Air handler (rotary heat exchanger drive controller) · Modbus register map

Swegon SILVER C / SILVER RX rotary heat exchanger controller (Modbus RTU) Modbus register map

Updated 19 November 2026

Short answer

SILVER C RX air handling units use a separate controller to drive the rotary heat recovery wheel. It is a Modbus RTU slave with coils for start/stop, alarm reset and settings, discrete inputs for rotor-guard and drive alarms, input registers for output, motor and rotor speed, current, power, temperature and versions, and holding registers for the speed set point, speed limits, ramps and alternative communication settings.

This page lists 57 Modbus registers for the Swegon SILVER C / SILVER RX rotary heat exchanger controller (Modbus RTU) — 25 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Swegon’s own free documentation (linked below) and checked against it.

Manufacturer
Swegon
Model
SILVER C / SILVER RX rotary heat exchanger controller (Modbus RTU)
Equipment type
Air handler (rotary heat exchanger drive controller)
Registers
57 (25 writable)
Transport
Modbus RTU
Default unit ID
79
Default serial
38400 baud, 8N1
Documented addressing
0-based (the number printed is the address on the wire)
Also known as
SILVER RX heat exchanger controller, SILVER C RX rotor drive, DRHX, SILVERCModbusHX
Source document
Modbus, rotary heat exchanger controls SILVER RX · SILVERCModbusHX.201115
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Swegon SILVER C / SILVER RX rotary heat exchanger controller (Modbus RTU)

Integration in brief

Set coil 7 (Control mode) to 0 for Modbus, write the speed set point to holding 0 and start with coil 0. Read input registers 2 (output %), 16 (rotor speed) and the discrete-input alarms 0-15.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
CO 0Motor ON/OFFBITMotor on/offRead/write
CO 7Control modeBITControl mode Modbus / 0-10 VRead/write
HR 0Setpoint / PrcSetUINT16Speed set pointRead/write
IR 2PrcOutUINT16Output %Read
IR 16Rotor Speed OutUINT16Rotor speedRead
DI 0Rotorguard AlarmBITRotor guard alarmRead
DI 10Internal StopBITRotor blockedRead
CO 1Reset AlarmsBITReset alarmsRead/write

Enable Modbus control & writes

Coil 7 Control mode: 0 = Modbus, 1 = 0-10 V (factory 1). Communication settings are changed over Modbus with a tool.

Byte order & addressing

Network setup

Watch out for

Swegon SILVER C / SILVER RX rotary heat exchanger controller (Modbus RTU) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

57 of 57 shown
Swegon SILVER C / SILVER RX rotary heat exchanger controller (Modbus RTU) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
CO0doc 0x0001Motor ON/OFF1 = on.BITRead/write0 = Off; 1 = On
CO1doc 0x0002Reset AlarmsWrite 1 to reset alarms.BITRead/write
CO3doc 0x0004Rotation direction1 = counter-clockwise.BITRead/write0 = Clockwise; 1 = Counter-clockwise
CO7doc 0x0008Control modeSpeed command source.BITRead/write0 = Modbus; 1 = 0-10 V
CO8doc 0x0009Use altern. comm. settings1 = use the alternative communication settings.BITRead/write
CO9doc 0x0010Autodetect communication1 = always also answer on the default settings.BITRead/write
CO10doc 0x0011Analog start signal1 = enable.BITRead/write
CO11doc 0x0012Autodetect control mode1 = enable.BITRead/write
CO14doc 0x0015High speed resolutionSets speed register resolution.BITRead/write0 = 0.1 rpm; 1 = 0.01 rpm
CO15doc 0x0016K-factor for Modbus1 = K-factor not used for Modbus.BITRead/write
CO17doc 0xx17Enable auto saving of UDF1 = user data stored automatically.BITRead/write
DI0doc 1x0001Rotorguard Alarm1 = Alarm.BITRead
DI1doc 1x0002V LO Alarm1 = Alarm (low voltage).BITRead
DI2doc 1x0003V HI Alarm1 = Alarm (high voltage).BITRead
DI3doc 1x0004I HI Alarm (Motor out short)1 = Alarm.BITRead
DI4doc 1x0005Temperature High1 = Warning.BITRead
DI8doc 1x0009Rotorguard Signal1 = Pulse from rotation sensor.BITRead
DI9doc 1x0010Overload / I_Limit1 = Warning.BITRead
DI10doc 1x0011Internal Stop1 = Alarm (stop).BITRead
DI11doc 1x0012Rotor Blocked1 = Alarm.BITRead
DI12doc 1x0013EEPROM error1 = Warning.BITRead
DI14doc 1x0015Motor Phase Error1 = Alarm.BITRead
DI15doc 1x0016Ripple1 = Warning.BITRead
DI19doc 1x0020MOC in bootloader1 = Alarm.BITRead
DI23doc 1x0024Rotation OK1 = rotor turning OK.BITRead
DI24doc 1x0025Test function active1 = active.BITRead
DI25doc 1x0026Purging active1 = purge running.BITRead
IR0doc 3x0001 / 0x0000DHX TypeController type code 0-14.UINT16Read
IR2doc 3x0003 / 0x0002PrcOutOutput, 0-100.00 %.UINT16× 0.01%Read
IR3doc 3x0004 / 0x0003Intern TempInternal controller temperature.INT16× 0.01°CRead
IR4doc 3x0005 / 0x0004Motor Speed OutMotor speed.UINT16× 0.01rpmRead
IR5doc 3x0006 / 0x0005V InSupply voltage.UINT16VRead
IR6doc 3x0007 / 0x0006I Out (RMS)Motor current.UINT16mARead
IR7doc 3x0008 / 0x0007Power InInput power.UINT16WRead
IR9doc 3x0010 / 0x0009Operation DayOperating days.UINT16daysRead
IR10doc 3x0011 / 0x000AOperation MinutesMinutes within the current day, 0-1439.UINT16minRead
IR11doc 3x0012 / 0x000BI RippleCurrent ripple.UINT16mARead
IR12doc 3x0013 / 0x000CV RippleVoltage ripple.UINT16VRead
IR13doc 3x0014 / 0x000DConfig file variantTwo ASCII characters (AA-ZZ).STRING[2]Read
IR14doc 3x0015 / 0x000EConfig file versionUINT16× 0.01Read
IR15doc 3x0016 / 0x000FMOC SW versionMotor controller software version.UINT16× 0.01Read
IR16doc 3x0017 / 0x0010Rotor Speed OutRotor speed.UINT16× 0.01rpmRead
IR17doc 3x0018 / 0x0011TorqueMotor torque.UINT16× 0.01NmRead
HR0doc 4x0001 / 0x0000Setpoint / PrcSetSpeed set point when control mode = Modbus, 0-100.00 %.UINT16× 0.01%Read/write
HR1doc 4x0002 / 0x0001Min. Motor SpeedUINT16× 0.01rpmRead/write
HR2doc 4x0003 / 0x0002Max. Motor SpeedUINT16× 0.01rpmRead/write
HR3doc 4x0004 / 0x0003Start I Out (Boost)Start current.UINT16mARead/write
HR4doc 4x0005 / 0x0004Start Time (Boost)UINT16sRead/write
HR8doc 4x0009 / 0x0008Prc Holding TorqueHolding torque, % of max.UINT16× 0.1%Read/write
HR9doc 4x0010 / 0x0009UpRampTimeRamp-up time, 15-300 s.UINT16sRead/write
HR10doc 4x0011 / 0x000ADownRampTimeRamp-down time, 15-300 s.UINT16sRead/write
HR11doc 4x0012 / 0x000BSwitchModeMotor switching frequency.UINT16Read/write0 = Auto; 1 = 8 kHz; 2 = 10 kHz
HR12doc 4x0013 / 0x000CDHX TypeController type setting.UINT16Read/write
HR13doc 4x0014 / 0x000DAlternative Modbus IDAlternative slave ID, 1-247.UINT16Read/write
HR14doc 4x0015 / 0x000EAlternative BaudRateUINT16Read/write0 = 9600; 1 = 19200; 2 = 38400; 3 = 57600; 4 = 115200
HR15doc 4x0016 / 0x000FAlternative ParityUINT16Read/write0 = None; 1 = Odd; 2 = Even
HR16doc 4x0017 / 0x0010Alternative Stop BitsUINT16Read/write0 = Invalid; 1 = 1; 2 = 2

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Swegon SILVER C / SILVER RX rotary heat exchanger controller (Modbus RTU)

What Modbus registers does the Swegon SILVER C / SILVER RX rotary heat exchanger controller (Modbus RTU) have?

This map lists 57 registers: 11 coils, 16 discrete inputs, 16 input registers, 14 holding registers. 25 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Swegon SILVER C / SILVER RX rotary heat exchanger controller (Modbus RTU) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Each table prints a register reference (0x0001, 1x0001, 3x0001, 4x0001) and an Address column one lower (0, or 0x0000 in hex). The Address column is the wire address: 4x0001 Setpoint is holding address 0.

What are the minimum Modbus registers to integrate the Swegon SILVER C / SILVER RX rotary heat exchanger controller (Modbus RTU)?

Start with CO 0 Motor ON/OFF (Motor on/off); CO 7 Control mode (Control mode Modbus / 0-10 V); HR 0 Setpoint / PrcSet (Speed set point); IR 2 PrcOut (Output %); IR 16 Rotor Speed Out (Rotor speed); DI 0 Rotorguard Alarm (Rotor guard alarm); DI 10 Internal Stop (Rotor blocked); CO 1 Reset Alarms (Reset alarms).

How do I enable Modbus control of the Swegon SILVER C / SILVER RX rotary heat exchanger controller (Modbus RTU)?

Coil 7 Control mode: 0 = Modbus, 1 = 0-10 V (factory 1). Communication settings are changed over Modbus with a tool.

Where is the official Swegon SILVER C / SILVER RX rotary heat exchanger controller (Modbus RTU) Modbus documentation?

The source is Modbus, rotary heat exchanger controls SILVER RX (SILVERCModbusHX.201115), published free by Swegon at https://www.swegon.com/globalassets/digizuite/12064-en-silvercrx_modbus_other_en.pdf.

More Swegon Modbus register maps

Other variable frequency drives register maps

All variable frequency drives Modbus register maps →

Source: Modbus, rotary heat exchanger controls SILVER RX · SILVERCModbusHX.201115. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.