Actuator / valve (ventilation damper and VAV actuator) · Modbus register map

Swegon REACT damper / VAV actuator (Modbus RTU, 2018 sheet) Modbus register map

Updated 19 November 2026

Short answer

Swegon's REACT dampers for demand-controlled ventilation can be fitted with a Modbus RTU actuator. All points are holding registers read with function 03 and written one at a time with 06: set point, override and command, actuator type, relative and absolute position and flow, an optional analog output, flow limits, bus-failure action, set point source mode, Modbus address and flow unit.

This page lists 18 Modbus registers for the Swegon REACT damper / VAV actuator (Modbus RTU, 2018 sheet) — 12 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Swegon’s own free documentation (linked below) and checked against it.

Manufacturer
Swegon
Model
REACT damper / VAV actuator (Modbus RTU, 2018 sheet)
Equipment type
Actuator / valve (ventilation damper and VAV actuator)
Registers
18 (12 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Documented addressing
0-based (the number printed is the address on the wire)
Also known as
REACT A, REACT Modbus, Swegon REACT damper, 309C-024-150-MB/SL8/ST15/SWE, 227VM-024-MB/SWE
Source document
REACT Modbus · rev. 2018-11-08
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Swegon REACT damper / VAV actuator (Modbus RTU, 2018 sheet)

Integration in brief

Set register 122 to 1 (or 2) so the set point comes from Modbus, then write the set point to register 0 and read relative position (4) and flow (6/7).

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 0Set pointUINT16Set pointRead/write
HR 4Relative positionUINT16Relative positionRead
HR 6Relative flowUINT16Relative flowRead
HR 7Absolute flowUINT16Absolute flowRead
HR 122Mode signal set point analog outputUINT16Set point source modeRead/write
HR 108Bus fail positionUINT16Bus fail positionRead/write

Enable Modbus control & writes

Register 122 Mode: 1 = set point via Modbus register 0 (0 = analog input, then register 0 is read-only).

Communication loss & watchdog

Bus fail position (108): 1 closes, 2 opens the damper when no bus traffic for 120 s; 0 disables monitoring.

Byte order & addressing

Network setup

Watch out for

Swegon REACT damper / VAV actuator (Modbus RTU, 2018 sheet) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

18 of 18 shown
Swegon REACT damper / VAV actuator (Modbus RTU, 2018 sheet) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0Set pointDamper / flow set point, 0-10000 = 0-100 %. Read-only when register 122 = 0.UINT16× 0.01%Read/write
HR1Override controlUINT16Read/write0 = Override control not available; 1 = Open; 2 = Close; 3 = Min; 4 = Max
HR2CommandUINT16Read/write1 = Adaption; 4 = Controller reset
HR3Device IDActuator type.UINT16Read1 = Standard actuator; 2 = VAV; 3 = Fire damper
HR4Relative position0-10000 = 0-100 %; 65535 = not supported.UINT16× 0.01%Read
HR5Absolute position0-65000 = 0-650.00 degrees; 65535 = not supported.UINT16× 0.01°Read
HR6Relative flowVAV flow, 0-10000 = 0-100 %.UINT16× 0.01%Read
HR7Absolute flowVAV flow in m³/h or l/s (unit per register 201).UINT16m³/h / l/sRead
HR10Analog outputOptional analog output, 0-10000 mV; see register 122.UINT16mVRead/write
HR103Software versionUINT16Read
HR105Min value relativeMinimum flow, % of nominal (0-10000 = 0-100 %).UINT16× 0.01%Read/write
HR106Max value relativeMaximum flow, % of nominal (0-10000 = 0-100 %).UINT16× 0.01%Read/write
HR108Bus fail positionAction on loss of bus (120 s timeout).UINT16Read/write0 = No bus monitoring; 1 = Close at timeout; 2 = Open at timeout
HR120Min value absoluteMinimum flow in m³/h or l/s.UINT16m³/h / l/sRead/write
HR121Max value absoluteMaximum flow in m³/h or l/s.UINT16m³/h / l/sRead/write
HR122Mode signal set point analog outputWhere the set point comes from and what the analog output shows.UINT16Read/write0 = Set point from analog in 1; output = absolute position; 1 = Set point via Modbus register 0; output = absolute position; 2 = Register 0 scaled min-max flow; output = register 10; 3 = Set point from analog in 1; output = register 10
HR130Modbus addressSlave address 1-247.UINT16Read/write
HR201Vnom unit/functionUnit for absolute flow values.UINT16Read/write0 = l/s; 1 = m³/h

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Swegon REACT damper / VAV actuator (Modbus RTU, 2018 sheet)

What Modbus registers does the Swegon REACT damper / VAV actuator (Modbus RTU, 2018 sheet) have?

This map lists 18 registers: 18 holding registers. 12 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Swegon REACT damper / VAV actuator (Modbus RTU, 2018 sheet) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The sheet prints a decimal 'Address' starting at 0 (Set point). Use the printed number as the wire address.

What are the minimum Modbus registers to integrate the Swegon REACT damper / VAV actuator (Modbus RTU, 2018 sheet)?

Start with HR 0 Set point (Set point); HR 4 Relative position (Relative position); HR 6 Relative flow (Relative flow); HR 7 Absolute flow (Absolute flow); HR 122 Mode signal set point analog output (Set point source mode); HR 108 Bus fail position (Bus fail position).

How do I enable Modbus control of the Swegon REACT damper / VAV actuator (Modbus RTU, 2018 sheet)?

Register 122 Mode: 1 = set point via Modbus register 0 (0 = analog input, then register 0 is read-only).

What happens when the Swegon REACT damper / VAV actuator (Modbus RTU, 2018 sheet) loses Modbus communication?

Bus fail position (108): 1 closes, 2 opens the damper when no bus traffic for 120 s; 0 disables monitoring.

Where is the official Swegon REACT damper / VAV actuator (Modbus RTU, 2018 sheet) Modbus documentation?

The source is REACT Modbus, revision 2018-11-08, published free by Swegon at https://www.swegon.com/siteassets/_products-documents-archive/flow-control/demand-controlled-ventilation/_en/reacta_modbus-m.pdf.

More Swegon Modbus register maps

Other valves, actuators & sensors register maps

All valves, actuators & sensors Modbus register maps →

Source: REACT Modbus · rev. 2018-11-08. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.