Water treatment controller (Sensor / controller) · Modbus register map

Walchem W900 water treatment controller (Modbus/TCP) Modbus register map

Updated 17 November 2026

Short answer

Walchem W-series and Intuition controllers run cooling tower, boiler and process water treatment. With the Modbus/TCP feature enabled they act as a Modbus TCP server on port 502. Data is laid out in 36-address blocks per object (system, network, each sensor input, digital input, relay); this map covers the system and network blocks and the key values of each I/O block, with 32-bit floats and integers sent low word first.

This page lists 138 Modbus registers for the Walchem W900 water treatment controller (Modbus/TCP) — 17 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Walchem’s own free documentation (linked below) and checked against it.

Manufacturer
Walchem
Model
W900 water treatment controller (Modbus/TCP)
Equipment type
Water treatment controller (Sensor / controller)
Registers
138 (17 writable)
Transport
Modbus TCP
Default unit ID
1
TCP port
502
Documented addressing
1-based (subtract 1 for the wire address)
32-bit word order
CDAB low word first (word-swapped)
Firmware
Controller software 3.01 and higher
Also known as
W900 series
Source document
Modbus Manual - Intuition-9 / Intuition-6 / W900 / W600 · 180676.K · rev. 2026-06
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Walchem W900 water treatment controller (Modbus/TCP)

Integration in brief

Enable Modbus/TCP in the controller's Remote Communications menu, connect to port 502 with any unit ID except 0, and read values as CDAB 32-bit pairs. Poll no faster than every 5 s.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 36Controller timeUINT32 CDABController time (proves comms)Read
HR 1152Sensor 1-1 primary valueFLOAT32 CDABSensor primary valueRead
HR 1186Sensor 1-1 statusUINT16Sensor status codeRead
HR 1187Sensor 1-1 alarm bitfieldBITMAP16Sensor alarm bitfieldRead
HR 609Digital input 1 stateUINT16Digital input 1 stateRead
HR 8959Relay 1 stateUINT16Relay 1 stateRead
HR 8961Relay 1 HOA settingUINT16Relay 1 HOA settingRead/write
HR 71System alarm bitfieldBITMAP16System alarm bitfieldRead

Enable Modbus control & writes

Modbus/TCP is a feature of the controller; enable it and set the port and data format (normal or inverse word order) in the Remote Communications menu. A 'Verbose Logging' option there logs every message for commissioning and turns itself off at restart.

Byte order & addressing

Network setup

Watch out for

Walchem W900 water treatment controller (Modbus/TCP) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

138 of 138 shown
Walchem W900 water treatment controller (Modbus/TCP) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR36doc x0037Controller timeUnix time (seconds since 1970).UINT32CDABsRead
HR38doc x0039Controller firmware versionFLOAT32CDABRead
HR40doc x0041Date of last data logUnix time.UINT32CDABsRead
HR42doc x0043Controller processor temperatureFLOAT32CDAB°CRead
HR44doc x0045Network card temperatureFLOAT32CDAB°CRead
HR46doc x0047Digital input card temperatureW900/Intuition-9 only.FLOAT32CDAB°CRead
HR48doc x0049I/O card 1 temperatureFLOAT32CDAB°CRead
HR50doc x0051I/O card 2 temperatureFLOAT32CDAB°CRead
HR52doc x0053I/O card 3 temperatureW900/Intuition-9 only.FLOAT32CDAB°CRead
HR54doc x0055I/O card 4 temperatureW900/Intuition-9 only.FLOAT32CDAB°CRead
HR62doc x0063Battery powerClock battery voltage.FLOAT32CDABVRead
HR64doc x0065+3.3 V supplyFLOAT32CDABVRead
HR66doc x0067+5 V supplyFLOAT32CDABVRead
HR68doc x0069+12 V supplyW900/Intuition-9 only.FLOAT32CDABVRead
HR71doc x0072System alarm bitfield8 alarm flags in the low byte.BITMAP16Readbit 0 = Temperature alarm; bit 1 = Battery low; bit 2 = Invalid setting; bit 3 = Software version (add-on card needs update); bit 4 = Board failure; bit 5 = Internal voltage out of range
HR144doc x0145Fluent last data timeUnix time.UINT32CDABsRead
HR146doc x0147Fluent last configuration timeUnix time.UINT32CDABsRead
HR148doc x0149Fluent refresh rate1-1440 minutes.FLOAT32CDABminRead/write
HR150doc x0151Fluent LiveConnect statusStatus code.UINT16Read0 = Error; 1 = None; 2 = Sensor: Auto Cal; 3 = Sensor: User Cal; 4 = DI State: Open; 5 = DI State: Closed; 6 = DI Interlock: Active; 7 = DI Interlock: Inactive; 8 = Relay: On; 9 = Relay: Off; 11 = Output Interlocked; 12 = Output Forced On; 13 = Output Timeout; 14 = Output Input Error; 15 = Output Error; 16 = Output Hold; 17 = Output HOA: Auto On; 18 = Output HOA: Auto Off; 19 = Output HOA: Hand; 20 = Output HOA: Off; 21 = Output Deadband; 22 = Relay Timeout; 23 = Relay OK; 24 = Daily Max Timeout; 25 = Biocide: Prebleed; 26 = Biocide: Hold; 27 = Biocide: Add; 28 = Time Proportional: Off; 29 = Bleed & Feed: Bleeding; 30 = Bleed & Feed: Timeout; 31 = Intermittent Sampling: Wait; 32 = Intermittent Sampling: Sample; 33 = Intermittent Sampling: Hold; 34 = Intermittent Sampling: Bleed; 35 = Probe Wash: On; 36 = Probe Wash: Hold
HR151doc x0152Web server statusStatus code (93-95 = web server modes).UINT16Read0 = Error; 1 = None; 2 = Sensor: Auto Cal; 3 = Sensor: User Cal; 4 = DI State: Open; 5 = DI State: Closed; 6 = DI Interlock: Active; 7 = DI Interlock: Inactive; 8 = Relay: On; 9 = Relay: Off; 11 = Output Interlocked; 12 = Output Forced On; 13 = Output Timeout; 14 = Output Input Error; 15 = Output Error; 16 = Output Hold; 17 = Output HOA: Auto On; 18 = Output HOA: Auto Off; 19 = Output HOA: Hand; 20 = Output HOA: Off; 21 = Output Deadband; 22 = Relay Timeout; 23 = Relay OK; 24 = Daily Max Timeout; 25 = Biocide: Prebleed; 26 = Biocide: Hold; 27 = Biocide: Add; 28 = Time Proportional: Off; 29 = Bleed & Feed: Bleeding; 30 = Bleed & Feed: Timeout; 31 = Intermittent Sampling: Wait; 32 = Intermittent Sampling: Sample; 33 = Intermittent Sampling: Hold; 34 = Intermittent Sampling: Bleed; 35 = Probe Wash: On; 36 = Probe Wash: Hold
HR179doc x0180Network alarm bitfieldBITMAP16Readbit 0 = Web server failure; bit 1 = Fluent data comm; bit 2 = Fluent LiveConnect; bit 3 = WiFi error
HR576doc x0577Digital input 1 last reset dateUnix time (DI State type).UINT32CDABsRead
HR578doc x0579Digital input 1 total timeAccumulated time (DI State type).UINT32CDABsRead
HR580doc x0581Digital input 1 cycle timeDI State type.UINT32CDABsRead
HR608doc x0609Digital input 1 reset total timeWrite 1 to reset (DI State type).UINT16Read/write
HR609doc x0610Digital input 1 stateDI State type.UINT16Read0 = Open; 1 = Closed
HR610doc x0611Digital input 1 interlock stateDI State type.UINT16Read0 = Inactive; 1 = Active interlock
HR611doc x0612Digital input 1 alarm bitfieldBITMAP16Readbit 0 = DI state alarm; bit 1 = Total; bit 2 = Total range; bit 3 = Input failure; bit 4 = Flow verify / Modbus alarm (type-specific); bit 5 = Low flow; bit 6 = High flow
HR645doc x0646Digital input 2 stateDI State type.UINT16Read0 = Open; 1 = Closed
HR647doc x0648Digital input 2 alarm bitfieldBITMAP16Readbit 0 = DI state alarm; bit 1 = Total; bit 2 = Total range; bit 3 = Input failure; bit 4 = Flow verify / Modbus alarm (type-specific); bit 5 = Low flow; bit 6 = High flow
HR681doc x0682Digital input 3 stateDI State type.UINT16Read0 = Open; 1 = Closed
HR683doc x0684Digital input 3 alarm bitfieldBITMAP16Readbit 0 = DI state alarm; bit 1 = Total; bit 2 = Total range; bit 3 = Input failure; bit 4 = Flow verify / Modbus alarm (type-specific); bit 5 = Low flow; bit 6 = High flow
HR717doc x0718Digital input 4 stateDI State type.UINT16Read0 = Open; 1 = Closed
HR719doc x0720Digital input 4 alarm bitfieldBITMAP16Readbit 0 = DI state alarm; bit 1 = Total; bit 2 = Total range; bit 3 = Input failure; bit 4 = Flow verify / Modbus alarm (type-specific); bit 5 = Low flow; bit 6 = High flow
HR753doc x0754Digital input 5 stateDI State type.UINT16Read0 = Open; 1 = Closed
HR755doc x0756Digital input 5 alarm bitfieldBITMAP16Readbit 0 = DI state alarm; bit 1 = Total; bit 2 = Total range; bit 3 = Input failure; bit 4 = Flow verify / Modbus alarm (type-specific); bit 5 = Low flow; bit 6 = High flow
HR789doc x0790Digital input 6 stateDI State type.UINT16Read0 = Open; 1 = Closed
HR791doc x0792Digital input 6 alarm bitfieldBITMAP16Readbit 0 = DI state alarm; bit 1 = Total; bit 2 = Total range; bit 3 = Input failure; bit 4 = Flow verify / Modbus alarm (type-specific); bit 5 = Low flow; bit 6 = High flow
HR825doc x0826Digital input 7 stateDI State type.UINT16Read0 = Open; 1 = Closed
HR827doc x0828Digital input 7 alarm bitfieldBITMAP16Readbit 0 = DI state alarm; bit 1 = Total; bit 2 = Total range; bit 3 = Input failure; bit 4 = Flow verify / Modbus alarm (type-specific); bit 5 = Low flow; bit 6 = High flow
HR861doc x0862Digital input 8 stateDI State type.UINT16Read0 = Open; 1 = Closed
HR863doc x0864Digital input 8 alarm bitfieldBITMAP16Readbit 0 = DI state alarm; bit 1 = Total; bit 2 = Total range; bit 3 = Input failure; bit 4 = Flow verify / Modbus alarm (type-specific); bit 5 = Low flow; bit 6 = High flow
HR897doc x0898Digital input 9 stateDI State type.UINT16Read0 = Open; 1 = Closed
HR899doc x0900Digital input 9 alarm bitfieldBITMAP16Readbit 0 = DI state alarm; bit 1 = Total; bit 2 = Total range; bit 3 = Input failure; bit 4 = Flow verify / Modbus alarm (type-specific); bit 5 = Low flow; bit 6 = High flow
HR933doc x0934Digital input 10 stateDI State type.UINT16Read0 = Open; 1 = Closed
HR935doc x0936Digital input 10 alarm bitfieldBITMAP16Readbit 0 = DI state alarm; bit 1 = Total; bit 2 = Total range; bit 3 = Input failure; bit 4 = Flow verify / Modbus alarm (type-specific); bit 5 = Low flow; bit 6 = High flow
HR969doc x0970Digital input 11 stateDI State type.UINT16Read0 = Open; 1 = Closed
HR971doc x0972Digital input 11 alarm bitfieldBITMAP16Readbit 0 = DI state alarm; bit 1 = Total; bit 2 = Total range; bit 3 = Input failure; bit 4 = Flow verify / Modbus alarm (type-specific); bit 5 = Low flow; bit 6 = High flow
HR1005doc x1006Digital input 12 stateDI State type.UINT16Read0 = Open; 1 = Closed
HR1007doc x1008Digital input 12 alarm bitfieldBITMAP16Readbit 0 = DI state alarm; bit 1 = Total; bit 2 = Total range; bit 3 = Input failure; bit 4 = Flow verify / Modbus alarm (type-specific); bit 5 = Low flow; bit 6 = High flow
HR1152doc x1153Sensor 1-1 primary valueMeasured value in the sensor's configured units.FLOAT32CDABRead
HR1154doc x1155Sensor 1-1 primary raw valueRaw signal: uS/cm, mV, mA or ohm depending on sensor type.FLOAT32CDABRead
HR1156doc x1157Sensor 1-1 last calibration dateUnix time.UINT32CDABsRead
HR1162doc x1163Sensor 1-1 deadbandAlarm deadband in sensor units.FLOAT32CDABRead/write
HR1164doc x1165Sensor 1-1 smoothing factor0-90 %.FLOAT32CDAB%Read/write
HR1166doc x1167Sensor 1-1 LoLo alarm setpointFLOAT32CDABRead/write
HR1168doc x1169Sensor 1-1 Low alarm setpointFLOAT32CDABRead/write
HR1170doc x1171Sensor 1-1 High alarm setpointFLOAT32CDABRead/write
HR1172doc x1173Sensor 1-1 HiHi alarm setpointFLOAT32CDABRead/write
HR1174doc x1175Sensor 1-1 24-hour minimumW900/Intuition-9 only.FLOAT32CDABRead
HR1176doc x1177Sensor 1-1 24-hour maximumW900/Intuition-9 only.FLOAT32CDABRead
HR1178doc x1179Sensor 1-1 24-hour averageW900/Intuition-9 only.FLOAT32CDABRead
HR1180doc x1181Sensor 1-1 Low alarmUINT16Read0 = Inactive; 1 = Alarm active
HR1181doc x1182Sensor 1-1 High alarmUINT16Read0 = Inactive; 1 = Alarm active
HR1182doc x1183Sensor 1-1 LoLo alarmUINT16Read0 = Inactive; 1 = Alarm active
HR1183doc x1184Sensor 1-1 HiHi alarmUINT16Read0 = Inactive; 1 = Alarm active
HR1184doc x1185Sensor 1-1 calibration requiredUINT16Read0 = Inactive; 1 = Alarm active
HR1185doc x1186Sensor 1-1 input failureUINT16Read0 = Inactive; 1 = Alarm active
HR1186doc x1187Sensor 1-1 statusStatus code.UINT16Read0 = Error; 1 = None; 2 = Sensor: Auto Cal; 3 = Sensor: User Cal; 4 = DI State: Open; 5 = DI State: Closed; 6 = DI Interlock: Active; 7 = DI Interlock: Inactive; 8 = Relay: On; 9 = Relay: Off; 11 = Output Interlocked; 12 = Output Forced On; 13 = Output Timeout; 14 = Output Input Error; 15 = Output Error; 16 = Output Hold; 17 = Output HOA: Auto On; 18 = Output HOA: Auto Off; 19 = Output HOA: Hand; 20 = Output HOA: Off; 21 = Output Deadband; 22 = Relay Timeout; 23 = Relay OK; 24 = Daily Max Timeout; 25 = Biocide: Prebleed; 26 = Biocide: Hold; 27 = Biocide: Add; 28 = Time Proportional: Off; 29 = Bleed & Feed: Bleeding; 30 = Bleed & Feed: Timeout; 31 = Intermittent Sampling: Wait; 32 = Intermittent Sampling: Sample; 33 = Intermittent Sampling: Hold; 34 = Intermittent Sampling: Bleed; 35 = Probe Wash: On; 36 = Probe Wash: Hold
HR1187doc x1188Sensor 1-1 alarm bitfieldBITMAP16Readbit 0 = Low; bit 1 = High; bit 2 = Low Low; bit 3 = High High; bit 4 = Type-specific (replace electrode / total / PV2 low); bit 5 = PV2 high (digital sensors only); bit 6 = Input failure; bit 7 = Calibration required
HR1188doc x1189Sensor 1-2 primary valueMeasured value in the sensor's configured units.FLOAT32CDABRead
HR1222doc x1223Sensor 1-2 statusStatus code.UINT16Read0 = Error; 1 = None; 2 = Sensor: Auto Cal; 3 = Sensor: User Cal; 4 = DI State: Open; 5 = DI State: Closed; 6 = DI Interlock: Active; 7 = DI Interlock: Inactive; 8 = Relay: On; 9 = Relay: Off; 11 = Output Interlocked; 12 = Output Forced On; 13 = Output Timeout; 14 = Output Input Error; 15 = Output Error; 16 = Output Hold; 17 = Output HOA: Auto On; 18 = Output HOA: Auto Off; 19 = Output HOA: Hand; 20 = Output HOA: Off; 21 = Output Deadband; 22 = Relay Timeout; 23 = Relay OK; 24 = Daily Max Timeout; 25 = Biocide: Prebleed; 26 = Biocide: Hold; 27 = Biocide: Add; 28 = Time Proportional: Off; 29 = Bleed & Feed: Bleeding; 30 = Bleed & Feed: Timeout; 31 = Intermittent Sampling: Wait; 32 = Intermittent Sampling: Sample; 33 = Intermittent Sampling: Hold; 34 = Intermittent Sampling: Bleed; 35 = Probe Wash: On; 36 = Probe Wash: Hold
HR1223doc x1224Sensor 1-2 alarm bitfieldBITMAP16Readbit 0 = Low; bit 1 = High; bit 2 = Low Low; bit 3 = High High; bit 4 = Type-specific (replace electrode / total / PV2 low); bit 5 = PV2 high (digital sensors only); bit 6 = Input failure; bit 7 = Calibration required
HR1224doc x1225Sensor 1-3 primary valueMeasured value in the sensor's configured units.FLOAT32CDABRead
HR1258doc x1259Sensor 1-3 statusStatus code.UINT16Read0 = Error; 1 = None; 2 = Sensor: Auto Cal; 3 = Sensor: User Cal; 4 = DI State: Open; 5 = DI State: Closed; 6 = DI Interlock: Active; 7 = DI Interlock: Inactive; 8 = Relay: On; 9 = Relay: Off; 11 = Output Interlocked; 12 = Output Forced On; 13 = Output Timeout; 14 = Output Input Error; 15 = Output Error; 16 = Output Hold; 17 = Output HOA: Auto On; 18 = Output HOA: Auto Off; 19 = Output HOA: Hand; 20 = Output HOA: Off; 21 = Output Deadband; 22 = Relay Timeout; 23 = Relay OK; 24 = Daily Max Timeout; 25 = Biocide: Prebleed; 26 = Biocide: Hold; 27 = Biocide: Add; 28 = Time Proportional: Off; 29 = Bleed & Feed: Bleeding; 30 = Bleed & Feed: Timeout; 31 = Intermittent Sampling: Wait; 32 = Intermittent Sampling: Sample; 33 = Intermittent Sampling: Hold; 34 = Intermittent Sampling: Bleed; 35 = Probe Wash: On; 36 = Probe Wash: Hold
HR1259doc x1260Sensor 1-3 alarm bitfieldBITMAP16Readbit 0 = Low; bit 1 = High; bit 2 = Low Low; bit 3 = High High; bit 4 = Type-specific (replace electrode / total / PV2 low); bit 5 = PV2 high (digital sensors only); bit 6 = Input failure; bit 7 = Calibration required
HR1260doc x1261Sensor 1-4 primary valueMeasured value in the sensor's configured units.FLOAT32CDABRead
HR1294doc x1295Sensor 1-4 statusStatus code.UINT16Read0 = Error; 1 = None; 2 = Sensor: Auto Cal; 3 = Sensor: User Cal; 4 = DI State: Open; 5 = DI State: Closed; 6 = DI Interlock: Active; 7 = DI Interlock: Inactive; 8 = Relay: On; 9 = Relay: Off; 11 = Output Interlocked; 12 = Output Forced On; 13 = Output Timeout; 14 = Output Input Error; 15 = Output Error; 16 = Output Hold; 17 = Output HOA: Auto On; 18 = Output HOA: Auto Off; 19 = Output HOA: Hand; 20 = Output HOA: Off; 21 = Output Deadband; 22 = Relay Timeout; 23 = Relay OK; 24 = Daily Max Timeout; 25 = Biocide: Prebleed; 26 = Biocide: Hold; 27 = Biocide: Add; 28 = Time Proportional: Off; 29 = Bleed & Feed: Bleeding; 30 = Bleed & Feed: Timeout; 31 = Intermittent Sampling: Wait; 32 = Intermittent Sampling: Sample; 33 = Intermittent Sampling: Hold; 34 = Intermittent Sampling: Bleed; 35 = Probe Wash: On; 36 = Probe Wash: Hold
HR1295doc x1296Sensor 1-4 alarm bitfieldBITMAP16Readbit 0 = Low; bit 1 = High; bit 2 = Low Low; bit 3 = High High; bit 4 = Type-specific (replace electrode / total / PV2 low); bit 5 = PV2 high (digital sensors only); bit 6 = Input failure; bit 7 = Calibration required
HR1296doc x1297Sensor 1-5 primary valueMeasured value in the sensor's configured units.FLOAT32CDABRead
HR1330doc x1331Sensor 1-5 statusStatus code.UINT16Read0 = Error; 1 = None; 2 = Sensor: Auto Cal; 3 = Sensor: User Cal; 4 = DI State: Open; 5 = DI State: Closed; 6 = DI Interlock: Active; 7 = DI Interlock: Inactive; 8 = Relay: On; 9 = Relay: Off; 11 = Output Interlocked; 12 = Output Forced On; 13 = Output Timeout; 14 = Output Input Error; 15 = Output Error; 16 = Output Hold; 17 = Output HOA: Auto On; 18 = Output HOA: Auto Off; 19 = Output HOA: Hand; 20 = Output HOA: Off; 21 = Output Deadband; 22 = Relay Timeout; 23 = Relay OK; 24 = Daily Max Timeout; 25 = Biocide: Prebleed; 26 = Biocide: Hold; 27 = Biocide: Add; 28 = Time Proportional: Off; 29 = Bleed & Feed: Bleeding; 30 = Bleed & Feed: Timeout; 31 = Intermittent Sampling: Wait; 32 = Intermittent Sampling: Sample; 33 = Intermittent Sampling: Hold; 34 = Intermittent Sampling: Bleed; 35 = Probe Wash: On; 36 = Probe Wash: Hold
HR1331doc x1332Sensor 1-5 alarm bitfieldBITMAP16Readbit 0 = Low; bit 1 = High; bit 2 = Low Low; bit 3 = High High; bit 4 = Type-specific (replace electrode / total / PV2 low); bit 5 = PV2 high (digital sensors only); bit 6 = Input failure; bit 7 = Calibration required
HR1332doc x1333Sensor 1-6 primary valueMeasured value in the sensor's configured units.FLOAT32CDABRead
HR1366doc x1367Sensor 1-6 statusStatus code.UINT16Read0 = Error; 1 = None; 2 = Sensor: Auto Cal; 3 = Sensor: User Cal; 4 = DI State: Open; 5 = DI State: Closed; 6 = DI Interlock: Active; 7 = DI Interlock: Inactive; 8 = Relay: On; 9 = Relay: Off; 11 = Output Interlocked; 12 = Output Forced On; 13 = Output Timeout; 14 = Output Input Error; 15 = Output Error; 16 = Output Hold; 17 = Output HOA: Auto On; 18 = Output HOA: Auto Off; 19 = Output HOA: Hand; 20 = Output HOA: Off; 21 = Output Deadband; 22 = Relay Timeout; 23 = Relay OK; 24 = Daily Max Timeout; 25 = Biocide: Prebleed; 26 = Biocide: Hold; 27 = Biocide: Add; 28 = Time Proportional: Off; 29 = Bleed & Feed: Bleeding; 30 = Bleed & Feed: Timeout; 31 = Intermittent Sampling: Wait; 32 = Intermittent Sampling: Sample; 33 = Intermittent Sampling: Hold; 34 = Intermittent Sampling: Bleed; 35 = Probe Wash: On; 36 = Probe Wash: Hold
HR1367doc x1368Sensor 1-6 alarm bitfieldBITMAP16Readbit 0 = Low; bit 1 = High; bit 2 = Low Low; bit 3 = High High; bit 4 = Type-specific (replace electrode / total / PV2 low); bit 5 = PV2 high (digital sensors only); bit 6 = Input failure; bit 7 = Calibration required
HR1728doc x1729Sensor 2-1 primary valueMeasured value in the sensor's configured units.FLOAT32CDABRead
HR1762doc x1763Sensor 2-1 statusStatus code.UINT16Read0 = Error; 1 = None; 2 = Sensor: Auto Cal; 3 = Sensor: User Cal; 4 = DI State: Open; 5 = DI State: Closed; 6 = DI Interlock: Active; 7 = DI Interlock: Inactive; 8 = Relay: On; 9 = Relay: Off; 11 = Output Interlocked; 12 = Output Forced On; 13 = Output Timeout; 14 = Output Input Error; 15 = Output Error; 16 = Output Hold; 17 = Output HOA: Auto On; 18 = Output HOA: Auto Off; 19 = Output HOA: Hand; 20 = Output HOA: Off; 21 = Output Deadband; 22 = Relay Timeout; 23 = Relay OK; 24 = Daily Max Timeout; 25 = Biocide: Prebleed; 26 = Biocide: Hold; 27 = Biocide: Add; 28 = Time Proportional: Off; 29 = Bleed & Feed: Bleeding; 30 = Bleed & Feed: Timeout; 31 = Intermittent Sampling: Wait; 32 = Intermittent Sampling: Sample; 33 = Intermittent Sampling: Hold; 34 = Intermittent Sampling: Bleed; 35 = Probe Wash: On; 36 = Probe Wash: Hold
HR1763doc x1764Sensor 2-1 alarm bitfieldBITMAP16Readbit 0 = Low; bit 1 = High; bit 2 = Low Low; bit 3 = High High; bit 4 = Type-specific (replace electrode / total / PV2 low); bit 5 = PV2 high (digital sensors only); bit 6 = Input failure; bit 7 = Calibration required
HR1764doc x1765Sensor 2-2 primary valueMeasured value in the sensor's configured units.FLOAT32CDABRead
HR1798doc x1799Sensor 2-2 statusStatus code.UINT16Read0 = Error; 1 = None; 2 = Sensor: Auto Cal; 3 = Sensor: User Cal; 4 = DI State: Open; 5 = DI State: Closed; 6 = DI Interlock: Active; 7 = DI Interlock: Inactive; 8 = Relay: On; 9 = Relay: Off; 11 = Output Interlocked; 12 = Output Forced On; 13 = Output Timeout; 14 = Output Input Error; 15 = Output Error; 16 = Output Hold; 17 = Output HOA: Auto On; 18 = Output HOA: Auto Off; 19 = Output HOA: Hand; 20 = Output HOA: Off; 21 = Output Deadband; 22 = Relay Timeout; 23 = Relay OK; 24 = Daily Max Timeout; 25 = Biocide: Prebleed; 26 = Biocide: Hold; 27 = Biocide: Add; 28 = Time Proportional: Off; 29 = Bleed & Feed: Bleeding; 30 = Bleed & Feed: Timeout; 31 = Intermittent Sampling: Wait; 32 = Intermittent Sampling: Sample; 33 = Intermittent Sampling: Hold; 34 = Intermittent Sampling: Bleed; 35 = Probe Wash: On; 36 = Probe Wash: Hold
HR1799doc x1800Sensor 2-2 alarm bitfieldBITMAP16Readbit 0 = Low; bit 1 = High; bit 2 = Low Low; bit 3 = High High; bit 4 = Type-specific (replace electrode / total / PV2 low); bit 5 = PV2 high (digital sensors only); bit 6 = Input failure; bit 7 = Calibration required
HR1800doc x1801Sensor 2-3 primary valueMeasured value in the sensor's configured units.FLOAT32CDABRead
HR1834doc x1835Sensor 2-3 statusStatus code.UINT16Read0 = Error; 1 = None; 2 = Sensor: Auto Cal; 3 = Sensor: User Cal; 4 = DI State: Open; 5 = DI State: Closed; 6 = DI Interlock: Active; 7 = DI Interlock: Inactive; 8 = Relay: On; 9 = Relay: Off; 11 = Output Interlocked; 12 = Output Forced On; 13 = Output Timeout; 14 = Output Input Error; 15 = Output Error; 16 = Output Hold; 17 = Output HOA: Auto On; 18 = Output HOA: Auto Off; 19 = Output HOA: Hand; 20 = Output HOA: Off; 21 = Output Deadband; 22 = Relay Timeout; 23 = Relay OK; 24 = Daily Max Timeout; 25 = Biocide: Prebleed; 26 = Biocide: Hold; 27 = Biocide: Add; 28 = Time Proportional: Off; 29 = Bleed & Feed: Bleeding; 30 = Bleed & Feed: Timeout; 31 = Intermittent Sampling: Wait; 32 = Intermittent Sampling: Sample; 33 = Intermittent Sampling: Hold; 34 = Intermittent Sampling: Bleed; 35 = Probe Wash: On; 36 = Probe Wash: Hold
HR1835doc x1836Sensor 2-3 alarm bitfieldBITMAP16Readbit 0 = Low; bit 1 = High; bit 2 = Low Low; bit 3 = High High; bit 4 = Type-specific (replace electrode / total / PV2 low); bit 5 = PV2 high (digital sensors only); bit 6 = Input failure; bit 7 = Calibration required
HR1836doc x1837Sensor 2-4 primary valueMeasured value in the sensor's configured units.FLOAT32CDABRead
HR1870doc x1871Sensor 2-4 statusStatus code.UINT16Read0 = Error; 1 = None; 2 = Sensor: Auto Cal; 3 = Sensor: User Cal; 4 = DI State: Open; 5 = DI State: Closed; 6 = DI Interlock: Active; 7 = DI Interlock: Inactive; 8 = Relay: On; 9 = Relay: Off; 11 = Output Interlocked; 12 = Output Forced On; 13 = Output Timeout; 14 = Output Input Error; 15 = Output Error; 16 = Output Hold; 17 = Output HOA: Auto On; 18 = Output HOA: Auto Off; 19 = Output HOA: Hand; 20 = Output HOA: Off; 21 = Output Deadband; 22 = Relay Timeout; 23 = Relay OK; 24 = Daily Max Timeout; 25 = Biocide: Prebleed; 26 = Biocide: Hold; 27 = Biocide: Add; 28 = Time Proportional: Off; 29 = Bleed & Feed: Bleeding; 30 = Bleed & Feed: Timeout; 31 = Intermittent Sampling: Wait; 32 = Intermittent Sampling: Sample; 33 = Intermittent Sampling: Hold; 34 = Intermittent Sampling: Bleed; 35 = Probe Wash: On; 36 = Probe Wash: Hold
HR1871doc x1872Sensor 2-4 alarm bitfieldBITMAP16Readbit 0 = Low; bit 1 = High; bit 2 = Low Low; bit 3 = High High; bit 4 = Type-specific (replace electrode / total / PV2 low); bit 5 = PV2 high (digital sensors only); bit 6 = Input failure; bit 7 = Calibration required
HR1872doc x1873Sensor 2-5 primary valueMeasured value in the sensor's configured units.FLOAT32CDABRead
HR1906doc x1907Sensor 2-5 statusStatus code.UINT16Read0 = Error; 1 = None; 2 = Sensor: Auto Cal; 3 = Sensor: User Cal; 4 = DI State: Open; 5 = DI State: Closed; 6 = DI Interlock: Active; 7 = DI Interlock: Inactive; 8 = Relay: On; 9 = Relay: Off; 11 = Output Interlocked; 12 = Output Forced On; 13 = Output Timeout; 14 = Output Input Error; 15 = Output Error; 16 = Output Hold; 17 = Output HOA: Auto On; 18 = Output HOA: Auto Off; 19 = Output HOA: Hand; 20 = Output HOA: Off; 21 = Output Deadband; 22 = Relay Timeout; 23 = Relay OK; 24 = Daily Max Timeout; 25 = Biocide: Prebleed; 26 = Biocide: Hold; 27 = Biocide: Add; 28 = Time Proportional: Off; 29 = Bleed & Feed: Bleeding; 30 = Bleed & Feed: Timeout; 31 = Intermittent Sampling: Wait; 32 = Intermittent Sampling: Sample; 33 = Intermittent Sampling: Hold; 34 = Intermittent Sampling: Bleed; 35 = Probe Wash: On; 36 = Probe Wash: Hold
HR1907doc x1908Sensor 2-5 alarm bitfieldBITMAP16Readbit 0 = Low; bit 1 = High; bit 2 = Low Low; bit 3 = High High; bit 4 = Type-specific (replace electrode / total / PV2 low); bit 5 = PV2 high (digital sensors only); bit 6 = Input failure; bit 7 = Calibration required
HR1908doc x1909Sensor 2-6 primary valueMeasured value in the sensor's configured units.FLOAT32CDABRead
HR1942doc x1943Sensor 2-6 statusStatus code.UINT16Read0 = Error; 1 = None; 2 = Sensor: Auto Cal; 3 = Sensor: User Cal; 4 = DI State: Open; 5 = DI State: Closed; 6 = DI Interlock: Active; 7 = DI Interlock: Inactive; 8 = Relay: On; 9 = Relay: Off; 11 = Output Interlocked; 12 = Output Forced On; 13 = Output Timeout; 14 = Output Input Error; 15 = Output Error; 16 = Output Hold; 17 = Output HOA: Auto On; 18 = Output HOA: Auto Off; 19 = Output HOA: Hand; 20 = Output HOA: Off; 21 = Output Deadband; 22 = Relay Timeout; 23 = Relay OK; 24 = Daily Max Timeout; 25 = Biocide: Prebleed; 26 = Biocide: Hold; 27 = Biocide: Add; 28 = Time Proportional: Off; 29 = Bleed & Feed: Bleeding; 30 = Bleed & Feed: Timeout; 31 = Intermittent Sampling: Wait; 32 = Intermittent Sampling: Sample; 33 = Intermittent Sampling: Hold; 34 = Intermittent Sampling: Bleed; 35 = Probe Wash: On; 36 = Probe Wash: Hold
HR1943doc x1944Sensor 2-6 alarm bitfieldBITMAP16Readbit 0 = Low; bit 1 = High; bit 2 = Low Low; bit 3 = High High; bit 4 = Type-specific (replace electrode / total / PV2 low); bit 5 = PV2 high (digital sensors only); bit 6 = Input failure; bit 7 = Calibration required
HR8928doc x8929Relay 1 time onCurrent on time.UINT32CDABsRead
HR8930doc x8931Relay 1 total timeAccumulated on time.UINT32CDABsRead
HR8959doc x8960Relay 1 stateUINT16Read0 = Off; 1 = On
HR8960doc x8961Relay 1 reset time totalWrite 1 to reset.UINT16Read/write
HR8961doc x8962Relay 1 HOA settingHand / Off / Auto.UINT16Read/write0 = Hand; 1 = Off; 2 = Auto
HR8962doc x8963Relay 1 statusStatus code.UINT16Read0 = Error; 1 = None; 2 = Sensor: Auto Cal; 3 = Sensor: User Cal; 4 = DI State: Open; 5 = DI State: Closed; 6 = DI Interlock: Active; 7 = DI Interlock: Inactive; 8 = Relay: On; 9 = Relay: Off; 11 = Output Interlocked; 12 = Output Forced On; 13 = Output Timeout; 14 = Output Input Error; 15 = Output Error; 16 = Output Hold; 17 = Output HOA: Auto On; 18 = Output HOA: Auto Off; 19 = Output HOA: Hand; 20 = Output HOA: Off; 21 = Output Deadband; 22 = Relay Timeout; 23 = Relay OK; 24 = Daily Max Timeout; 25 = Biocide: Prebleed; 26 = Biocide: Hold; 27 = Biocide: Add; 28 = Time Proportional: Off; 29 = Bleed & Feed: Bleeding; 30 = Bleed & Feed: Timeout; 31 = Intermittent Sampling: Wait; 32 = Intermittent Sampling: Sample; 33 = Intermittent Sampling: Hold; 34 = Intermittent Sampling: Bleed; 35 = Probe Wash: On; 36 = Probe Wash: Hold
HR8963doc x8964Relay 1 alarm bitfieldBITMAP16Readbit 0 = Output timeout; bit 1 = Relay event skipped / turnover limit; bit 2 = Control failure; bit 3 = State alarm; bit 4 = Daily max timeout
HR8995doc x8996Relay 2 stateUINT16Read0 = Off; 1 = On
HR8997doc x8998Relay 2 HOA settingHand / Off / Auto.UINT16Read/write0 = Hand; 1 = Off; 2 = Auto
HR8998doc x8999Relay 2 statusStatus code.UINT16Read0 = Error; 1 = None; 2 = Sensor: Auto Cal; 3 = Sensor: User Cal; 4 = DI State: Open; 5 = DI State: Closed; 6 = DI Interlock: Active; 7 = DI Interlock: Inactive; 8 = Relay: On; 9 = Relay: Off; 11 = Output Interlocked; 12 = Output Forced On; 13 = Output Timeout; 14 = Output Input Error; 15 = Output Error; 16 = Output Hold; 17 = Output HOA: Auto On; 18 = Output HOA: Auto Off; 19 = Output HOA: Hand; 20 = Output HOA: Off; 21 = Output Deadband; 22 = Relay Timeout; 23 = Relay OK; 24 = Daily Max Timeout; 25 = Biocide: Prebleed; 26 = Biocide: Hold; 27 = Biocide: Add; 28 = Time Proportional: Off; 29 = Bleed & Feed: Bleeding; 30 = Bleed & Feed: Timeout; 31 = Intermittent Sampling: Wait; 32 = Intermittent Sampling: Sample; 33 = Intermittent Sampling: Hold; 34 = Intermittent Sampling: Bleed; 35 = Probe Wash: On; 36 = Probe Wash: Hold
HR8999doc x9000Relay 2 alarm bitfieldBITMAP16Readbit 0 = Output timeout; bit 1 = Relay event skipped / turnover limit; bit 2 = Control failure; bit 3 = State alarm; bit 4 = Daily max timeout
HR9031doc x9032Relay 3 stateUINT16Read0 = Off; 1 = On
HR9033doc x9034Relay 3 HOA settingHand / Off / Auto.UINT16Read/write0 = Hand; 1 = Off; 2 = Auto
HR9034doc x9035Relay 3 statusStatus code.UINT16Read0 = Error; 1 = None; 2 = Sensor: Auto Cal; 3 = Sensor: User Cal; 4 = DI State: Open; 5 = DI State: Closed; 6 = DI Interlock: Active; 7 = DI Interlock: Inactive; 8 = Relay: On; 9 = Relay: Off; 11 = Output Interlocked; 12 = Output Forced On; 13 = Output Timeout; 14 = Output Input Error; 15 = Output Error; 16 = Output Hold; 17 = Output HOA: Auto On; 18 = Output HOA: Auto Off; 19 = Output HOA: Hand; 20 = Output HOA: Off; 21 = Output Deadband; 22 = Relay Timeout; 23 = Relay OK; 24 = Daily Max Timeout; 25 = Biocide: Prebleed; 26 = Biocide: Hold; 27 = Biocide: Add; 28 = Time Proportional: Off; 29 = Bleed & Feed: Bleeding; 30 = Bleed & Feed: Timeout; 31 = Intermittent Sampling: Wait; 32 = Intermittent Sampling: Sample; 33 = Intermittent Sampling: Hold; 34 = Intermittent Sampling: Bleed; 35 = Probe Wash: On; 36 = Probe Wash: Hold
HR9035doc x9036Relay 3 alarm bitfieldBITMAP16Readbit 0 = Output timeout; bit 1 = Relay event skipped / turnover limit; bit 2 = Control failure; bit 3 = State alarm; bit 4 = Daily max timeout
HR9067doc x9068Relay 4 stateUINT16Read0 = Off; 1 = On
HR9069doc x9070Relay 4 HOA settingHand / Off / Auto.UINT16Read/write0 = Hand; 1 = Off; 2 = Auto
HR9070doc x9071Relay 4 statusStatus code.UINT16Read0 = Error; 1 = None; 2 = Sensor: Auto Cal; 3 = Sensor: User Cal; 4 = DI State: Open; 5 = DI State: Closed; 6 = DI Interlock: Active; 7 = DI Interlock: Inactive; 8 = Relay: On; 9 = Relay: Off; 11 = Output Interlocked; 12 = Output Forced On; 13 = Output Timeout; 14 = Output Input Error; 15 = Output Error; 16 = Output Hold; 17 = Output HOA: Auto On; 18 = Output HOA: Auto Off; 19 = Output HOA: Hand; 20 = Output HOA: Off; 21 = Output Deadband; 22 = Relay Timeout; 23 = Relay OK; 24 = Daily Max Timeout; 25 = Biocide: Prebleed; 26 = Biocide: Hold; 27 = Biocide: Add; 28 = Time Proportional: Off; 29 = Bleed & Feed: Bleeding; 30 = Bleed & Feed: Timeout; 31 = Intermittent Sampling: Wait; 32 = Intermittent Sampling: Sample; 33 = Intermittent Sampling: Hold; 34 = Intermittent Sampling: Bleed; 35 = Probe Wash: On; 36 = Probe Wash: Hold
HR9071doc x9072Relay 4 alarm bitfieldBITMAP16Readbit 0 = Output timeout; bit 1 = Relay event skipped / turnover limit; bit 2 = Control failure; bit 3 = State alarm; bit 4 = Daily max timeout
HR9103doc x9104Relay 5 stateUINT16Read0 = Off; 1 = On
HR9105doc x9106Relay 5 HOA settingHand / Off / Auto.UINT16Read/write0 = Hand; 1 = Off; 2 = Auto
HR9106doc x9107Relay 5 statusStatus code.UINT16Read0 = Error; 1 = None; 2 = Sensor: Auto Cal; 3 = Sensor: User Cal; 4 = DI State: Open; 5 = DI State: Closed; 6 = DI Interlock: Active; 7 = DI Interlock: Inactive; 8 = Relay: On; 9 = Relay: Off; 11 = Output Interlocked; 12 = Output Forced On; 13 = Output Timeout; 14 = Output Input Error; 15 = Output Error; 16 = Output Hold; 17 = Output HOA: Auto On; 18 = Output HOA: Auto Off; 19 = Output HOA: Hand; 20 = Output HOA: Off; 21 = Output Deadband; 22 = Relay Timeout; 23 = Relay OK; 24 = Daily Max Timeout; 25 = Biocide: Prebleed; 26 = Biocide: Hold; 27 = Biocide: Add; 28 = Time Proportional: Off; 29 = Bleed & Feed: Bleeding; 30 = Bleed & Feed: Timeout; 31 = Intermittent Sampling: Wait; 32 = Intermittent Sampling: Sample; 33 = Intermittent Sampling: Hold; 34 = Intermittent Sampling: Bleed; 35 = Probe Wash: On; 36 = Probe Wash: Hold
HR9107doc x9108Relay 5 alarm bitfieldBITMAP16Readbit 0 = Output timeout; bit 1 = Relay event skipped / turnover limit; bit 2 = Control failure; bit 3 = State alarm; bit 4 = Daily max timeout
HR9139doc x9140Relay 6 stateUINT16Read0 = Off; 1 = On
HR9141doc x9142Relay 6 HOA settingHand / Off / Auto.UINT16Read/write0 = Hand; 1 = Off; 2 = Auto
HR9142doc x9143Relay 6 statusStatus code.UINT16Read0 = Error; 1 = None; 2 = Sensor: Auto Cal; 3 = Sensor: User Cal; 4 = DI State: Open; 5 = DI State: Closed; 6 = DI Interlock: Active; 7 = DI Interlock: Inactive; 8 = Relay: On; 9 = Relay: Off; 11 = Output Interlocked; 12 = Output Forced On; 13 = Output Timeout; 14 = Output Input Error; 15 = Output Error; 16 = Output Hold; 17 = Output HOA: Auto On; 18 = Output HOA: Auto Off; 19 = Output HOA: Hand; 20 = Output HOA: Off; 21 = Output Deadband; 22 = Relay Timeout; 23 = Relay OK; 24 = Daily Max Timeout; 25 = Biocide: Prebleed; 26 = Biocide: Hold; 27 = Biocide: Add; 28 = Time Proportional: Off; 29 = Bleed & Feed: Bleeding; 30 = Bleed & Feed: Timeout; 31 = Intermittent Sampling: Wait; 32 = Intermittent Sampling: Sample; 33 = Intermittent Sampling: Hold; 34 = Intermittent Sampling: Bleed; 35 = Probe Wash: On; 36 = Probe Wash: Hold
HR9143doc x9144Relay 6 alarm bitfieldBITMAP16Readbit 0 = Output timeout; bit 1 = Relay event skipped / turnover limit; bit 2 = Control failure; bit 3 = State alarm; bit 4 = Daily max timeout
HR9175doc x9176Relay 7 stateUINT16Read0 = Off; 1 = On
HR9177doc x9178Relay 7 HOA settingHand / Off / Auto.UINT16Read/write0 = Hand; 1 = Off; 2 = Auto
HR9178doc x9179Relay 7 statusStatus code.UINT16Read0 = Error; 1 = None; 2 = Sensor: Auto Cal; 3 = Sensor: User Cal; 4 = DI State: Open; 5 = DI State: Closed; 6 = DI Interlock: Active; 7 = DI Interlock: Inactive; 8 = Relay: On; 9 = Relay: Off; 11 = Output Interlocked; 12 = Output Forced On; 13 = Output Timeout; 14 = Output Input Error; 15 = Output Error; 16 = Output Hold; 17 = Output HOA: Auto On; 18 = Output HOA: Auto Off; 19 = Output HOA: Hand; 20 = Output HOA: Off; 21 = Output Deadband; 22 = Relay Timeout; 23 = Relay OK; 24 = Daily Max Timeout; 25 = Biocide: Prebleed; 26 = Biocide: Hold; 27 = Biocide: Add; 28 = Time Proportional: Off; 29 = Bleed & Feed: Bleeding; 30 = Bleed & Feed: Timeout; 31 = Intermittent Sampling: Wait; 32 = Intermittent Sampling: Sample; 33 = Intermittent Sampling: Hold; 34 = Intermittent Sampling: Bleed; 35 = Probe Wash: On; 36 = Probe Wash: Hold
HR9179doc x9180Relay 7 alarm bitfieldBITMAP16Readbit 0 = Output timeout; bit 1 = Relay event skipped / turnover limit; bit 2 = Control failure; bit 3 = State alarm; bit 4 = Daily max timeout
HR9211doc x9212Relay 8 stateUINT16Read0 = Off; 1 = On
HR9213doc x9214Relay 8 HOA settingHand / Off / Auto.UINT16Read/write0 = Hand; 1 = Off; 2 = Auto
HR9214doc x9215Relay 8 statusStatus code.UINT16Read0 = Error; 1 = None; 2 = Sensor: Auto Cal; 3 = Sensor: User Cal; 4 = DI State: Open; 5 = DI State: Closed; 6 = DI Interlock: Active; 7 = DI Interlock: Inactive; 8 = Relay: On; 9 = Relay: Off; 11 = Output Interlocked; 12 = Output Forced On; 13 = Output Timeout; 14 = Output Input Error; 15 = Output Error; 16 = Output Hold; 17 = Output HOA: Auto On; 18 = Output HOA: Auto Off; 19 = Output HOA: Hand; 20 = Output HOA: Off; 21 = Output Deadband; 22 = Relay Timeout; 23 = Relay OK; 24 = Daily Max Timeout; 25 = Biocide: Prebleed; 26 = Biocide: Hold; 27 = Biocide: Add; 28 = Time Proportional: Off; 29 = Bleed & Feed: Bleeding; 30 = Bleed & Feed: Timeout; 31 = Intermittent Sampling: Wait; 32 = Intermittent Sampling: Sample; 33 = Intermittent Sampling: Hold; 34 = Intermittent Sampling: Bleed; 35 = Probe Wash: On; 36 = Probe Wash: Hold
HR9215doc x9216Relay 8 alarm bitfieldBITMAP16Readbit 0 = Output timeout; bit 1 = Relay event skipped / turnover limit; bit 2 = Control failure; bit 3 = State alarm; bit 4 = Daily max timeout

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Walchem W900 water treatment controller (Modbus/TCP)

What Modbus registers does the Walchem W900 water treatment controller (Modbus/TCP) have?

This map lists 138 registers: 138 holding registers. 17 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Walchem W900 water treatment controller (Modbus/TCP) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Section 5.1 says the published addresses are 1-based while the packet is 0-based, so subtract 1 on the wire. Each object's address = its block start (xNNNN in the I/O channel map) + the index in its type-specific map; e.g. firmware version is block x0037 + index 2 = 30039/40039, wire address 38. The 'x' prefix stands for the table digit: the same address can be read as a holding register (FC3) or input register (FC4).

What byte order does the Walchem W900 water treatment controller (Modbus/TCP) use for 32-bit values?

Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Walchem W900 water treatment controller (Modbus/TCP)?

Start with HR 36 Controller time (Controller time (proves comms)); HR 1152 Sensor 1-1 primary value (Sensor primary value); HR 1186 Sensor 1-1 status (Sensor status code); HR 1187 Sensor 1-1 alarm bitfield (Sensor alarm bitfield); HR 609 Digital input 1 state (Digital input 1 state); HR 8959 Relay 1 state (Relay 1 state); HR 8961 Relay 1 HOA setting (Relay 1 HOA setting); HR 71 System alarm bitfield (System alarm bitfield).

How do I enable Modbus control of the Walchem W900 water treatment controller (Modbus/TCP)?

Modbus/TCP is a feature of the controller; enable it and set the port and data format (normal or inverse word order) in the Remote Communications menu. A 'Verbose Logging' option there logs every message for commissioning and turns itself off at restart.

Where is the official Walchem W900 water treatment controller (Modbus/TCP) Modbus documentation?

The source is Modbus Manual - Intuition-9 / Intuition-6 / W900 / W600 (180676.K), revision 2026-06, published free by Walchem at https://www.walchem.com/Literature/Controllers/Intuition/180676_W600_W900_Intuition_Modbus_Manual.pdf.

More Walchem Modbus register maps

Other valves, actuators & sensors register maps

All valves, actuators & sensors Modbus register maps →

Source: Modbus Manual - Intuition-9 / Intuition-6 / W900 / W600 · 180676.K · rev. 2026-06. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.