Variable frequency drive · Modbus register map
Mitsubishi Electric FR-E700 compact inverter (PU connector, Modbus RTU) Modbus register map
Updated 19 November 2026
Mitsubishi Electric's compact general-purpose inverter. The PU connector can run Modbus RTU, giving system variables (control word, operation mode, frequency command) at 40002-40015, a real-time monitor block from 40201, fault history at 40501 and every parameter at 41000 + parameter number. This map covers control, status, monitors, fault codes and the communication parameters.
This page lists 51 Modbus registers for the Mitsubishi Electric FR-E700 compact inverter (PU connector, Modbus RTU) — 22 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Mitsubishi Electric’s own free documentation (linked below) and checked against it.
- Manufacturer
- Mitsubishi Electric
- Model
- FR-E700 compact inverter (PU connector, Modbus RTU)
- Equipment type
- Variable frequency drive
- Registers
- 51 (22 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Default serial
- 19200 baud, 8E1
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- Also known as
- FR-E720, FR-E740, FR-E720S, FR-E710W, FR-E700-SC
Integration notes: Mitsubishi Electric FR-E700 compact inverter (PU connector, Modbus RTU)
Set Pr.549 = 1, Pr.117 to 1-247 and Pr.122 to 9999 (or a real interval), reset, then switch to NET mode by writing H0014 to 40010. Write the frequency to 40014 (0.01 Hz) and run bits to 40009; poll 40009, 40201, 40202 and 40501.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 8 | Inverter status / control input instruction | BITMAP16 | Run/stop command and inverter status | Read/write |
| HR 9 | Operation mode / inverter setting | UINT16 | Operation mode (write H0014 for NET) | Read/write |
| HR 13 | Running frequency (RAM) | UINT16 | Frequency command (RAM) | Read/write |
| HR 200 | Output frequency / speed | UINT16 | Output frequency | Read |
| HR 201 | Output current | UINT16 | Output current | Read |
| HR 500 | Fault record 1 | UINT16 | Latest fault code | Read/write |
Enable Modbus control & writes
Pr.549 = 1 selects Modbus RTU on the PU connector; set Pr.117 (station), Pr.118 (speed) and Pr.120 (parity) and reset. The PU connector must be the NET command source (Pr.550 = 2, or 9999 with no communication option fitted). Operation and frequency commands need NET mode (write H0014 to 40010; allowed depending on Pr.79/Pr.340).
Communication loss & watchdog
Pr.122 is the communication check interval (0.1-999.8 s) with Pr.502 choosing coast or decelerate on E.PUE. Initial value 0 trips E.PUE as soon as the drive enters NET mode, so set 9999 or an interval before switching.
Byte order & addressing
- Request address = register - 40001.
- Station 0 is broadcast and never replies; the initial Pr.117 is 0.
- 40009 means control input when written and inverter status when read.
Network setup
- Pr.118 initial 192 = 19200 bps; Pr.120 initial 2 = even parity, 1 stop bit.
- With Pr.549 = 1 and Pr.118 = 384, the FR-PU04/FR-PU07 parameter unit stops working; use the built-in panel.
- Modbus RTU cannot be used in PU operation mode.
Watch out for
- Pr.122 = 0 (initial) makes the drive trip E.PUE the moment it goes to NET mode.
Mitsubishi Electric FR-E700 compact inverter (PU connector, Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 1doc 40002 | Inverter reset | Write any value to reset the inverter. | UINT16 | Write | ||||
| HR | 2doc 40003 | Parameter clear | Write H965A. | UINT16 | Write | ||||
| HR | 3doc 40004 | All parameter clear | Write H99AA. | UINT16 | Write | ||||
| HR | 5doc 40006 | Parameter clear (keep comm settings) | Write H5A96; communication parameters are kept. | UINT16 | Write | ||||
| HR | 6doc 40007 | All parameter clear (keep comm settings) | Write HAA99; communication parameters are kept. | UINT16 | Write | ||||
| HR | 8doc 40009 | Inverter status / control input instruction | Write = control input, read = inverter status. | BITMAP16 | Read/write | bit 0 = Write: stop command / Read: RUN (inverter running); bit 1 = Write: forward rotation / Read: during forward rotation; bit 2 = Write: reverse rotation / Read: during reverse rotation; bit 3 = Write: RH (high speed) / Read: SU (up to frequency); bit 4 = Write: RM (middle speed) / Read: OL (overload); bit 5 = Write: RL (low speed); bit 6 = Read: FU (frequency detection); bit 7 = Write: RT (second function) / Read: ABC (fault); bit 8 = Write: AU (current input selection); bit 10 = Write: MRS (output stop); bit 12 = Write: RES (reset); bit 15 = Read: fault occurrence | |||
| HR | 9doc 40010 | Operation mode / inverter setting | Read = current mode; write H0010 EXT, H0011 PU, H0014 NET. | UINT16 | Read/write | 0 = Read: EXT; 1 = Read: PU; 2 = Read: EXT JOG; 3 = Read: PU JOG; 4 = Read: NET; 5 = Read: PU + EXT; 16 = Write: EXT (H0010); 17 = Write: PU (H0011); 20 = Write: NET (H0014) | |||
| HR | 13doc 40014 | Running frequency (RAM) | Frequency command, not stored in EEPROM. | UINT16 | × 0.01 | Hz | Read/write | ||
| HR | 14doc 40015 | Running frequency (EEPROM) | Frequency command, also stored in EEPROM. | UINT16 | × 0.01 | Hz | Write | ||
| HR | 200doc 40201 | Output frequency / speed | 0.01 Hz, or 1 r/min when Pr.37 = 0.01-9998. | UINT16 | × 0.01 | Hz | Read | ||
| HR | 201doc 40202 | Output current | UINT16 | × 0.01 | A | Read | |||
| HR | 202doc 40203 | Output voltage | UINT16 | × 0.1 | V | Read | |||
| HR | 204doc 40205 | Set frequency / speed setting | 0.01 Hz, or 1 r/min when Pr.37 = 0.01-9998. | UINT16 | × 0.01 | Hz | Read | ||
| HR | 207doc 40208 | Converter output voltage | DC bus voltage. | UINT16 | × 0.1 | V | Read | ||
| HR | 208doc 40209 | Regenerative brake duty | UINT16 | × 0.1 | % | Read | |||
| HR | 209doc 40210 | Electronic thermal relay load factor | UINT16 | × 0.1 | % | Read | |||
| HR | 210doc 40211 | Output current peak value | UINT16 | × 0.01 | A | Read | |||
| HR | 211doc 40212 | Converter output voltage peak value | UINT16 | × 0.1 | V | Read | |||
| HR | 213doc 40214 | Output power | UINT16 | × 0.01 | kW | Read | |||
| HR | 214doc 40215 | Input terminal status | 1 = on. | BITMAP16 | Read | bit 0 = STF; bit 1 = STR; bit 4 = RL; bit 5 = RM; bit 6 = RH; bit 8 = MRS; bit 10 = RES | |||
| HR | 215doc 40216 | Output terminal status | 1 = on. | BITMAP16 | Read | bit 0 = RUN; bit 4 = FU; bit 5 = ABC | |||
| HR | 219doc 40220 | Cumulative energization time | UINT16 | h | Read | ||||
| HR | 222doc 40223 | Actual operation time | UINT16 | h | Read | ||||
| HR | 223doc 40224 | Motor load factor | Output current as % of rated inverter current. | UINT16 | × 0.1 | % | Read | ||
| HR | 224doc 40225 | Cumulative power | UINT16 | kWh | Read | ||||
| HR | 251doc 40252 | PID set point | UINT16 | × 0.1 | % | Read | |||
| HR | 252doc 40253 | PID measured value | UINT16 | × 0.1 | % | Read | |||
| HR | 260doc 40261 | Motor thermal load factor | UINT16 | × 0.1 | % | Read | |||
| HR | 261doc 40262 | Inverter thermal load factor | UINT16 | × 0.1 | % | Read | |||
| HR | 262doc 40263 | Cumulative power 2 | Only on units built after the version-up noted in the manual. | UINT16 | × 0.01 | kWh | Read | ||
| HR | 500doc 40501 | Fault record 1 | Low byte = fault code (H00xx). Write any value to clear history. | UINT16 | Read/write | 0 = No fault; 16 = E.OC1; 17 = E.OC2; 18 = E.OC3; 32 = E.OV1; 33 = E.OV2; 34 = E.OV3; 48 = E.THT; 49 = E.THM; 64 = E.FIN; 82 = E.ILF; 96 = E.OLT; 112 = E.BE; 128 = E.GF; 129 = E.LF; 144 = E.OHT; 160 = E.OPT; 161 = E.OP1; 176 = E.PE; 177 = E.PUE; 178 = E.RET; 179 = E.PE2; 192 = E.CPU; 197 = E.IOH; 199 = E.AIE; 200 = E.USB; 201 = E.SAF; 216 = E.MB4; 217 = E.MB5; 218 = E.MB6; 219 = E.MB7; 241 = E.1; 245 = E.5; 246 = E.6; 247 = E.7; 253 = E.13 | |||
| HR | 501doc 40502 | Fault record 2 | Low byte = fault code (H00xx). | UINT16 | Read | 0 = No fault; 16 = E.OC1; 17 = E.OC2; 18 = E.OC3; 32 = E.OV1; 33 = E.OV2; 34 = E.OV3; 48 = E.THT; 49 = E.THM; 64 = E.FIN; 82 = E.ILF; 96 = E.OLT; 112 = E.BE; 128 = E.GF; 129 = E.LF; 144 = E.OHT; 160 = E.OPT; 161 = E.OP1; 176 = E.PE; 177 = E.PUE; 178 = E.RET; 179 = E.PE2; 192 = E.CPU; 197 = E.IOH; 199 = E.AIE; 200 = E.USB; 201 = E.SAF; 216 = E.MB4; 217 = E.MB5; 218 = E.MB6; 219 = E.MB7; 241 = E.1; 245 = E.5; 246 = E.6; 247 = E.7; 253 = E.13 | |||
| HR | 502doc 40503 | Fault record 3 | Low byte = fault code (H00xx). | UINT16 | Read | 0 = No fault; 16 = E.OC1; 17 = E.OC2; 18 = E.OC3; 32 = E.OV1; 33 = E.OV2; 34 = E.OV3; 48 = E.THT; 49 = E.THM; 64 = E.FIN; 82 = E.ILF; 96 = E.OLT; 112 = E.BE; 128 = E.GF; 129 = E.LF; 144 = E.OHT; 160 = E.OPT; 161 = E.OP1; 176 = E.PE; 177 = E.PUE; 178 = E.RET; 179 = E.PE2; 192 = E.CPU; 197 = E.IOH; 199 = E.AIE; 200 = E.USB; 201 = E.SAF; 216 = E.MB4; 217 = E.MB5; 218 = E.MB6; 219 = E.MB7; 241 = E.1; 245 = E.5; 246 = E.6; 247 = E.7; 253 = E.13 | |||
| HR | 503doc 40504 | Fault record 4 | Low byte = fault code (H00xx). | UINT16 | Read | 0 = No fault; 16 = E.OC1; 17 = E.OC2; 18 = E.OC3; 32 = E.OV1; 33 = E.OV2; 34 = E.OV3; 48 = E.THT; 49 = E.THM; 64 = E.FIN; 82 = E.ILF; 96 = E.OLT; 112 = E.BE; 128 = E.GF; 129 = E.LF; 144 = E.OHT; 160 = E.OPT; 161 = E.OP1; 176 = E.PE; 177 = E.PUE; 178 = E.RET; 179 = E.PE2; 192 = E.CPU; 197 = E.IOH; 199 = E.AIE; 200 = E.USB; 201 = E.SAF; 216 = E.MB4; 217 = E.MB5; 218 = E.MB6; 219 = E.MB7; 241 = E.1; 245 = E.5; 246 = E.6; 247 = E.7; 253 = E.13 | |||
| HR | 504doc 40505 | Fault record 5 | Low byte = fault code (H00xx). | UINT16 | Read | 0 = No fault; 16 = E.OC1; 17 = E.OC2; 18 = E.OC3; 32 = E.OV1; 33 = E.OV2; 34 = E.OV3; 48 = E.THT; 49 = E.THM; 64 = E.FIN; 82 = E.ILF; 96 = E.OLT; 112 = E.BE; 128 = E.GF; 129 = E.LF; 144 = E.OHT; 160 = E.OPT; 161 = E.OP1; 176 = E.PE; 177 = E.PUE; 178 = E.RET; 179 = E.PE2; 192 = E.CPU; 197 = E.IOH; 199 = E.AIE; 200 = E.USB; 201 = E.SAF; 216 = E.MB4; 217 = E.MB5; 218 = E.MB6; 219 = E.MB7; 241 = E.1; 245 = E.5; 246 = E.6; 247 = E.7; 253 = E.13 | |||
| HR | 505doc 40506 | Fault record 6 | Low byte = fault code (H00xx). | UINT16 | Read | 0 = No fault; 16 = E.OC1; 17 = E.OC2; 18 = E.OC3; 32 = E.OV1; 33 = E.OV2; 34 = E.OV3; 48 = E.THT; 49 = E.THM; 64 = E.FIN; 82 = E.ILF; 96 = E.OLT; 112 = E.BE; 128 = E.GF; 129 = E.LF; 144 = E.OHT; 160 = E.OPT; 161 = E.OP1; 176 = E.PE; 177 = E.PUE; 178 = E.RET; 179 = E.PE2; 192 = E.CPU; 197 = E.IOH; 199 = E.AIE; 200 = E.USB; 201 = E.SAF; 216 = E.MB4; 217 = E.MB5; 218 = E.MB6; 219 = E.MB7; 241 = E.1; 245 = E.5; 246 = E.6; 247 = E.7; 253 = E.13 | |||
| HR | 506doc 40507 | Fault record 7 | Low byte = fault code (H00xx). | UINT16 | Read | 0 = No fault; 16 = E.OC1; 17 = E.OC2; 18 = E.OC3; 32 = E.OV1; 33 = E.OV2; 34 = E.OV3; 48 = E.THT; 49 = E.THM; 64 = E.FIN; 82 = E.ILF; 96 = E.OLT; 112 = E.BE; 128 = E.GF; 129 = E.LF; 144 = E.OHT; 160 = E.OPT; 161 = E.OP1; 176 = E.PE; 177 = E.PUE; 178 = E.RET; 179 = E.PE2; 192 = E.CPU; 197 = E.IOH; 199 = E.AIE; 200 = E.USB; 201 = E.SAF; 216 = E.MB4; 217 = E.MB5; 218 = E.MB6; 219 = E.MB7; 241 = E.1; 245 = E.5; 246 = E.6; 247 = E.7; 253 = E.13 | |||
| HR | 507doc 40508 | Fault record 8 | Low byte = fault code (H00xx). | UINT16 | Read | 0 = No fault; 16 = E.OC1; 17 = E.OC2; 18 = E.OC3; 32 = E.OV1; 33 = E.OV2; 34 = E.OV3; 48 = E.THT; 49 = E.THM; 64 = E.FIN; 82 = E.ILF; 96 = E.OLT; 112 = E.BE; 128 = E.GF; 129 = E.LF; 144 = E.OHT; 160 = E.OPT; 161 = E.OP1; 176 = E.PE; 177 = E.PUE; 178 = E.RET; 179 = E.PE2; 192 = E.CPU; 197 = E.IOH; 199 = E.AIE; 200 = E.USB; 201 = E.SAF; 216 = E.MB4; 217 = E.MB5; 218 = E.MB6; 219 = E.MB7; 241 = E.1; 245 = E.5; 246 = E.6; 247 = E.7; 253 = E.13 | |||
| HR | 1000doc 41001 | Pr.1 Maximum frequency | UINT16 | × 0.01 | Hz | Read/write | |||
| HR | 1001doc 41002 | Pr.2 Minimum frequency | UINT16 | × 0.01 | Hz | Read/write | |||
| HR | 1003doc 41004 | Pr.4 Multi-speed setting (high speed) | UINT16 | × 0.01 | Hz | Read/write | |||
| HR | 1004doc 41005 | Pr.5 Multi-speed setting (middle speed) | UINT16 | × 0.01 | Hz | Read/write | |||
| HR | 1005doc 41006 | Pr.6 Multi-speed setting (low speed) | UINT16 | × 0.01 | Hz | Read/write | |||
| HR | 1078doc 41079 | Pr.79 Operation mode selection | UINT16 | Read/write | 0 = External/PU switchover (External at power-on); 1 = Fixed PU operation; 2 = Fixed External operation (NET switchable); 3 = External/PU combined mode 1; 4 = External/PU combined mode 2; 6 = Switchover mode; 7 = External operation (PU interlock) | ||||
| HR | 1116doc 41117 | Pr.117 PU communication station number | 0 = no reply (broadcast only); set 1-247. | UINT16 | Read/write | ||||
| HR | 1117doc 41118 | Pr.118 PU communication speed | Setting x 100 = bps (initial 192 = 19200). | UINT16 | Read/write | ||||
| HR | 1119doc 41120 | Pr.120 PU communication parity check | UINT16 | Read/write | 0 = No parity, 2 stop bits; 1 = Odd parity, 1 stop bit; 2 = Even parity, 1 stop bit | ||||
| HR | 1121doc 41122 | Pr.122 PU communication check time interval | 0 = E.PUE as soon as NET mode is entered; 9999 = no check. | UINT16 | × 0.1 | s | Read/write | ||
| HR | 1342doc 41343 | Pr.343 Communication error count | Modbus RTU error count (RAM, cleared at reset). | UINT16 | Read | ||||
| HR | 1501doc 41502 | Pr.502 Stop mode selection at communication error | UINT16 | Read/write | 0 = Coast to stop, E.PUE; 1 = Decelerate, E.PUE after stop; 2 = Decelerate, E.PUE after stop, automatic restart on removal; 3 = Coast to stop, E.PUE | ||||
| HR | 1548doc 41549 | Pr.549 Protocol selection | UINT16 | Read/write | 0 = Mitsubishi inverter protocol (computer link); 1 = MODBUS RTU |
Notes on this map
- All registers are single 16-bit words.
- Modbus RTU runs on the PU connector (RJ45-type RS-485 port), configured with the PU communication parameters Pr.117-Pr.122, not on separate terminals.
- Frequency registers use 0.01 Hz; with Pr.37 (speed display) set they switch to 1 r/min. The 0.01 Hz unit for 40014/40015 is from the same manual's computer-link set-frequency description (H0000-HFFFF in 0.01 Hz increments).
- Fault history registers hold the fault code in the low byte; the values listed are the manual's fault code list.
- Parameters with a 9999 (function off) setting, such as the communication check interval, are listed with their normal increment; the manual does not say how the 9999 setting itself is encoded on the wire, so read the parameter back after setting it from the panel.
- Parameters 0-999 sit at 41000 + Pr. number; calibration parameters C2-C25 have their own registers and are not listed. Pr.7/Pr.8 are left out (increment depends on Pr.21 / capacity).
- Left out because the sign is not stated: motor torque 40207 and PID deviation 40254. Option terminal monitors 40258-40260 (FR-A7AX/A7AY E kit) are not listed.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Mitsubishi Electric FR-E700 compact inverter (PU connector, Modbus RTU)
What Modbus registers does the Mitsubishi Electric FR-E700 compact inverter (PU connector, Modbus RTU) have?
This map lists 51 registers: 51 holding registers. 22 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Mitsubishi Electric FR-E700 compact inverter (PU connector, Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual prints Modicon-style register numbers (40002, 41004) and states: starting address = register number - 40001. Its example reads 41004 (Pr.4) with start address H03EB (1003).
What are the minimum Modbus registers to integrate the Mitsubishi Electric FR-E700 compact inverter (PU connector, Modbus RTU)?
Start with HR 8 Inverter status / control input instruction (Run/stop command and inverter status); HR 9 Operation mode / inverter setting (Operation mode (write H0014 for NET)); HR 13 Running frequency (RAM) (Frequency command (RAM)); HR 200 Output frequency / speed (Output frequency); HR 201 Output current (Output current); HR 500 Fault record 1 (Latest fault code).
How do I enable Modbus control of the Mitsubishi Electric FR-E700 compact inverter (PU connector, Modbus RTU)?
Pr.549 = 1 selects Modbus RTU on the PU connector; set Pr.117 (station), Pr.118 (speed) and Pr.120 (parity) and reset. The PU connector must be the NET command source (Pr.550 = 2, or 9999 with no communication option fitted). Operation and frequency commands need NET mode (write H0014 to 40010; allowed depending on Pr.79/Pr.340).
What happens when the Mitsubishi Electric FR-E700 compact inverter (PU connector, Modbus RTU) loses Modbus communication?
Pr.122 is the communication check interval (0.1-999.8 s) with Pr.502 choosing coast or decelerate on E.PUE. Initial value 0 trips E.PUE as soon as the drive enters NET mode, so set 9999 or an interval before switching.
Where is the official Mitsubishi Electric FR-E700 compact inverter (PU connector, Modbus RTU) Modbus documentation?
The source is FR-E700 Instruction Manual (Applied) (IB(NA)-0600277ENG-G), revision 2018-07, published free by Mitsubishi Electric at https://dl.mitsubishielectric.com/dl/fa/document/manual/inv/ib0600277eng/ib0600277engg.pdf.
More Mitsubishi Electric Modbus register maps
- Variable frequency drive
Mitsubishi Electric FR-A700 inverter (RS-485 terminals, Modbus RTU)
FR-A700 series inverters (FR-A720-0.4K to 90K, FR-A740-0.4K to 500K) using the RS-485 terminals with Pr.549 = 1 (Modbus-RTU); Instruction Manual (Applied) revision E.
Also known as: FR-A720, FR-A740, FR-A700 series - Variable frequency drive
Mitsubishi Electric FR-A800 inverter (RS-485 terminals, Modbus RTU)
FR-A800 series inverters (FR-A820/A840/A842/A846, incl. -GF) using the built-in RS-485 terminals with Pr.549 = 1 (MODBUS RTU); Instruction Manual (Detailed) revision P.
Also known as: FR-A820, FR-A840, FR-A842, FR-A846, FR-A800-GF, FR-A800 series - Variable frequency drive
Mitsubishi Electric FR-D700 compact inverter (PU connector, Modbus RTU)
FR-D700 series (FR-D720/D740/D720S/D710W) using the PU connector with Pr.549 = 1; Instruction Manual (Applied) revision H.
Also known as: FR-D720, FR-D740, FR-D720S, FR-D710W - Variable frequency drive
Mitsubishi Electric FR-F800 fan and pump inverter (RS-485 terminals, Modbus RTU)
FR-F800 series inverters (FR-F820/F840/F842/F846) using the built-in RS-485 terminals with Pr.549 = 1 (MODBUS RTU); Instruction Manual (Detailed) revision G.
Also known as: FR-F820, FR-F840, FR-F842, FR-F846, FR-F800 series - VRF / split AC gateway
Mitsubishi Electric MelcoBEMS MINI (A1M) gateway for Air-To-Air split units
Procon MelcoBEMS MINI (A1M) on the CN105/CN92 connector of a Mitsubishi Electric Air-To-Air indoor unit, installation manual v1.1.11 (firmware 3.0.28 for revision 2-4 hardware, 3.1.1 for revision 5).
Also known as: MelcoBEMS MINI (A1M), A1M, Procon A1M, MelcoBEMS MINI - Air handler (heat recovery ventilation unit)
Mitsubishi Electric MelcoBEMS MINI (A1M+ / A1M) gateway for Lossnay heat recovery ventilators (LGH and VL series)
Procon MelcoBEMS MINI A1M+ (manual v1.0.3, firmware 4.1.1) on Lossnay LGH-15..200RVX-E1, LGH-150..250RVXT-E1 and VL-250..500CZPVU-R/L-E; the older A1M (manual v1.1.11) prints the identical Lossnay table.
Also known as: A1M+ Lossnay, MelcoBEMS MINI Lossnay, Procon A1M+, Procon A1M, A1M, Lossnay LGH-RVX Modbus, LGH-15RVX-E1, LGH-200RVX-E1, LGH-150RVXT-E1, LGH-250RVXT-E1, VL-250CZPVU-R-E, VL-500CZPVU-L-E, Lossnay VL Vertical - VRF / split AC gateway
Mitsubishi Electric MelcoBEMS MINI (A1M+) gateway for Air-To-Air split units (M, S and P series)
MelcoBEMS MINI (A1M+) on the CN105 connector of a Mitsubishi Electric Air-To-Air indoor unit (M series MSZ/MFZ/MLZ, S series SEZ/SLZ, P series per Appendix A), installation manual v1.0.3, firmware 4.1.1.
Also known as: A1M+, MelcoBEMS MINI, Procon A1M+, MelcoBEMS MINI A1M PLUS, A1M+ ATA - Chiller / heat pump gateway (VRF / split AC gateway)
Mitsubishi Electric MelcoBEMS MINI (A1M+) gateway for CAHV / CRHV / QAHV heat pumps and EAHV / EACV e-series chillers
Procon MelcoBEMS MINI (A1M+) firmware 4.1.0 on Mitsubishi Electric CAHV and CRHV heat pumps, QAHV CO2 heat pumps and EAHV / EACV e-series chillers (master and slave units); holding-register table only.
Also known as: A1M+, MelcoBEMS MINI, Procon A1M+, CAHV, CRHV, QAHV, EAHV, EACV, e-series chiller - Heat pump (VRF / split AC gateway)
Mitsubishi Electric MelcoBEMS MINI (A1M+) gateway for Ecodan FTC4/FTC5/FTC6 air-to-water systems
Procon MelcoBEMS MINI (A1M+) firmware 4.1.0 connected to an Ecodan FTC4, FTC5 or FTC6 air-to-water controller; holding-register table only.
Also known as: A1M+, MelcoBEMS MINI, Procon A1M+, Ecodan FTC4, Ecodan FTC5, Ecodan FTC6 - Air handler DX interface (VRF / split AC gateway)
Mitsubishi Electric PAC-IF013B-E / PAC-SIF013B-E air handling unit interface (Modbus RTU)
PAC-IF013B-E and PAC-SIF013B-E interface controllers linking a Mitsubishi Electric outdoor unit to an AHU coil, Modbus manual dated September 2015 (RG79F084H01).
Also known as: PAC-IF013B-E, PAC-SIF013B-E, PAC-(S)IF013B-E - VRF / split AC gateway (retail controller)
Mitsubishi Electric Procon MelcoRETAIL MINI controller for Air-To-Air split units
Procon MelcoRETAIL MINI on the CN105/CN92 connector of Mitsubishi Electric M, S and P series Air-To-Air indoor units, installation manual v1.0.6, firmware 1.0.3.
Also known as: MelcoRETAIL MINI, Procon MelcoRETAIL MINI - Air handler (computer room air conditioner)
Mitsubishi Electric s-MEXT-G00 computer room air conditioner (ME28 relC)
Mitsubishi Electric (Hydronics & IT Cooling) s-MEXT-G00 006-044 close-control units with ME28-relC software and the Modbus serial board.
Also known as: s-MEXT, s-MEXT-G00 006-044, s-MEXT G00, ME28 relC
Other variable frequency drives register maps
- Variable frequency drive
Schneider Electric Altivar Process ATV900 (ATV930/ATV950, embedded Modbus serial / Modbus TCP)
Altivar Process ATV900 drives (ATV930, ATV950) on the built-in Modbus serial port and the embedded Ethernet port (Modbus TCP). Per Communication Parameters file NHA80944 V4.6.
Also known as: ATV900, ATV930, ATV950, Altivar Process 900, Altivar 930, Altivar 950, ATV930U, ATV930D, ATV950U - Air handler (rotary heat exchanger drive controller)
Swegon SILVER C / SILVER RX rotary heat exchanger controller (Modbus RTU)
The rotary heat exchanger (rotor) drive controller in Swegon SILVER C RX air handling units, per sheet SILVERCModbusHX.201115.
Also known as: SILVER RX heat exchanger controller, SILVER C RX rotor drive, DRHX, SILVERCModbusHX - Variable frequency drive
Toshiba TOSVERT VF-AS3 inverter (RS485 Modbus RTU)
Toshiba TOSVERT VF-AS3 inverters on RS485 port 1 or 2 with the protocol set to MODBUS (F807/F827 = 1); RS485 Communication Function Instruction Manual E6582143.
Also known as: VF-AS3, TOSVERT VF-AS3 - Variable frequency drive
Yaskawa F7 drive (CIMR-F7U, legacy) - Modbus RTU
Yaskawa F7 (CIMR-F7U) general-purpose drives using the built-in RS-422/485 terminals R+/R-/S+/S-, per user manual TM.F7.01 Appendix D, with parameter and monitor addresses from TM.F7.11.
Also known as: CIMR-F7U, F7U, F7 Drive - Variable frequency drive
Yaskawa HV600 HVAC fan and pump drive (MEMOBUS/Modbus RTU)
Yaskawa HV600 drives using the built-in RS-485 port with H5-08 = 0 (MEMOBUS/Modbus), per technical reference SIEPC71061732 revision F.
Also known as: CIPR-HV60, HV600 HVAC drive - Variable frequency drive (HVAC bypass package)
Yaskawa P1000 Bypass for industrial fans and pumps (MEMOBUS/Modbus RTU)
P1000 Bypass bypass controller RS-485 port with Z3-01 = 0 (Modbus); Technical Manual SIEP YAIP1B 01D, appendix D.
Also known as: P1000 Bypass, P1B
All variable frequency drives Modbus register maps →
Source: FR-E700 Instruction Manual (Applied) · IB(NA)-0600277ENG-G · rev. 2018-07. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.