- Home
- Modbus register maps
- Swegon
- REACT Parasol Zenith with Belimo actuator (Modbus RTU)
Actuator / valve (comfort module air damper) · Modbus register map
Swegon REACT Parasol Zenith with Belimo actuator (Modbus RTU) Modbus register map
Updated 17 November 2026
The REACT version of the Parasol Zenith comfort module uses a Belimo actuator with a Modbus RTU interface. Over the bus a BMS can set the damper or flow setpoint, force open/close/min/max, run adaption or test, and read position, relative and absolute airflow, sensor input, service flags and the bus-watchdog settings.
This page lists 27 Modbus registers for the Swegon REACT Parasol Zenith with Belimo actuator (Modbus RTU) — 11 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Swegon’s own free documentation (linked below) and checked against it.
- Manufacturer
- Swegon
- Model
- REACT Parasol Zenith with Belimo actuator (Modbus RTU)
- Equipment type
- Actuator / valve (comfort module air damper)
- Registers
- 27 (11 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Default serial
- 19200 baud, 8E1
- Documented addressing
- 0-based (the number printed is the address on the wire)
- 32-bit word order
- CDAB low word first (word-swapped)
- Also known as
- Parasol Zenith REACT, REACT damper actuator
Integration notes: Swegon REACT Parasol Zenith with Belimo actuator (Modbus RTU)
Write the setpoint in 0.01 % to address 0 (with Setpoint Source = Bus) and read relative position (address 4) and relative or absolute flow (addresses 6-7). Use Override Control (address 1) to force open/close and the bus watchdog (addresses 108-109) for a safe position on comms loss.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 0 | Setpoint | UINT16 | Setpoint % | Read/write |
| HR 1 | Override Control | UINT16 | Override control | Read/write |
| HR 4 | Relative Position | UINT16 | Relative position | Read |
| HR 6 | Relative volumetric flow | UINT16 | Relative flow | Read |
| HR 7 | Absolute volumetric flow | UINT16 | Absolute flow m³/h | Read |
| HR 104 | Malfunction and Service Information | BITMAP16 | Malfunction flags | Read |
| HR 118 | Setpoint Source | UINT16 | Setpoint source | Read/write |
Enable Modbus control & writes
Setpoint Source (address 118) must be Bus for Modbus setpoints. Bus termination is set with the actuator configuration tools.
Communication loss & watchdog
Bus Fail Position (address 108) and Timeout for Bus Watchdog (address 109, 0-3600 s; 0 = off). If neither setpoint nor override is rewritten within the timeout, the actuator goes to the fail position and sets bit 10 in address 104.
Byte order & addressing
- Register numbers in the sheet start at 1; send Address = No. - 1.
- 32-bit flows are low word first.
Network setup
- External 120 ohm termination at the line ends; No. 100 shows whether the built-in terminator is active.
- Max 32 nodes without a repeater.
Watch out for
- Vmax must stay above 20 % and at or above Vmin.
Swegon REACT Parasol Zenith with Belimo actuator (Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0doc No. 1 / Address 0 | Setpoint | Actuator setpoint between Min (No. 106) and Max (No. 107). | UINT16 | × 0.01 | % | Read/write | ||
| HR | 1doc No. 2 / Address 1 | Override Control | UINT16 | Read/write | 0 = None; 1 = Open; 2 = Close; 3 = Min; 4 = Mid; 5 = Max | ||||
| HR | 2doc No. 3 / Address 2 | Command | Returns to 0 after the command; Reset clears service info. | UINT16 | Read/write | 0 = None; 1 = Adaption; 2 = Test; 3 = Sync; 4 = Reset | |||
| HR | 3doc No. 4 / Address 3 | Actuator Type | UINT16 | Read | 0 = Actuator not connected; 1 = Air / Water; 2 = VAV / EPIV; 3 = Fire; 4 = Energy Valve; 5 = 6-way EPIV | ||||
| HR | 4doc No. 5 / Address 4 | Relative Position | UINT16 | × 0.01 | % | Read | |||
| HR | 5doc No. 6 / Address 5 | Absolute Position | Degrees for rotary, mm for linear actuators. | UINT16 | Read | ||||
| HR | 6doc No. 7 / Address 6 | Relative volumetric flow | Percent of Vnom. | UINT16 | × 0.01 | % | Read | ||
| HR | 7doc No. 8 / Address 7 | Absolute volumetric flow | 0 to Vnom; the unit column reads 'm³/h Pa'. | UINT16 | m³/h | Read | |||
| HR | 8doc No. 9 / Address 8 | Sensor 1 Value | mV if sensor type is Active, 0/1 if Switch. | UINT16 | Read | ||||
| HR | 10doc No. 11 / Address 10 | Absolute volumetric flow (unit selected) | Flow in the unit chosen in No. 118; low word at No. 11. | UINT32 | CDAB | × 0.001 | Read | ||
| HR | 12doc No. 13 / Address 12 | Setpoint Analog | Setpoint when the actuator follows the analog signal. | UINT16 | × 0.01 | % | Read | ||
| HR | 99doc No. 100 / Address 99 | Bus Termination | Shows whether the 120 ohm terminator is on; set it with the configuration tools. | UINT16 | Read | 0 = Inactive; 1 = Active (120 ohm) | |||
| HR | 100doc No. 101 / Address 100 | Series Number 1st part | UINT16 | Read | |||||
| HR | 101doc No. 102 / Address 101 | Series Number 2nd part | UINT16 | Read | |||||
| HR | 102doc No. 103 / Address 102 | Series Number 4th part | UINT16 | Read | |||||
| HR | 103doc No. 104 / Address 103 | Firmware Version | e.g. 302 = version 3.02. | UINT16 | Read | ||||
| HR | 104doc No. 105 / Address 104 | Malfunction and Service Information | Bit-coded; more than one bit can be set. | BITMAP16 | Read | bit 1 = Mechanical travel increased; bit 2 = Actuator cannot move; bit 8 = Internal activity; bit 9 = Gear disengaged; bit 10 = Bus watchdog triggered | |||
| HR | 105doc No. 106 / Address 105 | Vmin | Must be at most Vmax. | UINT16 | × 0.01 | % | Read/write | ||
| HR | 106doc No. 107 / Address 106 | Vmax | Must be at least Vmin and above 20 %. | UINT16 | × 0.01 | % | Read/write | ||
| HR | 107doc No. 108 / Address 107 | Sensor 1 Type | UINT16 | Read/write | 0 = None; 1 = Active / Hybrid; 4 = Switch | ||||
| HR | 108doc No. 109 / Address 108 | Bus Fail Position | Position taken when the bus watchdog expires. | UINT16 | Read/write | 0 = None / last setpoint; 1 = Fast close; 2 = Fast open; 3 = Mid position | |||
| HR | 109doc No. 110 / Address 109 | Timeout for Bus Watchdog | 0 = watchdog off, max 3600 s. | UINT16 | s | Read/write | |||
| HR | 110doc No. 111 / Address 110 | Nominal volumetric flow | UINT16 | m³/h | Read | ||||
| HR | 112doc No. 113 / Address 112 | Nominal volumetric flow (unit selected) | Vnom in the unit chosen in No. 118; low word at No. 113. | UINT32 | CDAB | × 0.001 | Read | ||
| HR | 116doc No. 117 / Address 116 | Control Mode | UINT16 | Read/write | 0 = Position control; 1 = Flow control | ||||
| HR | 117doc No. 118 / Address 117 | Unit Selection Flow | UINT16 | Read/write | 0 = m³/s; 1 = m³/h; 2 = l/s; 3 = l/min; 4 = l/h; 5 = gpm; 6 = cfm | ||||
| HR | 118doc No. 119 / Address 118 | Setpoint Source | UINT16 | Read/write | 0 = Analog (0-10 V on wire 3); 1 = Bus (Modbus No. 1) |
Notes on this map
- The two 32-bit flow values are split as LowWord (lower 16 bits) at the first register and HighWord at the next, so they are CDAB; scale 0.001 in the unit chosen in No. 118.
- Registers No. 10, 112, 115 and 116 are unused (dash) and not listed.
- Absolute position (No. 6) is in degrees or mm depending on the actuator type.
- Default communication setting 14: 19200 baud, 8 data bits, even parity, 1 stop bit, 0 ms delay; also selectable 9600-115200 baud and 8N2, 8N1, 8E1, 8O1.
- Bus termination (No. 100) is read-only in the register overview but marked R/W in the description table, which also says it is set with the configuration tools; it is listed here as read-only.
- The Swedish column on page 5 places the LW/HW labels one row higher than the English text; the English description (No. 113 = lower 16 bits, No. 114 = upper 16 bits) and the overview table are followed here.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Swegon REACT Parasol Zenith with Belimo actuator (Modbus RTU)
What Modbus registers does the Swegon REACT Parasol Zenith with Belimo actuator (Modbus RTU) have?
This map lists 27 registers: 27 holding registers. 11 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Swegon REACT Parasol Zenith with Belimo actuator (Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Every table gives both a register number (No.) and the protocol Address, with Address = No. - 1 (No. 1 = address 0). The Address column is used here; the 'documented' field shows both.
What byte order does the Swegon REACT Parasol Zenith with Belimo actuator (Modbus RTU) use for 32-bit values?
Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Swegon REACT Parasol Zenith with Belimo actuator (Modbus RTU)?
Start with HR 0 Setpoint (Setpoint %); HR 1 Override Control (Override control); HR 4 Relative Position (Relative position); HR 6 Relative volumetric flow (Relative flow); HR 7 Absolute volumetric flow (Absolute flow m³/h); HR 104 Malfunction and Service Information (Malfunction flags); HR 118 Setpoint Source (Setpoint source).
How do I enable Modbus control of the Swegon REACT Parasol Zenith with Belimo actuator (Modbus RTU)?
Setpoint Source (address 118) must be Bus for Modbus setpoints. Bus termination is set with the actuator configuration tools.
What happens when the Swegon REACT Parasol Zenith with Belimo actuator (Modbus RTU) loses Modbus communication?
Bus Fail Position (address 108) and Timeout for Bus Watchdog (address 109, 0-3600 s; 0 = off). If neither setpoint nor override is rewritten within the timeout, the actuator goes to the fail position and sets bit 10 in address 104.
Where is the official Swegon REACT Parasol Zenith with Belimo actuator (Modbus RTU) Modbus documentation?
The source is REACT Parasol Zenith - Modbus settings / Modbus-installningar (Belimo actuator), revision 2022-08-10, published free by Swegon at https://www.swegon.com/siteassets/_products-documents-archive/room-management-systems/_en/react_parasol_zenith-modbus-m.pdf.
More Swegon Modbus register maps
- Thermostat / room controller (chilled beam, fan coil water circuits)
Swegon CONDUCTOR W1 room controller (waterborne cooling/heating, Modbus RTU)
Swegon CONDUCTOR W1 room controller, software 1.38 and later (technical manual updated 2015-06-15).
Also known as: CONDUCTOR RE W1, Conductor W1, 942334001 - Thermostat / room controller (chilled beam with supply and extract air dampers)
Swegon CONDUCTOR W3 room controller (air and water, Modbus RTU)
Swegon CONDUCTOR W3 room controller, software 1.38 and later (technical manual updated 2015-06-15).
Also known as: CONDUCTOR RE W3, Conductor W3 - Thermostat / room controller (chilled beam with measured airflow and CO2)
Swegon CONDUCTOR W4 room controller (airflow and water, Modbus RTU)
Swegon CONDUCTOR W4 room controller, software 1.12 (technical manual updated 2014-11-21).
Also known as: CONDUCTOR RE W4, CONDUCTOR RE W4 1, Conductor W4 - Actuator / valve (ventilation damper and VAV actuator)
Swegon REACT damper / VAV actuator (Modbus RTU, 2018 sheet)
Swegon REACT demand-controlled-ventilation dampers with the Modbus actuators named in the sheet (309C-024-150-MB/SL8/ST15/SWE, 227VM-024-**-MB/SWE), sheet dated 2018-11-08.
Also known as: REACT A, REACT Modbus, Swegon REACT damper, 309C-024-150-MB/SL8/ST15/SWE, 227VM-024-MB/SWE - Air handler (rotary heat exchanger drive controller)
Swegon SILVER C / SILVER RX rotary heat exchanger controller (Modbus RTU)
The rotary heat exchanger (rotor) drive controller in Swegon SILVER C RX air handling units, per sheet SILVERCModbusHX.201115.
Also known as: SILVER RX heat exchanger controller, SILVER C RX rotor drive, DRHX, SILVERCModbusHX - Air handler fan motor control
Swegon SILVER C fan motor control (RX/PX/CX/SD, generation E/F)
The EC/FC fan motor controllers inside Swegon SILVER C air handling units, generation E/F, document SILVERCModbus.210809.
Also known as: SILVER C RX, SILVER C PX, SILVER C CX, SILVER C SD, SILVER C generation E, SILVER C generation F - Air handler (heat recovery unit controller)
Swegon TAC5 DG/DM/DT controller (Global HRglobal, HRup, HRflat, HRtotal, HRmural)
Swegon (Global) TAC5 DG, DM and DT regulation boards with the SAT MODBUS (RTU) or SAT WIFI/ETHERNET (TCP) satellite; TAC5 + MODBUS TABLE Cid 050338 (2021-09-20). The TAC5 SC/F single-flow boards use other registers and are not covered.
Also known as: TAC5 DG, TAC5 DM, TAC5 DT, Global HRglobal, Global HRup, Global HRflat, Global HRtotal, Global HRmural, SAT MODBUS - Air handler (heat recovery unit controller)
Swegon TAC6 controller (Global units)
Swegon (Global) units with the TAC6 regulation board and a Modbus satellite; TAC6 + MODBUS TABLE Cid 050360 (2021-05-20).
Also known as: Global TAC6, SAT WIFI-ETHERNET (TAC6)
Other valves, actuators & sensors register maps
- Sensor (CO2 / pressure)
Teracom TSM400-4-CP Modbus CO2 and barometric pressure sensor
TSM400-4-CP per the Teracom TSM400-4-CP user manual TSM400-4-CP-R1.9.
Also known as: TSM400-4-CP - Sensor (dew point transmitter)
Vaisala DMT143 miniature dew point transmitter (Modbus RTU)
DMT143 dew point transmitters ordered with the Modbus RTU option (user guide M211435EN-L).
Also known as: DMT143, DRYCAP DMT143 - Sensor (humidity and temperature module)
Vaisala HMM170 humidity module (Modbus RTU)
HMM170 OEM humidity and temperature module with the Modbus RTU interface (user guide M212259EN-D).
Also known as: HMM170, HUMICAP HMM170 - Sensor (transformer oil monitor)
Vaisala MHT410 moisture, hydrogen and temperature transmitter for transformer oil (Modbus RTU)
MHT410 transformer oil monitor, Modbus RTU on the RS-485 screw terminals (user guide M211737EN-J).
Also known as: MHT410 - Sensor
VTS CO2-SENS-D-MODRTU
VTS CO2-SENS-D-MODRTU duct CO2 transducer (MH-Z19B sensing module), manual ver. 2.0 (11.2021).
Also known as: CO2 transducer CO2-SENS-D-MODRTU, VTS duct CO2 sensor - Sensor (limit controller)
Yokogawa UTAdvanced UT35A-L limit controller
Yokogawa UT35A-L limit controllers with RS-485 (Modbus RTU/ASCII); process monitoring D registers from IM 05P07A01-01EN chapter 12.
Also known as: UT35A-L
All valves, actuators & sensors Modbus register maps →
Source: REACT Parasol Zenith - Modbus settings / Modbus-installningar (Belimo actuator) · rev. 2022-08-10. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.