Air handler DX interface (VRF / split AC gateway) · Modbus register map

Mitsubishi Electric PAC-IF013B-E / PAC-SIF013B-E air handling unit interface (Modbus RTU) Modbus register map

Updated 19 November 2026

Short answer

Interface board that lets a third-party air handling unit controller run a Mitsubishi Electric outdoor unit on a DX coil. Its RS-485 port is a Modbus RTU slave: in manual step mode the AHU controller sends a capacity step (off, 1-11 or auto) and the mode; in auto step mode it sends on/off, mode and a setpoint. Thermistor temperatures, error code, output status and step status can be read back.

This page lists 20 Modbus registers for the Mitsubishi Electric PAC-IF013B-E / PAC-SIF013B-E air handling unit interface (Modbus RTU) — 5 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Mitsubishi Electric’s own free documentation (linked below) and checked against it.

Manufacturer
Mitsubishi Electric
Model
PAC-IF013B-E / PAC-SIF013B-E air handling unit interface (Modbus RTU)
Equipment type
Air handler DX interface (VRF / split AC gateway)
Registers
20 (5 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
Also known as
PAC-IF013B-E, PAC-SIF013B-E, PAC-(S)IF013B-E
Source document
INTERFACE PAC-IF013B-E / PAC-SIF013B-E Modbus manual · RG79F084H01 · rev. 2015-09
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Mitsubishi Electric PAC-IF013B-E / PAC-SIF013B-E air handling unit interface (Modbus RTU)

Integration in brief

Pick manual or auto step mode on the DIP switches, then write either the capacity step (40001) or on/off and setpoint (00001 / 40004, 40003) together with the mode (40002). Poll the step status, error code and temperatures every 10 seconds or so.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 0Capacity requestUINT16Capacity step (manual step mode)Read/write
HR 1Drive modeUINT16Operating modeRead/write
HR 3Drive ON/OFFUINT16On/off (auto step mode)Read/write
HR 2Temperature setpointUINT16Setpoint x10 (auto step mode)Read/write
HR 6Step statusUINT16Running capacity stepRead
HR 5Error code (decimal)UINT16Error code (8000 = none)Read
IR 0TH11 heat exchanger inlet air temperatureINT16AHU coil inlet air temperatureRead

Enable Modbus control & writes

Set DIP SW1-1 to 1-3 and SW6 for 'Modbus' (manual step) or 'No input' (auto step mode), as listed in the manual's system table.

Communication loss & watchdog

Send a query or command at least every 10 minutes (10 seconds recommended). After more than 10 minutes without a query, on/off control is handed back to the remote controller.

Byte order & addressing

Network setup

Watch out for

Mitsubishi Electric PAC-IF013B-E / PAC-SIF013B-E air handling unit interface (Modbus RTU) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

20 of 20 shown
Mitsubishi Electric PAC-IF013B-E / PAC-SIF013B-E air handling unit interface (Modbus RTU) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
CO0doc 00001Drive ON/OFFRun command; auto step mode systems (5 and 7 column) only.BITRead/write0 = Off; 1 = On
IR0doc 30001TH11 heat exchanger inlet air temperatureRange -39 to 88.5 °C. Open 0xFC19, short 0x03E7.INT16× 0.1°CRead
IR1doc 30002TH1 target air temperatureRange -39 to 88.5 °C. Open 0xFC19, short 0x03E7.INT16× 0.1°CRead
IR2doc 30003TH5 two-phase temperatureRange -39 to 88.5 °C. Open 0xFC19, short 0x03E7.INT16× 0.1°CRead
IR3doc 30004TH2 refrigerant liquid temperatureRange -39 to 88.5 °C. Open 0xFC19, short 0x03E7.INT16× 0.1°CRead
IR4doc 30005TH7 outdoor temperatureRange -15 to 46 °C.INT16× 0.1°CRead
IR6doc 30007Error code (hex)0x8000 = no error; otherwise the error code.UINT16Read32768 = No error
IR7doc 30008Error code (decimal)8000 = no error; otherwise the error code (see notes).UINT16Read8000 = No error
IR8doc 30009External outputsMirror of the eight output signals.BITMAP16Readbit 0 = OUT1 on/off; bit 1 = OUT2 error; bit 2 = OUT3 compressor; bit 3 = OUT4 defrost; bit 4 = OUT5 cooling mode; bit 5 = OUT6 heating mode; bit 6 = OUT7 self protection; bit 7 = OUT8 pre-defrost
IR9doc 30010Refrigerant addressOutdoor unit refrigerant address 0-15.UINT16Read
IR10doc 30011Modbus comms counterCounts valid Modbus commands; wraps after 65535.UINT16Read
HR0doc 40001Capacity requestManual step mode only. 0 = off, other = on; read only in auto step mode.UINT16Read/write0 = Off; 1 = Step 1 (min); 2 = Step 2; 3 = Step 3; 4 = Step 4; 5 = Step 5; 6 = Step 6; 7 = Step 7; 8 = Step 8; 9 = Step 9; 10 = Step 10; 11 = Step 11 (max); 12 = Auto step mode
HR1doc 40002Drive modeUINT16Read/write1 = Heating; 3 = Cooling; 7 = Fan; 8 = Auto changeover
HR2doc 40003Temperature setpointAuto step mode only. Cooling 12-30 °C, heating / auto 17-28 °C, 1 °C steps.UINT16× 0.1°CRead/write
HR3doc 40004Drive ON/OFFAuto step mode only (5 and 7 column).UINT16Read/write0 = Off; 1 = On
HR4doc 40005Error code (hex)0x8000 = no error.UINT16Read32768 = No error
HR5doc 40006Error code (decimal)8000 = no error.UINT16Read8000 = No error
HR6doc 40007Step statusCapacity step actually running; per unit with multiple outdoor unit control.UINT16Read0 = Off; 1 = Step 1 (min); 2 = Step 2; 3 = Step 3; 4 = Step 4; 5 = Step 5; 6 = Step 6; 7 = Step 7; 8 = Step 8; 9 = Step 9; 10 = Step 10; 11 = Step 11 (max); 12 = Auto step mode
HR7doc 40008Refrigerant address0-15.UINT16Read
HR8doc 40009Modbus comms counterCounts valid Modbus commands; wraps after 65535.UINT16Read

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Mitsubishi Electric PAC-IF013B-E / PAC-SIF013B-E air handling unit interface (Modbus RTU)

What Modbus registers does the Mitsubishi Electric PAC-IF013B-E / PAC-SIF013B-E air handling unit interface (Modbus RTU) have?

This map lists 20 registers: 1 coil, 10 input registers, 9 holding registers. 5 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Mitsubishi Electric PAC-IF013B-E / PAC-SIF013B-E air handling unit interface (Modbus RTU) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Every table prints the 0-based 'Address' next to the Modicon address (coil 00001 = 0, input 30001 = 0, holding 40001 = 0). The 0-based address is sent on the wire.

What are the minimum Modbus registers to integrate the Mitsubishi Electric PAC-IF013B-E / PAC-SIF013B-E air handling unit interface (Modbus RTU)?

Start with HR 0 Capacity request (Capacity step (manual step mode)); HR 1 Drive mode (Operating mode); HR 3 Drive ON/OFF (On/off (auto step mode)); HR 2 Temperature setpoint (Setpoint x10 (auto step mode)); HR 6 Step status (Running capacity step); HR 5 Error code (decimal) (Error code (8000 = none)); IR 0 TH11 heat exchanger inlet air temperature (AHU coil inlet air temperature).

How do I enable Modbus control of the Mitsubishi Electric PAC-IF013B-E / PAC-SIF013B-E air handling unit interface (Modbus RTU)?

Set DIP SW1-1 to 1-3 and SW6 for 'Modbus' (manual step) or 'No input' (auto step mode), as listed in the manual's system table.

What happens when the Mitsubishi Electric PAC-IF013B-E / PAC-SIF013B-E air handling unit interface (Modbus RTU) loses Modbus communication?

Send a query or command at least every 10 minutes (10 seconds recommended). After more than 10 minutes without a query, on/off control is handed back to the remote controller.

Where is the official Mitsubishi Electric PAC-IF013B-E / PAC-SIF013B-E air handling unit interface (Modbus RTU) Modbus documentation?

The source is INTERFACE PAC-IF013B-E / PAC-SIF013B-E Modbus manual (RG79F084H01), revision 2015-09, published free by Mitsubishi Electric at https://library.mitsubishielectric.co.uk/pdf/download_full/3004.

More Mitsubishi Electric Modbus register maps

Other ac & vrf gateways register maps

All ac & vrf gateways Modbus register maps →

Source: INTERFACE PAC-IF013B-E / PAC-SIF013B-E Modbus manual · RG79F084H01 · rev. 2015-09. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.