- Procon MelcoRETAIL MINI controller for Air-To-Air split units
VRF / split AC gateway (retail controller) · Modbus register map
Mitsubishi Electric Procon MelcoRETAIL MINI controller for Air-To-Air split units Modbus register map
Updated 19 November 2026
Small Procon controller that plugs into one Mitsubishi Electric split indoor unit and adds retail-style local I/O (status relays, force/lock inputs, analogue mode, fan, setpoint and occupancy inputs) plus a Modbus RTU slave on RS-485. Over Modbus it exposes mode, setpoint, fan, vane, on/off, room temperature and fault code, occupancy-based setpoints, setpoint limits, deadband settings and relay overrides.
This page lists 70 Modbus registers for the Mitsubishi Electric Procon MelcoRETAIL MINI controller for Air-To-Air split units — 38 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Mitsubishi Electric’s own free documentation (linked below) and checked against it.
- Manufacturer
- Mitsubishi Electric
- Model
- Procon MelcoRETAIL MINI controller for Air-To-Air split units
- Equipment type
- VRF / split AC gateway (retail controller)
- Registers
- 70 (38 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- 32-bit word order
- CDAB low word first (word-swapped)
- Firmware
- 1.0.3
- Also known as
- MelcoRETAIL MINI, Procon MelcoRETAIL MINI
Integration notes: Mitsubishi Electric Procon MelcoRETAIL MINI controller for Air-To-Air split units
Set DIP 1-7 ON (Modbus RTU), pick the slave ID on DIP 1-1 to 1-5 and use DIP 1-6 ON for 9600 / no parity. Then write mode, setpoint, fan and on/off at holding 0-3 and 7 and poll room temperature (8) and fault code (12).
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 7 | Drive On/Off | UINT16 | On/off | Read/write |
| HR 0 | Drive mode | UINT16 | Mode | Read/write |
| HR 1 | Temperature setpoint | UINT16 | Setpoint (x10) | Read/write |
| HR 2 | Fan speed | UINT16 | Fan speed | Read/write |
| HR 8 | Room temperature | UINT16 | Room temperature (x10) | Read |
| HR 12 | Fault code (decimal) | UINT16 | Fault code (8000 = none) | Read |
| DI 7 | Fault relay state | BIT | Fault relay state | Read |
Enable Modbus control & writes
DIP CONFIG 1-7 ON selects Modbus RTU (OFF is reserved). Power-cycle after any DIP change.
Byte order & addressing
- Slave ID from DIP 1-1 to 1-5 (1-30); all ON means the ID comes from holding 4; all OFF is invalid.
- DIP 1-6 ON fixes 9600 baud, no parity; OFF uses holding 5 and 6. Data bits 8 and stop bits 1 are fixed.
- Writing 0 to the BMS room temperature (15/16) turns the setpoint offset feature off.
Network setup
- Plug the flying lead into CN105/CN92 on the indoor unit PCB; the unit is powered from there.
- RS-485 needs A, B and GND, shielded cable, daisy chain only; shield to GND at one end.
- Cannot be used together with a MAC-397IF / MAC-333IF interface (same connector).
Watch out for
- Relay manual override (51) times out after 20 minutes.
- Setpoint limits and deadband settings depend on the matching DIP features (2-2 setpoint limiting, 2-1 deadband).
Mitsubishi Electric Procon MelcoRETAIL MINI controller for Air-To-Air split units Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| CO | 0doc 00001 | Drive On/Off | Same as holding register 7. | BIT | Read/write | 0 = Drive off; 1 = Drive on | |||
| DI | 0doc 10001 | Force ON input state | BIT | Read | 0 = Input off (open); 1 = Input on (closed) | ||||
| DI | 1doc 10002 | Force OFF input state | BIT | Read | 0 = Input off (open); 1 = Input on (closed) | ||||
| DI | 2doc 10003 | Lock/Auto input state | BIT | Read | 0 = Input off (open); 1 = Input on (closed) | ||||
| DI | 3doc 10004 | External fault input state | BIT | Read | 0 = Input off (open); 1 = Input on (closed) | ||||
| DI | 4doc 10005 | Running status relay state | BIT | Read | 0 = Relay de-energised; 1 = Relay energised | ||||
| DI | 5doc 10006 | Heating status relay state | BIT | Read | 0 = Relay de-energised; 1 = Relay energised | ||||
| DI | 6doc 10007 | Cooling status relay state | BIT | Read | 0 = Relay de-energised; 1 = Relay energised | ||||
| DI | 7doc 10008 | Fault relay state | BIT | Read | 0 = Relay de-energised; 1 = Relay energised | ||||
| DI | 8doc 10009 | Comms settings switch (DIP 1-6) | Reports the switch position; the table's meaning text is the reverse of the DIP section. | BIT | Read | 0 = DIP 1-6 OFF; 1 = DIP 1-6 ON | |||
| DI | 9doc 9 / 10000 | Protocol selection switch (DIP 1-7) | Modicon number printed as 10000 in the manual. | BIT | Read | 0 = Reserved; 1 = Modbus RTU | |||
| DI | 10doc 10011 | Auto/Lock mode selection switch (DIP 1-8) | BIT | Read | 0 = Auto mode; 1 = Lock mode | ||||
| DI | 11doc 10012 | Deadband switch (DIP 2-1) | BIT | Read | 0 = Disabled; 1 = Enabled | ||||
| DI | 12doc 10013 | Setpoint limiting switch (DIP 2-2) | BIT | Read | 0 = Disabled; 1 = Enabled | ||||
| DI | 13doc 10014 | Timeout switch (DIP 2-3) | BIT | Read | 0 = Disabled; 1 = Enabled | ||||
| DI | 14doc 10015 | Analogue input type switch (DIP 2-4) | BIT | Read | 0 = Voltage; 1 = Resistance | ||||
| IR | 0doc 30001 | Room temperature | UINT16 | × 0.1 | °C | Read | |||
| IR | 1doc 30002 | Fault code (hex) | 0x8000 = no error, 0x6999 = no comms with indoor unit. | UINT16 | Read | 27033 = Bad communication with indoor unit; 32768 = No error | |||
| IR | 3doc 30004 | Firmware version | UINT16 | Read | |||||
| IR | 5doc 30006 | Modbus comms counter | Counts valid Modbus commands; wraps after 65535. | UINT16 | Read | ||||
| IR | 8doc 30009 | Fault code (decimal) | UINT16 | Read | 6999 = Bad communication with indoor unit; 8000 = No error | ||||
| IR | 10doc 30011 | Current DIP switch values | Raw DIP switch value (bit layout not given). | UINT16 | Read | ||||
| IR | 11doc 30012 / 30013 | Occupancy mode input value | mV (voltage inputs) or ohm (resistance inputs). | UINT32 | CDAB | mV / ohm | Read | ||
| IR | 13doc 30014 / 30015 | Fan speed input value | mV (voltage inputs) or ohm (resistance inputs). | UINT32 | CDAB | mV / ohm | Read | ||
| IR | 15doc 30016 / 30017 | Mode input value | mV (voltage inputs) or ohm (resistance inputs). | UINT32 | CDAB | mV / ohm | Read | ||
| IR | 17doc 30018 / 30019 | Setpoint input value | mV (voltage inputs) or ohm (resistance inputs). | UINT32 | CDAB | mV / ohm | Read | ||
| HR | 0doc 40001 | Drive mode | i-see codes are read only. | UINT16 | Read/write | 1 = Heating; 2 = Humidity reduction; 3 = Cooling; 7 = Ventilation / clean air; 8 = Auto; 9 = i-see heating (read only); 10 = i-see humidity reduction (read only); 11 = i-see cooling (read only) | |||
| HR | 1doc 40002 | Temperature setpoint | UINT16 | × 0.1 | °C | Read/write | |||
| HR | 2doc 40003 | Fan speed | UINT16 | Read/write | 0 = Auto; 2 = Quiet; 3 = Weak; 5 = Strong; 6 = Very strong (SH i) | ||||
| HR | 3doc 40004 | Air direction | UINT16 | Read/write | 0 = Auto; 1 = Position 1; 2 = Position 2; 3 = Position 3; 4 = Position 4; 5 = Position 5; 7 = Swing | ||||
| HR | 4doc 40005 | Modbus slave ID | 1-247; used when DIP 1-1 to 1-5 are all ON. | UINT16 | Read/write | ||||
| HR | 5doc 40006 | RS-485 baud rate | Used when DIP 1-6 is OFF. | UINT16 | Read/write | 0 = 9600; 1 = 1200; 2 = 2400; 3 = 4800; 4 = 9600; 5 = 14400; 6 = 19200; 7 = 28800; 8 = 38400; 9 = 56000; 10 = 57600; 11 = 115200 | |||
| HR | 6doc 40007 | RS-485 parity | Used when DIP 1-6 is OFF. | UINT16 | Read/write | 0 = None; 1 = Even; 2 = Odd | |||
| HR | 7doc 40008 | Drive On/Off | UINT16 | Read/write | 0 = Drive off; 1 = Drive on | ||||
| HR | 8doc 40009 | Room temperature | UINT16 | × 0.1 | °C | Read | |||
| HR | 9doc 40010 | Fault code (hex) | 0x8000 = no error. | UINT16 | Read | 27033 = Bad communication with indoor unit; 32768 = No error | |||
| HR | 10doc 40011 | Firmware version | UINT16 | Read | |||||
| HR | 11doc 40012 | Modbus comms counter | UINT16 | Read | |||||
| HR | 12doc 40013 | Fault code (decimal) | UINT16 | Read | 6999 = Bad communication with indoor unit; 8000 = No error | ||||
| HR | 13doc 40014 | System type detected | UINT16 | Read | 0 = Air-to-air; 1 = Air-to-water | ||||
| HR | 14doc 40015 | Deadband enabled state | Value text in the manual says 'DIP switch 8'; deadband is DIP 2-1 on this unit. | UINT16 | Read | 0 = Disabled; 1 = Enabled | |||
| HR | 15doc 40016 | BMS room temperature (signed) | Room reading from the BMS for the setpoint offset feature. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 16doc 40017 | BMS room temperature | Unsigned version, 0-50 °C. | UINT16 | × 0.1 | °C | Read/write | ||
| HR | 17doc 40018 | BMS virtual setpoint | Whole degrees. | UINT16 | °C | Read/write | |||
| HR | 18doc 40019 | Deadband heating setpoint | At least 2 °C below the deadband cooling setpoint. Default 19 °C. | UINT16 | °C | Read/write | |||
| HR | 19doc 40020 | Deadband cooling setpoint | At least 2 °C above the deadband heating setpoint. Default 23 °C. | UINT16 | °C | Read/write | |||
| HR | 32doc 40033 | Auto mode setpoint high limit | Default 30 °C. | UINT16 | °C | Read/write | |||
| HR | 33doc 40034 | Auto mode setpoint low limit | Default 16 °C. | UINT16 | °C | Read/write | |||
| HR | 34doc 40035 | Cooling mode setpoint high limit | Default 30 °C. | UINT16 | °C | Read/write | |||
| HR | 35doc 40036 | Cooling mode setpoint low limit | Default 16 °C. | UINT16 | °C | Read/write | |||
| HR | 36doc 40037 | Heating mode setpoint high limit | Default 30 °C. | UINT16 | °C | Read/write | |||
| HR | 37doc 40038 | Heating mode setpoint low limit | Default 16 °C. | UINT16 | °C | Read/write | |||
| HR | 38doc 40039 | In-occupancy cooling setpoint | Occupancy mode. Default 23 °C. | UINT16 | °C | Read/write | |||
| HR | 39doc 40040 | In-occupancy heating setpoint | Occupancy mode. Default 21 °C. | UINT16 | °C | Read/write | |||
| HR | 40doc 40041 | Staff-in cooling setpoint | Occupancy mode. Default 24 °C. | UINT16 | °C | Read/write | |||
| HR | 41doc 40042 | Staff-in heating setpoint | Occupancy mode. Default 18 °C. | UINT16 | °C | Read/write | |||
| HR | 42doc 40043 | Unoccupied cooling setpoint | Occupancy mode. Default 26 °C. | UINT16 | °C | Read/write | |||
| HR | 43doc 40044 | Unoccupied heating setpoint | Occupancy mode. Default 16 °C. | UINT16 | °C | Read/write | |||
| HR | 44doc 40045 | Deadband cooling setpoint (2) | Second deadband cooling row in the manual. Default 23 °C. | UINT16 | °C | Read/write | |||
| HR | 45doc 40046 | Deadband heating setpoint (2) | Second deadband heating row in the manual. Default 19 °C. | UINT16 | °C | Read/write | |||
| HR | 46doc 40047 | Auto mode timeout | Time in auto mode before the unit drops to fan mode. Default 300 s. | UINT16 | s | Read/write | |||
| HR | 51doc 40052 | Relay manual override start/stop | 1 = allow override via 52-55; times out after 20 minutes. | UINT16 | Read/write | 0 = End override; 1 = Start override | |||
| HR | 52doc 40053 | Relay 1 override (ON/OFF) | UINT16 | Read/write | 0 = De-energise relay; 1 = Energise relay | ||||
| HR | 53doc 40054 | Relay 2 override (HEATING) | UINT16 | Read/write | 0 = De-energise relay; 1 = Energise relay | ||||
| HR | 54doc 40055 | Relay 3 override (COOLING) | UINT16 | Read/write | 0 = De-energise relay; 1 = Energise relay | ||||
| HR | 55doc 40056 | Relay 4 override (FAULT) | UINT16 | Read/write | 0 = De-energise relay; 1 = Energise relay | ||||
| HR | 56doc 40057 | Auto mode timeout override | Write a number of seconds to shorten the current Auto Mode run. | UINT16 | s | Read/write | |||
| HR | 57doc 40058 | Heating relay temperature offset | Drop below setpoint before the heating relay energises. | UINT16 | °C | Read/write | |||
| HR | 58doc 40059 | Cooling relay temperature offset | Rise above setpoint before the cooling relay energises. | UINT16 | °C | Read/write | |||
| HR | 59doc 40060 | Relay switching delay | Delay before the on/off, heating and cooling relays change. | UINT16 | s | Read/write |
Notes on this map
- Input and coil values are mirrored as holding registers (marked read only) for BMSs that only read holding registers.
- The four analogue input readings (inputs 11-18) are 32-bit values split over two registers; the manual labels the lower address 'least significant register' and the higher 'most significant register', so they are listed as UINT32 low word first (CDAB). Signedness is not stated; the values are mV (0-10 V inputs) or ohm, so they never reach the sign bit.
- Rows that the manual describes as 'temperature value in °C multiplied by 10' use scale 0.1; rows described as 'temperature in °C' (virtual setpoint, deadband, limits, occupancy setpoints, relay offsets) are whole degrees.
- Holding 44/45 repeat the names of 18/19 (deadband cooling / heating setpoint) with the same defaults; both are listed as printed.
- Discrete input 9 is printed with Modicon number 10000; it sits between 10009 and 10011, so it is listed at address 9.
- Holding 20-31 and 47-50 are not printed. Inputs 2, 4, 6 and 7 are not printed; input 9 is printed as 'Unused' and left out.
- Fault codes other than 8000 / 0x8000 and 6999 / 0x6999 are the indoor unit's own codes.
- Discrete input 8 (DIP 1-6): the register table gives 0 = fixed 9600 / no parity and 1 = software settings, the opposite of the DIP switch section (OFF = software, ON = 9600). Only the switch position (0 = OFF, 1 = ON) is listed.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Mitsubishi Electric Procon MelcoRETAIL MINI controller for Air-To-Air split units
What Modbus registers does the Mitsubishi Electric Procon MelcoRETAIL MINI controller for Air-To-Air split units have?
This map lists 70 registers: 1 coil, 15 discrete inputs, 10 input registers, 44 holding registers. 38 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Mitsubishi Electric Procon MelcoRETAIL MINI controller for Air-To-Air split units Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Every table prints a 0-based 'Address' next to the Modicon address (40001 = holding 0, 30001 = input 0, 10001 = discrete input 0, 00001 = coil 0). The 0-based address is the wire address.
What byte order does the Mitsubishi Electric Procon MelcoRETAIL MINI controller for Air-To-Air split units use for 32-bit values?
Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Mitsubishi Electric Procon MelcoRETAIL MINI controller for Air-To-Air split units?
Start with HR 7 Drive On/Off (On/off); HR 0 Drive mode (Mode); HR 1 Temperature setpoint (Setpoint (x10)); HR 2 Fan speed (Fan speed); HR 8 Room temperature (Room temperature (x10)); HR 12 Fault code (decimal) (Fault code (8000 = none)); DI 7 Fault relay state (Fault relay state).
How do I enable Modbus control of the Mitsubishi Electric Procon MelcoRETAIL MINI controller for Air-To-Air split units?
DIP CONFIG 1-7 ON selects Modbus RTU (OFF is reserved). Power-cycle after any DIP change.
Where is the official Mitsubishi Electric Procon MelcoRETAIL MINI controller for Air-To-Air split units Modbus documentation?
The source is Procon MelcoRETAIL MINI Installation Manual (Manual version 1.0.6), revision 2018-02-08, published free by Mitsubishi Electric at https://library.mitsubishielectric.co.uk/pdf/download_full/3632.
More Mitsubishi Electric Modbus register maps
- Variable frequency drive
Mitsubishi Electric FR-A700 inverter (RS-485 terminals, Modbus RTU)
FR-A700 series inverters (FR-A720-0.4K to 90K, FR-A740-0.4K to 500K) using the RS-485 terminals with Pr.549 = 1 (Modbus-RTU); Instruction Manual (Applied) revision E.
Also known as: FR-A720, FR-A740, FR-A700 series - Variable frequency drive
Mitsubishi Electric FR-A800 inverter (RS-485 terminals, Modbus RTU)
FR-A800 series inverters (FR-A820/A840/A842/A846, incl. -GF) using the built-in RS-485 terminals with Pr.549 = 1 (MODBUS RTU); Instruction Manual (Detailed) revision P.
Also known as: FR-A820, FR-A840, FR-A842, FR-A846, FR-A800-GF, FR-A800 series - Variable frequency drive
Mitsubishi Electric FR-D700 compact inverter (PU connector, Modbus RTU)
FR-D700 series (FR-D720/D740/D720S/D710W) using the PU connector with Pr.549 = 1; Instruction Manual (Applied) revision H.
Also known as: FR-D720, FR-D740, FR-D720S, FR-D710W - Variable frequency drive
Mitsubishi Electric FR-E700 compact inverter (PU connector, Modbus RTU)
FR-E700 series (FR-E720/E740/E720S/E710W, incl. SC safety-stop models) using the PU connector with Pr.549 = 1; Instruction Manual (Applied) revision G.
Also known as: FR-E720, FR-E740, FR-E720S, FR-E710W, FR-E700-SC - Variable frequency drive
Mitsubishi Electric FR-F800 fan and pump inverter (RS-485 terminals, Modbus RTU)
FR-F800 series inverters (FR-F820/F840/F842/F846) using the built-in RS-485 terminals with Pr.549 = 1 (MODBUS RTU); Instruction Manual (Detailed) revision G.
Also known as: FR-F820, FR-F840, FR-F842, FR-F846, FR-F800 series - VRF / split AC gateway
Mitsubishi Electric MelcoBEMS MINI (A1M) gateway for Air-To-Air split units
Procon MelcoBEMS MINI (A1M) on the CN105/CN92 connector of a Mitsubishi Electric Air-To-Air indoor unit, installation manual v1.1.11 (firmware 3.0.28 for revision 2-4 hardware, 3.1.1 for revision 5).
Also known as: MelcoBEMS MINI (A1M), A1M, Procon A1M, MelcoBEMS MINI - Air handler (heat recovery ventilation unit)
Mitsubishi Electric MelcoBEMS MINI (A1M+ / A1M) gateway for Lossnay heat recovery ventilators (LGH and VL series)
Procon MelcoBEMS MINI A1M+ (manual v1.0.3, firmware 4.1.1) on Lossnay LGH-15..200RVX-E1, LGH-150..250RVXT-E1 and VL-250..500CZPVU-R/L-E; the older A1M (manual v1.1.11) prints the identical Lossnay table.
Also known as: A1M+ Lossnay, MelcoBEMS MINI Lossnay, Procon A1M+, Procon A1M, A1M, Lossnay LGH-RVX Modbus, LGH-15RVX-E1, LGH-200RVX-E1, LGH-150RVXT-E1, LGH-250RVXT-E1, VL-250CZPVU-R-E, VL-500CZPVU-L-E, Lossnay VL Vertical - VRF / split AC gateway
Mitsubishi Electric MelcoBEMS MINI (A1M+) gateway for Air-To-Air split units (M, S and P series)
MelcoBEMS MINI (A1M+) on the CN105 connector of a Mitsubishi Electric Air-To-Air indoor unit (M series MSZ/MFZ/MLZ, S series SEZ/SLZ, P series per Appendix A), installation manual v1.0.3, firmware 4.1.1.
Also known as: A1M+, MelcoBEMS MINI, Procon A1M+, MelcoBEMS MINI A1M PLUS, A1M+ ATA - Chiller / heat pump gateway (VRF / split AC gateway)
Mitsubishi Electric MelcoBEMS MINI (A1M+) gateway for CAHV / CRHV / QAHV heat pumps and EAHV / EACV e-series chillers
Procon MelcoBEMS MINI (A1M+) firmware 4.1.0 on Mitsubishi Electric CAHV and CRHV heat pumps, QAHV CO2 heat pumps and EAHV / EACV e-series chillers (master and slave units); holding-register table only.
Also known as: A1M+, MelcoBEMS MINI, Procon A1M+, CAHV, CRHV, QAHV, EAHV, EACV, e-series chiller - Heat pump (VRF / split AC gateway)
Mitsubishi Electric MelcoBEMS MINI (A1M+) gateway for Ecodan FTC4/FTC5/FTC6 air-to-water systems
Procon MelcoBEMS MINI (A1M+) firmware 4.1.0 connected to an Ecodan FTC4, FTC5 or FTC6 air-to-water controller; holding-register table only.
Also known as: A1M+, MelcoBEMS MINI, Procon A1M+, Ecodan FTC4, Ecodan FTC5, Ecodan FTC6 - Air handler DX interface (VRF / split AC gateway)
Mitsubishi Electric PAC-IF013B-E / PAC-SIF013B-E air handling unit interface (Modbus RTU)
PAC-IF013B-E and PAC-SIF013B-E interface controllers linking a Mitsubishi Electric outdoor unit to an AHU coil, Modbus manual dated September 2015 (RG79F084H01).
Also known as: PAC-IF013B-E, PAC-SIF013B-E, PAC-(S)IF013B-E - Air handler (computer room air conditioner)
Mitsubishi Electric s-MEXT-G00 computer room air conditioner (ME28 relC)
Mitsubishi Electric (Hydronics & IT Cooling) s-MEXT-G00 006-044 close-control units with ME28-relC software and the Modbus serial board.
Also known as: s-MEXT, s-MEXT-G00 006-044, s-MEXT G00, ME28 relC
Other ac & vrf gateways register maps
- VRF / split AC gateway (built-in indoor-unit Modbus)
Sinclair UNI SPLIT DC inverter indoor units (integrated Modbus RTU)
Sinclair All DC Inverter UNI SPLIT indoor units with the built-in Modbus RTU interface, per the UNI SPLIT Modbus user's manual.
Also known as: Sinclair UNI SPLIT, UNI SPLIT Modbus, All DC Inverter UNI SPLIT - Split AC unit (VRF / split AC gateway built in)
Aermec LPG series DC inverter air conditioners (built-in Modbus)
Aermec LPG series DC inverter units whose indoor-unit controller has the built-in Modbus RTU interface; ModBus Protocol LPG series 5385759_02 (EN 25.05).
Also known as: LPG - Sensor / controller (CO2 condensing unit gateway)
Danfoss Optyma iCO2 gateway (OP-MPAM015 / OP-MPAM005)
Danfoss Optyma iCO2 CO2 condensing units (4.6 kW MT and 20 kW MT / 10 kW LT) through their Modbus gateway, software 1.0x.
Also known as: OP-MPAM015, OP-MPAM005, Optyma iCO2 4.6 kW MT, Optyma iCO2 20 kW MT / 10 kW LT - VRF / split AC gateway
Intesis (HMS Networks) IN485SAM001R000 Samsung AC to Modbus RTU / BACnet MS/TP gateway
Samsung indoor units on the F3F4 remote-controller bus, gateway set to Modbus RTU (SW1-5 ON); user manual version 1.0.0.
Also known as: IN485SAM001R000, Intesis Samsung BACnet MS/TP Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSDAI001I000 Daikin domestic AC to Modbus RTU gateway
Single Daikin domestic (S21-connector) indoor unit via INMBSDAI001I000, user manual v1.0.2.
Also known as: INMBSDAI001I000, Intesis Daikin domestic Modbus - VRF / split AC gateway
Intesis (HMS Networks) INMBSHIS016O000 Hisense VRF to Modbus RTU / TCP gateway (16 / 64 indoor units)
Intesis Modbus Server - Hisense VRF, order codes INMBSHIS016O000 / INMBSHIS064O000 (legacy HS-AC-MBS-16 / HS-AC-MBS-64), user manual User Manual r1.0 EN.
Also known as: INMBSHIS016O000, INMBSHIS064O000, HS-AC-MBS-16, HS-AC-MBS-64, Intesis Modbus Server Hisense VRF
All ac & vrf gateways Modbus register maps →
Source: Procon MelcoRETAIL MINI Installation Manual · Manual version 1.0.6 · rev. 2018-02-08. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.