Variable frequency drive · Modbus register map

Mitsubishi Electric FR-E700 compact inverter (PU connector, Modbus RTU) Modbus register map

Updated 19 November 2026

Short answer

Mitsubishi Electric's compact general-purpose inverter. The PU connector can run Modbus RTU, giving system variables (control word, operation mode, frequency command) at 40002-40015, a real-time monitor block from 40201, fault history at 40501 and every parameter at 41000 + parameter number. This map covers control, status, monitors, fault codes and the communication parameters.

This page lists 51 Modbus registers for the Mitsubishi Electric FR-E700 compact inverter (PU connector, Modbus RTU) — 22 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Mitsubishi Electric’s own free documentation (linked below) and checked against it.

Manufacturer
Mitsubishi Electric
Model
FR-E700 compact inverter (PU connector, Modbus RTU)
Equipment type
Variable frequency drive
Registers
51 (22 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Default serial
19200 baud, 8E1
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
Also known as
FR-E720, FR-E740, FR-E720S, FR-E710W, FR-E700-SC
Source document
FR-E700 Instruction Manual (Applied) · IB(NA)-0600277ENG-G · rev. 2018-07
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Mitsubishi Electric FR-E700 compact inverter (PU connector, Modbus RTU)

Integration in brief

Set Pr.549 = 1, Pr.117 to 1-247 and Pr.122 to 9999 (or a real interval), reset, then switch to NET mode by writing H0014 to 40010. Write the frequency to 40014 (0.01 Hz) and run bits to 40009; poll 40009, 40201, 40202 and 40501.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 8Inverter status / control input instructionBITMAP16Run/stop command and inverter statusRead/write
HR 9Operation mode / inverter settingUINT16Operation mode (write H0014 for NET)Read/write
HR 13Running frequency (RAM)UINT16Frequency command (RAM)Read/write
HR 200Output frequency / speedUINT16Output frequencyRead
HR 201Output currentUINT16Output currentRead
HR 500Fault record 1UINT16Latest fault codeRead/write

Enable Modbus control & writes

Pr.549 = 1 selects Modbus RTU on the PU connector; set Pr.117 (station), Pr.118 (speed) and Pr.120 (parity) and reset. The PU connector must be the NET command source (Pr.550 = 2, or 9999 with no communication option fitted). Operation and frequency commands need NET mode (write H0014 to 40010; allowed depending on Pr.79/Pr.340).

Communication loss & watchdog

Pr.122 is the communication check interval (0.1-999.8 s) with Pr.502 choosing coast or decelerate on E.PUE. Initial value 0 trips E.PUE as soon as the drive enters NET mode, so set 9999 or an interval before switching.

Byte order & addressing

Network setup

Watch out for

Mitsubishi Electric FR-E700 compact inverter (PU connector, Modbus RTU) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

51 of 51 shown
Mitsubishi Electric FR-E700 compact inverter (PU connector, Modbus RTU) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR1doc 40002Inverter resetWrite any value to reset the inverter.UINT16Write
HR2doc 40003Parameter clearWrite H965A.UINT16Write
HR3doc 40004All parameter clearWrite H99AA.UINT16Write
HR5doc 40006Parameter clear (keep comm settings)Write H5A96; communication parameters are kept.UINT16Write
HR6doc 40007All parameter clear (keep comm settings)Write HAA99; communication parameters are kept.UINT16Write
HR8doc 40009Inverter status / control input instructionWrite = control input, read = inverter status.BITMAP16Read/writebit 0 = Write: stop command / Read: RUN (inverter running); bit 1 = Write: forward rotation / Read: during forward rotation; bit 2 = Write: reverse rotation / Read: during reverse rotation; bit 3 = Write: RH (high speed) / Read: SU (up to frequency); bit 4 = Write: RM (middle speed) / Read: OL (overload); bit 5 = Write: RL (low speed); bit 6 = Read: FU (frequency detection); bit 7 = Write: RT (second function) / Read: ABC (fault); bit 8 = Write: AU (current input selection); bit 10 = Write: MRS (output stop); bit 12 = Write: RES (reset); bit 15 = Read: fault occurrence
HR9doc 40010Operation mode / inverter settingRead = current mode; write H0010 EXT, H0011 PU, H0014 NET.UINT16Read/write0 = Read: EXT; 1 = Read: PU; 2 = Read: EXT JOG; 3 = Read: PU JOG; 4 = Read: NET; 5 = Read: PU + EXT; 16 = Write: EXT (H0010); 17 = Write: PU (H0011); 20 = Write: NET (H0014)
HR13doc 40014Running frequency (RAM)Frequency command, not stored in EEPROM.UINT16× 0.01HzRead/write
HR14doc 40015Running frequency (EEPROM)Frequency command, also stored in EEPROM.UINT16× 0.01HzWrite
HR200doc 40201Output frequency / speed0.01 Hz, or 1 r/min when Pr.37 = 0.01-9998.UINT16× 0.01HzRead
HR201doc 40202Output currentUINT16× 0.01ARead
HR202doc 40203Output voltageUINT16× 0.1VRead
HR204doc 40205Set frequency / speed setting0.01 Hz, or 1 r/min when Pr.37 = 0.01-9998.UINT16× 0.01HzRead
HR207doc 40208Converter output voltageDC bus voltage.UINT16× 0.1VRead
HR208doc 40209Regenerative brake dutyUINT16× 0.1%Read
HR209doc 40210Electronic thermal relay load factorUINT16× 0.1%Read
HR210doc 40211Output current peak valueUINT16× 0.01ARead
HR211doc 40212Converter output voltage peak valueUINT16× 0.1VRead
HR213doc 40214Output powerUINT16× 0.01kWRead
HR214doc 40215Input terminal status1 = on.BITMAP16Readbit 0 = STF; bit 1 = STR; bit 4 = RL; bit 5 = RM; bit 6 = RH; bit 8 = MRS; bit 10 = RES
HR215doc 40216Output terminal status1 = on.BITMAP16Readbit 0 = RUN; bit 4 = FU; bit 5 = ABC
HR219doc 40220Cumulative energization timeUINT16hRead
HR222doc 40223Actual operation timeUINT16hRead
HR223doc 40224Motor load factorOutput current as % of rated inverter current.UINT16× 0.1%Read
HR224doc 40225Cumulative powerUINT16kWhRead
HR251doc 40252PID set pointUINT16× 0.1%Read
HR252doc 40253PID measured valueUINT16× 0.1%Read
HR260doc 40261Motor thermal load factorUINT16× 0.1%Read
HR261doc 40262Inverter thermal load factorUINT16× 0.1%Read
HR262doc 40263Cumulative power 2Only on units built after the version-up noted in the manual.UINT16× 0.01kWhRead
HR500doc 40501Fault record 1Low byte = fault code (H00xx). Write any value to clear history.UINT16Read/write0 = No fault; 16 = E.OC1; 17 = E.OC2; 18 = E.OC3; 32 = E.OV1; 33 = E.OV2; 34 = E.OV3; 48 = E.THT; 49 = E.THM; 64 = E.FIN; 82 = E.ILF; 96 = E.OLT; 112 = E.BE; 128 = E.GF; 129 = E.LF; 144 = E.OHT; 160 = E.OPT; 161 = E.OP1; 176 = E.PE; 177 = E.PUE; 178 = E.RET; 179 = E.PE2; 192 = E.CPU; 197 = E.IOH; 199 = E.AIE; 200 = E.USB; 201 = E.SAF; 216 = E.MB4; 217 = E.MB5; 218 = E.MB6; 219 = E.MB7; 241 = E.1; 245 = E.5; 246 = E.6; 247 = E.7; 253 = E.13
HR501doc 40502Fault record 2Low byte = fault code (H00xx).UINT16Read0 = No fault; 16 = E.OC1; 17 = E.OC2; 18 = E.OC3; 32 = E.OV1; 33 = E.OV2; 34 = E.OV3; 48 = E.THT; 49 = E.THM; 64 = E.FIN; 82 = E.ILF; 96 = E.OLT; 112 = E.BE; 128 = E.GF; 129 = E.LF; 144 = E.OHT; 160 = E.OPT; 161 = E.OP1; 176 = E.PE; 177 = E.PUE; 178 = E.RET; 179 = E.PE2; 192 = E.CPU; 197 = E.IOH; 199 = E.AIE; 200 = E.USB; 201 = E.SAF; 216 = E.MB4; 217 = E.MB5; 218 = E.MB6; 219 = E.MB7; 241 = E.1; 245 = E.5; 246 = E.6; 247 = E.7; 253 = E.13
HR502doc 40503Fault record 3Low byte = fault code (H00xx).UINT16Read0 = No fault; 16 = E.OC1; 17 = E.OC2; 18 = E.OC3; 32 = E.OV1; 33 = E.OV2; 34 = E.OV3; 48 = E.THT; 49 = E.THM; 64 = E.FIN; 82 = E.ILF; 96 = E.OLT; 112 = E.BE; 128 = E.GF; 129 = E.LF; 144 = E.OHT; 160 = E.OPT; 161 = E.OP1; 176 = E.PE; 177 = E.PUE; 178 = E.RET; 179 = E.PE2; 192 = E.CPU; 197 = E.IOH; 199 = E.AIE; 200 = E.USB; 201 = E.SAF; 216 = E.MB4; 217 = E.MB5; 218 = E.MB6; 219 = E.MB7; 241 = E.1; 245 = E.5; 246 = E.6; 247 = E.7; 253 = E.13
HR503doc 40504Fault record 4Low byte = fault code (H00xx).UINT16Read0 = No fault; 16 = E.OC1; 17 = E.OC2; 18 = E.OC3; 32 = E.OV1; 33 = E.OV2; 34 = E.OV3; 48 = E.THT; 49 = E.THM; 64 = E.FIN; 82 = E.ILF; 96 = E.OLT; 112 = E.BE; 128 = E.GF; 129 = E.LF; 144 = E.OHT; 160 = E.OPT; 161 = E.OP1; 176 = E.PE; 177 = E.PUE; 178 = E.RET; 179 = E.PE2; 192 = E.CPU; 197 = E.IOH; 199 = E.AIE; 200 = E.USB; 201 = E.SAF; 216 = E.MB4; 217 = E.MB5; 218 = E.MB6; 219 = E.MB7; 241 = E.1; 245 = E.5; 246 = E.6; 247 = E.7; 253 = E.13
HR504doc 40505Fault record 5Low byte = fault code (H00xx).UINT16Read0 = No fault; 16 = E.OC1; 17 = E.OC2; 18 = E.OC3; 32 = E.OV1; 33 = E.OV2; 34 = E.OV3; 48 = E.THT; 49 = E.THM; 64 = E.FIN; 82 = E.ILF; 96 = E.OLT; 112 = E.BE; 128 = E.GF; 129 = E.LF; 144 = E.OHT; 160 = E.OPT; 161 = E.OP1; 176 = E.PE; 177 = E.PUE; 178 = E.RET; 179 = E.PE2; 192 = E.CPU; 197 = E.IOH; 199 = E.AIE; 200 = E.USB; 201 = E.SAF; 216 = E.MB4; 217 = E.MB5; 218 = E.MB6; 219 = E.MB7; 241 = E.1; 245 = E.5; 246 = E.6; 247 = E.7; 253 = E.13
HR505doc 40506Fault record 6Low byte = fault code (H00xx).UINT16Read0 = No fault; 16 = E.OC1; 17 = E.OC2; 18 = E.OC3; 32 = E.OV1; 33 = E.OV2; 34 = E.OV3; 48 = E.THT; 49 = E.THM; 64 = E.FIN; 82 = E.ILF; 96 = E.OLT; 112 = E.BE; 128 = E.GF; 129 = E.LF; 144 = E.OHT; 160 = E.OPT; 161 = E.OP1; 176 = E.PE; 177 = E.PUE; 178 = E.RET; 179 = E.PE2; 192 = E.CPU; 197 = E.IOH; 199 = E.AIE; 200 = E.USB; 201 = E.SAF; 216 = E.MB4; 217 = E.MB5; 218 = E.MB6; 219 = E.MB7; 241 = E.1; 245 = E.5; 246 = E.6; 247 = E.7; 253 = E.13
HR506doc 40507Fault record 7Low byte = fault code (H00xx).UINT16Read0 = No fault; 16 = E.OC1; 17 = E.OC2; 18 = E.OC3; 32 = E.OV1; 33 = E.OV2; 34 = E.OV3; 48 = E.THT; 49 = E.THM; 64 = E.FIN; 82 = E.ILF; 96 = E.OLT; 112 = E.BE; 128 = E.GF; 129 = E.LF; 144 = E.OHT; 160 = E.OPT; 161 = E.OP1; 176 = E.PE; 177 = E.PUE; 178 = E.RET; 179 = E.PE2; 192 = E.CPU; 197 = E.IOH; 199 = E.AIE; 200 = E.USB; 201 = E.SAF; 216 = E.MB4; 217 = E.MB5; 218 = E.MB6; 219 = E.MB7; 241 = E.1; 245 = E.5; 246 = E.6; 247 = E.7; 253 = E.13
HR507doc 40508Fault record 8Low byte = fault code (H00xx).UINT16Read0 = No fault; 16 = E.OC1; 17 = E.OC2; 18 = E.OC3; 32 = E.OV1; 33 = E.OV2; 34 = E.OV3; 48 = E.THT; 49 = E.THM; 64 = E.FIN; 82 = E.ILF; 96 = E.OLT; 112 = E.BE; 128 = E.GF; 129 = E.LF; 144 = E.OHT; 160 = E.OPT; 161 = E.OP1; 176 = E.PE; 177 = E.PUE; 178 = E.RET; 179 = E.PE2; 192 = E.CPU; 197 = E.IOH; 199 = E.AIE; 200 = E.USB; 201 = E.SAF; 216 = E.MB4; 217 = E.MB5; 218 = E.MB6; 219 = E.MB7; 241 = E.1; 245 = E.5; 246 = E.6; 247 = E.7; 253 = E.13
HR1000doc 41001Pr.1 Maximum frequencyUINT16× 0.01HzRead/write
HR1001doc 41002Pr.2 Minimum frequencyUINT16× 0.01HzRead/write
HR1003doc 41004Pr.4 Multi-speed setting (high speed)UINT16× 0.01HzRead/write
HR1004doc 41005Pr.5 Multi-speed setting (middle speed)UINT16× 0.01HzRead/write
HR1005doc 41006Pr.6 Multi-speed setting (low speed)UINT16× 0.01HzRead/write
HR1078doc 41079Pr.79 Operation mode selectionUINT16Read/write0 = External/PU switchover (External at power-on); 1 = Fixed PU operation; 2 = Fixed External operation (NET switchable); 3 = External/PU combined mode 1; 4 = External/PU combined mode 2; 6 = Switchover mode; 7 = External operation (PU interlock)
HR1116doc 41117Pr.117 PU communication station number0 = no reply (broadcast only); set 1-247.UINT16Read/write
HR1117doc 41118Pr.118 PU communication speedSetting x 100 = bps (initial 192 = 19200).UINT16Read/write
HR1119doc 41120Pr.120 PU communication parity checkUINT16Read/write0 = No parity, 2 stop bits; 1 = Odd parity, 1 stop bit; 2 = Even parity, 1 stop bit
HR1121doc 41122Pr.122 PU communication check time interval0 = E.PUE as soon as NET mode is entered; 9999 = no check.UINT16× 0.1sRead/write
HR1342doc 41343Pr.343 Communication error countModbus RTU error count (RAM, cleared at reset).UINT16Read
HR1501doc 41502Pr.502 Stop mode selection at communication errorUINT16Read/write0 = Coast to stop, E.PUE; 1 = Decelerate, E.PUE after stop; 2 = Decelerate, E.PUE after stop, automatic restart on removal; 3 = Coast to stop, E.PUE
HR1548doc 41549Pr.549 Protocol selectionUINT16Read/write0 = Mitsubishi inverter protocol (computer link); 1 = MODBUS RTU

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Mitsubishi Electric FR-E700 compact inverter (PU connector, Modbus RTU)

What Modbus registers does the Mitsubishi Electric FR-E700 compact inverter (PU connector, Modbus RTU) have?

This map lists 51 registers: 51 holding registers. 22 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Mitsubishi Electric FR-E700 compact inverter (PU connector, Modbus RTU) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual prints Modicon-style register numbers (40002, 41004) and states: starting address = register number - 40001. Its example reads 41004 (Pr.4) with start address H03EB (1003).

What are the minimum Modbus registers to integrate the Mitsubishi Electric FR-E700 compact inverter (PU connector, Modbus RTU)?

Start with HR 8 Inverter status / control input instruction (Run/stop command and inverter status); HR 9 Operation mode / inverter setting (Operation mode (write H0014 for NET)); HR 13 Running frequency (RAM) (Frequency command (RAM)); HR 200 Output frequency / speed (Output frequency); HR 201 Output current (Output current); HR 500 Fault record 1 (Latest fault code).

How do I enable Modbus control of the Mitsubishi Electric FR-E700 compact inverter (PU connector, Modbus RTU)?

Pr.549 = 1 selects Modbus RTU on the PU connector; set Pr.117 (station), Pr.118 (speed) and Pr.120 (parity) and reset. The PU connector must be the NET command source (Pr.550 = 2, or 9999 with no communication option fitted). Operation and frequency commands need NET mode (write H0014 to 40010; allowed depending on Pr.79/Pr.340).

What happens when the Mitsubishi Electric FR-E700 compact inverter (PU connector, Modbus RTU) loses Modbus communication?

Pr.122 is the communication check interval (0.1-999.8 s) with Pr.502 choosing coast or decelerate on E.PUE. Initial value 0 trips E.PUE as soon as the drive enters NET mode, so set 9999 or an interval before switching.

Where is the official Mitsubishi Electric FR-E700 compact inverter (PU connector, Modbus RTU) Modbus documentation?

The source is FR-E700 Instruction Manual (Applied) (IB(NA)-0600277ENG-G), revision 2018-07, published free by Mitsubishi Electric at https://dl.mitsubishielectric.com/dl/fa/document/manual/inv/ib0600277eng/ib0600277engg.pdf.

More Mitsubishi Electric Modbus register maps

Other variable frequency drives register maps

All variable frequency drives Modbus register maps →

Source: FR-E700 Instruction Manual (Applied) · IB(NA)-0600277ENG-G · rev. 2018-07. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.