VRF / split AC gateway · Modbus register map

Intesis (HMS Networks) IN770AIR***O000 700 Series Air Gateway, Bosch application (Modbus) Modbus register map

Updated 19 November 2026

Short answer

Intesis 700 Series gateway on the XYE bus of Bosch commercial / VRF systems serving Modbus RTU and TCP. Each unit index gets a 100-register block with on/off, mode, setpoint, fan, vanes, room temperature, errors and locks; low addresses hold all-unit commands.

This page lists 38 Modbus registers for the Intesis (HMS Networks) IN770AIR***O000 700 Series Air Gateway, Bosch application (Modbus) — 33 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Intesis (HMS Networks)’s own free documentation (linked below) and checked against it.

Manufacturer
Intesis (HMS Networks)
Model
IN770AIR***O000 700 Series Air Gateway, Bosch application (Modbus)
Equipment type
VRF / split AC gateway
Registers
38 (33 writable)
Transport
Modbus RTU, Modbus TCP
Default unit ID
Not stated
Documented addressing
0-based (the number printed is the address on the wire)
Also known as
IN770AIR00MO000, IN770AIR00SO000, IN770AIRXXSO000
Source document
700 Series Air Gateway - IN770AIR***O000, Bosch to Modbus, KNX, BACnet, MQTT and Home Automation - User Manual · User Manual Version 1.0.13 · rev. 2025-12-09
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Intesis (HMS Networks) IN770AIR***O000 700 Series Air Gateway, Bosch application (Modbus)

Integration in brief

Pick the Bosch application and the Modbus interface in Intesis MAPS, discover or add the units, send the project, then read and write each unit's block.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 100IU on/offUINT16On/offRead/write
HR 101IU operation modeUINT16ModeRead/write
HR 102IU temperature setpointUINT16Setpoint (x10)Read/write
HR 103IU fan speedUINT16Fan speedRead/write
HR 105IU room temperatureINT16Room temperature (x10)Read
HR 106IU unit error codeUINT16Error codeRead
HR 107IU communication errorUINT16Communication errorRead

Enable Modbus control & writes

The units must be set up in Intesis MAPS; the unit index used in the formulas is the one shown on the Signals tab.

Byte order & addressing

Network setup

Watch out for

Intesis (HMS Networks) IN770AIR***O000 700 Series Air Gateway, Bosch application (Modbus) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

38 of 38 shown
Intesis (HMS Networks) IN770AIR***O000 700 Series Air Gateway, Bosch application (Modbus) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0On (all units)UINT16Write1 = Set the units on
HR1Off (all units)UINT16Write1 = Set the units off
HR2Mode Auto (all units)UINT16Write1 = Execute
HR3Mode Heat (all units)UINT16Write1 = Execute
HR4Mode Dry (all units)UINT16Write1 = Execute
HR5Mode Fan (all units)UINT16Write1 = Execute
HR6Mode Cool (all units)UINT16Write1 = Execute
HR7Fan speed Auto (all units)UINT16Write1 = Execute
HR8Fan speed Low (all units)UINT16Write1 = Execute
HR9Fan speed Mid (all units)UINT16Write1 = Execute
HR10Fan speed High (all units)UINT16Write1 = Execute
HR11Swing on (all units)UINT16Write1 = Execute
HR12Swing off (all units)UINT16Write1 = Execute
HR13Temperature setpoint (all units)Tenths of °C, 17..30.UINT16× 0.1°CWrite
HR14Operating mode force on (all units)UINT16Write1 = Force operating mode
HR15Operating mode force off (all units)UINT16Write1 = Unforce operating mode
HR16Remote control lock on (all units)UINT16Write1 = Lock remote control
HR17Remote control lock off (all units)UINT16Write1 = Unlock remote control
HR18Fan speed (all units)UINT16Write0 = Auto; 1 = Speed 1; 2 = Speed 2; 3 = Speed 3; 4 = Speed 4; 5 = Speed 5; 6 = Speed 6; 7 = Speed 7
HR19Vane left/right (all units)UINT16Write0 = Stop; 1 = Step 1; 2 = Step 2; 3 = Step 3; 4 = Step 4; 5 = Step 5; 6 = Swing
HR20Vane up/down (all units)UINT16Write0 = Stop; 1 = Step 1; 2 = Step 2; 3 = Step 3; 4 = Step 4; 5 = Step 5; 6 = Swing
HR100doc (IU address[1..N] × 100) + 0IU on/offUnit index 1 shown; see notes.UINT16Read/write0 = Off; 1 = On
HR101doc (IU address[1..N] × 100) + 1IU operation modeCodes 5..8 are read-only.UINT16Read/write0 = Heat; 1 = Cool; 2 = Fan; 3 = Dry; 4 = Auto; 5 = AutoHeat; 6 = AutoCool; 7 = AutoDry; 8 = AutoFan
HR102doc (IU address[1..N] × 100) + 2IU temperature setpointTenths of °C, 17..30.UINT16× 0.1°CRead/write
HR103doc (IU address[1..N] × 100) + 3IU fan speedThe manual also prints an extended set (0 Auto, 1..7) at this address.UINT16Read/write0 = Auto; 1 = Low; 2 = Med; 3 = High
HR104doc (IU address[1..N] × 100) + 4IU vane swingUINT16Read/write0 = Swing off; 1 = Swing on
HR105doc (IU address[1..N] × 100) + 5IU room temperatureTenths of °C, -20..100.INT16× 0.1°CRead
HR106doc (IU address[1..N] × 100) + 6IU unit error code0 = no error; 1..255 (extended signal 1..260) = error.UINT16Read0 = No error
HR107doc (IU address[1..N] × 100) + 7IU communication errorUINT16Read0 = No error; 1 = Error
HR108doc (IU address[1..N] × 100) + 8IU remote control lockUINT16Read/write0 = Unlock; 1 = Lock
HR109doc (IU address[1..N] × 100) + 9IU force operating modeUINT16Read/write0 = No force; 1 = Force
HR128doc (IU address[1..N] × 100) + 28IU vane left/rightUINT16Read/write0 = Stop; 1 = Step 1; 2 = Step 2; 3 = Step 3; 4 = Step 4; 5 = Step 5; 6 = Swing
HR129doc (IU address[1..N] × 100) + 29IU vane up/downUINT16Read/write0 = Stop; 1 = Step 1; 2 = Step 2; 3 = Step 3; 4 = Step 4; 5 = Step 5; 6 = Swing
HR132doc (IU address[1..N] × 100) + 32IU control lock, mode HeatUINT16Read/write0 = Unlock; 1 = Lock
HR133doc (IU address[1..N] × 100) + 33IU control lock, mode CoolUINT16Read/write0 = Unlock; 1 = Lock
HR134doc (IU address[1..N] × 100) + 34IU control lock, mode FanUINT16Read/write0 = Unlock; 1 = Lock
HR10000doc (OU address[1..N] × 10000) + 0OU 1 error code0 = no error, 1..260 = error. Outdoor index 1 shown.UINT16Read0 = No error
HR10001doc (OU address[1..N] × 10000) + 1OU 1 communication errorUINT16Read0 = No error; 1 = Error

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Intesis (HMS Networks) IN770AIR***O000 700 Series Air Gateway, Bosch application (Modbus)

What Modbus registers does the Intesis (HMS Networks) IN770AIR***O000 700 Series Air Gateway, Bosch application (Modbus) have?

This map lists 38 registers: 38 holding registers. 33 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Intesis (HMS Networks) IN770AIR***O000 700 Series Air Gateway, Bosch application (Modbus) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual states no address base and gives no example frame; the first all-unit register is printed at Modbus address 0 and nothing in the tables contradicts that, so printed addresses are taken as wire addresses. Unit index n (1..N, as shown in MAPS) uses n x 100 + offset; outdoor index n uses n x 10000 + offset. This file lists unit 1 (100..134) and outdoor unit 1 (10000..10001).

What are the minimum Modbus registers to integrate the Intesis (HMS Networks) IN770AIR***O000 700 Series Air Gateway, Bosch application (Modbus)?

Start with HR 100 IU on/off (On/off); HR 101 IU operation mode (Mode); HR 102 IU temperature setpoint (Setpoint (x10)); HR 103 IU fan speed (Fan speed); HR 105 IU room temperature (Room temperature (x10)); HR 106 IU unit error code (Error code); HR 107 IU communication error (Communication error).

How do I enable Modbus control of the Intesis (HMS Networks) IN770AIR***O000 700 Series Air Gateway, Bosch application (Modbus)?

The units must be set up in Intesis MAPS; the unit index used in the formulas is the one shown on the Signals tab.

Where is the official Intesis (HMS Networks) IN770AIR***O000 700 Series Air Gateway, Bosch application (Modbus) Modbus documentation?

The source is 700 Series Air Gateway - IN770AIR***O000, Bosch to Modbus, KNX, BACnet, MQTT and Home Automation - User Manual (User Manual Version 1.0.13), revision 2025-12-09, published free by Intesis (HMS Networks) at https://www.hms-networks.com/docs/default-source/products/intesis/manuals-and-guides---manuals/user-manual-in770bosxxxo000.pdf.

More Intesis (HMS Networks) Modbus register maps

Other ac & vrf gateways register maps

All ac & vrf gateways Modbus register maps →

Source: 700 Series Air Gateway - IN770AIR***O000, Bosch to Modbus, KNX, BACnet, MQTT and Home Automation - User Manual · User Manual Version 1.0.13 · rev. 2025-12-09. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.