and selection of which indoor unit on the bus is reported.

This page lists 29 Modbus registers for the Intesis (HMS Networks) INMBSSAM001R100 Samsung NASA AC to Modbus RTU gateway — 16 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Intesis (HMS Networks)’s own free documentation (linked below) and checked against it.

Manufacturer
Intesis (HMS Networks)
Model
INMBSSAM001R100 Samsung NASA AC to Modbus RTU gateway
Equipment type
VRF / split AC gateway
Registers
29 (16 writable)
Transport
Modbus RTU
Default unit ID
1
Default serial
9600 baud, 8N2
Documented addressing
0-based (the number printed is the address on the wire)
Also known as
INMBSSAM001R100, Intesis Samsung NASA Modbus
Source document
Intesis INMBSSAM001R100 (Samsung NASA) Modbus RTU (EIA-485) Interface for Samsung air conditioners - User's Manual · User's Manual r1.4 EN · rev. 2024-01
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Intesis (HMS Networks) INMBSSAM001R100 Samsung NASA AC to Modbus RTU gateway

Integration in brief

Write 0-4 for control and poll 5, 10, 11, 44 and 66. With several indoor units on one RC bus, use 68/69 to see which unit's status is being reported.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 0AC unit On/OffUINT16On/offRead/write
HR 1AC unit modeUINT16ModeRead/write
HR 4AC unit temperature setpointINT16SetpointRead/write
HR 5AC unit temperature referenceINT16Control temperatureRead
HR 11Error codeUINT16Error codeRead
HR 44Filter statusUINT16Filter statusRead

Enable Modbus control & writes

No enable step; register 7 = 1 disables the gateway.

Byte order & addressing

Network setup

Watch out for

Intesis (HMS Networks) INMBSSAM001R100 Samsung NASA AC to Modbus RTU gateway Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

29 of 29 shown
Intesis (HMS Networks) INMBSSAM001R100 Samsung NASA AC to Modbus RTU gateway Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0AC unit On/OffUINT16Read/write0 = Off; 1 = On
HR1AC unit modeAvailable modes depend on the indoor unit.UINT16Read/write0 = Auto; 1 = Heat; 2 = Dry; 3 = Fan; 4 = Cool
HR2AC unit fan speedAvailable speeds depend on the indoor unit.UINT16Read/write0 = Auto; 1 = Low; 2 = Mid; 3 = High; 4 = Turbo
HR3AC unit up/down vaneUINT16Read/write0 = Swing off (Auto); 10 = Swing on
HR4AC unit temperature setpointCool 18..30 °C, heat 16..30 °C. SW4 x1 °C assumed (x10: 0.1, or °F).INT16°CRead/write-32768 = Initialisation value / no value (0x8000)
HR5AC unit temperature reference-41..38 °C; control temperature. SW4 x1 °C assumed (x10: 0.1, or °F).INT16°CRead-32768 = Initialisation value / no value (0x8000)
HR6Window contactVirtual window contact written from Modbus.UINT16Read/write0 = Closed; 1 = Open
HR7Gateway disablementNon-volatile.UINT16Read/write0 = Gateway enabled; 1 = Gateway disabled
HR8AC remote control disablementNon-volatile.UINT16Read/write0 = Remote controller enabled; 1 = Remote controller disabled
HR9AC unit operation timeHours in On state, 0..65535. Non-volatile.UINT16hRead/write
HR10AC unit alarm statusUINT16Read0 = No alarm; 1 = Alarm
HR11Error codeSamsung error code; see manual section 7.UINT16Read0 = No error; 65535 = Gateway cannot talk to the indoor unit (-1)
HR13Open Window switch-off timeoutMinutes from window open to unit off, 0..30 (default 30).UINT16minRead/write
HR14Modbus RTU baud rateRate set on SW3/SW4 (2400..115200, default 9600).UINT16Read
HR15Modbus slave addressAddress set on SW3, 1..63.UINT16Read
HR22External ambient temperature (from Modbus)Sent to the RC bus; 0x8000 = none. SW4 x1 °C assumed (x10: 0.1, or °F).INT16°CRead/write-32768 = Initialisation value / no value (0x8000)
HR23AC real temperature setpointSetpoint used by the unit, 16..31 °C. SW4 x1 °C assumed (x10: 0.1, or °F).INT16°CRead
HR26AC unit left/right vaneUINT16Read/write0 = Swing off (Auto); 10 = Swing on
HR40Window contact on/off disablementShows whether the window contact is currently blocking on/off.UINT16Read0 = Not disabling on/off; 1 = Disabling on/off
HR43Filter resetUINT16Write1 = Filter reset
HR44Filter statusUINT16Read0 = OK; 1 = Filter cleaning
HR49Device IDReads 0x2E00.UINT16Read
HR50Software versionUINT16Read
HR66Return path temperatureReturn-air sensor. SW4 x1 °C assumed (x10: 0.1, or °F).INT16°CRead-32768 = Initialisation value / no value (0x8000)
HR67Number of indoor units connectedUnits on the same RC bus.UINT16Read
HR68Internal IU addressPosition in the gateway's sorted list of the unit whose status is shown.UINT16Read/write
HR69IU address status reportedAddress of the indoor unit whose status is reported.UINT16Read
HR97Block periodic sendingsBlocked = only changed values are forwarded. Firmware 0.1+.UINT16Read/write0 = Non-blocked; 1 = Blocked
HR99Reset / reboot deviceUINT16Write1 = Reset

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Intesis (HMS Networks) INMBSSAM001R100 Samsung NASA AC to Modbus RTU gateway

What Modbus registers does the Intesis (HMS Networks) INMBSSAM001R100 Samsung NASA AC to Modbus RTU gateway have?

This map lists 29 registers: 29 holding registers. 16 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Intesis (HMS Networks) INMBSSAM001R100 Samsung NASA AC to Modbus RTU gateway Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Tables give a 'protocol address' (base 0) and a 'PLC address' (base 1); the protocol address is the wire address and is used for 'documented'.

What are the minimum Modbus registers to integrate the Intesis (HMS Networks) INMBSSAM001R100 Samsung NASA AC to Modbus RTU gateway?

Start with HR 0 AC unit On/Off (On/off); HR 1 AC unit mode (Mode); HR 4 AC unit temperature setpoint (Setpoint); HR 5 AC unit temperature reference (Control temperature); HR 11 Error code (Error code); HR 44 Filter status (Filter status).

How do I enable Modbus control of the Intesis (HMS Networks) INMBSSAM001R100 Samsung NASA AC to Modbus RTU gateway?

No enable step; register 7 = 1 disables the gateway.

Where is the official Intesis (HMS Networks) INMBSSAM001R100 Samsung NASA AC to Modbus RTU gateway Modbus documentation?

The source is Intesis INMBSSAM001R100 (Samsung NASA) Modbus RTU (EIA-485) Interface for Samsung air conditioners - User's Manual (User's Manual r1.4 EN), revision 2024-01, published free by Intesis (HMS Networks) at https://www.hms-networks.com/docs/default-source/products/intesis/manuals-and-guides---manuals/user-manual-inmbssam001r100.pdf.