Easy Modbus
  1. Home
  2. Modbus register maps
  3. Mitsubishi Electric
  4. Procon MelcoRETAIL MINI controller for Air-To-Air split units

VRF / split AC gateway (retail controller) · Modbus register map

Mitsubishi Electric Procon MelcoRETAIL MINI controller for Air-To-Air split units Modbus register map

Updated 19 November 2026

Short answer

Small Procon controller that plugs into one Mitsubishi Electric split indoor unit and adds retail-style local I/O (status relays, force/lock inputs, analogue mode, fan, setpoint and occupancy inputs) plus a Modbus RTU slave on RS-485. Over Modbus it exposes mode, setpoint, fan, vane, on/off, room temperature and fault code, occupancy-based setpoints, setpoint limits, deadband settings and relay overrides.

This page lists 70 Modbus registers for the Mitsubishi Electric Procon MelcoRETAIL MINI controller for Air-To-Air split units — 38 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Mitsubishi Electric’s own free documentation (linked below) and checked against it.

Manufacturer
Mitsubishi Electric
Model
Procon MelcoRETAIL MINI controller for Air-To-Air split units
Equipment type
VRF / split AC gateway (retail controller)
Registers
70 (38 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
32-bit word order
CDAB low word first (word-swapped)
Firmware
1.0.3
Also known as
MelcoRETAIL MINI, Procon MelcoRETAIL MINI
Source document
Procon MelcoRETAIL MINI Installation Manual · Manual version 1.0.6 · rev. 2018-02-08
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Mitsubishi Electric Procon MelcoRETAIL MINI controller for Air-To-Air split units

Integration in brief

Set DIP 1-7 ON (Modbus RTU), pick the slave ID on DIP 1-1 to 1-5 and use DIP 1-6 ON for 9600 / no parity. Then write mode, setpoint, fan and on/off at holding 0-3 and 7 and poll room temperature (8) and fault code (12).

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 7Drive On/OffUINT16On/offRead/write
HR 0Drive modeUINT16ModeRead/write
HR 1Temperature setpointUINT16Setpoint (x10)Read/write
HR 2Fan speedUINT16Fan speedRead/write
HR 8Room temperatureUINT16Room temperature (x10)Read
HR 12Fault code (decimal)UINT16Fault code (8000 = none)Read
DI 7Fault relay stateBITFault relay stateRead

Enable Modbus control & writes

DIP CONFIG 1-7 ON selects Modbus RTU (OFF is reserved). Power-cycle after any DIP change.

Byte order & addressing

Network setup

Watch out for

Mitsubishi Electric Procon MelcoRETAIL MINI controller for Air-To-Air split units Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

70 of 70 shown
Mitsubishi Electric Procon MelcoRETAIL MINI controller for Air-To-Air split units Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
CO0doc 00001Drive On/OffSame as holding register 7.BITRead/write0 = Drive off; 1 = Drive on
DI0doc 10001Force ON input stateBITRead0 = Input off (open); 1 = Input on (closed)
DI1doc 10002Force OFF input stateBITRead0 = Input off (open); 1 = Input on (closed)
DI2doc 10003Lock/Auto input stateBITRead0 = Input off (open); 1 = Input on (closed)
DI3doc 10004External fault input stateBITRead0 = Input off (open); 1 = Input on (closed)
DI4doc 10005Running status relay stateBITRead0 = Relay de-energised; 1 = Relay energised
DI5doc 10006Heating status relay stateBITRead0 = Relay de-energised; 1 = Relay energised
DI6doc 10007Cooling status relay stateBITRead0 = Relay de-energised; 1 = Relay energised
DI7doc 10008Fault relay stateBITRead0 = Relay de-energised; 1 = Relay energised
DI8doc 10009Comms settings switch (DIP 1-6)Reports the switch position; the table's meaning text is the reverse of the DIP section.BITRead0 = DIP 1-6 OFF; 1 = DIP 1-6 ON
DI9doc 9 / 10000Protocol selection switch (DIP 1-7)Modicon number printed as 10000 in the manual.BITRead0 = Reserved; 1 = Modbus RTU
DI10doc 10011Auto/Lock mode selection switch (DIP 1-8)BITRead0 = Auto mode; 1 = Lock mode
DI11doc 10012Deadband switch (DIP 2-1)BITRead0 = Disabled; 1 = Enabled
DI12doc 10013Setpoint limiting switch (DIP 2-2)BITRead0 = Disabled; 1 = Enabled
DI13doc 10014Timeout switch (DIP 2-3)BITRead0 = Disabled; 1 = Enabled
DI14doc 10015Analogue input type switch (DIP 2-4)BITRead0 = Voltage; 1 = Resistance
IR0doc 30001Room temperatureUINT16× 0.1°CRead
IR1doc 30002Fault code (hex)0x8000 = no error, 0x6999 = no comms with indoor unit.UINT16Read27033 = Bad communication with indoor unit; 32768 = No error
IR3doc 30004Firmware versionUINT16Read
IR5doc 30006Modbus comms counterCounts valid Modbus commands; wraps after 65535.UINT16Read
IR8doc 30009Fault code (decimal)UINT16Read6999 = Bad communication with indoor unit; 8000 = No error
IR10doc 30011Current DIP switch valuesRaw DIP switch value (bit layout not given).UINT16Read
IR11doc 30012 / 30013Occupancy mode input valuemV (voltage inputs) or ohm (resistance inputs).UINT32CDABmV / ohmRead
IR13doc 30014 / 30015Fan speed input valuemV (voltage inputs) or ohm (resistance inputs).UINT32CDABmV / ohmRead
IR15doc 30016 / 30017Mode input valuemV (voltage inputs) or ohm (resistance inputs).UINT32CDABmV / ohmRead
IR17doc 30018 / 30019Setpoint input valuemV (voltage inputs) or ohm (resistance inputs).UINT32CDABmV / ohmRead
HR0doc 40001Drive modei-see codes are read only.UINT16Read/write1 = Heating; 2 = Humidity reduction; 3 = Cooling; 7 = Ventilation / clean air; 8 = Auto; 9 = i-see heating (read only); 10 = i-see humidity reduction (read only); 11 = i-see cooling (read only)
HR1doc 40002Temperature setpointUINT16× 0.1°CRead/write
HR2doc 40003Fan speedUINT16Read/write0 = Auto; 2 = Quiet; 3 = Weak; 5 = Strong; 6 = Very strong (SH i)
HR3doc 40004Air directionUINT16Read/write0 = Auto; 1 = Position 1; 2 = Position 2; 3 = Position 3; 4 = Position 4; 5 = Position 5; 7 = Swing
HR4doc 40005Modbus slave ID1-247; used when DIP 1-1 to 1-5 are all ON.UINT16Read/write
HR5doc 40006RS-485 baud rateUsed when DIP 1-6 is OFF.UINT16Read/write0 = 9600; 1 = 1200; 2 = 2400; 3 = 4800; 4 = 9600; 5 = 14400; 6 = 19200; 7 = 28800; 8 = 38400; 9 = 56000; 10 = 57600; 11 = 115200
HR6doc 40007RS-485 parityUsed when DIP 1-6 is OFF.UINT16Read/write0 = None; 1 = Even; 2 = Odd
HR7doc 40008Drive On/OffUINT16Read/write0 = Drive off; 1 = Drive on
HR8doc 40009Room temperatureUINT16× 0.1°CRead
HR9doc 40010Fault code (hex)0x8000 = no error.UINT16Read27033 = Bad communication with indoor unit; 32768 = No error
HR10doc 40011Firmware versionUINT16Read
HR11doc 40012Modbus comms counterUINT16Read
HR12doc 40013Fault code (decimal)UINT16Read6999 = Bad communication with indoor unit; 8000 = No error
HR13doc 40014System type detectedUINT16Read0 = Air-to-air; 1 = Air-to-water
HR14doc 40015Deadband enabled stateValue text in the manual says 'DIP switch 8'; deadband is DIP 2-1 on this unit.UINT16Read0 = Disabled; 1 = Enabled
HR15doc 40016BMS room temperature (signed)Room reading from the BMS for the setpoint offset feature.INT16× 0.1°CRead/write
HR16doc 40017BMS room temperatureUnsigned version, 0-50 °C.UINT16× 0.1°CRead/write
HR17doc 40018BMS virtual setpointWhole degrees.UINT16°CRead/write
HR18doc 40019Deadband heating setpointAt least 2 °C below the deadband cooling setpoint. Default 19 °C.UINT16°CRead/write
HR19doc 40020Deadband cooling setpointAt least 2 °C above the deadband heating setpoint. Default 23 °C.UINT16°CRead/write
HR32doc 40033Auto mode setpoint high limitDefault 30 °C.UINT16°CRead/write
HR33doc 40034Auto mode setpoint low limitDefault 16 °C.UINT16°CRead/write
HR34doc 40035Cooling mode setpoint high limitDefault 30 °C.UINT16°CRead/write
HR35doc 40036Cooling mode setpoint low limitDefault 16 °C.UINT16°CRead/write
HR36doc 40037Heating mode setpoint high limitDefault 30 °C.UINT16°CRead/write
HR37doc 40038Heating mode setpoint low limitDefault 16 °C.UINT16°CRead/write
HR38doc 40039In-occupancy cooling setpointOccupancy mode. Default 23 °C.UINT16°CRead/write
HR39doc 40040In-occupancy heating setpointOccupancy mode. Default 21 °C.UINT16°CRead/write
HR40doc 40041Staff-in cooling setpointOccupancy mode. Default 24 °C.UINT16°CRead/write
HR41doc 40042Staff-in heating setpointOccupancy mode. Default 18 °C.UINT16°CRead/write
HR42doc 40043Unoccupied cooling setpointOccupancy mode. Default 26 °C.UINT16°CRead/write
HR43doc 40044Unoccupied heating setpointOccupancy mode. Default 16 °C.UINT16°CRead/write
HR44doc 40045Deadband cooling setpoint (2)Second deadband cooling row in the manual. Default 23 °C.UINT16°CRead/write
HR45doc 40046Deadband heating setpoint (2)Second deadband heating row in the manual. Default 19 °C.UINT16°CRead/write
HR46doc 40047Auto mode timeoutTime in auto mode before the unit drops to fan mode. Default 300 s.UINT16sRead/write
HR51doc 40052Relay manual override start/stop1 = allow override via 52-55; times out after 20 minutes.UINT16Read/write0 = End override; 1 = Start override
HR52doc 40053Relay 1 override (ON/OFF)UINT16Read/write0 = De-energise relay; 1 = Energise relay
HR53doc 40054Relay 2 override (HEATING)UINT16Read/write0 = De-energise relay; 1 = Energise relay
HR54doc 40055Relay 3 override (COOLING)UINT16Read/write0 = De-energise relay; 1 = Energise relay
HR55doc 40056Relay 4 override (FAULT)UINT16Read/write0 = De-energise relay; 1 = Energise relay
HR56doc 40057Auto mode timeout overrideWrite a number of seconds to shorten the current Auto Mode run.UINT16sRead/write
HR57doc 40058Heating relay temperature offsetDrop below setpoint before the heating relay energises.UINT16°CRead/write
HR58doc 40059Cooling relay temperature offsetRise above setpoint before the cooling relay energises.UINT16°CRead/write
HR59doc 40060Relay switching delayDelay before the on/off, heating and cooling relays change.UINT16sRead/write

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Mitsubishi Electric Procon MelcoRETAIL MINI controller for Air-To-Air split units

What Modbus registers does the Mitsubishi Electric Procon MelcoRETAIL MINI controller for Air-To-Air split units have?

This map lists 70 registers: 1 coil, 15 discrete inputs, 10 input registers, 44 holding registers. 38 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Mitsubishi Electric Procon MelcoRETAIL MINI controller for Air-To-Air split units Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Every table prints a 0-based 'Address' next to the Modicon address (40001 = holding 0, 30001 = input 0, 10001 = discrete input 0, 00001 = coil 0). The 0-based address is the wire address.

What byte order does the Mitsubishi Electric Procon MelcoRETAIL MINI controller for Air-To-Air split units use for 32-bit values?

Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Mitsubishi Electric Procon MelcoRETAIL MINI controller for Air-To-Air split units?

Start with HR 7 Drive On/Off (On/off); HR 0 Drive mode (Mode); HR 1 Temperature setpoint (Setpoint (x10)); HR 2 Fan speed (Fan speed); HR 8 Room temperature (Room temperature (x10)); HR 12 Fault code (decimal) (Fault code (8000 = none)); DI 7 Fault relay state (Fault relay state).

How do I enable Modbus control of the Mitsubishi Electric Procon MelcoRETAIL MINI controller for Air-To-Air split units?

DIP CONFIG 1-7 ON selects Modbus RTU (OFF is reserved). Power-cycle after any DIP change.

Where is the official Mitsubishi Electric Procon MelcoRETAIL MINI controller for Air-To-Air split units Modbus documentation?

The source is Procon MelcoRETAIL MINI Installation Manual (Manual version 1.0.6), revision 2018-02-08, published free by Mitsubishi Electric at https://library.mitsubishielectric.co.uk/pdf/download_full/3632.

More Mitsubishi Electric Modbus register maps

Other ac & vrf gateways register maps

All ac & vrf gateways Modbus register maps →

Source: Procon MelcoRETAIL MINI Installation Manual · Manual version 1.0.6 · rev. 2018-02-08. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.