- SILVER C / SILVER RX rotary heat exchanger controller (Modbus RTU)
Air handler (rotary heat exchanger drive controller) · Modbus register map
Swegon SILVER C / SILVER RX rotary heat exchanger controller (Modbus RTU) Modbus register map
Updated 19 November 2026
SILVER C RX air handling units use a separate controller to drive the rotary heat recovery wheel. It is a Modbus RTU slave with coils for start/stop, alarm reset and settings, discrete inputs for rotor-guard and drive alarms, input registers for output, motor and rotor speed, current, power, temperature and versions, and holding registers for the speed set point, speed limits, ramps and alternative communication settings.
This page lists 57 Modbus registers for the Swegon SILVER C / SILVER RX rotary heat exchanger controller (Modbus RTU) — 25 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Swegon’s own free documentation (linked below) and checked against it.
- Manufacturer
- Swegon
- Model
- SILVER C / SILVER RX rotary heat exchanger controller (Modbus RTU)
- Equipment type
- Air handler (rotary heat exchanger drive controller)
- Registers
- 57 (25 writable)
- Transport
- Modbus RTU
- Default unit ID
- 79
- Default serial
- 38400 baud, 8N1
- Documented addressing
- 0-based (the number printed is the address on the wire)
- Also known as
- SILVER RX heat exchanger controller, SILVER C RX rotor drive, DRHX, SILVERCModbusHX
Integration notes: Swegon SILVER C / SILVER RX rotary heat exchanger controller (Modbus RTU)
Set coil 7 (Control mode) to 0 for Modbus, write the speed set point to holding 0 and start with coil 0. Read input registers 2 (output %), 16 (rotor speed) and the discrete-input alarms 0-15.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| CO 0 | Motor ON/OFF | BIT | Motor on/off | Read/write |
| CO 7 | Control mode | BIT | Control mode Modbus / 0-10 V | Read/write |
| HR 0 | Setpoint / PrcSet | UINT16 | Speed set point | Read/write |
| IR 2 | PrcOut | UINT16 | Output % | Read |
| IR 16 | Rotor Speed Out | UINT16 | Rotor speed | Read |
| DI 0 | Rotorguard Alarm | BIT | Rotor guard alarm | Read |
| DI 10 | Internal Stop | BIT | Rotor blocked | Read |
| CO 1 | Reset Alarms | BIT | Reset alarms | Read/write |
Enable Modbus control & writes
Coil 7 Control mode: 0 = Modbus, 1 = 0-10 V (factory 1). Communication settings are changed over Modbus with a tool.
Byte order & addressing
- Write coils with 0xFF00 for ON (function 05).
- With Autodetect communication on (coil 9, default), the controller keeps answering on ID 79 / 38400 / no parity even after switching to the alternative settings.
Network setup
- Default ID 79, 38400 baud, no parity, 1 stop bit.
- Alternative ID, baud, parity and stop bits are in holding 13-16 and take effect when coil 8 is set.
Watch out for
- This is the rotor drive controller only, not the AHU's main controller.
Swegon SILVER C / SILVER RX rotary heat exchanger controller (Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| CO | 0doc 0x0001 | Motor ON/OFF | 1 = on. | BIT | Read/write | 0 = Off; 1 = On | |||
| CO | 1doc 0x0002 | Reset Alarms | Write 1 to reset alarms. | BIT | Read/write | ||||
| CO | 3doc 0x0004 | Rotation direction | 1 = counter-clockwise. | BIT | Read/write | 0 = Clockwise; 1 = Counter-clockwise | |||
| CO | 7doc 0x0008 | Control mode | Speed command source. | BIT | Read/write | 0 = Modbus; 1 = 0-10 V | |||
| CO | 8doc 0x0009 | Use altern. comm. settings | 1 = use the alternative communication settings. | BIT | Read/write | ||||
| CO | 9doc 0x0010 | Autodetect communication | 1 = always also answer on the default settings. | BIT | Read/write | ||||
| CO | 10doc 0x0011 | Analog start signal | 1 = enable. | BIT | Read/write | ||||
| CO | 11doc 0x0012 | Autodetect control mode | 1 = enable. | BIT | Read/write | ||||
| CO | 14doc 0x0015 | High speed resolution | Sets speed register resolution. | BIT | Read/write | 0 = 0.1 rpm; 1 = 0.01 rpm | |||
| CO | 15doc 0x0016 | K-factor for Modbus | 1 = K-factor not used for Modbus. | BIT | Read/write | ||||
| CO | 17doc 0xx17 | Enable auto saving of UDF | 1 = user data stored automatically. | BIT | Read/write | ||||
| DI | 0doc 1x0001 | Rotorguard Alarm | 1 = Alarm. | BIT | Read | ||||
| DI | 1doc 1x0002 | V LO Alarm | 1 = Alarm (low voltage). | BIT | Read | ||||
| DI | 2doc 1x0003 | V HI Alarm | 1 = Alarm (high voltage). | BIT | Read | ||||
| DI | 3doc 1x0004 | I HI Alarm (Motor out short) | 1 = Alarm. | BIT | Read | ||||
| DI | 4doc 1x0005 | Temperature High | 1 = Warning. | BIT | Read | ||||
| DI | 8doc 1x0009 | Rotorguard Signal | 1 = Pulse from rotation sensor. | BIT | Read | ||||
| DI | 9doc 1x0010 | Overload / I_Limit | 1 = Warning. | BIT | Read | ||||
| DI | 10doc 1x0011 | Internal Stop | 1 = Alarm (stop). | BIT | Read | ||||
| DI | 11doc 1x0012 | Rotor Blocked | 1 = Alarm. | BIT | Read | ||||
| DI | 12doc 1x0013 | EEPROM error | 1 = Warning. | BIT | Read | ||||
| DI | 14doc 1x0015 | Motor Phase Error | 1 = Alarm. | BIT | Read | ||||
| DI | 15doc 1x0016 | Ripple | 1 = Warning. | BIT | Read | ||||
| DI | 19doc 1x0020 | MOC in bootloader | 1 = Alarm. | BIT | Read | ||||
| DI | 23doc 1x0024 | Rotation OK | 1 = rotor turning OK. | BIT | Read | ||||
| DI | 24doc 1x0025 | Test function active | 1 = active. | BIT | Read | ||||
| DI | 25doc 1x0026 | Purging active | 1 = purge running. | BIT | Read | ||||
| IR | 0doc 3x0001 / 0x0000 | DHX Type | Controller type code 0-14. | UINT16 | Read | ||||
| IR | 2doc 3x0003 / 0x0002 | PrcOut | Output, 0-100.00 %. | UINT16 | × 0.01 | % | Read | ||
| IR | 3doc 3x0004 / 0x0003 | Intern Temp | Internal controller temperature. | INT16 | × 0.01 | °C | Read | ||
| IR | 4doc 3x0005 / 0x0004 | Motor Speed Out | Motor speed. | UINT16 | × 0.01 | rpm | Read | ||
| IR | 5doc 3x0006 / 0x0005 | V In | Supply voltage. | UINT16 | V | Read | |||
| IR | 6doc 3x0007 / 0x0006 | I Out (RMS) | Motor current. | UINT16 | mA | Read | |||
| IR | 7doc 3x0008 / 0x0007 | Power In | Input power. | UINT16 | W | Read | |||
| IR | 9doc 3x0010 / 0x0009 | Operation Day | Operating days. | UINT16 | days | Read | |||
| IR | 10doc 3x0011 / 0x000A | Operation Minutes | Minutes within the current day, 0-1439. | UINT16 | min | Read | |||
| IR | 11doc 3x0012 / 0x000B | I Ripple | Current ripple. | UINT16 | mA | Read | |||
| IR | 12doc 3x0013 / 0x000C | V Ripple | Voltage ripple. | UINT16 | V | Read | |||
| IR | 13doc 3x0014 / 0x000D | Config file variant | Two ASCII characters (AA-ZZ). | STRING[2] | Read | ||||
| IR | 14doc 3x0015 / 0x000E | Config file version | UINT16 | × 0.01 | Read | ||||
| IR | 15doc 3x0016 / 0x000F | MOC SW version | Motor controller software version. | UINT16 | × 0.01 | Read | |||
| IR | 16doc 3x0017 / 0x0010 | Rotor Speed Out | Rotor speed. | UINT16 | × 0.01 | rpm | Read | ||
| IR | 17doc 3x0018 / 0x0011 | Torque | Motor torque. | UINT16 | × 0.01 | Nm | Read | ||
| HR | 0doc 4x0001 / 0x0000 | Setpoint / PrcSet | Speed set point when control mode = Modbus, 0-100.00 %. | UINT16 | × 0.01 | % | Read/write | ||
| HR | 1doc 4x0002 / 0x0001 | Min. Motor Speed | UINT16 | × 0.01 | rpm | Read/write | |||
| HR | 2doc 4x0003 / 0x0002 | Max. Motor Speed | UINT16 | × 0.01 | rpm | Read/write | |||
| HR | 3doc 4x0004 / 0x0003 | Start I Out (Boost) | Start current. | UINT16 | mA | Read/write | |||
| HR | 4doc 4x0005 / 0x0004 | Start Time (Boost) | UINT16 | s | Read/write | ||||
| HR | 8doc 4x0009 / 0x0008 | Prc Holding Torque | Holding torque, % of max. | UINT16 | × 0.1 | % | Read/write | ||
| HR | 9doc 4x0010 / 0x0009 | UpRampTime | Ramp-up time, 15-300 s. | UINT16 | s | Read/write | |||
| HR | 10doc 4x0011 / 0x000A | DownRampTime | Ramp-down time, 15-300 s. | UINT16 | s | Read/write | |||
| HR | 11doc 4x0012 / 0x000B | SwitchMode | Motor switching frequency. | UINT16 | Read/write | 0 = Auto; 1 = 8 kHz; 2 = 10 kHz | |||
| HR | 12doc 4x0013 / 0x000C | DHX Type | Controller type setting. | UINT16 | Read/write | ||||
| HR | 13doc 4x0014 / 0x000D | Alternative Modbus ID | Alternative slave ID, 1-247. | UINT16 | Read/write | ||||
| HR | 14doc 4x0015 / 0x000E | Alternative BaudRate | UINT16 | Read/write | 0 = 9600; 1 = 19200; 2 = 38400; 3 = 57600; 4 = 115200 | ||||
| HR | 15doc 4x0016 / 0x000F | Alternative Parity | UINT16 | Read/write | 0 = None; 1 = Odd; 2 = Even | ||||
| HR | 16doc 4x0017 / 0x0010 | Alternative Stop Bits | UINT16 | Read/write | 0 = Invalid; 1 = 1; 2 = 2 |
Notes on this map
- Coil and discrete-input tables print the address in decimal and the register reference with a 0x/1x prefix in decimal (e.g. 0x0010 = address 9); input and holding tables print the address in hex.
- The last coil is printed with register '0xx17' and address 17; the address column is used.
- Page 2 has a second communication table (address 54, even parity, 2 stop bits); the 'Modbus addressing' section and the footnote on p. 3 both give ID 79, 38400 baud, no parity, 1 stop bit, which are used as defaults here.
- Intern Temp (range -50.00 to 150.00 °C) is typed INT16; the sheet does not state signedness.
- Footnote 4 on I Ripple is not printed in the sheet.
- All values are 16-bit; there are no 32-bit registers.
- Input registers printed 3x0020-3x0029 (MOC Boot SW, motor/rotor/user-data config variant and version, V DC Bus peak, V Motor peak) are left out: from that row on the sheet's hex Address column equals the register number instead of one lower (3x0020 is printed with 0x0014), so the wire address cannot be settled.
- Speed registers are listed at 0.01 rpm, which applies with coil 14 High speed resolution = 1 (factory setting); with coil 14 = 0 the resolution is 0.1 rpm.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Swegon SILVER C / SILVER RX rotary heat exchanger controller (Modbus RTU)
What Modbus registers does the Swegon SILVER C / SILVER RX rotary heat exchanger controller (Modbus RTU) have?
This map lists 57 registers: 11 coils, 16 discrete inputs, 16 input registers, 14 holding registers. 25 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Swegon SILVER C / SILVER RX rotary heat exchanger controller (Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Each table prints a register reference (0x0001, 1x0001, 3x0001, 4x0001) and an Address column one lower (0, or 0x0000 in hex). The Address column is the wire address: 4x0001 Setpoint is holding address 0.
What are the minimum Modbus registers to integrate the Swegon SILVER C / SILVER RX rotary heat exchanger controller (Modbus RTU)?
Start with CO 0 Motor ON/OFF (Motor on/off); CO 7 Control mode (Control mode Modbus / 0-10 V); HR 0 Setpoint / PrcSet (Speed set point); IR 2 PrcOut (Output %); IR 16 Rotor Speed Out (Rotor speed); DI 0 Rotorguard Alarm (Rotor guard alarm); DI 10 Internal Stop (Rotor blocked); CO 1 Reset Alarms (Reset alarms).
How do I enable Modbus control of the Swegon SILVER C / SILVER RX rotary heat exchanger controller (Modbus RTU)?
Coil 7 Control mode: 0 = Modbus, 1 = 0-10 V (factory 1). Communication settings are changed over Modbus with a tool.
Where is the official Swegon SILVER C / SILVER RX rotary heat exchanger controller (Modbus RTU) Modbus documentation?
The source is Modbus, rotary heat exchanger controls SILVER RX (SILVERCModbusHX.201115), published free by Swegon at https://www.swegon.com/globalassets/digizuite/12064-en-silvercrx_modbus_other_en.pdf.
More Swegon Modbus register maps
- Thermostat / room controller (chilled beam, fan coil water circuits)
Swegon CONDUCTOR W1 room controller (waterborne cooling/heating, Modbus RTU)
Swegon CONDUCTOR W1 room controller, software 1.38 and later (technical manual updated 2015-06-15).
Also known as: CONDUCTOR RE W1, Conductor W1, 942334001 - Thermostat / room controller (chilled beam with supply and extract air dampers)
Swegon CONDUCTOR W3 room controller (air and water, Modbus RTU)
Swegon CONDUCTOR W3 room controller, software 1.38 and later (technical manual updated 2015-06-15).
Also known as: CONDUCTOR RE W3, Conductor W3 - Thermostat / room controller (chilled beam with measured airflow and CO2)
Swegon CONDUCTOR W4 room controller (airflow and water, Modbus RTU)
Swegon CONDUCTOR W4 room controller, software 1.12 (technical manual updated 2014-11-21).
Also known as: CONDUCTOR RE W4, CONDUCTOR RE W4 1, Conductor W4 - Actuator / valve (ventilation damper and VAV actuator)
Swegon REACT damper / VAV actuator (Modbus RTU, 2018 sheet)
Swegon REACT demand-controlled-ventilation dampers with the Modbus actuators named in the sheet (309C-024-150-MB/SL8/ST15/SWE, 227VM-024-**-MB/SWE), sheet dated 2018-11-08.
Also known as: REACT A, REACT Modbus, Swegon REACT damper, 309C-024-150-MB/SL8/ST15/SWE, 227VM-024-MB/SWE - Actuator / valve (comfort module air damper)
Swegon REACT Parasol Zenith with Belimo actuator (Modbus RTU)
Swegon REACT Parasol Zenith comfort modules fitted with the Belimo Modbus actuator; Swegon Modbus settings sheet dated 2022-08-10.
Also known as: Parasol Zenith REACT, REACT damper actuator - Air handler fan motor control
Swegon SILVER C fan motor control (RX/PX/CX/SD, generation E/F)
The EC/FC fan motor controllers inside Swegon SILVER C air handling units, generation E/F, document SILVERCModbus.210809.
Also known as: SILVER C RX, SILVER C PX, SILVER C CX, SILVER C SD, SILVER C generation E, SILVER C generation F - Air handler (heat recovery unit controller)
Swegon TAC5 DG/DM/DT controller (Global HRglobal, HRup, HRflat, HRtotal, HRmural)
Swegon (Global) TAC5 DG, DM and DT regulation boards with the SAT MODBUS (RTU) or SAT WIFI/ETHERNET (TCP) satellite; TAC5 + MODBUS TABLE Cid 050338 (2021-09-20). The TAC5 SC/F single-flow boards use other registers and are not covered.
Also known as: TAC5 DG, TAC5 DM, TAC5 DT, Global HRglobal, Global HRup, Global HRflat, Global HRtotal, Global HRmural, SAT MODBUS - Air handler (heat recovery unit controller)
Swegon TAC6 controller (Global units)
Swegon (Global) units with the TAC6 regulation board and a Modbus satellite; TAC6 + MODBUS TABLE Cid 050360 (2021-05-20).
Also known as: Global TAC6, SAT WIFI-ETHERNET (TAC6)
Other variable frequency drives register maps
- Variable frequency drive
Toshiba TOSVERT VF-AS3 inverter (RS485 Modbus RTU)
Toshiba TOSVERT VF-AS3 inverters on RS485 port 1 or 2 with the protocol set to MODBUS (F807/F827 = 1); RS485 Communication Function Instruction Manual E6582143.
Also known as: VF-AS3, TOSVERT VF-AS3 - Variable frequency drive
Yaskawa F7 drive (CIMR-F7U, legacy) - Modbus RTU
Yaskawa F7 (CIMR-F7U) general-purpose drives using the built-in RS-422/485 terminals R+/R-/S+/S-, per user manual TM.F7.01 Appendix D, with parameter and monitor addresses from TM.F7.11.
Also known as: CIMR-F7U, F7U, F7 Drive - Variable frequency drive
Yaskawa HV600 HVAC fan and pump drive (MEMOBUS/Modbus RTU)
Yaskawa HV600 drives using the built-in RS-485 port with H5-08 = 0 (MEMOBUS/Modbus), per technical reference SIEPC71061732 revision F.
Also known as: CIPR-HV60, HV600 HVAC drive - Variable frequency drive (HVAC bypass package)
Yaskawa P1000 Bypass for industrial fans and pumps (MEMOBUS/Modbus RTU)
P1000 Bypass bypass controller RS-485 port with Z3-01 = 0 (Modbus); Technical Manual SIEP YAIP1B 01D, appendix D.
Also known as: P1000 Bypass, P1B - Variable frequency drive (HVAC bypass package)
Yaskawa Z1000 Bypass for HVAC fans and pumps (MEMOBUS/Modbus RTU)
Z1000 Bypass bypass controller RS-485 port with Z3-01 = 0 (Modbus); Technical Manual SIEP YAIZ1B 01F, appendix D.
Also known as: Z1000 Bypass, Z1B1 - Variable frequency drive
ABB ACS180 machinery drive (embedded Modbus RTU)
ACS180 drives running the machinery control program, built-in EIA-485 Modbus RTU terminal (embedded fieldbus, EFB), addressing mode 0 (default); firmware manual 3AXD50000467860 Rev D.
Also known as: ACS180-04, ACS180 machinery control program
All variable frequency drives Modbus register maps →
Source: Modbus, rotary heat exchanger controls SILVER RX · SILVERCModbusHX.201115. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.