- Home
- Modbus register maps
- Swegon
- REACT damper / VAV actuator (Modbus RTU, 2018 sheet)
Actuator / valve (ventilation damper and VAV actuator) · Modbus register map
Swegon REACT damper / VAV actuator (Modbus RTU, 2018 sheet) Modbus register map
Updated 19 November 2026
Swegon's REACT dampers for demand-controlled ventilation can be fitted with a Modbus RTU actuator. All points are holding registers read with function 03 and written one at a time with 06: set point, override and command, actuator type, relative and absolute position and flow, an optional analog output, flow limits, bus-failure action, set point source mode, Modbus address and flow unit.
This page lists 18 Modbus registers for the Swegon REACT damper / VAV actuator (Modbus RTU, 2018 sheet) — 12 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Swegon’s own free documentation (linked below) and checked against it.
- Manufacturer
- Swegon
- Model
- REACT damper / VAV actuator (Modbus RTU, 2018 sheet)
- Equipment type
- Actuator / valve (ventilation damper and VAV actuator)
- Registers
- 18 (12 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Documented addressing
- 0-based (the number printed is the address on the wire)
- Also known as
- REACT A, REACT Modbus, Swegon REACT damper, 309C-024-150-MB/SL8/ST15/SWE, 227VM-024-MB/SWE
- Source document
- REACT Modbus · rev. 2018-11-08
Integration notes: Swegon REACT damper / VAV actuator (Modbus RTU, 2018 sheet)
Set register 122 to 1 (or 2) so the set point comes from Modbus, then write the set point to register 0 and read relative position (4) and flow (6/7).
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 0 | Set point | UINT16 | Set point | Read/write |
| HR 4 | Relative position | UINT16 | Relative position | Read |
| HR 6 | Relative flow | UINT16 | Relative flow | Read |
| HR 7 | Absolute flow | UINT16 | Absolute flow | Read |
| HR 122 | Mode signal set point analog output | UINT16 | Set point source mode | Read/write |
| HR 108 | Bus fail position | UINT16 | Bus fail position | Read/write |
Enable Modbus control & writes
Register 122 Mode: 1 = set point via Modbus register 0 (0 = analog input, then register 0 is read-only).
Communication loss & watchdog
Bus fail position (108): 1 closes, 2 opens the damper when no bus traffic for 120 s; 0 disables monitoring.
Byte order & addressing
- Set point, relative position and relative flow use 0-10000 for 0-100 %.
- 65535 in position registers means the function is not supported.
Network setup
- Default serial setting depends on the actuator (19200 8E1 for 227VM, 38400 8N1 for 309C); 120 ohm termination is external.
- A response delay can be set in 3 ms steps for slow masters.
Watch out for
- Flow units (l/s or m³/h) follow register 201.
Swegon REACT damper / VAV actuator (Modbus RTU, 2018 sheet) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0 | Set point | Damper / flow set point, 0-10000 = 0-100 %. Read-only when register 122 = 0. | UINT16 | × 0.01 | % | Read/write | ||
| HR | 1 | Override control | UINT16 | Read/write | 0 = Override control not available; 1 = Open; 2 = Close; 3 = Min; 4 = Max | ||||
| HR | 2 | Command | UINT16 | Read/write | 1 = Adaption; 4 = Controller reset | ||||
| HR | 3 | Device ID | Actuator type. | UINT16 | Read | 1 = Standard actuator; 2 = VAV; 3 = Fire damper | |||
| HR | 4 | Relative position | 0-10000 = 0-100 %; 65535 = not supported. | UINT16 | × 0.01 | % | Read | ||
| HR | 5 | Absolute position | 0-65000 = 0-650.00 degrees; 65535 = not supported. | UINT16 | × 0.01 | ° | Read | ||
| HR | 6 | Relative flow | VAV flow, 0-10000 = 0-100 %. | UINT16 | × 0.01 | % | Read | ||
| HR | 7 | Absolute flow | VAV flow in m³/h or l/s (unit per register 201). | UINT16 | m³/h / l/s | Read | |||
| HR | 10 | Analog output | Optional analog output, 0-10000 mV; see register 122. | UINT16 | mV | Read/write | |||
| HR | 103 | Software version | UINT16 | Read | |||||
| HR | 105 | Min value relative | Minimum flow, % of nominal (0-10000 = 0-100 %). | UINT16 | × 0.01 | % | Read/write | ||
| HR | 106 | Max value relative | Maximum flow, % of nominal (0-10000 = 0-100 %). | UINT16 | × 0.01 | % | Read/write | ||
| HR | 108 | Bus fail position | Action on loss of bus (120 s timeout). | UINT16 | Read/write | 0 = No bus monitoring; 1 = Close at timeout; 2 = Open at timeout | |||
| HR | 120 | Min value absolute | Minimum flow in m³/h or l/s. | UINT16 | m³/h / l/s | Read/write | |||
| HR | 121 | Max value absolute | Maximum flow in m³/h or l/s. | UINT16 | m³/h / l/s | Read/write | |||
| HR | 122 | Mode signal set point analog output | Where the set point comes from and what the analog output shows. | UINT16 | Read/write | 0 = Set point from analog in 1; output = absolute position; 1 = Set point via Modbus register 0; output = absolute position; 2 = Register 0 scaled min-max flow; output = register 10; 3 = Set point from analog in 1; output = register 10 | |||
| HR | 130 | Modbus address | Slave address 1-247. | UINT16 | Read/write | ||||
| HR | 201 | Vnom unit/function | Unit for absolute flow values. | UINT16 | Read/write | 0 = l/s; 1 = m³/h |
Notes on this map
- This is the REACT sheet for the actuators named above; the REACT Parasol Zenith with Belimo actuator has its own map in the library.
- Factory communication setting differs by actuator: page 1 and footnote 4 give setting 14 (19200 baud, 8 data bits, even parity, 1 stop bit) for the 227VM-024-**-MB/SWE, while footnote 1 marks setting 24 (38400 baud, no parity, 1 stop bit) as the default for the 309C-024-150-MB/SL8/ST15/SWE. Settings 1-24 are listed in the sheet. Default slave address is not stated.
- Only function codes 03 and 06 are implemented. The sheet notes settings 1-3 and 19 limit a read to 8 registers.
- Command values 0, 2 and 3 and Device ID 0 are printed as '- - -' (unused).
- All values are 16-bit WORD; the protocol line mentions floats but none are listed.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Swegon REACT damper / VAV actuator (Modbus RTU, 2018 sheet)
What Modbus registers does the Swegon REACT damper / VAV actuator (Modbus RTU, 2018 sheet) have?
This map lists 18 registers: 18 holding registers. 12 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Swegon REACT damper / VAV actuator (Modbus RTU, 2018 sheet) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The sheet prints a decimal 'Address' starting at 0 (Set point). Use the printed number as the wire address.
What are the minimum Modbus registers to integrate the Swegon REACT damper / VAV actuator (Modbus RTU, 2018 sheet)?
Start with HR 0 Set point (Set point); HR 4 Relative position (Relative position); HR 6 Relative flow (Relative flow); HR 7 Absolute flow (Absolute flow); HR 122 Mode signal set point analog output (Set point source mode); HR 108 Bus fail position (Bus fail position).
How do I enable Modbus control of the Swegon REACT damper / VAV actuator (Modbus RTU, 2018 sheet)?
Register 122 Mode: 1 = set point via Modbus register 0 (0 = analog input, then register 0 is read-only).
What happens when the Swegon REACT damper / VAV actuator (Modbus RTU, 2018 sheet) loses Modbus communication?
Bus fail position (108): 1 closes, 2 opens the damper when no bus traffic for 120 s; 0 disables monitoring.
Where is the official Swegon REACT damper / VAV actuator (Modbus RTU, 2018 sheet) Modbus documentation?
The source is REACT Modbus, revision 2018-11-08, published free by Swegon at https://www.swegon.com/siteassets/_products-documents-archive/flow-control/demand-controlled-ventilation/_en/reacta_modbus-m.pdf.
More Swegon Modbus register maps
- Thermostat / room controller (chilled beam, fan coil water circuits)
Swegon CONDUCTOR W1 room controller (waterborne cooling/heating, Modbus RTU)
Swegon CONDUCTOR W1 room controller, software 1.38 and later (technical manual updated 2015-06-15).
Also known as: CONDUCTOR RE W1, Conductor W1, 942334001 - Thermostat / room controller (chilled beam with supply and extract air dampers)
Swegon CONDUCTOR W3 room controller (air and water, Modbus RTU)
Swegon CONDUCTOR W3 room controller, software 1.38 and later (technical manual updated 2015-06-15).
Also known as: CONDUCTOR RE W3, Conductor W3 - Thermostat / room controller (chilled beam with measured airflow and CO2)
Swegon CONDUCTOR W4 room controller (airflow and water, Modbus RTU)
Swegon CONDUCTOR W4 room controller, software 1.12 (technical manual updated 2014-11-21).
Also known as: CONDUCTOR RE W4, CONDUCTOR RE W4 1, Conductor W4 - Actuator / valve (comfort module air damper)
Swegon REACT Parasol Zenith with Belimo actuator (Modbus RTU)
Swegon REACT Parasol Zenith comfort modules fitted with the Belimo Modbus actuator; Swegon Modbus settings sheet dated 2022-08-10.
Also known as: Parasol Zenith REACT, REACT damper actuator - Air handler (rotary heat exchanger drive controller)
Swegon SILVER C / SILVER RX rotary heat exchanger controller (Modbus RTU)
The rotary heat exchanger (rotor) drive controller in Swegon SILVER C RX air handling units, per sheet SILVERCModbusHX.201115.
Also known as: SILVER RX heat exchanger controller, SILVER C RX rotor drive, DRHX, SILVERCModbusHX - Air handler fan motor control
Swegon SILVER C fan motor control (RX/PX/CX/SD, generation E/F)
The EC/FC fan motor controllers inside Swegon SILVER C air handling units, generation E/F, document SILVERCModbus.210809.
Also known as: SILVER C RX, SILVER C PX, SILVER C CX, SILVER C SD, SILVER C generation E, SILVER C generation F - Air handler (heat recovery unit controller)
Swegon TAC5 DG/DM/DT controller (Global HRglobal, HRup, HRflat, HRtotal, HRmural)
Swegon (Global) TAC5 DG, DM and DT regulation boards with the SAT MODBUS (RTU) or SAT WIFI/ETHERNET (TCP) satellite; TAC5 + MODBUS TABLE Cid 050338 (2021-09-20). The TAC5 SC/F single-flow boards use other registers and are not covered.
Also known as: TAC5 DG, TAC5 DM, TAC5 DT, Global HRglobal, Global HRup, Global HRflat, Global HRtotal, Global HRmural, SAT MODBUS - Air handler (heat recovery unit controller)
Swegon TAC6 controller (Global units)
Swegon (Global) units with the TAC6 regulation board and a Modbus satellite; TAC6 + MODBUS TABLE Cid 050360 (2021-05-20).
Also known as: Global TAC6, SAT WIFI-ETHERNET (TAC6)
Other valves, actuators & sensors register maps
- Sensor (humidity / temperature)
Teracom TSH331 IP54 Modbus RTU humidity and temperature sensor
TSH331 per the Teracom TSH331 user manual Rev. 1.5, firmware v1.08 or later.
Also known as: TSH331 - Sensor (dew point probe)
Vaisala DMP Series dew point probes (DMP5, DMP6, DMP7, DMP8) (Modbus RTU)
Vaisala DMP5, DMP6, DMP7 and DMP8 dew point and temperature probes, Modbus RTU interface (user guide M212357EN-F).
Also known as: DMP5, DMP6, DMP7, DMP8, DRYCAP DMP series - Sensor (humidity and temperature transmitter)
Vaisala HMDW110 series humidity and temperature transmitters with TMI110 (Modbus RTU)
HMDW110-series duct, wall and outdoor transmitters and TMI110 ordered with the Modbus RTU option (user guide M211726EN-L).
Also known as: HMD110, HMD112, HMW110, HMW112, HMW112D, HMS110, HMS112, TMW110, TMW112, TMW112D, TMI110 - Sensor transmitter (host for Vaisala probes)
Vaisala Indigo510 / Indigo520 transmitters (Modbus TCP)
Indigo510 and Indigo520 transmitter registers (unit ID 240) over Modbus TCP (user guide M212287EN-AJ).
Also known as: Indigo510, Indigo520, Indigo500 series - Sensor (CO2/humidity wall transmitter)
Vaisala XMW85 CO2, humidity and temperature wall transmitter (Modbus RTU)
XMW85 wall transmitter, Modbus RTU interface (user guide M213257EN-B).
Also known as: XMW85 - Sensor (digital indicator with alarms)
Yokogawa UTAdvanced UM33A digital indicator with alarms
Yokogawa UM33A indicators with RS-485 (Modbus RTU/ASCII); process monitoring D registers from IM 05P07A01-01EN chapter 10.
Also known as: UM33A
All valves, actuators & sensors Modbus register maps →
Source: REACT Modbus · rev. 2018-11-08. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.