- MelcoBEMS MINI (A1M+) gateway for Air-To-Air split units (M, S and P series)
VRF / split AC gateway · Modbus register map
Mitsubishi Electric MelcoBEMS MINI (A1M+) gateway for Air-To-Air split units (M, S and P series) Modbus register map
Updated 19 November 2026
Small Procon protocol converter that plugs into the CN105 connector of one Mitsubishi Electric split indoor unit and serves Modbus RTU (RS-485) or Modbus TCP. For air-to-air units it exposes mode, setpoint, fan, vane and on/off, room temperature and fault code, plus a BMS room-sensor offset feature and an optional deadband auto-changeover.
This page lists 34 Modbus registers for the Mitsubishi Electric MelcoBEMS MINI (A1M+) gateway for Air-To-Air split units (M, S and P series) — 20 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Mitsubishi Electric’s own free documentation (linked below) and checked against it.
- Manufacturer
- Mitsubishi Electric
- Model
- MelcoBEMS MINI (A1M+) gateway for Air-To-Air split units (M, S and P series)
- Equipment type
- VRF / split AC gateway
- Registers
- 34 (20 writable)
- Transport
- Modbus RTU, Modbus TCP
- Default unit ID
- Not stated
- TCP port
- 502
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- Firmware
- 4.1.1
- Also known as
- A1M+, MelcoBEMS MINI, Procon A1M+, MelcoBEMS MINI A1M PLUS, A1M+ ATA
Integration notes: Mitsubishi Electric MelcoBEMS MINI (A1M+) gateway for Air-To-Air split units (M, S and P series)
Set DIP 7 on for Modbus RTU, pick the slave address on DIP 1-5 and DIP 6 on for 9600 / no parity, then use holding registers 0-3 and 7 for mode, setpoint, fan, vane and on/off, and poll 8-9 for room temperature and fault.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 7 | Drive on/off | UINT16 | On/off | Read/write |
| HR 0 | Drive mode | UINT16 | Mode | Read/write |
| HR 1 | Temperature setpoint | UINT16 | Setpoint (x10) | Read/write |
| HR 2 | Fan speed | UINT16 | Fan speed | Read/write |
| HR 8 | Room temperature | UINT16 | Room temperature (x10) | Read |
| HR 9 | Fault code (hex) | UINT16 | Fault code (0x8000 = none) | Read |
| HR 13 | System type detected | UINT16 | Confirms an air-to-air unit was detected | Read |
Enable Modbus control & writes
DIP switch 7 on selects Modbus RTU on RS-485 (off = BACnet MS/TP and BACnet IP). Modbus TCP on the Ethernet port came with firmware 4.1.0; the manual says the Ethernet protocol follows the DIP switch setting and needs application mode (DIP switches not all off).
Byte order & addressing
- Fault code 0x8000 (decimal register: 8000) means no fault; 0x6999 / 6999 means the gateway cannot talk to the indoor unit.
- Fan speed codes skip 1 and 4: 0 Auto, 2 Quiet, 3 Weak, 5 Strong, 6 Very strong.
- The i-see mode codes 9-11 are read-only.
Network setup
- RS-485 A, B and GND must all be connected; shielded cable, daisy chain only.
- Factory IP 192.168.92.114, Modbus TCP port 502.
- Node address 1..30 on DIP 1-5 (binary); all off = 1.
Watch out for
- The gateway detects ATA vs ATW by itself; check register 13 reads 0 before trusting the ATA map.
Mitsubishi Electric MelcoBEMS MINI (A1M+) gateway for Air-To-Air split units (M, S and P series) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| CO | 0doc 00001 | Drive on/off | Same as holding register 7. | BIT | Read/write | 0 = Drive off; 1 = Drive on | |||
| IR | 0doc 30001 | Room temperature | °C x 10. | UINT16 | × 0.1 | °C | Read | ||
| IR | 1doc 30002 | Fault code (hex) | UINT16 | Read | 27033 = Bad communication with indoor unit (0x6999); 32768 = No error (0x8000) | ||||
| IR | 3doc 30004 | Firmware version | UINT16 | Read | |||||
| IR | 5doc 30006 | Modbus comms counter | UINT16 | Read | |||||
| IR | 8doc 30009 | Fault code (decimal) | UINT16 | Read | 6999 = Bad communication with indoor unit; 8000 = No error | ||||
| IR | 9doc 30010 | System type detected | UINT16 | Read | 0 = ATA (air-to-air); 1 = ATW (air-to-water); 2 = Lossnay; 255 = Undetermined (no unit detected yet) | ||||
| IR | 10doc 30011 | Deadband enabled state | UINT16 | Read | 0 = Deadband disabled (DIP 8 off); 1 = Deadband enabled (DIP 8 on) | ||||
| HR | 0doc 40001 | Drive mode | Codes marked read-only (i-see) cannot be written. | UINT16 | Read/write | 1 = Heating; 2 = Humidity reduction; 3 = Cooling; 7 = Ventilation / clean air; 8 = Auto; 9 = i-see heating (read only); 10 = i-see humidity reduction (read only); 11 = i-see cooling (read only) | |||
| HR | 1doc 40002 | Temperature setpoint | °C x 10 (200 = 20 °C). | UINT16 | × 0.1 | °C | Read/write | ||
| HR | 2doc 40003 | Fan speed | UINT16 | Read/write | 0 = Auto; 2 = Quiet; 3 = Weak; 5 = Strong; 6 = Very strong (SHi) | ||||
| HR | 3doc 40004 | Air direction | UINT16 | Read/write | 0 = Auto; 1 = Position 1; 2 = Position 2; 3 = Position 3; 4 = Position 4; 5 = Position 5; 7 = Swing | ||||
| HR | 4doc 40005 | Modbus slave ID / BACnet station ID | Slave ID 1..247 (Modbus) or station 1..127 (BACnet); used when DIP 1-5 are all on. | UINT16 | Read/write | ||||
| HR | 5doc 40006 | RS-485 baud rate | Used when DIP 6 is off. BACnet accepts only 0, 4, 6, 8, 11. | UINT16 | Read/write | 0 = 9600; 1 = 1200; 2 = 2400; 3 = 4800; 4 = 9600; 5 = 14400; 6 = 19200; 7 = 28800; 8 = 38400; 9 = 56000; 10 = 57600; 11 = 76800; 12 = 115200 | |||
| HR | 6doc 40007 | RS-485 parity | Used when DIP 6 is off. | UINT16 | Read/write | 0 = None; 1 = Even; 2 = Odd | |||
| HR | 7doc 40008 | Drive on/off | UINT16 | Read/write | 0 = Drive off; 1 = Drive on | ||||
| HR | 8doc 40009 | Room temperature | Return air, °C x 10. Same as input register 0. | UINT16 | × 0.1 | °C | Read | ||
| HR | 9doc 40010 | Fault code (hex) | Indoor unit fault code in hex form; see indoor unit documentation. | UINT16 | Read | 27033 = Bad communication with indoor unit (0x6999); 32768 = No error (0x8000) | |||
| HR | 10doc 40011 | Firmware version | UINT16 | Read | |||||
| HR | 11doc 40012 | Modbus comms counter | Counts valid Modbus commands; wraps after 65535. | UINT16 | Read | ||||
| HR | 12doc 40013 | Fault code (decimal) | UINT16 | Read | 6999 = Bad communication with indoor unit; 8000 = No error | ||||
| HR | 13doc 40014 | System type detected | UINT16 | Read | 0 = ATA (air-to-air); 1 = ATW (air-to-water); 2 = Lossnay; 255 = Undetermined (no unit detected yet) | ||||
| HR | 14doc 40015 | Deadband enabled state | UINT16 | Read | 0 = Deadband disabled (DIP 8 off); 1 = Deadband enabled (DIP 8 on) | ||||
| HR | 15doc 40016 | BMS room temperature (signed) | °C x 10 from the BMS sensor; 0xFF9C = -10 °C .. 0x01F4 = 50 °C. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 16doc 40017 | BMS room temperature | Unsigned twin, °C x 10, 0..500. Not kept over power loss. | UINT16 | × 0.1 | °C | Read/write | ||
| HR | 17doc 40018 | BMS virtual setpoint | °C x 10, 100..400. Non-volatile. | UINT16 | × 0.1 | °C | Read/write | ||
| HR | 18doc 40019 | Deadband heating setpoint | Whole °C, default 19; at least 2 °C below the cooling setpoint. | UINT16 | °C | Read/write | |||
| HR | 19doc 40020 | Deadband cooling setpoint | Whole °C, default 23; at least 2 °C above the heating setpoint. | UINT16 | °C | Read/write | |||
| HR | 272doc 40273 | BACnet device instance (high 16 bits) | UINT16 | Read/write | |||||
| HR | 273doc 40274 | BACnet device instance (low 16 bits) | UINT16 | Read/write | |||||
| HR | 274doc 40275 | BACnet max master | UINT16 | Read/write | |||||
| HR | 275doc 40276 | BACnet max info frames | UINT16 | Read/write | |||||
| HR | 276doc 40277 | BACnet APDU timeout | UINT16 | ms | Read/write | ||||
| HR | 277doc 40278 | BACnet APDU retries | UINT16 | Read/write |
Notes on this map
- This file covers only the Air-To-Air tables (section 10). The same device has separate Air-To-Water and Lossnay tables; the ATW map is a separate file in this library.
- Registers are 16-bit unsigned except BMS room temperature (signed) at 40016, which the manual gives as signed °C x 10 with an unsigned twin at 40017.
- All input registers and the coil are mirrored as read-only holding registers for BMSs that read only holding registers.
- Deadband heating/cooling setpoints (40019/40020) are printed in whole °C, unlike the x10 setpoint and temperature registers.
- With the BMS room temperature and virtual setpoint written, the gateway shifts the unit's setpoint by the difference between the BMS sensor and the unit's return-air reading.
- DIP switches: 1-5 slave address (all off = 1, all on = use register 40005), 6 on = 9600 no parity (off = registers 40006/40007), 7 on = Modbus RTU (off = BACnet), 8 = deadband mode. Data bits 8 and stop bits 1 are fixed.
- Unit ID, baud rate and parity are chosen with the unit's DIP/rotary switches; the manual does not give factory defaults for them.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Mitsubishi Electric MelcoBEMS MINI (A1M+) gateway for Air-To-Air split units (M, S and P series)
What Modbus registers does the Mitsubishi Electric MelcoBEMS MINI (A1M+) gateway for Air-To-Air split units (M, S and P series) have?
This map lists 34 registers: 1 coil, 7 input registers, 26 holding registers. 20 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Mitsubishi Electric MelcoBEMS MINI (A1M+) gateway for Air-To-Air split units (M, S and P series) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Each row prints both an 'Address' (0-based) and a 'Modicon address' (40001 = holding address 0, 30001 = input address 0, 00001 = coil 0). The 0-based address is the wire address.
What are the minimum Modbus registers to integrate the Mitsubishi Electric MelcoBEMS MINI (A1M+) gateway for Air-To-Air split units (M, S and P series)?
Start with HR 7 Drive on/off (On/off); HR 0 Drive mode (Mode); HR 1 Temperature setpoint (Setpoint (x10)); HR 2 Fan speed (Fan speed); HR 8 Room temperature (Room temperature (x10)); HR 9 Fault code (hex) (Fault code (0x8000 = none)); HR 13 System type detected (Confirms an air-to-air unit was detected).
How do I enable Modbus control of the Mitsubishi Electric MelcoBEMS MINI (A1M+) gateway for Air-To-Air split units (M, S and P series)?
DIP switch 7 on selects Modbus RTU on RS-485 (off = BACnet MS/TP and BACnet IP). Modbus TCP on the Ethernet port came with firmware 4.1.0; the manual says the Ethernet protocol follows the DIP switch setting and needs application mode (DIP switches not all off).
Where is the official Mitsubishi Electric MelcoBEMS MINI (A1M+) gateway for Air-To-Air split units (M, S and P series) Modbus documentation?
The source is Procon MelcoBEMS MINI (A1M+) Installation Manual (Manual version 1.0.3), revision 2025-09-18, published free by Mitsubishi Electric at https://library.mitsubishielectric.co.uk/pdf/download_full/5538.
More Mitsubishi Electric Modbus register maps
- Variable frequency drive
Mitsubishi Electric FR-A700 inverter (RS-485 terminals, Modbus RTU)
FR-A700 series inverters (FR-A720-0.4K to 90K, FR-A740-0.4K to 500K) using the RS-485 terminals with Pr.549 = 1 (Modbus-RTU); Instruction Manual (Applied) revision E.
Also known as: FR-A720, FR-A740, FR-A700 series - Variable frequency drive
Mitsubishi Electric FR-A800 inverter (RS-485 terminals, Modbus RTU)
FR-A800 series inverters (FR-A820/A840/A842/A846, incl. -GF) using the built-in RS-485 terminals with Pr.549 = 1 (MODBUS RTU); Instruction Manual (Detailed) revision P.
Also known as: FR-A820, FR-A840, FR-A842, FR-A846, FR-A800-GF, FR-A800 series - Variable frequency drive
Mitsubishi Electric FR-D700 compact inverter (PU connector, Modbus RTU)
FR-D700 series (FR-D720/D740/D720S/D710W) using the PU connector with Pr.549 = 1; Instruction Manual (Applied) revision H.
Also known as: FR-D720, FR-D740, FR-D720S, FR-D710W - Variable frequency drive
Mitsubishi Electric FR-E700 compact inverter (PU connector, Modbus RTU)
FR-E700 series (FR-E720/E740/E720S/E710W, incl. SC safety-stop models) using the PU connector with Pr.549 = 1; Instruction Manual (Applied) revision G.
Also known as: FR-E720, FR-E740, FR-E720S, FR-E710W, FR-E700-SC - Variable frequency drive
Mitsubishi Electric FR-F800 fan and pump inverter (RS-485 terminals, Modbus RTU)
FR-F800 series inverters (FR-F820/F840/F842/F846) using the built-in RS-485 terminals with Pr.549 = 1 (MODBUS RTU); Instruction Manual (Detailed) revision G.
Also known as: FR-F820, FR-F840, FR-F842, FR-F846, FR-F800 series - VRF / split AC gateway
Mitsubishi Electric MelcoBEMS MINI (A1M) gateway for Air-To-Air split units
Procon MelcoBEMS MINI (A1M) on the CN105/CN92 connector of a Mitsubishi Electric Air-To-Air indoor unit, installation manual v1.1.11 (firmware 3.0.28 for revision 2-4 hardware, 3.1.1 for revision 5).
Also known as: MelcoBEMS MINI (A1M), A1M, Procon A1M, MelcoBEMS MINI - Air handler (heat recovery ventilation unit)
Mitsubishi Electric MelcoBEMS MINI (A1M+ / A1M) gateway for Lossnay heat recovery ventilators (LGH and VL series)
Procon MelcoBEMS MINI A1M+ (manual v1.0.3, firmware 4.1.1) on Lossnay LGH-15..200RVX-E1, LGH-150..250RVXT-E1 and VL-250..500CZPVU-R/L-E; the older A1M (manual v1.1.11) prints the identical Lossnay table.
Also known as: A1M+ Lossnay, MelcoBEMS MINI Lossnay, Procon A1M+, Procon A1M, A1M, Lossnay LGH-RVX Modbus, LGH-15RVX-E1, LGH-200RVX-E1, LGH-150RVXT-E1, LGH-250RVXT-E1, VL-250CZPVU-R-E, VL-500CZPVU-L-E, Lossnay VL Vertical - Chiller / heat pump gateway (VRF / split AC gateway)
Mitsubishi Electric MelcoBEMS MINI (A1M+) gateway for CAHV / CRHV / QAHV heat pumps and EAHV / EACV e-series chillers
Procon MelcoBEMS MINI (A1M+) firmware 4.1.0 on Mitsubishi Electric CAHV and CRHV heat pumps, QAHV CO2 heat pumps and EAHV / EACV e-series chillers (master and slave units); holding-register table only.
Also known as: A1M+, MelcoBEMS MINI, Procon A1M+, CAHV, CRHV, QAHV, EAHV, EACV, e-series chiller - Heat pump (VRF / split AC gateway)
Mitsubishi Electric MelcoBEMS MINI (A1M+) gateway for Ecodan FTC4/FTC5/FTC6 air-to-water systems
Procon MelcoBEMS MINI (A1M+) firmware 4.1.0 connected to an Ecodan FTC4, FTC5 or FTC6 air-to-water controller; holding-register table only.
Also known as: A1M+, MelcoBEMS MINI, Procon A1M+, Ecodan FTC4, Ecodan FTC5, Ecodan FTC6 - Air handler DX interface (VRF / split AC gateway)
Mitsubishi Electric PAC-IF013B-E / PAC-SIF013B-E air handling unit interface (Modbus RTU)
PAC-IF013B-E and PAC-SIF013B-E interface controllers linking a Mitsubishi Electric outdoor unit to an AHU coil, Modbus manual dated September 2015 (RG79F084H01).
Also known as: PAC-IF013B-E, PAC-SIF013B-E, PAC-(S)IF013B-E - VRF / split AC gateway (retail controller)
Mitsubishi Electric Procon MelcoRETAIL MINI controller for Air-To-Air split units
Procon MelcoRETAIL MINI on the CN105/CN92 connector of Mitsubishi Electric M, S and P series Air-To-Air indoor units, installation manual v1.0.6, firmware 1.0.3.
Also known as: MelcoRETAIL MINI, Procon MelcoRETAIL MINI - Air handler (computer room air conditioner)
Mitsubishi Electric s-MEXT-G00 computer room air conditioner (ME28 relC)
Mitsubishi Electric (Hydronics & IT Cooling) s-MEXT-G00 006-044 close-control units with ME28-relC software and the Modbus serial board.
Also known as: s-MEXT, s-MEXT-G00 006-044, s-MEXT G00, ME28 relC
Other ac & vrf gateways register maps
- Boiler / heat pump gateway
Remeha GTW-08 Modbus gateway for Remeha / De Dietrich appliances
GTW-08 Modbus RTU gateway on the L-Bus of Remeha / De Dietrich (BDR Thermea) boilers, heat pumps and hybrids, configuration manual 7854678 v.01 (2023-09-15), English section.
Also known as: GTW-08 Modbus, GTW08, De Dietrich GTW-08, BDR Thermea GTW-08 - Sensor (1-Wire to Modbus gateway)
Teracom TCW320x-WMG 1-Wire to Modbus gateway
TCW320E-WMG (Ethernet) and TCW320W-WMG (Wi-Fi) per the user manual Revision R1.0; both share one fixed register map.
Also known as: TCW320E-WMG, TCW320W-WMG - VRF / split AC gateway (IR-to-Modbus controller)
Cuby Cuby smart AC controller (Modbus RTU)
Cuby smart IR controllers for mini-split air conditioners with the Modbus RTU firmware described in the 2025 'MODBUS REGISTERS' sheet (fixed address 1).
Also known as: Cuby Smart, Cuby AC controller, Cuby minisplit controller - VRF / split AC gateway
Gree Modbus Gateway (Mini) ME30-24/E6(M) for GMV multi VRF systems
Gree Modbus Gateway (Mini) on CAN-bus multi VRF systems (GMV5, GMV5 C/E/HR/MAX/MINI/SLIM, GMV Water, energy-recovery ventilation); Communication Protocol V2.0, multi VRF part only.
Also known as: ME30-24/E6(M), Modbus Gateway(Mini), GMV5 Modbus gateway - VRF / split AC gateway
Intesis (HMS Networks) IN770AIR***O000 700 Series Air Gateway, Mitsubishi Electric City Multi application (Modbus)
Intesis 700 Series Air Gateway IN770AIR***O000 with the Mitsubishi Electric City Multi application (M-NET centralised controllers (AE-200, EW-50, G-50 and others)), Modbus RTU / TCP server, user manual version 1.0.19 (2026-03-16).
Also known as: IN770AIR00MO000, IN770AIR00SO000, IN770AIRXXSO000 - VRF / split AC gateway
Intesis (HMS Networks) INMBSFGL001I000 Fujitsu domestic AC to Modbus RTU gateway
One Fujitsu domestic (RAC) or compatible VRF indoor unit, connected to the CN65/CN12/CN6 socket on the indoor board via INMBSFGL001I000, user manual v1.5 (01/2024).
Also known as: INMBSFGL001I000, FJ-AC-MBS-1, Intesis Fujitsu domestic Modbus
All ac & vrf gateways Modbus register maps →
Source: Procon MelcoBEMS MINI (A1M+) Installation Manual · Manual version 1.0.3 · rev. 2025-09-18. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.