Easy Modbus
  1. Home
  2. Modbus register maps
  3. Vaisala
  4. HMDW110 series humidity and temperature transmitters with TMI110 (Modbus RTU)

Sensor (humidity and temperature transmitter) · Modbus register map

Vaisala HMDW110 series humidity and temperature transmitters with TMI110 (Modbus RTU) Modbus register map

Updated 19 November 2026

Short answer

The HMDW110 series are Vaisala humidity and temperature transmitters for building automation (duct, wall, outdoor and immersion versions). Units ordered with the Modbus option are Modbus RTU slaves on RS-485. This map covers the humidity, temperature and calculated readings, device status, filtering, serial settings and test registers.

This page lists 16 Modbus registers for the Vaisala HMDW110 series humidity and temperature transmitters with TMI110 (Modbus RTU) — 7 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Vaisala’s own free documentation (linked below) and checked against it.

Manufacturer
Vaisala
Model
HMDW110 series humidity and temperature transmitters with TMI110 (Modbus RTU)
Equipment type
Sensor (humidity and temperature transmitter)
Registers
16 (7 writable)
Transport
Modbus RTU
Default unit ID
240
Default serial
19200 baud, 8N2
Documented addressing
1-based (subtract 1 for the wire address)
32-bit word order
CDAB low word first (word-swapped)
Also known as
HMD110, HMD112, HMW110, HMW112, HMW112D, HMS110, HMS112, TMW110, TMW112, TMW112D, TMI110
Source document
HMDW110 with TMI110 User Guide · M211726EN-L · rev. 2026-09
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Vaisala HMDW110 series humidity and temperature transmitters with TMI110 (Modbus RTU)

Integration in brief

Read holding registers 1-4 for RH and temperature (CDAB floats); 9-10 adds dew point. Register 513 reads 1 when no error is active.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 0Relative humidityFLOAT32 CDABRelative humidityRead
HR 2TemperatureFLOAT32 CDABTemperatureRead
HR 8Dew/frost point temperatureFLOAT32 CDABDew pointRead
HR 512Device statusUINT16Device statusRead

Enable Modbus control & writes

Order the transmitter with the factory-activated Modbus RTU option, or set the start-up serial mode to Modbus with the smode command on the service port.

Byte order & addressing

Network setup

Watch out for

Vaisala HMDW110 series humidity and temperature transmitters with TMI110 (Modbus RTU) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

16 of 16 shown
Vaisala HMDW110 series humidity and temperature transmitters with TMI110 (Modbus RTU) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0doc 1Relative humidityHumidity models only.FLOAT32CDAB%RHRead
HR2doc 3TemperatureFLOAT32CDAB°CRead
HR8doc 9Dew/frost point temperatureHumidity models only.FLOAT32CDAB°CRead
HR18doc 19Wet-bulb temperatureHumidity models only.FLOAT32CDAB°CRead
HR26doc 27EnthalpyHumidity models only.FLOAT32CDABkJ/kgRead
HR512doc 513Device statusUINT16Read1 = No errors
HR784doc 785Filtering factor0.001 = maximum filtering, 1.000 = none.FLOAT32CDABRead/write
HR1536doc 1537Modbus address1-247.INT16Read/write
HR1537doc 1538Bit rateTakes effect after restart.UINT16Read/write5 = 9600; 6 = 19200; 7 = 38400; 8 = 57600
HR1538doc 1539Parity, data, stop bitsTakes effect after restart.UINT16Read/write0 = None, 8, 1; 1 = None, 8, 2; 2 = Even, 8, 1; 3 = Even, 8, 2; 4 = Odd, 8, 1; 5 = Odd, 8, 2
HR1539doc 1540Response delay0-1020 ms.INT16msRead/write
HR1540doc 1541ProtocolUINT16Read/write6 = Modbus RTU
HR1541doc 1542Restart deviceWrite 1 to restart.INT16Write
HR7936doc 7937Signed integer testAlways reads -12345.INT16Read
HR7937doc 7938Floating point testAlways reads -123.45.FLOAT32CDABRead
HR7939doc 7940Text string testReads the text "-123.45".STRING[8]Read

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Vaisala HMDW110 series humidity and temperature transmitters with TMI110 (Modbus RTU)

What Modbus registers does the Vaisala HMDW110 series humidity and temperature transmitters with TMI110 (Modbus RTU) have?

This map lists 16 registers: 16 holding registers. 7 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Vaisala HMDW110 series humidity and temperature transmitters with TMI110 (Modbus RTU) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The guide numbers registers in decimal starting at 1 and also prints the 0-based hex address used in the request; register number 1 is address 0x0000 on the wire.

What byte order does the Vaisala HMDW110 series humidity and temperature transmitters with TMI110 (Modbus RTU) use for 32-bit values?

Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Vaisala HMDW110 series humidity and temperature transmitters with TMI110 (Modbus RTU)?

Start with HR 0 Relative humidity (Relative humidity); HR 2 Temperature (Temperature); HR 8 Dew/frost point temperature (Dew point); HR 512 Device status (Device status).

How do I enable Modbus control of the Vaisala HMDW110 series humidity and temperature transmitters with TMI110 (Modbus RTU)?

Order the transmitter with the factory-activated Modbus RTU option, or set the start-up serial mode to Modbus with the smode command on the service port.

Where is the official Vaisala HMDW110 series humidity and temperature transmitters with TMI110 (Modbus RTU) Modbus documentation?

The source is HMDW110 with TMI110 User Guide (M211726EN-L), revision 2026-09, published free by Vaisala at https://docs.vaisala.com/r/M211726EN-L/en-US.

More Vaisala Modbus register maps

Other valves, actuators & sensors register maps

All valves, actuators & sensors Modbus register maps →

Source: HMDW110 with TMI110 User Guide · M211726EN-L · rev. 2026-09. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.