- PAC-IF013B-E / PAC-SIF013B-E air handling unit interface (Modbus RTU)
Air handler DX interface (VRF / split AC gateway) · Modbus register map
Mitsubishi Electric PAC-IF013B-E / PAC-SIF013B-E air handling unit interface (Modbus RTU) Modbus register map
Updated 19 November 2026
Interface board that lets a third-party air handling unit controller run a Mitsubishi Electric outdoor unit on a DX coil. Its RS-485 port is a Modbus RTU slave: in manual step mode the AHU controller sends a capacity step (off, 1-11 or auto) and the mode; in auto step mode it sends on/off, mode and a setpoint. Thermistor temperatures, error code, output status and step status can be read back.
This page lists 20 Modbus registers for the Mitsubishi Electric PAC-IF013B-E / PAC-SIF013B-E air handling unit interface (Modbus RTU) — 5 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Mitsubishi Electric’s own free documentation (linked below) and checked against it.
- Manufacturer
- Mitsubishi Electric
- Model
- PAC-IF013B-E / PAC-SIF013B-E air handling unit interface (Modbus RTU)
- Equipment type
- Air handler DX interface (VRF / split AC gateway)
- Registers
- 20 (5 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- Also known as
- PAC-IF013B-E, PAC-SIF013B-E, PAC-(S)IF013B-E
Integration notes: Mitsubishi Electric PAC-IF013B-E / PAC-SIF013B-E air handling unit interface (Modbus RTU)
Pick manual or auto step mode on the DIP switches, then write either the capacity step (40001) or on/off and setpoint (00001 / 40004, 40003) together with the mode (40002). Poll the step status, error code and temperatures every 10 seconds or so.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 0 | Capacity request | UINT16 | Capacity step (manual step mode) | Read/write |
| HR 1 | Drive mode | UINT16 | Operating mode | Read/write |
| HR 3 | Drive ON/OFF | UINT16 | On/off (auto step mode) | Read/write |
| HR 2 | Temperature setpoint | UINT16 | Setpoint x10 (auto step mode) | Read/write |
| HR 6 | Step status | UINT16 | Running capacity step | Read |
| HR 5 | Error code (decimal) | UINT16 | Error code (8000 = none) | Read |
| IR 0 | TH11 heat exchanger inlet air temperature | INT16 | AHU coil inlet air temperature | Read |
Enable Modbus control & writes
Set DIP SW1-1 to 1-3 and SW6 for 'Modbus' (manual step) or 'No input' (auto step mode), as listed in the manual's system table.
Communication loss & watchdog
Send a query or command at least every 10 minutes (10 seconds recommended). After more than 10 minutes without a query, on/off control is handed back to the remote controller.
Byte order & addressing
- Leave at least 1 minute between operation commands, whatever the baud rate.
- The slave answers about 50 ms after a request.
- Broadcast is accepted for coil writes and for FC06/16 holding writes.
Network setup
- Slave address 1-31 on DIP SW4-1 to 4-5 (all off = 1); the manual does not state a factory setting.
- Baud 1200-57600 on SW3-6 to 3-8; parity odd/even/none on SW4-6/4-7; stop bits on SW4-8.
- Wire the Modbus master to TB63 (A, B, SG); earth the shield at one end only.
- No termination resistor is fitted on the board: add 120 ohm if the interface is at a line end.
Watch out for
- With multiple outdoor unit control, send the capacity step and mode to the main interface only; sub interfaces read back 12 (auto) in 40001.
- LED4 lit means a communication error, blinking means traffic.
Mitsubishi Electric PAC-IF013B-E / PAC-SIF013B-E air handling unit interface (Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| CO | 0doc 00001 | Drive ON/OFF | Run command; auto step mode systems (5 and 7 column) only. | BIT | Read/write | 0 = Off; 1 = On | |||
| IR | 0doc 30001 | TH11 heat exchanger inlet air temperature | Range -39 to 88.5 °C. Open 0xFC19, short 0x03E7. | INT16 | × 0.1 | °C | Read | ||
| IR | 1doc 30002 | TH1 target air temperature | Range -39 to 88.5 °C. Open 0xFC19, short 0x03E7. | INT16 | × 0.1 | °C | Read | ||
| IR | 2doc 30003 | TH5 two-phase temperature | Range -39 to 88.5 °C. Open 0xFC19, short 0x03E7. | INT16 | × 0.1 | °C | Read | ||
| IR | 3doc 30004 | TH2 refrigerant liquid temperature | Range -39 to 88.5 °C. Open 0xFC19, short 0x03E7. | INT16 | × 0.1 | °C | Read | ||
| IR | 4doc 30005 | TH7 outdoor temperature | Range -15 to 46 °C. | INT16 | × 0.1 | °C | Read | ||
| IR | 6doc 30007 | Error code (hex) | 0x8000 = no error; otherwise the error code. | UINT16 | Read | 32768 = No error | |||
| IR | 7doc 30008 | Error code (decimal) | 8000 = no error; otherwise the error code (see notes). | UINT16 | Read | 8000 = No error | |||
| IR | 8doc 30009 | External outputs | Mirror of the eight output signals. | BITMAP16 | Read | bit 0 = OUT1 on/off; bit 1 = OUT2 error; bit 2 = OUT3 compressor; bit 3 = OUT4 defrost; bit 4 = OUT5 cooling mode; bit 5 = OUT6 heating mode; bit 6 = OUT7 self protection; bit 7 = OUT8 pre-defrost | |||
| IR | 9doc 30010 | Refrigerant address | Outdoor unit refrigerant address 0-15. | UINT16 | Read | ||||
| IR | 10doc 30011 | Modbus comms counter | Counts valid Modbus commands; wraps after 65535. | UINT16 | Read | ||||
| HR | 0doc 40001 | Capacity request | Manual step mode only. 0 = off, other = on; read only in auto step mode. | UINT16 | Read/write | 0 = Off; 1 = Step 1 (min); 2 = Step 2; 3 = Step 3; 4 = Step 4; 5 = Step 5; 6 = Step 6; 7 = Step 7; 8 = Step 8; 9 = Step 9; 10 = Step 10; 11 = Step 11 (max); 12 = Auto step mode | |||
| HR | 1doc 40002 | Drive mode | UINT16 | Read/write | 1 = Heating; 3 = Cooling; 7 = Fan; 8 = Auto changeover | ||||
| HR | 2doc 40003 | Temperature setpoint | Auto step mode only. Cooling 12-30 °C, heating / auto 17-28 °C, 1 °C steps. | UINT16 | × 0.1 | °C | Read/write | ||
| HR | 3doc 40004 | Drive ON/OFF | Auto step mode only (5 and 7 column). | UINT16 | Read/write | 0 = Off; 1 = On | |||
| HR | 4doc 40005 | Error code (hex) | 0x8000 = no error. | UINT16 | Read | 32768 = No error | |||
| HR | 5doc 40006 | Error code (decimal) | 8000 = no error. | UINT16 | Read | 8000 = No error | |||
| HR | 6doc 40007 | Step status | Capacity step actually running; per unit with multiple outdoor unit control. | UINT16 | Read | 0 = Off; 1 = Step 1 (min); 2 = Step 2; 3 = Step 3; 4 = Step 4; 5 = Step 5; 6 = Step 6; 7 = Step 7; 8 = Step 8; 9 = Step 9; 10 = Step 10; 11 = Step 11 (max); 12 = Auto step mode | |||
| HR | 7doc 40008 | Refrigerant address | 0-15. | UINT16 | Read | ||||
| HR | 8doc 40009 | Modbus comms counter | Counts valid Modbus commands; wraps after 65535. | UINT16 | Read |
Notes on this map
- The manual lists seven system layouts. Systems 1-4 write in manual step mode (capacity request 40001 and drive mode 40002 only; do not send setpoint or on/off) and system 5 writes in auto step mode (coil 00001 / 40004 on/off, 40002 mode, 40003 setpoint; do not send a capacity request). Systems 6 (manual step via analog or remote-switch input) and 7 (auto step, no input) use Modbus for monitoring only. The register tables mark availability per column 1-4,6 and 5,7.
- Manual step mode by Modbus needs DIP SW1-1, 1-2, 1-3 ON and SW6-1, 6-2 OFF; auto step mode by Modbus needs SW1-1 OFF, SW1-2 and 1-3 ON, SW6-1 and 6-2 OFF.
- Input address 5 (Modicon 30006) is not listed in the manual and is left out.
- Temperatures are sent as degrees x 10 in two's complement (0xFFFF = -0.1 °C, 0xFC19 = -99.9 °C), so they are listed as INT16 with scale 0.1. A setpoint value that is not a whole degree is rounded down.
- Modbus error codes and the matching remote-controller codes: 5101 P1, 5102 P2, 1503 P6 (freezing), 1504 P6 (overheating), 5103 P9, 6831/6834 E0 or E4, 6201 E1, 6202 E2, 6832/6833 E3 or E5, 6840/6843 E6, 6842 E7, 0404 Fb, 1514 PL, 5111 PU, 7130 EE.
- Writes with any value outside the listed codes are discarded by the interface.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Mitsubishi Electric PAC-IF013B-E / PAC-SIF013B-E air handling unit interface (Modbus RTU)
What Modbus registers does the Mitsubishi Electric PAC-IF013B-E / PAC-SIF013B-E air handling unit interface (Modbus RTU) have?
This map lists 20 registers: 1 coil, 10 input registers, 9 holding registers. 5 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Mitsubishi Electric PAC-IF013B-E / PAC-SIF013B-E air handling unit interface (Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Every table prints the 0-based 'Address' next to the Modicon address (coil 00001 = 0, input 30001 = 0, holding 40001 = 0). The 0-based address is sent on the wire.
What are the minimum Modbus registers to integrate the Mitsubishi Electric PAC-IF013B-E / PAC-SIF013B-E air handling unit interface (Modbus RTU)?
Start with HR 0 Capacity request (Capacity step (manual step mode)); HR 1 Drive mode (Operating mode); HR 3 Drive ON/OFF (On/off (auto step mode)); HR 2 Temperature setpoint (Setpoint x10 (auto step mode)); HR 6 Step status (Running capacity step); HR 5 Error code (decimal) (Error code (8000 = none)); IR 0 TH11 heat exchanger inlet air temperature (AHU coil inlet air temperature).
How do I enable Modbus control of the Mitsubishi Electric PAC-IF013B-E / PAC-SIF013B-E air handling unit interface (Modbus RTU)?
Set DIP SW1-1 to 1-3 and SW6 for 'Modbus' (manual step) or 'No input' (auto step mode), as listed in the manual's system table.
What happens when the Mitsubishi Electric PAC-IF013B-E / PAC-SIF013B-E air handling unit interface (Modbus RTU) loses Modbus communication?
Send a query or command at least every 10 minutes (10 seconds recommended). After more than 10 minutes without a query, on/off control is handed back to the remote controller.
Where is the official Mitsubishi Electric PAC-IF013B-E / PAC-SIF013B-E air handling unit interface (Modbus RTU) Modbus documentation?
The source is INTERFACE PAC-IF013B-E / PAC-SIF013B-E Modbus manual (RG79F084H01), revision 2015-09, published free by Mitsubishi Electric at https://library.mitsubishielectric.co.uk/pdf/download_full/3004.
More Mitsubishi Electric Modbus register maps
- Variable frequency drive
Mitsubishi Electric FR-A700 inverter (RS-485 terminals, Modbus RTU)
FR-A700 series inverters (FR-A720-0.4K to 90K, FR-A740-0.4K to 500K) using the RS-485 terminals with Pr.549 = 1 (Modbus-RTU); Instruction Manual (Applied) revision E.
Also known as: FR-A720, FR-A740, FR-A700 series - Variable frequency drive
Mitsubishi Electric FR-A800 inverter (RS-485 terminals, Modbus RTU)
FR-A800 series inverters (FR-A820/A840/A842/A846, incl. -GF) using the built-in RS-485 terminals with Pr.549 = 1 (MODBUS RTU); Instruction Manual (Detailed) revision P.
Also known as: FR-A820, FR-A840, FR-A842, FR-A846, FR-A800-GF, FR-A800 series - Variable frequency drive
Mitsubishi Electric FR-D700 compact inverter (PU connector, Modbus RTU)
FR-D700 series (FR-D720/D740/D720S/D710W) using the PU connector with Pr.549 = 1; Instruction Manual (Applied) revision H.
Also known as: FR-D720, FR-D740, FR-D720S, FR-D710W - Variable frequency drive
Mitsubishi Electric FR-E700 compact inverter (PU connector, Modbus RTU)
FR-E700 series (FR-E720/E740/E720S/E710W, incl. SC safety-stop models) using the PU connector with Pr.549 = 1; Instruction Manual (Applied) revision G.
Also known as: FR-E720, FR-E740, FR-E720S, FR-E710W, FR-E700-SC - Variable frequency drive
Mitsubishi Electric FR-F800 fan and pump inverter (RS-485 terminals, Modbus RTU)
FR-F800 series inverters (FR-F820/F840/F842/F846) using the built-in RS-485 terminals with Pr.549 = 1 (MODBUS RTU); Instruction Manual (Detailed) revision G.
Also known as: FR-F820, FR-F840, FR-F842, FR-F846, FR-F800 series - VRF / split AC gateway
Mitsubishi Electric MelcoBEMS MINI (A1M) gateway for Air-To-Air split units
Procon MelcoBEMS MINI (A1M) on the CN105/CN92 connector of a Mitsubishi Electric Air-To-Air indoor unit, installation manual v1.1.11 (firmware 3.0.28 for revision 2-4 hardware, 3.1.1 for revision 5).
Also known as: MelcoBEMS MINI (A1M), A1M, Procon A1M, MelcoBEMS MINI - Air handler (heat recovery ventilation unit)
Mitsubishi Electric MelcoBEMS MINI (A1M+ / A1M) gateway for Lossnay heat recovery ventilators (LGH and VL series)
Procon MelcoBEMS MINI A1M+ (manual v1.0.3, firmware 4.1.1) on Lossnay LGH-15..200RVX-E1, LGH-150..250RVXT-E1 and VL-250..500CZPVU-R/L-E; the older A1M (manual v1.1.11) prints the identical Lossnay table.
Also known as: A1M+ Lossnay, MelcoBEMS MINI Lossnay, Procon A1M+, Procon A1M, A1M, Lossnay LGH-RVX Modbus, LGH-15RVX-E1, LGH-200RVX-E1, LGH-150RVXT-E1, LGH-250RVXT-E1, VL-250CZPVU-R-E, VL-500CZPVU-L-E, Lossnay VL Vertical - VRF / split AC gateway
Mitsubishi Electric MelcoBEMS MINI (A1M+) gateway for Air-To-Air split units (M, S and P series)
MelcoBEMS MINI (A1M+) on the CN105 connector of a Mitsubishi Electric Air-To-Air indoor unit (M series MSZ/MFZ/MLZ, S series SEZ/SLZ, P series per Appendix A), installation manual v1.0.3, firmware 4.1.1.
Also known as: A1M+, MelcoBEMS MINI, Procon A1M+, MelcoBEMS MINI A1M PLUS, A1M+ ATA - Chiller / heat pump gateway (VRF / split AC gateway)
Mitsubishi Electric MelcoBEMS MINI (A1M+) gateway for CAHV / CRHV / QAHV heat pumps and EAHV / EACV e-series chillers
Procon MelcoBEMS MINI (A1M+) firmware 4.1.0 on Mitsubishi Electric CAHV and CRHV heat pumps, QAHV CO2 heat pumps and EAHV / EACV e-series chillers (master and slave units); holding-register table only.
Also known as: A1M+, MelcoBEMS MINI, Procon A1M+, CAHV, CRHV, QAHV, EAHV, EACV, e-series chiller - Heat pump (VRF / split AC gateway)
Mitsubishi Electric MelcoBEMS MINI (A1M+) gateway for Ecodan FTC4/FTC5/FTC6 air-to-water systems
Procon MelcoBEMS MINI (A1M+) firmware 4.1.0 connected to an Ecodan FTC4, FTC5 or FTC6 air-to-water controller; holding-register table only.
Also known as: A1M+, MelcoBEMS MINI, Procon A1M+, Ecodan FTC4, Ecodan FTC5, Ecodan FTC6 - VRF / split AC gateway (retail controller)
Mitsubishi Electric Procon MelcoRETAIL MINI controller for Air-To-Air split units
Procon MelcoRETAIL MINI on the CN105/CN92 connector of Mitsubishi Electric M, S and P series Air-To-Air indoor units, installation manual v1.0.6, firmware 1.0.3.
Also known as: MelcoRETAIL MINI, Procon MelcoRETAIL MINI - Air handler (computer room air conditioner)
Mitsubishi Electric s-MEXT-G00 computer room air conditioner (ME28 relC)
Mitsubishi Electric (Hydronics & IT Cooling) s-MEXT-G00 006-044 close-control units with ME28-relC software and the Modbus serial board.
Also known as: s-MEXT, s-MEXT-G00 006-044, s-MEXT G00, ME28 relC
Other ac & vrf gateways register maps
- Air handler (rack-mounted room cooling unit, split DX)
Schneider Electric Uniflair Rack Mounted Room Cooling ACRMD4K
Schneider Electric Uniflair Rack Mounted Room Cooling units ACRMD4Kxxx (indoor rack unit with matching outdoor unit), register map part number 990-91589.
Also known as: ACRMD4K, ACRMD4Kxxx, Uniflair rack mounted room cooling, 990-91589 - Split AC unit (VRF / split AC gateway built in)
Aermec LCG series DC inverter air conditioners (built-in Modbus)
Aermec LCG series DC inverter units whose indoor-unit controller has the built-in Modbus RTU interface; Modbus Protocol user manual LCG 5385758_02 (24.01).
Also known as: LCG - VRF / split AC gateway
Daikin EKMBPP1 / EKMBPP1A Modbus adapter (Sky Air / VRV P1P2)
EKMBPP1 and EKMBPP1A adapters on the P1P2 bus of Sky Air / VRV indoor units (up to 16), installation manual 4P720139-1C (2024.11).
Also known as: EKMBPP1, EKMBPP1A - Heat pump gateway (VRF / split AC gateway)
Intesis (HMS Networks) IN485MIT001A000 Mitsubishi Electric Ecodan air-to-water to Modbus RTU / BACnet MS/TP gateway
Intesis (HMS Networks) IN485MIT001A000 gateway on the CN105 socket of Mitsubishi Electric Ecodan air-to-water heat pumps, set to Modbus RTU, per user manual version 1.0.3 (2025-12-02).
Also known as: IN485MIT001A000, Ecodan Modbus, Mitsubishi Ecodan Modbus RTU, Intesis Ecodan, HMS Ecodan gateway - VRF / split AC gateway
Intesis (HMS Networks) INMBSACA004I000 / 008I000 / 032I000 XYE-bus air conditioner to Modbus RTU interface (4 to 32 units)
INMBSACA004I000 / INMBSACA008I000 / INMBSACA032I000, user manual v1.8 EN; up to 4, 8 or 32 indoor units on one XYE bus.
Also known as: INMBSACA004I000, INMBSACA008I000, INMBSACA032I000 - VRF / split AC gateway
Intesis (HMS Networks) INMBSHIS001R000 Hisense AC to Modbus RTU gateway
Hisense commercial-line indoor units on the AB remote-controller bus, user manual v1.6 (01/2024).
Also known as: INMBSHIS001R000, HS-RC-MBS-1, Intesis Hisense Modbus
All ac & vrf gateways Modbus register maps →
Source: INTERFACE PAC-IF013B-E / PAC-SIF013B-E Modbus manual · RG79F084H01 · rev. 2015-09. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.