Vaisala GMD110 duct CO2 transmitter (Modbus RTU) Modbus register map

Updated 19 November 2026

Short answer

The GMD110 is a Vaisala CARBOCAP duct transmitter for CO2 in ventilation ducts. It has analog outputs and a Modbus RTU interface on RS-485. This map covers the CO2 and temperature readings, serial settings, filtering and the status registers.

This page lists 12 Modbus registers for the Vaisala GMD110 duct CO2 transmitter (Modbus RTU) — 5 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Vaisala’s own free documentation (linked below) and checked against it.

Manufacturer
Vaisala
Model
GMD110 duct CO2 transmitter (Modbus RTU)
Equipment type
Sensor (CO2 duct transmitter)
Registers
12 (5 writable)
Transport
Modbus RTU
Default unit ID
240
Default serial
19200 baud, 8N2
Documented addressing
1-based (subtract 1 for the wire address)
32-bit word order
CDAB low word first (word-swapped)
Also known as
GMD110, CARBOCAP GMD110
Source document
GMD110 User Guide · M212885EN-B · rev. 2023-09
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Vaisala GMD110 duct CO2 transmitter (Modbus RTU)

Integration in brief

Read holding registers 1-2 for CO2 as a CDAB float (or 257 as an integer) and 2049-2050 for status.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 0Measured CO2FLOAT32 CDABCO2 ppmRead
HR 4Measured TFLOAT32 CDABTemperatureRead
HR 2048Device statusBITMAP16Device statusRead
HR 2049CO2 statusBITMAP16CO2 statusRead

Enable Modbus control & writes

Set the output mode switch inside the transmitter to Digital; RS-485 is only active in that position (Analog enables the analog outputs instead). Modbus settings can also be changed in Vaisala Insight PC software via the service port.

Byte order & addressing

Network setup

Watch out for

Vaisala GMD110 duct CO2 transmitter (Modbus RTU) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

12 of 12 shown
Vaisala GMD110 duct CO2 transmitter (Modbus RTU) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0doc 1Measured CO2FLOAT32CDABppmRead
HR2doc 3Compensation TTemperature used for compensation.FLOAT32CDAB°CRead
HR4doc 5Measured TFLOAT32CDAB°CRead
HR256doc 257Measured CO2 (integer)Valid up to 32000 ppm.INT16ppmRead
HR257doc 258Measured CO2 (integer, x10)Scaled; multiply raw by 10.INT16× 10ppmRead
HR768doc 769Modbus address1-247, default 240.INT16Read/write
HR769doc 770Serial speedUINT16Read/write0 = 4800; 1 = 9600; 2 = 19200; 3 = 38400; 4 = 57600; 5 = 115200
HR770doc 771Serial parityUINT16Read/write0 = None; 1 = Even; 2 = Odd
HR771doc 772Serial stop bits1 or 2, default 2.INT16Read/write
HR776doc 777CO2 filtering factor0-100; 100 = no filtering.INT16Read/write
HR2048doc 2049Device status0 = OK; values add up.BITMAP16Readbit 0 = Critical error; bit 1 = Error; bit 2 = Warning
HR2049doc 2050CO2 status0 = OK.BITMAP16Readbit 1 = CO2 reading not reliable (start-up); bit 8 = Measurement not ready (start-up)

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Vaisala GMD110 duct CO2 transmitter (Modbus RTU)

What Modbus registers does the Vaisala GMD110 duct CO2 transmitter (Modbus RTU) have?

This map lists 12 registers: 12 holding registers. 5 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Vaisala GMD110 duct CO2 transmitter (Modbus RTU) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The guide numbers registers in decimal starting at 1 and also prints the 0-based hex address used in the request; register number 1 is address 0x0000 on the wire.

What byte order does the Vaisala GMD110 duct CO2 transmitter (Modbus RTU) use for 32-bit values?

Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Vaisala GMD110 duct CO2 transmitter (Modbus RTU)?

Start with HR 0 Measured CO2 (CO2 ppm); HR 4 Measured T (Temperature); HR 2048 Device status (Device status); HR 2049 CO2 status (CO2 status).

How do I enable Modbus control of the Vaisala GMD110 duct CO2 transmitter (Modbus RTU)?

Set the output mode switch inside the transmitter to Digital; RS-485 is only active in that position (Analog enables the analog outputs instead). Modbus settings can also be changed in Vaisala Insight PC software via the service port.

Where is the official Vaisala GMD110 duct CO2 transmitter (Modbus RTU) Modbus documentation?

The source is GMD110 User Guide (M212885EN-B), revision 2023-09, published free by Vaisala at https://docs.vaisala.com/r/M212885EN-B/en-US.