Swegon REACT Parasol Zenith with Belimo actuator (Modbus RTU) Modbus register map

Updated 17 November 2026

Short answer

The REACT version of the Parasol Zenith comfort module uses a Belimo actuator with a Modbus RTU interface. Over the bus a BMS can set the damper or flow setpoint, force open/close/min/max, run adaption or test, and read position, relative and absolute airflow, sensor input, service flags and the bus-watchdog settings.

This page lists 27 Modbus registers for the Swegon REACT Parasol Zenith with Belimo actuator (Modbus RTU) — 11 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Swegon’s own free documentation (linked below) and checked against it.

Manufacturer
Swegon
Model
REACT Parasol Zenith with Belimo actuator (Modbus RTU)
Equipment type
Actuator / valve (comfort module air damper)
Registers
27 (11 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Default serial
19200 baud, 8E1
Documented addressing
0-based (the number printed is the address on the wire)
32-bit word order
CDAB low word first (word-swapped)
Also known as
Parasol Zenith REACT, REACT damper actuator
Source document
REACT Parasol Zenith - Modbus settings / Modbus-installningar (Belimo actuator) · rev. 2022-08-10
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Swegon REACT Parasol Zenith with Belimo actuator (Modbus RTU)

Integration in brief

Write the setpoint in 0.01 % to address 0 (with Setpoint Source = Bus) and read relative position (address 4) and relative or absolute flow (addresses 6-7). Use Override Control (address 1) to force open/close and the bus watchdog (addresses 108-109) for a safe position on comms loss.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 0SetpointUINT16Setpoint %Read/write
HR 1Override ControlUINT16Override controlRead/write
HR 4Relative PositionUINT16Relative positionRead
HR 6Relative volumetric flowUINT16Relative flowRead
HR 7Absolute volumetric flowUINT16Absolute flow m³/hRead
HR 104Malfunction and Service InformationBITMAP16Malfunction flagsRead
HR 118Setpoint SourceUINT16Setpoint sourceRead/write

Enable Modbus control & writes

Setpoint Source (address 118) must be Bus for Modbus setpoints. Bus termination is set with the actuator configuration tools.

Communication loss & watchdog

Bus Fail Position (address 108) and Timeout for Bus Watchdog (address 109, 0-3600 s; 0 = off). If neither setpoint nor override is rewritten within the timeout, the actuator goes to the fail position and sets bit 10 in address 104.

Byte order & addressing

Network setup

Watch out for

Swegon REACT Parasol Zenith with Belimo actuator (Modbus RTU) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

27 of 27 shown
Swegon REACT Parasol Zenith with Belimo actuator (Modbus RTU) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0doc No. 1 / Address 0SetpointActuator setpoint between Min (No. 106) and Max (No. 107).UINT16× 0.01%Read/write
HR1doc No. 2 / Address 1Override ControlUINT16Read/write0 = None; 1 = Open; 2 = Close; 3 = Min; 4 = Mid; 5 = Max
HR2doc No. 3 / Address 2CommandReturns to 0 after the command; Reset clears service info.UINT16Read/write0 = None; 1 = Adaption; 2 = Test; 3 = Sync; 4 = Reset
HR3doc No. 4 / Address 3Actuator TypeUINT16Read0 = Actuator not connected; 1 = Air / Water; 2 = VAV / EPIV; 3 = Fire; 4 = Energy Valve; 5 = 6-way EPIV
HR4doc No. 5 / Address 4Relative PositionUINT16× 0.01%Read
HR5doc No. 6 / Address 5Absolute PositionDegrees for rotary, mm for linear actuators.UINT16Read
HR6doc No. 7 / Address 6Relative volumetric flowPercent of Vnom.UINT16× 0.01%Read
HR7doc No. 8 / Address 7Absolute volumetric flow0 to Vnom; the unit column reads 'm³/h Pa'.UINT16m³/hRead
HR8doc No. 9 / Address 8Sensor 1 ValuemV if sensor type is Active, 0/1 if Switch.UINT16Read
HR10doc No. 11 / Address 10Absolute volumetric flow (unit selected)Flow in the unit chosen in No. 118; low word at No. 11.UINT32CDAB× 0.001Read
HR12doc No. 13 / Address 12Setpoint AnalogSetpoint when the actuator follows the analog signal.UINT16× 0.01%Read
HR99doc No. 100 / Address 99Bus TerminationShows whether the 120 ohm terminator is on; set it with the configuration tools.UINT16Read0 = Inactive; 1 = Active (120 ohm)
HR100doc No. 101 / Address 100Series Number 1st partUINT16Read
HR101doc No. 102 / Address 101Series Number 2nd partUINT16Read
HR102doc No. 103 / Address 102Series Number 4th partUINT16Read
HR103doc No. 104 / Address 103Firmware Versione.g. 302 = version 3.02.UINT16Read
HR104doc No. 105 / Address 104Malfunction and Service InformationBit-coded; more than one bit can be set.BITMAP16Readbit 1 = Mechanical travel increased; bit 2 = Actuator cannot move; bit 8 = Internal activity; bit 9 = Gear disengaged; bit 10 = Bus watchdog triggered
HR105doc No. 106 / Address 105VminMust be at most Vmax.UINT16× 0.01%Read/write
HR106doc No. 107 / Address 106VmaxMust be at least Vmin and above 20 %.UINT16× 0.01%Read/write
HR107doc No. 108 / Address 107Sensor 1 TypeUINT16Read/write0 = None; 1 = Active / Hybrid; 4 = Switch
HR108doc No. 109 / Address 108Bus Fail PositionPosition taken when the bus watchdog expires.UINT16Read/write0 = None / last setpoint; 1 = Fast close; 2 = Fast open; 3 = Mid position
HR109doc No. 110 / Address 109Timeout for Bus Watchdog0 = watchdog off, max 3600 s.UINT16sRead/write
HR110doc No. 111 / Address 110Nominal volumetric flowUINT16m³/hRead
HR112doc No. 113 / Address 112Nominal volumetric flow (unit selected)Vnom in the unit chosen in No. 118; low word at No. 113.UINT32CDAB× 0.001Read
HR116doc No. 117 / Address 116Control ModeUINT16Read/write0 = Position control; 1 = Flow control
HR117doc No. 118 / Address 117Unit Selection FlowUINT16Read/write0 = m³/s; 1 = m³/h; 2 = l/s; 3 = l/min; 4 = l/h; 5 = gpm; 6 = cfm
HR118doc No. 119 / Address 118Setpoint SourceUINT16Read/write0 = Analog (0-10 V on wire 3); 1 = Bus (Modbus No. 1)

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Swegon REACT Parasol Zenith with Belimo actuator (Modbus RTU)

What Modbus registers does the Swegon REACT Parasol Zenith with Belimo actuator (Modbus RTU) have?

This map lists 27 registers: 27 holding registers. 11 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Swegon REACT Parasol Zenith with Belimo actuator (Modbus RTU) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Every table gives both a register number (No.) and the protocol Address, with Address = No. - 1 (No. 1 = address 0). The Address column is used here; the 'documented' field shows both.

What byte order does the Swegon REACT Parasol Zenith with Belimo actuator (Modbus RTU) use for 32-bit values?

Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Swegon REACT Parasol Zenith with Belimo actuator (Modbus RTU)?

Start with HR 0 Setpoint (Setpoint %); HR 1 Override Control (Override control); HR 4 Relative Position (Relative position); HR 6 Relative volumetric flow (Relative flow); HR 7 Absolute volumetric flow (Absolute flow m³/h); HR 104 Malfunction and Service Information (Malfunction flags); HR 118 Setpoint Source (Setpoint source).

How do I enable Modbus control of the Swegon REACT Parasol Zenith with Belimo actuator (Modbus RTU)?

Setpoint Source (address 118) must be Bus for Modbus setpoints. Bus termination is set with the actuator configuration tools.

What happens when the Swegon REACT Parasol Zenith with Belimo actuator (Modbus RTU) loses Modbus communication?

Bus Fail Position (address 108) and Timeout for Bus Watchdog (address 109, 0-3600 s; 0 = off). If neither setpoint nor override is rewritten within the timeout, the actuator goes to the fail position and sets bit 10 in address 104.

Where is the official Swegon REACT Parasol Zenith with Belimo actuator (Modbus RTU) Modbus documentation?

The source is REACT Parasol Zenith - Modbus settings / Modbus-installningar (Belimo actuator), revision 2022-08-10, published free by Swegon at https://www.swegon.com/siteassets/_products-documents-archive/room-management-systems/_en/react_parasol_zenith-modbus-m.pdf.

More Swegon Modbus register maps

Other valves, actuators & sensors register maps

All valves, actuators & sensors Modbus register maps →

Source: REACT Parasol Zenith - Modbus settings / Modbus-installningar (Belimo actuator) · rev. 2022-08-10. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.