VRF / split AC gateway · Modbus register map

Mitsubishi Electric MelcoBEMS MINI (A1M+) gateway for Air-To-Air split units (M, S and P series) Modbus register map

Updated 19 November 2026

Short answer

Small Procon protocol converter that plugs into the CN105 connector of one Mitsubishi Electric split indoor unit and serves Modbus RTU (RS-485) or Modbus TCP. For air-to-air units it exposes mode, setpoint, fan, vane and on/off, room temperature and fault code, plus a BMS room-sensor offset feature and an optional deadband auto-changeover.

This page lists 34 Modbus registers for the Mitsubishi Electric MelcoBEMS MINI (A1M+) gateway for Air-To-Air split units (M, S and P series) — 20 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Mitsubishi Electric’s own free documentation (linked below) and checked against it.

Manufacturer
Mitsubishi Electric
Model
MelcoBEMS MINI (A1M+) gateway for Air-To-Air split units (M, S and P series)
Equipment type
VRF / split AC gateway
Registers
34 (20 writable)
Transport
Modbus RTU, Modbus TCP
Default unit ID
Not stated
TCP port
502
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
Firmware
4.1.1
Also known as
A1M+, MelcoBEMS MINI, Procon A1M+, MelcoBEMS MINI A1M PLUS, A1M+ ATA
Source document
Procon MelcoBEMS MINI (A1M+) Installation Manual · Manual version 1.0.3 · rev. 2025-09-18
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Mitsubishi Electric MelcoBEMS MINI (A1M+) gateway for Air-To-Air split units (M, S and P series)

Integration in brief

Set DIP 7 on for Modbus RTU, pick the slave address on DIP 1-5 and DIP 6 on for 9600 / no parity, then use holding registers 0-3 and 7 for mode, setpoint, fan, vane and on/off, and poll 8-9 for room temperature and fault.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 7Drive on/offUINT16On/offRead/write
HR 0Drive modeUINT16ModeRead/write
HR 1Temperature setpointUINT16Setpoint (x10)Read/write
HR 2Fan speedUINT16Fan speedRead/write
HR 8Room temperatureUINT16Room temperature (x10)Read
HR 9Fault code (hex)UINT16Fault code (0x8000 = none)Read
HR 13System type detectedUINT16Confirms an air-to-air unit was detectedRead

Enable Modbus control & writes

DIP switch 7 on selects Modbus RTU on RS-485 (off = BACnet MS/TP and BACnet IP). Modbus TCP on the Ethernet port came with firmware 4.1.0; the manual says the Ethernet protocol follows the DIP switch setting and needs application mode (DIP switches not all off).

Byte order & addressing

Network setup

Watch out for

Mitsubishi Electric MelcoBEMS MINI (A1M+) gateway for Air-To-Air split units (M, S and P series) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

34 of 34 shown
Mitsubishi Electric MelcoBEMS MINI (A1M+) gateway for Air-To-Air split units (M, S and P series) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
CO0doc 00001Drive on/offSame as holding register 7.BITRead/write0 = Drive off; 1 = Drive on
IR0doc 30001Room temperature°C x 10.UINT16× 0.1°CRead
IR1doc 30002Fault code (hex)UINT16Read27033 = Bad communication with indoor unit (0x6999); 32768 = No error (0x8000)
IR3doc 30004Firmware versionUINT16Read
IR5doc 30006Modbus comms counterUINT16Read
IR8doc 30009Fault code (decimal)UINT16Read6999 = Bad communication with indoor unit; 8000 = No error
IR9doc 30010System type detectedUINT16Read0 = ATA (air-to-air); 1 = ATW (air-to-water); 2 = Lossnay; 255 = Undetermined (no unit detected yet)
IR10doc 30011Deadband enabled stateUINT16Read0 = Deadband disabled (DIP 8 off); 1 = Deadband enabled (DIP 8 on)
HR0doc 40001Drive modeCodes marked read-only (i-see) cannot be written.UINT16Read/write1 = Heating; 2 = Humidity reduction; 3 = Cooling; 7 = Ventilation / clean air; 8 = Auto; 9 = i-see heating (read only); 10 = i-see humidity reduction (read only); 11 = i-see cooling (read only)
HR1doc 40002Temperature setpoint°C x 10 (200 = 20 °C).UINT16× 0.1°CRead/write
HR2doc 40003Fan speedUINT16Read/write0 = Auto; 2 = Quiet; 3 = Weak; 5 = Strong; 6 = Very strong (SHi)
HR3doc 40004Air directionUINT16Read/write0 = Auto; 1 = Position 1; 2 = Position 2; 3 = Position 3; 4 = Position 4; 5 = Position 5; 7 = Swing
HR4doc 40005Modbus slave ID / BACnet station IDSlave ID 1..247 (Modbus) or station 1..127 (BACnet); used when DIP 1-5 are all on.UINT16Read/write
HR5doc 40006RS-485 baud rateUsed when DIP 6 is off. BACnet accepts only 0, 4, 6, 8, 11.UINT16Read/write0 = 9600; 1 = 1200; 2 = 2400; 3 = 4800; 4 = 9600; 5 = 14400; 6 = 19200; 7 = 28800; 8 = 38400; 9 = 56000; 10 = 57600; 11 = 76800; 12 = 115200
HR6doc 40007RS-485 parityUsed when DIP 6 is off.UINT16Read/write0 = None; 1 = Even; 2 = Odd
HR7doc 40008Drive on/offUINT16Read/write0 = Drive off; 1 = Drive on
HR8doc 40009Room temperatureReturn air, °C x 10. Same as input register 0.UINT16× 0.1°CRead
HR9doc 40010Fault code (hex)Indoor unit fault code in hex form; see indoor unit documentation.UINT16Read27033 = Bad communication with indoor unit (0x6999); 32768 = No error (0x8000)
HR10doc 40011Firmware versionUINT16Read
HR11doc 40012Modbus comms counterCounts valid Modbus commands; wraps after 65535.UINT16Read
HR12doc 40013Fault code (decimal)UINT16Read6999 = Bad communication with indoor unit; 8000 = No error
HR13doc 40014System type detectedUINT16Read0 = ATA (air-to-air); 1 = ATW (air-to-water); 2 = Lossnay; 255 = Undetermined (no unit detected yet)
HR14doc 40015Deadband enabled stateUINT16Read0 = Deadband disabled (DIP 8 off); 1 = Deadband enabled (DIP 8 on)
HR15doc 40016BMS room temperature (signed)°C x 10 from the BMS sensor; 0xFF9C = -10 °C .. 0x01F4 = 50 °C.INT16× 0.1°CRead/write
HR16doc 40017BMS room temperatureUnsigned twin, °C x 10, 0..500. Not kept over power loss.UINT16× 0.1°CRead/write
HR17doc 40018BMS virtual setpoint°C x 10, 100..400. Non-volatile.UINT16× 0.1°CRead/write
HR18doc 40019Deadband heating setpointWhole °C, default 19; at least 2 °C below the cooling setpoint.UINT16°CRead/write
HR19doc 40020Deadband cooling setpointWhole °C, default 23; at least 2 °C above the heating setpoint.UINT16°CRead/write
HR272doc 40273BACnet device instance (high 16 bits)UINT16Read/write
HR273doc 40274BACnet device instance (low 16 bits)UINT16Read/write
HR274doc 40275BACnet max masterUINT16Read/write
HR275doc 40276BACnet max info framesUINT16Read/write
HR276doc 40277BACnet APDU timeoutUINT16msRead/write
HR277doc 40278BACnet APDU retriesUINT16Read/write

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Mitsubishi Electric MelcoBEMS MINI (A1M+) gateway for Air-To-Air split units (M, S and P series)

What Modbus registers does the Mitsubishi Electric MelcoBEMS MINI (A1M+) gateway for Air-To-Air split units (M, S and P series) have?

This map lists 34 registers: 1 coil, 7 input registers, 26 holding registers. 20 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Mitsubishi Electric MelcoBEMS MINI (A1M+) gateway for Air-To-Air split units (M, S and P series) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Each row prints both an 'Address' (0-based) and a 'Modicon address' (40001 = holding address 0, 30001 = input address 0, 00001 = coil 0). The 0-based address is the wire address.

What are the minimum Modbus registers to integrate the Mitsubishi Electric MelcoBEMS MINI (A1M+) gateway for Air-To-Air split units (M, S and P series)?

Start with HR 7 Drive on/off (On/off); HR 0 Drive mode (Mode); HR 1 Temperature setpoint (Setpoint (x10)); HR 2 Fan speed (Fan speed); HR 8 Room temperature (Room temperature (x10)); HR 9 Fault code (hex) (Fault code (0x8000 = none)); HR 13 System type detected (Confirms an air-to-air unit was detected).

How do I enable Modbus control of the Mitsubishi Electric MelcoBEMS MINI (A1M+) gateway for Air-To-Air split units (M, S and P series)?

DIP switch 7 on selects Modbus RTU on RS-485 (off = BACnet MS/TP and BACnet IP). Modbus TCP on the Ethernet port came with firmware 4.1.0; the manual says the Ethernet protocol follows the DIP switch setting and needs application mode (DIP switches not all off).

Where is the official Mitsubishi Electric MelcoBEMS MINI (A1M+) gateway for Air-To-Air split units (M, S and P series) Modbus documentation?

The source is Procon MelcoBEMS MINI (A1M+) Installation Manual (Manual version 1.0.3), revision 2025-09-18, published free by Mitsubishi Electric at https://library.mitsubishielectric.co.uk/pdf/download_full/5538.