Water treatment controller (Sensor / controller) · Modbus register map
Walchem W600 water treatment controller (Modbus/TCP) Modbus register map
Updated 17 November 2026
Walchem W-series and Intuition controllers run cooling tower, boiler and process water treatment. With the Modbus/TCP feature enabled they act as a Modbus TCP server on port 502. Data is laid out in 36-address blocks per object (system, network, each sensor input, digital input, relay); this map covers the system and network blocks and the key values of each I/O block, with 32-bit floats and integers sent low word first.
This page lists 93 Modbus registers for the Walchem W600 water treatment controller (Modbus/TCP) — 15 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Walchem’s own free documentation (linked below) and checked against it.
- Manufacturer
- Walchem
- Model
- W600 water treatment controller (Modbus/TCP)
- Equipment type
- Water treatment controller (Sensor / controller)
- Registers
- 93 (15 writable)
- Transport
- Modbus TCP
- Default unit ID
- 1
- TCP port
- 502
- Documented addressing
- 1-based (subtract 1 for the wire address)
- 32-bit word order
- CDAB low word first (word-swapped)
- Firmware
- Controller software 3.01 and higher
- Also known as
- W600 series
Integration notes: Walchem W600 water treatment controller (Modbus/TCP)
Enable Modbus/TCP in the controller's Remote Communications menu, connect to port 502 with any unit ID except 0, and read values as CDAB 32-bit pairs. Poll no faster than every 5 s.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 36 | Controller time | UINT32 CDAB | Controller time (proves comms) | Read |
| HR 576 | Sensor 1-1 primary value | FLOAT32 CDAB | Sensor primary value | Read |
| HR 610 | Sensor 1-1 status | UINT16 | Sensor status code | Read |
| HR 611 | Sensor 1-1 alarm bitfield | BITMAP16 | Sensor alarm bitfield | Read |
| HR 321 | Digital input 1 state | UINT16 | Digital input 1 state | Read |
| HR 8959 | Relay 1 state | UINT16 | Relay 1 state | Read |
| HR 8961 | Relay 1 HOA setting | UINT16 | Relay 1 HOA setting | Read/write |
| HR 71 | System alarm bitfield | BITMAP16 | System alarm bitfield | Read |
Enable Modbus control & writes
Modbus/TCP is a feature of the controller; enable it and set the port and data format (normal or inverse word order) in the Remote Communications menu. A 'Verbose Logging' option there logs every message for commissioning and turns itself off at restart.
Byte order & addressing
- Addresses are 1-based: subtract 1 for the wire address.
- Floats and 32-bit integers are low word first (CDAB) unless 'inverse' format is selected.
- Unit ID 0 is treated as broadcast: the request is processed but no reply is sent.
- FC1/FC2 and FC3/FC4 are interchangeable on reads.
Network setup
- Network address, port (default 502) and data format are set on the controller's communications menus.
- Read up to 125 registers per request.
Watch out for
- Polling faster than once every 5 seconds is unsupported.
- Block start addresses depend on the controller model and on which I/O cards are fitted; confirm the I/O channel map for your unit.
- Modbus RTU is not supported; serial masters need a TCP gateway.
Walchem W600 water treatment controller (Modbus/TCP) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 36doc x0037 | Controller time | Unix time (seconds since 1970). | UINT32 | CDAB | s | Read | ||
| HR | 38doc x0039 | Controller firmware version | FLOAT32 | CDAB | Read | ||||
| HR | 40doc x0041 | Date of last data log | Unix time. | UINT32 | CDAB | s | Read | ||
| HR | 42doc x0043 | Controller processor temperature | FLOAT32 | CDAB | °C | Read | |||
| HR | 44doc x0045 | Network card temperature | FLOAT32 | CDAB | °C | Read | |||
| HR | 48doc x0049 | I/O card 1 temperature | FLOAT32 | CDAB | °C | Read | |||
| HR | 50doc x0051 | I/O card 2 temperature | FLOAT32 | CDAB | °C | Read | |||
| HR | 62doc x0063 | Battery power | Clock battery voltage. | FLOAT32 | CDAB | V | Read | ||
| HR | 64doc x0065 | +3.3 V supply | FLOAT32 | CDAB | V | Read | |||
| HR | 66doc x0067 | +5 V supply | FLOAT32 | CDAB | V | Read | |||
| HR | 71doc x0072 | System alarm bitfield | 8 alarm flags in the low byte. | BITMAP16 | Read | bit 0 = Temperature alarm; bit 1 = Battery low; bit 2 = Invalid setting; bit 3 = Software version (add-on card needs update); bit 4 = Board failure; bit 5 = Internal voltage out of range | |||
| HR | 144doc x0145 | Fluent last data time | Unix time. | UINT32 | CDAB | s | Read | ||
| HR | 146doc x0147 | Fluent last configuration time | Unix time. | UINT32 | CDAB | s | Read | ||
| HR | 148doc x0149 | Fluent refresh rate | 1-1440 minutes. | FLOAT32 | CDAB | min | Read/write | ||
| HR | 150doc x0151 | Fluent LiveConnect status | Status code. | UINT16 | Read | 0 = Error; 1 = None; 2 = Sensor: Auto Cal; 3 = Sensor: User Cal; 4 = DI State: Open; 5 = DI State: Closed; 6 = DI Interlock: Active; 7 = DI Interlock: Inactive; 8 = Relay: On; 9 = Relay: Off; 11 = Output Interlocked; 12 = Output Forced On; 13 = Output Timeout; 14 = Output Input Error; 15 = Output Error; 16 = Output Hold; 17 = Output HOA: Auto On; 18 = Output HOA: Auto Off; 19 = Output HOA: Hand; 20 = Output HOA: Off; 21 = Output Deadband; 22 = Relay Timeout; 23 = Relay OK; 24 = Daily Max Timeout; 25 = Biocide: Prebleed; 26 = Biocide: Hold; 27 = Biocide: Add; 28 = Time Proportional: Off; 29 = Bleed & Feed: Bleeding; 30 = Bleed & Feed: Timeout; 31 = Intermittent Sampling: Wait; 32 = Intermittent Sampling: Sample; 33 = Intermittent Sampling: Hold; 34 = Intermittent Sampling: Bleed; 35 = Probe Wash: On; 36 = Probe Wash: Hold | |||
| HR | 151doc x0152 | Web server status | Status code (93-95 = web server modes). | UINT16 | Read | 0 = Error; 1 = None; 2 = Sensor: Auto Cal; 3 = Sensor: User Cal; 4 = DI State: Open; 5 = DI State: Closed; 6 = DI Interlock: Active; 7 = DI Interlock: Inactive; 8 = Relay: On; 9 = Relay: Off; 11 = Output Interlocked; 12 = Output Forced On; 13 = Output Timeout; 14 = Output Input Error; 15 = Output Error; 16 = Output Hold; 17 = Output HOA: Auto On; 18 = Output HOA: Auto Off; 19 = Output HOA: Hand; 20 = Output HOA: Off; 21 = Output Deadband; 22 = Relay Timeout; 23 = Relay OK; 24 = Daily Max Timeout; 25 = Biocide: Prebleed; 26 = Biocide: Hold; 27 = Biocide: Add; 28 = Time Proportional: Off; 29 = Bleed & Feed: Bleeding; 30 = Bleed & Feed: Timeout; 31 = Intermittent Sampling: Wait; 32 = Intermittent Sampling: Sample; 33 = Intermittent Sampling: Hold; 34 = Intermittent Sampling: Bleed; 35 = Probe Wash: On; 36 = Probe Wash: Hold | |||
| HR | 179doc x0180 | Network alarm bitfield | BITMAP16 | Read | bit 0 = Web server failure; bit 1 = Fluent data comm; bit 2 = Fluent LiveConnect; bit 3 = WiFi error | ||||
| HR | 288doc x0289 | Digital input 1 last reset date | Unix time (DI State type). | UINT32 | CDAB | s | Read | ||
| HR | 290doc x0291 | Digital input 1 total time | Accumulated time (DI State type). | UINT32 | CDAB | s | Read | ||
| HR | 292doc x0293 | Digital input 1 cycle time | DI State type. | UINT32 | CDAB | s | Read | ||
| HR | 320doc x0321 | Digital input 1 reset total time | Write 1 to reset (DI State type). | UINT16 | Read/write | ||||
| HR | 321doc x0322 | Digital input 1 state | DI State type. | UINT16 | Read | 0 = Open; 1 = Closed | |||
| HR | 322doc x0323 | Digital input 1 interlock state | DI State type. | UINT16 | Read | 0 = Inactive; 1 = Active interlock | |||
| HR | 323doc x0324 | Digital input 1 alarm bitfield | BITMAP16 | Read | bit 0 = DI state alarm; bit 1 = Total; bit 2 = Total range; bit 3 = Input failure; bit 4 = Flow verify / Modbus alarm (type-specific); bit 5 = Low flow; bit 6 = High flow | ||||
| HR | 357doc x0358 | Digital input 2 state | DI State type. | UINT16 | Read | 0 = Open; 1 = Closed | |||
| HR | 359doc x0360 | Digital input 2 alarm bitfield | BITMAP16 | Read | bit 0 = DI state alarm; bit 1 = Total; bit 2 = Total range; bit 3 = Input failure; bit 4 = Flow verify / Modbus alarm (type-specific); bit 5 = Low flow; bit 6 = High flow | ||||
| HR | 393doc x0394 | Digital input 3 state | DI State type. | UINT16 | Read | 0 = Open; 1 = Closed | |||
| HR | 395doc x0396 | Digital input 3 alarm bitfield | BITMAP16 | Read | bit 0 = DI state alarm; bit 1 = Total; bit 2 = Total range; bit 3 = Input failure; bit 4 = Flow verify / Modbus alarm (type-specific); bit 5 = Low flow; bit 6 = High flow | ||||
| HR | 429doc x0430 | Digital input 4 state | DI State type. | UINT16 | Read | 0 = Open; 1 = Closed | |||
| HR | 431doc x0432 | Digital input 4 alarm bitfield | BITMAP16 | Read | bit 0 = DI state alarm; bit 1 = Total; bit 2 = Total range; bit 3 = Input failure; bit 4 = Flow verify / Modbus alarm (type-specific); bit 5 = Low flow; bit 6 = High flow | ||||
| HR | 465doc x0466 | Digital input 5 state | DI State type. | UINT16 | Read | 0 = Open; 1 = Closed | |||
| HR | 467doc x0468 | Digital input 5 alarm bitfield | BITMAP16 | Read | bit 0 = DI state alarm; bit 1 = Total; bit 2 = Total range; bit 3 = Input failure; bit 4 = Flow verify / Modbus alarm (type-specific); bit 5 = Low flow; bit 6 = High flow | ||||
| HR | 501doc x0502 | Digital input 6 state | DI State type. | UINT16 | Read | 0 = Open; 1 = Closed | |||
| HR | 503doc x0504 | Digital input 6 alarm bitfield | BITMAP16 | Read | bit 0 = DI state alarm; bit 1 = Total; bit 2 = Total range; bit 3 = Input failure; bit 4 = Flow verify / Modbus alarm (type-specific); bit 5 = Low flow; bit 6 = High flow | ||||
| HR | 576doc x0577 | Sensor 1-1 primary value | Measured value in the sensor's configured units. | FLOAT32 | CDAB | Read | |||
| HR | 578doc x0579 | Sensor 1-1 primary raw value | Raw signal: uS/cm, mV, mA or ohm depending on sensor type. | FLOAT32 | CDAB | Read | |||
| HR | 580doc x0581 | Sensor 1-1 last calibration date | Unix time. | UINT32 | CDAB | s | Read | ||
| HR | 586doc x0587 | Sensor 1-1 deadband | Alarm deadband in sensor units. | FLOAT32 | CDAB | Read/write | |||
| HR | 588doc x0589 | Sensor 1-1 smoothing factor | 0-90 %. | FLOAT32 | CDAB | % | Read/write | ||
| HR | 590doc x0591 | Sensor 1-1 LoLo alarm setpoint | FLOAT32 | CDAB | Read/write | ||||
| HR | 592doc x0593 | Sensor 1-1 Low alarm setpoint | FLOAT32 | CDAB | Read/write | ||||
| HR | 594doc x0595 | Sensor 1-1 High alarm setpoint | FLOAT32 | CDAB | Read/write | ||||
| HR | 596doc x0597 | Sensor 1-1 HiHi alarm setpoint | FLOAT32 | CDAB | Read/write | ||||
| HR | 604doc x0605 | Sensor 1-1 Low alarm | UINT16 | Read | 0 = Inactive; 1 = Alarm active | ||||
| HR | 605doc x0606 | Sensor 1-1 High alarm | UINT16 | Read | 0 = Inactive; 1 = Alarm active | ||||
| HR | 606doc x0607 | Sensor 1-1 LoLo alarm | UINT16 | Read | 0 = Inactive; 1 = Alarm active | ||||
| HR | 607doc x0608 | Sensor 1-1 HiHi alarm | UINT16 | Read | 0 = Inactive; 1 = Alarm active | ||||
| HR | 608doc x0609 | Sensor 1-1 calibration required | UINT16 | Read | 0 = Inactive; 1 = Alarm active | ||||
| HR | 609doc x0610 | Sensor 1-1 input failure | UINT16 | Read | 0 = Inactive; 1 = Alarm active | ||||
| HR | 610doc x0611 | Sensor 1-1 status | Status code. | UINT16 | Read | 0 = Error; 1 = None; 2 = Sensor: Auto Cal; 3 = Sensor: User Cal; 4 = DI State: Open; 5 = DI State: Closed; 6 = DI Interlock: Active; 7 = DI Interlock: Inactive; 8 = Relay: On; 9 = Relay: Off; 11 = Output Interlocked; 12 = Output Forced On; 13 = Output Timeout; 14 = Output Input Error; 15 = Output Error; 16 = Output Hold; 17 = Output HOA: Auto On; 18 = Output HOA: Auto Off; 19 = Output HOA: Hand; 20 = Output HOA: Off; 21 = Output Deadband; 22 = Relay Timeout; 23 = Relay OK; 24 = Daily Max Timeout; 25 = Biocide: Prebleed; 26 = Biocide: Hold; 27 = Biocide: Add; 28 = Time Proportional: Off; 29 = Bleed & Feed: Bleeding; 30 = Bleed & Feed: Timeout; 31 = Intermittent Sampling: Wait; 32 = Intermittent Sampling: Sample; 33 = Intermittent Sampling: Hold; 34 = Intermittent Sampling: Bleed; 35 = Probe Wash: On; 36 = Probe Wash: Hold | |||
| HR | 611doc x0612 | Sensor 1-1 alarm bitfield | BITMAP16 | Read | bit 0 = Low; bit 1 = High; bit 2 = Low Low; bit 3 = High High; bit 4 = Type-specific (replace electrode / total / PV2 low); bit 5 = PV2 high (digital sensors only); bit 6 = Input failure; bit 7 = Calibration required | ||||
| HR | 612doc x0613 | Sensor 1-2 primary value | Measured value in the sensor's configured units. | FLOAT32 | CDAB | Read | |||
| HR | 646doc x0647 | Sensor 1-2 status | Status code. | UINT16 | Read | 0 = Error; 1 = None; 2 = Sensor: Auto Cal; 3 = Sensor: User Cal; 4 = DI State: Open; 5 = DI State: Closed; 6 = DI Interlock: Active; 7 = DI Interlock: Inactive; 8 = Relay: On; 9 = Relay: Off; 11 = Output Interlocked; 12 = Output Forced On; 13 = Output Timeout; 14 = Output Input Error; 15 = Output Error; 16 = Output Hold; 17 = Output HOA: Auto On; 18 = Output HOA: Auto Off; 19 = Output HOA: Hand; 20 = Output HOA: Off; 21 = Output Deadband; 22 = Relay Timeout; 23 = Relay OK; 24 = Daily Max Timeout; 25 = Biocide: Prebleed; 26 = Biocide: Hold; 27 = Biocide: Add; 28 = Time Proportional: Off; 29 = Bleed & Feed: Bleeding; 30 = Bleed & Feed: Timeout; 31 = Intermittent Sampling: Wait; 32 = Intermittent Sampling: Sample; 33 = Intermittent Sampling: Hold; 34 = Intermittent Sampling: Bleed; 35 = Probe Wash: On; 36 = Probe Wash: Hold | |||
| HR | 647doc x0648 | Sensor 1-2 alarm bitfield | BITMAP16 | Read | bit 0 = Low; bit 1 = High; bit 2 = Low Low; bit 3 = High High; bit 4 = Type-specific (replace electrode / total / PV2 low); bit 5 = PV2 high (digital sensors only); bit 6 = Input failure; bit 7 = Calibration required | ||||
| HR | 648doc x0649 | Sensor 1-3 primary value | Measured value in the sensor's configured units. | FLOAT32 | CDAB | Read | |||
| HR | 682doc x0683 | Sensor 1-3 status | Status code. | UINT16 | Read | 0 = Error; 1 = None; 2 = Sensor: Auto Cal; 3 = Sensor: User Cal; 4 = DI State: Open; 5 = DI State: Closed; 6 = DI Interlock: Active; 7 = DI Interlock: Inactive; 8 = Relay: On; 9 = Relay: Off; 11 = Output Interlocked; 12 = Output Forced On; 13 = Output Timeout; 14 = Output Input Error; 15 = Output Error; 16 = Output Hold; 17 = Output HOA: Auto On; 18 = Output HOA: Auto Off; 19 = Output HOA: Hand; 20 = Output HOA: Off; 21 = Output Deadband; 22 = Relay Timeout; 23 = Relay OK; 24 = Daily Max Timeout; 25 = Biocide: Prebleed; 26 = Biocide: Hold; 27 = Biocide: Add; 28 = Time Proportional: Off; 29 = Bleed & Feed: Bleeding; 30 = Bleed & Feed: Timeout; 31 = Intermittent Sampling: Wait; 32 = Intermittent Sampling: Sample; 33 = Intermittent Sampling: Hold; 34 = Intermittent Sampling: Bleed; 35 = Probe Wash: On; 36 = Probe Wash: Hold | |||
| HR | 683doc x0684 | Sensor 1-3 alarm bitfield | BITMAP16 | Read | bit 0 = Low; bit 1 = High; bit 2 = Low Low; bit 3 = High High; bit 4 = Type-specific (replace electrode / total / PV2 low); bit 5 = PV2 high (digital sensors only); bit 6 = Input failure; bit 7 = Calibration required | ||||
| HR | 864doc x0865 | Sensor 2-1 primary value | Measured value in the sensor's configured units. | FLOAT32 | CDAB | Read | |||
| HR | 898doc x0899 | Sensor 2-1 status | Status code. | UINT16 | Read | 0 = Error; 1 = None; 2 = Sensor: Auto Cal; 3 = Sensor: User Cal; 4 = DI State: Open; 5 = DI State: Closed; 6 = DI Interlock: Active; 7 = DI Interlock: Inactive; 8 = Relay: On; 9 = Relay: Off; 11 = Output Interlocked; 12 = Output Forced On; 13 = Output Timeout; 14 = Output Input Error; 15 = Output Error; 16 = Output Hold; 17 = Output HOA: Auto On; 18 = Output HOA: Auto Off; 19 = Output HOA: Hand; 20 = Output HOA: Off; 21 = Output Deadband; 22 = Relay Timeout; 23 = Relay OK; 24 = Daily Max Timeout; 25 = Biocide: Prebleed; 26 = Biocide: Hold; 27 = Biocide: Add; 28 = Time Proportional: Off; 29 = Bleed & Feed: Bleeding; 30 = Bleed & Feed: Timeout; 31 = Intermittent Sampling: Wait; 32 = Intermittent Sampling: Sample; 33 = Intermittent Sampling: Hold; 34 = Intermittent Sampling: Bleed; 35 = Probe Wash: On; 36 = Probe Wash: Hold | |||
| HR | 899doc x0900 | Sensor 2-1 alarm bitfield | BITMAP16 | Read | bit 0 = Low; bit 1 = High; bit 2 = Low Low; bit 3 = High High; bit 4 = Type-specific (replace electrode / total / PV2 low); bit 5 = PV2 high (digital sensors only); bit 6 = Input failure; bit 7 = Calibration required | ||||
| HR | 900doc x0901 | Sensor 2-2 primary value | Measured value in the sensor's configured units. | FLOAT32 | CDAB | Read | |||
| HR | 934doc x0935 | Sensor 2-2 status | Status code. | UINT16 | Read | 0 = Error; 1 = None; 2 = Sensor: Auto Cal; 3 = Sensor: User Cal; 4 = DI State: Open; 5 = DI State: Closed; 6 = DI Interlock: Active; 7 = DI Interlock: Inactive; 8 = Relay: On; 9 = Relay: Off; 11 = Output Interlocked; 12 = Output Forced On; 13 = Output Timeout; 14 = Output Input Error; 15 = Output Error; 16 = Output Hold; 17 = Output HOA: Auto On; 18 = Output HOA: Auto Off; 19 = Output HOA: Hand; 20 = Output HOA: Off; 21 = Output Deadband; 22 = Relay Timeout; 23 = Relay OK; 24 = Daily Max Timeout; 25 = Biocide: Prebleed; 26 = Biocide: Hold; 27 = Biocide: Add; 28 = Time Proportional: Off; 29 = Bleed & Feed: Bleeding; 30 = Bleed & Feed: Timeout; 31 = Intermittent Sampling: Wait; 32 = Intermittent Sampling: Sample; 33 = Intermittent Sampling: Hold; 34 = Intermittent Sampling: Bleed; 35 = Probe Wash: On; 36 = Probe Wash: Hold | |||
| HR | 935doc x0936 | Sensor 2-2 alarm bitfield | BITMAP16 | Read | bit 0 = Low; bit 1 = High; bit 2 = Low Low; bit 3 = High High; bit 4 = Type-specific (replace electrode / total / PV2 low); bit 5 = PV2 high (digital sensors only); bit 6 = Input failure; bit 7 = Calibration required | ||||
| HR | 936doc x0937 | Sensor 2-3 primary value | Measured value in the sensor's configured units. | FLOAT32 | CDAB | Read | |||
| HR | 970doc x0971 | Sensor 2-3 status | Status code. | UINT16 | Read | 0 = Error; 1 = None; 2 = Sensor: Auto Cal; 3 = Sensor: User Cal; 4 = DI State: Open; 5 = DI State: Closed; 6 = DI Interlock: Active; 7 = DI Interlock: Inactive; 8 = Relay: On; 9 = Relay: Off; 11 = Output Interlocked; 12 = Output Forced On; 13 = Output Timeout; 14 = Output Input Error; 15 = Output Error; 16 = Output Hold; 17 = Output HOA: Auto On; 18 = Output HOA: Auto Off; 19 = Output HOA: Hand; 20 = Output HOA: Off; 21 = Output Deadband; 22 = Relay Timeout; 23 = Relay OK; 24 = Daily Max Timeout; 25 = Biocide: Prebleed; 26 = Biocide: Hold; 27 = Biocide: Add; 28 = Time Proportional: Off; 29 = Bleed & Feed: Bleeding; 30 = Bleed & Feed: Timeout; 31 = Intermittent Sampling: Wait; 32 = Intermittent Sampling: Sample; 33 = Intermittent Sampling: Hold; 34 = Intermittent Sampling: Bleed; 35 = Probe Wash: On; 36 = Probe Wash: Hold | |||
| HR | 971doc x0972 | Sensor 2-3 alarm bitfield | BITMAP16 | Read | bit 0 = Low; bit 1 = High; bit 2 = Low Low; bit 3 = High High; bit 4 = Type-specific (replace electrode / total / PV2 low); bit 5 = PV2 high (digital sensors only); bit 6 = Input failure; bit 7 = Calibration required | ||||
| HR | 8928doc x8929 | Relay 1 time on | Current on time. | UINT32 | CDAB | s | Read | ||
| HR | 8930doc x8931 | Relay 1 total time | Accumulated on time. | UINT32 | CDAB | s | Read | ||
| HR | 8959doc x8960 | Relay 1 state | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 8960doc x8961 | Relay 1 reset time total | Write 1 to reset. | UINT16 | Read/write | ||||
| HR | 8961doc x8962 | Relay 1 HOA setting | Hand / Off / Auto. | UINT16 | Read/write | 0 = Hand; 1 = Off; 2 = Auto | |||
| HR | 8962doc x8963 | Relay 1 status | Status code. | UINT16 | Read | 0 = Error; 1 = None; 2 = Sensor: Auto Cal; 3 = Sensor: User Cal; 4 = DI State: Open; 5 = DI State: Closed; 6 = DI Interlock: Active; 7 = DI Interlock: Inactive; 8 = Relay: On; 9 = Relay: Off; 11 = Output Interlocked; 12 = Output Forced On; 13 = Output Timeout; 14 = Output Input Error; 15 = Output Error; 16 = Output Hold; 17 = Output HOA: Auto On; 18 = Output HOA: Auto Off; 19 = Output HOA: Hand; 20 = Output HOA: Off; 21 = Output Deadband; 22 = Relay Timeout; 23 = Relay OK; 24 = Daily Max Timeout; 25 = Biocide: Prebleed; 26 = Biocide: Hold; 27 = Biocide: Add; 28 = Time Proportional: Off; 29 = Bleed & Feed: Bleeding; 30 = Bleed & Feed: Timeout; 31 = Intermittent Sampling: Wait; 32 = Intermittent Sampling: Sample; 33 = Intermittent Sampling: Hold; 34 = Intermittent Sampling: Bleed; 35 = Probe Wash: On; 36 = Probe Wash: Hold | |||
| HR | 8963doc x8964 | Relay 1 alarm bitfield | BITMAP16 | Read | bit 0 = Output timeout; bit 1 = Relay event skipped / turnover limit; bit 2 = Control failure; bit 3 = State alarm; bit 4 = Daily max timeout | ||||
| HR | 8995doc x8996 | Relay 2 state | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 8997doc x8998 | Relay 2 HOA setting | Hand / Off / Auto. | UINT16 | Read/write | 0 = Hand; 1 = Off; 2 = Auto | |||
| HR | 8998doc x8999 | Relay 2 status | Status code. | UINT16 | Read | 0 = Error; 1 = None; 2 = Sensor: Auto Cal; 3 = Sensor: User Cal; 4 = DI State: Open; 5 = DI State: Closed; 6 = DI Interlock: Active; 7 = DI Interlock: Inactive; 8 = Relay: On; 9 = Relay: Off; 11 = Output Interlocked; 12 = Output Forced On; 13 = Output Timeout; 14 = Output Input Error; 15 = Output Error; 16 = Output Hold; 17 = Output HOA: Auto On; 18 = Output HOA: Auto Off; 19 = Output HOA: Hand; 20 = Output HOA: Off; 21 = Output Deadband; 22 = Relay Timeout; 23 = Relay OK; 24 = Daily Max Timeout; 25 = Biocide: Prebleed; 26 = Biocide: Hold; 27 = Biocide: Add; 28 = Time Proportional: Off; 29 = Bleed & Feed: Bleeding; 30 = Bleed & Feed: Timeout; 31 = Intermittent Sampling: Wait; 32 = Intermittent Sampling: Sample; 33 = Intermittent Sampling: Hold; 34 = Intermittent Sampling: Bleed; 35 = Probe Wash: On; 36 = Probe Wash: Hold | |||
| HR | 8999doc x9000 | Relay 2 alarm bitfield | BITMAP16 | Read | bit 0 = Output timeout; bit 1 = Relay event skipped / turnover limit; bit 2 = Control failure; bit 3 = State alarm; bit 4 = Daily max timeout | ||||
| HR | 9031doc x9032 | Relay 3 state | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 9033doc x9034 | Relay 3 HOA setting | Hand / Off / Auto. | UINT16 | Read/write | 0 = Hand; 1 = Off; 2 = Auto | |||
| HR | 9034doc x9035 | Relay 3 status | Status code. | UINT16 | Read | 0 = Error; 1 = None; 2 = Sensor: Auto Cal; 3 = Sensor: User Cal; 4 = DI State: Open; 5 = DI State: Closed; 6 = DI Interlock: Active; 7 = DI Interlock: Inactive; 8 = Relay: On; 9 = Relay: Off; 11 = Output Interlocked; 12 = Output Forced On; 13 = Output Timeout; 14 = Output Input Error; 15 = Output Error; 16 = Output Hold; 17 = Output HOA: Auto On; 18 = Output HOA: Auto Off; 19 = Output HOA: Hand; 20 = Output HOA: Off; 21 = Output Deadband; 22 = Relay Timeout; 23 = Relay OK; 24 = Daily Max Timeout; 25 = Biocide: Prebleed; 26 = Biocide: Hold; 27 = Biocide: Add; 28 = Time Proportional: Off; 29 = Bleed & Feed: Bleeding; 30 = Bleed & Feed: Timeout; 31 = Intermittent Sampling: Wait; 32 = Intermittent Sampling: Sample; 33 = Intermittent Sampling: Hold; 34 = Intermittent Sampling: Bleed; 35 = Probe Wash: On; 36 = Probe Wash: Hold | |||
| HR | 9035doc x9036 | Relay 3 alarm bitfield | BITMAP16 | Read | bit 0 = Output timeout; bit 1 = Relay event skipped / turnover limit; bit 2 = Control failure; bit 3 = State alarm; bit 4 = Daily max timeout | ||||
| HR | 9067doc x9068 | Relay 4 state | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 9069doc x9070 | Relay 4 HOA setting | Hand / Off / Auto. | UINT16 | Read/write | 0 = Hand; 1 = Off; 2 = Auto | |||
| HR | 9070doc x9071 | Relay 4 status | Status code. | UINT16 | Read | 0 = Error; 1 = None; 2 = Sensor: Auto Cal; 3 = Sensor: User Cal; 4 = DI State: Open; 5 = DI State: Closed; 6 = DI Interlock: Active; 7 = DI Interlock: Inactive; 8 = Relay: On; 9 = Relay: Off; 11 = Output Interlocked; 12 = Output Forced On; 13 = Output Timeout; 14 = Output Input Error; 15 = Output Error; 16 = Output Hold; 17 = Output HOA: Auto On; 18 = Output HOA: Auto Off; 19 = Output HOA: Hand; 20 = Output HOA: Off; 21 = Output Deadband; 22 = Relay Timeout; 23 = Relay OK; 24 = Daily Max Timeout; 25 = Biocide: Prebleed; 26 = Biocide: Hold; 27 = Biocide: Add; 28 = Time Proportional: Off; 29 = Bleed & Feed: Bleeding; 30 = Bleed & Feed: Timeout; 31 = Intermittent Sampling: Wait; 32 = Intermittent Sampling: Sample; 33 = Intermittent Sampling: Hold; 34 = Intermittent Sampling: Bleed; 35 = Probe Wash: On; 36 = Probe Wash: Hold | |||
| HR | 9071doc x9072 | Relay 4 alarm bitfield | BITMAP16 | Read | bit 0 = Output timeout; bit 1 = Relay event skipped / turnover limit; bit 2 = Control failure; bit 3 = State alarm; bit 4 = Daily max timeout | ||||
| HR | 9103doc x9104 | Relay 5 state | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 9105doc x9106 | Relay 5 HOA setting | Hand / Off / Auto. | UINT16 | Read/write | 0 = Hand; 1 = Off; 2 = Auto | |||
| HR | 9106doc x9107 | Relay 5 status | Status code. | UINT16 | Read | 0 = Error; 1 = None; 2 = Sensor: Auto Cal; 3 = Sensor: User Cal; 4 = DI State: Open; 5 = DI State: Closed; 6 = DI Interlock: Active; 7 = DI Interlock: Inactive; 8 = Relay: On; 9 = Relay: Off; 11 = Output Interlocked; 12 = Output Forced On; 13 = Output Timeout; 14 = Output Input Error; 15 = Output Error; 16 = Output Hold; 17 = Output HOA: Auto On; 18 = Output HOA: Auto Off; 19 = Output HOA: Hand; 20 = Output HOA: Off; 21 = Output Deadband; 22 = Relay Timeout; 23 = Relay OK; 24 = Daily Max Timeout; 25 = Biocide: Prebleed; 26 = Biocide: Hold; 27 = Biocide: Add; 28 = Time Proportional: Off; 29 = Bleed & Feed: Bleeding; 30 = Bleed & Feed: Timeout; 31 = Intermittent Sampling: Wait; 32 = Intermittent Sampling: Sample; 33 = Intermittent Sampling: Hold; 34 = Intermittent Sampling: Bleed; 35 = Probe Wash: On; 36 = Probe Wash: Hold | |||
| HR | 9107doc x9108 | Relay 5 alarm bitfield | BITMAP16 | Read | bit 0 = Output timeout; bit 1 = Relay event skipped / turnover limit; bit 2 = Control failure; bit 3 = State alarm; bit 4 = Daily max timeout | ||||
| HR | 9139doc x9140 | Relay 6 state | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 9141doc x9142 | Relay 6 HOA setting | Hand / Off / Auto. | UINT16 | Read/write | 0 = Hand; 1 = Off; 2 = Auto | |||
| HR | 9142doc x9143 | Relay 6 status | Status code. | UINT16 | Read | 0 = Error; 1 = None; 2 = Sensor: Auto Cal; 3 = Sensor: User Cal; 4 = DI State: Open; 5 = DI State: Closed; 6 = DI Interlock: Active; 7 = DI Interlock: Inactive; 8 = Relay: On; 9 = Relay: Off; 11 = Output Interlocked; 12 = Output Forced On; 13 = Output Timeout; 14 = Output Input Error; 15 = Output Error; 16 = Output Hold; 17 = Output HOA: Auto On; 18 = Output HOA: Auto Off; 19 = Output HOA: Hand; 20 = Output HOA: Off; 21 = Output Deadband; 22 = Relay Timeout; 23 = Relay OK; 24 = Daily Max Timeout; 25 = Biocide: Prebleed; 26 = Biocide: Hold; 27 = Biocide: Add; 28 = Time Proportional: Off; 29 = Bleed & Feed: Bleeding; 30 = Bleed & Feed: Timeout; 31 = Intermittent Sampling: Wait; 32 = Intermittent Sampling: Sample; 33 = Intermittent Sampling: Hold; 34 = Intermittent Sampling: Bleed; 35 = Probe Wash: On; 36 = Probe Wash: Hold | |||
| HR | 9143doc x9144 | Relay 6 alarm bitfield | BITMAP16 | Read | bit 0 = Output timeout; bit 1 = Relay event skipped / turnover limit; bit 2 = Control failure; bit 3 = State alarm; bit 4 = Daily max timeout |
Notes on this map
- 32-bit integers and floats are sent least significant word first (CDAB) by default. The Remote Communications menu has an 'inverse' data format that swaps to high word first (ABCD); if values look wrong, check that setting.
- All 32-bit integers are unsigned; times are Unix seconds since 1970-01-01.
- Every address can be read as a holding register (FC3) or input register (FC4); this map lists them as holding registers. Booleans (the bold rows in the manual) can also be read as coils/discrete inputs at the same number.
- Sensor blocks use the general sensor map (all sensor types except Digital Sensor and Analog Input Flowmeter, which have their own maps). The full block is listed for the first sensor only; for the others only primary value, status and alarm bitfield are listed - the same indices apply to every sensor block.
- Digital input blocks are shown for the DI State type. Flow meter, counter, flow monitor and remote Modbus DI types use different maps (section 5.3.4).
- Relay entries use the indices common to every relay control mode (time on, total time, state, reset, HOA, status, alarm bitfield). Mode-specific set points live at other indices in section 5.3.6. Pulse relay maps (section 5.3.7) differ and are not included.
- Status register codes 37 and above are not listed in the values here; see section 5.4. Alarm bit 5 meanings vary by sensor or DI type.
- Analog outputs, virtual inputs and fields marked as W900/Intuition-9 only are left out.
- Block start addresses are from the W600 I/O channel map (p. 12): sensors 1-1..2-3 at x0577/x0613/x0649/x0865/x0901/x0937, digital inputs 1-6 at x0289..x0469, relays 1-6 at x8929..x9109.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Walchem W600 water treatment controller (Modbus/TCP)
What Modbus registers does the Walchem W600 water treatment controller (Modbus/TCP) have?
This map lists 93 registers: 93 holding registers. 15 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Walchem W600 water treatment controller (Modbus/TCP) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Section 5.1 says the published addresses are 1-based while the packet is 0-based, so subtract 1 on the wire. Each object's address = its block start (xNNNN in the I/O channel map) + the index in its type-specific map; e.g. firmware version is block x0037 + index 2 = 30039/40039, wire address 38. The 'x' prefix stands for the table digit: the same address can be read as a holding register (FC3) or input register (FC4).
What byte order does the Walchem W600 water treatment controller (Modbus/TCP) use for 32-bit values?
Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Walchem W600 water treatment controller (Modbus/TCP)?
Start with HR 36 Controller time (Controller time (proves comms)); HR 576 Sensor 1-1 primary value (Sensor primary value); HR 610 Sensor 1-1 status (Sensor status code); HR 611 Sensor 1-1 alarm bitfield (Sensor alarm bitfield); HR 321 Digital input 1 state (Digital input 1 state); HR 8959 Relay 1 state (Relay 1 state); HR 8961 Relay 1 HOA setting (Relay 1 HOA setting); HR 71 System alarm bitfield (System alarm bitfield).
How do I enable Modbus control of the Walchem W600 water treatment controller (Modbus/TCP)?
Modbus/TCP is a feature of the controller; enable it and set the port and data format (normal or inverse word order) in the Remote Communications menu. A 'Verbose Logging' option there logs every message for commissioning and turns itself off at restart.
Where is the official Walchem W600 water treatment controller (Modbus/TCP) Modbus documentation?
The source is Modbus Manual - Intuition-9 / Intuition-6 / W900 / W600 (180676.K), revision 2026-06, published free by Walchem at https://www.walchem.com/Literature/Controllers/Intuition/180676_W600_W900_Intuition_Modbus_Manual.pdf.
More Walchem Modbus register maps
- Water treatment controller (Sensor / controller)
Walchem W900 water treatment controller (Modbus/TCP)
Walchem W900 controllers (software 3.01 and up) with the Modbus/TCP feature, per Modbus manual 180676.K. W600, Intuition-6 and Intuition-9 use the same type maps but different block start addresses.
Also known as: W900 series - Water treatment controller (Sensor / controller)
Walchem WebMaster / WebMaster ONE (WM1) Modbus TCP/IP option
Walchem WebMaster and WebMaster ONE controllers with the Modbus TCP/IP option, software s800/s801/s802/s811/s830 v017 and higher, per manual 180422 Rev G.
Also known as: WebMaster, WebMaster ONE, WM1, s800, s801, s802, s811, s830 - Water treatment controller (Sensor / controller)
Walchem WebMaster WIND series Modbus TCP/IP option (s825)
Walchem WebMaster WIND-series controllers with the Modbus TCP/IP option, software s825v008 and higher, per manual 180413 Rev A1.
Also known as: WIND, WebMaster WIND, s825
Other valves, actuators & sensors register maps
- Sensor (room temperature / humidity)
ACI (Automation Components Inc.) Wall Plate Series BACnet/Modbus temperature/RH sensor
ACI Wall Plate Series stainless wall-plate temperature, RH and temperature/RH sensors with the BACnet MS/TP / Modbus RTU interface (guide I0000931).
Also known as: A/RH-BM wall plate, Wall Plate Series BACnet Modbus - Sensor (particulate matter)
DFRobot SEN0662 Gravity BMV080 PM2.5 air quality sensor (UART Modbus RTU)
DFRobot SEN0662 Gravity BMV080 module with its DIP switch set to UART, firmware V1.0.0 / register map version 4, per the DFRobot wiki register page.
Also known as: SEN0662, Gravity BMV080, BMV080 PM2.5 sensor, DFRobot BMV080 - Sensor (dissolved oxygen)
JUMO digiLine O-DO S10 optical oxygen sensor (Modbus RTU)
JUMO digiLine O-DO S10 digital oxygen sensor on RS-485 Modbus RTU (interface description V2.00, 2021-08-20).
Also known as: JUMO digiLine O-DO S10, digiLine O-DO - Sensor (load-cell weight indicator)
Laumas WLIGHT weight indicator / transmitter (Modbus RTU)
Laumas WLIGHT, installation and user manual version 1.03.
Also known as: WLIGHT, W LIGHT - Sensor (CO2, humidity, temperature module)
Sensirion SCD30 CO2, humidity and temperature sensor module
Sensirion SCD30 sensor module with the SEL pin pulled high at power-up (Modbus mode), per interface description version 1.0.
Also known as: SCD30 - Sensor (flow transmitter)
Siemens SITRANS F C MASS 6000 with USM II Modbus RTU module
SITRANS F C MASS 6000 Coriolis flow transmitters fitted with the USM II Modbus RTU RS-485 add-on module (operating instructions 03/2021).
Also known as: MASS 6000, SITRANS FC MASS 6000