Water treatment controller (Sensor / controller) · Modbus register map
Walchem W900 water treatment controller (Modbus/TCP) Modbus register map
Updated 17 November 2026
Walchem W-series and Intuition controllers run cooling tower, boiler and process water treatment. With the Modbus/TCP feature enabled they act as a Modbus TCP server on port 502. Data is laid out in 36-address blocks per object (system, network, each sensor input, digital input, relay); this map covers the system and network blocks and the key values of each I/O block, with 32-bit floats and integers sent low word first.
This page lists 138 Modbus registers for the Walchem W900 water treatment controller (Modbus/TCP) — 17 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Walchem’s own free documentation (linked below) and checked against it.
- Manufacturer
- Walchem
- Model
- W900 water treatment controller (Modbus/TCP)
- Equipment type
- Water treatment controller (Sensor / controller)
- Registers
- 138 (17 writable)
- Transport
- Modbus TCP
- Default unit ID
- 1
- TCP port
- 502
- Documented addressing
- 1-based (subtract 1 for the wire address)
- 32-bit word order
- CDAB low word first (word-swapped)
- Firmware
- Controller software 3.01 and higher
- Also known as
- W900 series
Integration notes: Walchem W900 water treatment controller (Modbus/TCP)
Enable Modbus/TCP in the controller's Remote Communications menu, connect to port 502 with any unit ID except 0, and read values as CDAB 32-bit pairs. Poll no faster than every 5 s.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 36 | Controller time | UINT32 CDAB | Controller time (proves comms) | Read |
| HR 1152 | Sensor 1-1 primary value | FLOAT32 CDAB | Sensor primary value | Read |
| HR 1186 | Sensor 1-1 status | UINT16 | Sensor status code | Read |
| HR 1187 | Sensor 1-1 alarm bitfield | BITMAP16 | Sensor alarm bitfield | Read |
| HR 609 | Digital input 1 state | UINT16 | Digital input 1 state | Read |
| HR 8959 | Relay 1 state | UINT16 | Relay 1 state | Read |
| HR 8961 | Relay 1 HOA setting | UINT16 | Relay 1 HOA setting | Read/write |
| HR 71 | System alarm bitfield | BITMAP16 | System alarm bitfield | Read |
Enable Modbus control & writes
Modbus/TCP is a feature of the controller; enable it and set the port and data format (normal or inverse word order) in the Remote Communications menu. A 'Verbose Logging' option there logs every message for commissioning and turns itself off at restart.
Byte order & addressing
- Addresses are 1-based: subtract 1 for the wire address.
- Floats and 32-bit integers are low word first (CDAB) unless 'inverse' format is selected.
- Unit ID 0 is treated as broadcast: the request is processed but no reply is sent.
- FC1/FC2 and FC3/FC4 are interchangeable on reads.
Network setup
- Network address, port (default 502) and data format are set on the controller's communications menus.
- Read up to 125 registers per request.
Watch out for
- Polling faster than once every 5 seconds is unsupported.
- Block start addresses depend on the controller model and on which I/O cards are fitted; confirm the I/O channel map for your unit.
- Modbus RTU is not supported; serial masters need a TCP gateway.
Walchem W900 water treatment controller (Modbus/TCP) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 36doc x0037 | Controller time | Unix time (seconds since 1970). | UINT32 | CDAB | s | Read | ||
| HR | 38doc x0039 | Controller firmware version | FLOAT32 | CDAB | Read | ||||
| HR | 40doc x0041 | Date of last data log | Unix time. | UINT32 | CDAB | s | Read | ||
| HR | 42doc x0043 | Controller processor temperature | FLOAT32 | CDAB | °C | Read | |||
| HR | 44doc x0045 | Network card temperature | FLOAT32 | CDAB | °C | Read | |||
| HR | 46doc x0047 | Digital input card temperature | W900/Intuition-9 only. | FLOAT32 | CDAB | °C | Read | ||
| HR | 48doc x0049 | I/O card 1 temperature | FLOAT32 | CDAB | °C | Read | |||
| HR | 50doc x0051 | I/O card 2 temperature | FLOAT32 | CDAB | °C | Read | |||
| HR | 52doc x0053 | I/O card 3 temperature | W900/Intuition-9 only. | FLOAT32 | CDAB | °C | Read | ||
| HR | 54doc x0055 | I/O card 4 temperature | W900/Intuition-9 only. | FLOAT32 | CDAB | °C | Read | ||
| HR | 62doc x0063 | Battery power | Clock battery voltage. | FLOAT32 | CDAB | V | Read | ||
| HR | 64doc x0065 | +3.3 V supply | FLOAT32 | CDAB | V | Read | |||
| HR | 66doc x0067 | +5 V supply | FLOAT32 | CDAB | V | Read | |||
| HR | 68doc x0069 | +12 V supply | W900/Intuition-9 only. | FLOAT32 | CDAB | V | Read | ||
| HR | 71doc x0072 | System alarm bitfield | 8 alarm flags in the low byte. | BITMAP16 | Read | bit 0 = Temperature alarm; bit 1 = Battery low; bit 2 = Invalid setting; bit 3 = Software version (add-on card needs update); bit 4 = Board failure; bit 5 = Internal voltage out of range | |||
| HR | 144doc x0145 | Fluent last data time | Unix time. | UINT32 | CDAB | s | Read | ||
| HR | 146doc x0147 | Fluent last configuration time | Unix time. | UINT32 | CDAB | s | Read | ||
| HR | 148doc x0149 | Fluent refresh rate | 1-1440 minutes. | FLOAT32 | CDAB | min | Read/write | ||
| HR | 150doc x0151 | Fluent LiveConnect status | Status code. | UINT16 | Read | 0 = Error; 1 = None; 2 = Sensor: Auto Cal; 3 = Sensor: User Cal; 4 = DI State: Open; 5 = DI State: Closed; 6 = DI Interlock: Active; 7 = DI Interlock: Inactive; 8 = Relay: On; 9 = Relay: Off; 11 = Output Interlocked; 12 = Output Forced On; 13 = Output Timeout; 14 = Output Input Error; 15 = Output Error; 16 = Output Hold; 17 = Output HOA: Auto On; 18 = Output HOA: Auto Off; 19 = Output HOA: Hand; 20 = Output HOA: Off; 21 = Output Deadband; 22 = Relay Timeout; 23 = Relay OK; 24 = Daily Max Timeout; 25 = Biocide: Prebleed; 26 = Biocide: Hold; 27 = Biocide: Add; 28 = Time Proportional: Off; 29 = Bleed & Feed: Bleeding; 30 = Bleed & Feed: Timeout; 31 = Intermittent Sampling: Wait; 32 = Intermittent Sampling: Sample; 33 = Intermittent Sampling: Hold; 34 = Intermittent Sampling: Bleed; 35 = Probe Wash: On; 36 = Probe Wash: Hold | |||
| HR | 151doc x0152 | Web server status | Status code (93-95 = web server modes). | UINT16 | Read | 0 = Error; 1 = None; 2 = Sensor: Auto Cal; 3 = Sensor: User Cal; 4 = DI State: Open; 5 = DI State: Closed; 6 = DI Interlock: Active; 7 = DI Interlock: Inactive; 8 = Relay: On; 9 = Relay: Off; 11 = Output Interlocked; 12 = Output Forced On; 13 = Output Timeout; 14 = Output Input Error; 15 = Output Error; 16 = Output Hold; 17 = Output HOA: Auto On; 18 = Output HOA: Auto Off; 19 = Output HOA: Hand; 20 = Output HOA: Off; 21 = Output Deadband; 22 = Relay Timeout; 23 = Relay OK; 24 = Daily Max Timeout; 25 = Biocide: Prebleed; 26 = Biocide: Hold; 27 = Biocide: Add; 28 = Time Proportional: Off; 29 = Bleed & Feed: Bleeding; 30 = Bleed & Feed: Timeout; 31 = Intermittent Sampling: Wait; 32 = Intermittent Sampling: Sample; 33 = Intermittent Sampling: Hold; 34 = Intermittent Sampling: Bleed; 35 = Probe Wash: On; 36 = Probe Wash: Hold | |||
| HR | 179doc x0180 | Network alarm bitfield | BITMAP16 | Read | bit 0 = Web server failure; bit 1 = Fluent data comm; bit 2 = Fluent LiveConnect; bit 3 = WiFi error | ||||
| HR | 576doc x0577 | Digital input 1 last reset date | Unix time (DI State type). | UINT32 | CDAB | s | Read | ||
| HR | 578doc x0579 | Digital input 1 total time | Accumulated time (DI State type). | UINT32 | CDAB | s | Read | ||
| HR | 580doc x0581 | Digital input 1 cycle time | DI State type. | UINT32 | CDAB | s | Read | ||
| HR | 608doc x0609 | Digital input 1 reset total time | Write 1 to reset (DI State type). | UINT16 | Read/write | ||||
| HR | 609doc x0610 | Digital input 1 state | DI State type. | UINT16 | Read | 0 = Open; 1 = Closed | |||
| HR | 610doc x0611 | Digital input 1 interlock state | DI State type. | UINT16 | Read | 0 = Inactive; 1 = Active interlock | |||
| HR | 611doc x0612 | Digital input 1 alarm bitfield | BITMAP16 | Read | bit 0 = DI state alarm; bit 1 = Total; bit 2 = Total range; bit 3 = Input failure; bit 4 = Flow verify / Modbus alarm (type-specific); bit 5 = Low flow; bit 6 = High flow | ||||
| HR | 645doc x0646 | Digital input 2 state | DI State type. | UINT16 | Read | 0 = Open; 1 = Closed | |||
| HR | 647doc x0648 | Digital input 2 alarm bitfield | BITMAP16 | Read | bit 0 = DI state alarm; bit 1 = Total; bit 2 = Total range; bit 3 = Input failure; bit 4 = Flow verify / Modbus alarm (type-specific); bit 5 = Low flow; bit 6 = High flow | ||||
| HR | 681doc x0682 | Digital input 3 state | DI State type. | UINT16 | Read | 0 = Open; 1 = Closed | |||
| HR | 683doc x0684 | Digital input 3 alarm bitfield | BITMAP16 | Read | bit 0 = DI state alarm; bit 1 = Total; bit 2 = Total range; bit 3 = Input failure; bit 4 = Flow verify / Modbus alarm (type-specific); bit 5 = Low flow; bit 6 = High flow | ||||
| HR | 717doc x0718 | Digital input 4 state | DI State type. | UINT16 | Read | 0 = Open; 1 = Closed | |||
| HR | 719doc x0720 | Digital input 4 alarm bitfield | BITMAP16 | Read | bit 0 = DI state alarm; bit 1 = Total; bit 2 = Total range; bit 3 = Input failure; bit 4 = Flow verify / Modbus alarm (type-specific); bit 5 = Low flow; bit 6 = High flow | ||||
| HR | 753doc x0754 | Digital input 5 state | DI State type. | UINT16 | Read | 0 = Open; 1 = Closed | |||
| HR | 755doc x0756 | Digital input 5 alarm bitfield | BITMAP16 | Read | bit 0 = DI state alarm; bit 1 = Total; bit 2 = Total range; bit 3 = Input failure; bit 4 = Flow verify / Modbus alarm (type-specific); bit 5 = Low flow; bit 6 = High flow | ||||
| HR | 789doc x0790 | Digital input 6 state | DI State type. | UINT16 | Read | 0 = Open; 1 = Closed | |||
| HR | 791doc x0792 | Digital input 6 alarm bitfield | BITMAP16 | Read | bit 0 = DI state alarm; bit 1 = Total; bit 2 = Total range; bit 3 = Input failure; bit 4 = Flow verify / Modbus alarm (type-specific); bit 5 = Low flow; bit 6 = High flow | ||||
| HR | 825doc x0826 | Digital input 7 state | DI State type. | UINT16 | Read | 0 = Open; 1 = Closed | |||
| HR | 827doc x0828 | Digital input 7 alarm bitfield | BITMAP16 | Read | bit 0 = DI state alarm; bit 1 = Total; bit 2 = Total range; bit 3 = Input failure; bit 4 = Flow verify / Modbus alarm (type-specific); bit 5 = Low flow; bit 6 = High flow | ||||
| HR | 861doc x0862 | Digital input 8 state | DI State type. | UINT16 | Read | 0 = Open; 1 = Closed | |||
| HR | 863doc x0864 | Digital input 8 alarm bitfield | BITMAP16 | Read | bit 0 = DI state alarm; bit 1 = Total; bit 2 = Total range; bit 3 = Input failure; bit 4 = Flow verify / Modbus alarm (type-specific); bit 5 = Low flow; bit 6 = High flow | ||||
| HR | 897doc x0898 | Digital input 9 state | DI State type. | UINT16 | Read | 0 = Open; 1 = Closed | |||
| HR | 899doc x0900 | Digital input 9 alarm bitfield | BITMAP16 | Read | bit 0 = DI state alarm; bit 1 = Total; bit 2 = Total range; bit 3 = Input failure; bit 4 = Flow verify / Modbus alarm (type-specific); bit 5 = Low flow; bit 6 = High flow | ||||
| HR | 933doc x0934 | Digital input 10 state | DI State type. | UINT16 | Read | 0 = Open; 1 = Closed | |||
| HR | 935doc x0936 | Digital input 10 alarm bitfield | BITMAP16 | Read | bit 0 = DI state alarm; bit 1 = Total; bit 2 = Total range; bit 3 = Input failure; bit 4 = Flow verify / Modbus alarm (type-specific); bit 5 = Low flow; bit 6 = High flow | ||||
| HR | 969doc x0970 | Digital input 11 state | DI State type. | UINT16 | Read | 0 = Open; 1 = Closed | |||
| HR | 971doc x0972 | Digital input 11 alarm bitfield | BITMAP16 | Read | bit 0 = DI state alarm; bit 1 = Total; bit 2 = Total range; bit 3 = Input failure; bit 4 = Flow verify / Modbus alarm (type-specific); bit 5 = Low flow; bit 6 = High flow | ||||
| HR | 1005doc x1006 | Digital input 12 state | DI State type. | UINT16 | Read | 0 = Open; 1 = Closed | |||
| HR | 1007doc x1008 | Digital input 12 alarm bitfield | BITMAP16 | Read | bit 0 = DI state alarm; bit 1 = Total; bit 2 = Total range; bit 3 = Input failure; bit 4 = Flow verify / Modbus alarm (type-specific); bit 5 = Low flow; bit 6 = High flow | ||||
| HR | 1152doc x1153 | Sensor 1-1 primary value | Measured value in the sensor's configured units. | FLOAT32 | CDAB | Read | |||
| HR | 1154doc x1155 | Sensor 1-1 primary raw value | Raw signal: uS/cm, mV, mA or ohm depending on sensor type. | FLOAT32 | CDAB | Read | |||
| HR | 1156doc x1157 | Sensor 1-1 last calibration date | Unix time. | UINT32 | CDAB | s | Read | ||
| HR | 1162doc x1163 | Sensor 1-1 deadband | Alarm deadband in sensor units. | FLOAT32 | CDAB | Read/write | |||
| HR | 1164doc x1165 | Sensor 1-1 smoothing factor | 0-90 %. | FLOAT32 | CDAB | % | Read/write | ||
| HR | 1166doc x1167 | Sensor 1-1 LoLo alarm setpoint | FLOAT32 | CDAB | Read/write | ||||
| HR | 1168doc x1169 | Sensor 1-1 Low alarm setpoint | FLOAT32 | CDAB | Read/write | ||||
| HR | 1170doc x1171 | Sensor 1-1 High alarm setpoint | FLOAT32 | CDAB | Read/write | ||||
| HR | 1172doc x1173 | Sensor 1-1 HiHi alarm setpoint | FLOAT32 | CDAB | Read/write | ||||
| HR | 1174doc x1175 | Sensor 1-1 24-hour minimum | W900/Intuition-9 only. | FLOAT32 | CDAB | Read | |||
| HR | 1176doc x1177 | Sensor 1-1 24-hour maximum | W900/Intuition-9 only. | FLOAT32 | CDAB | Read | |||
| HR | 1178doc x1179 | Sensor 1-1 24-hour average | W900/Intuition-9 only. | FLOAT32 | CDAB | Read | |||
| HR | 1180doc x1181 | Sensor 1-1 Low alarm | UINT16 | Read | 0 = Inactive; 1 = Alarm active | ||||
| HR | 1181doc x1182 | Sensor 1-1 High alarm | UINT16 | Read | 0 = Inactive; 1 = Alarm active | ||||
| HR | 1182doc x1183 | Sensor 1-1 LoLo alarm | UINT16 | Read | 0 = Inactive; 1 = Alarm active | ||||
| HR | 1183doc x1184 | Sensor 1-1 HiHi alarm | UINT16 | Read | 0 = Inactive; 1 = Alarm active | ||||
| HR | 1184doc x1185 | Sensor 1-1 calibration required | UINT16 | Read | 0 = Inactive; 1 = Alarm active | ||||
| HR | 1185doc x1186 | Sensor 1-1 input failure | UINT16 | Read | 0 = Inactive; 1 = Alarm active | ||||
| HR | 1186doc x1187 | Sensor 1-1 status | Status code. | UINT16 | Read | 0 = Error; 1 = None; 2 = Sensor: Auto Cal; 3 = Sensor: User Cal; 4 = DI State: Open; 5 = DI State: Closed; 6 = DI Interlock: Active; 7 = DI Interlock: Inactive; 8 = Relay: On; 9 = Relay: Off; 11 = Output Interlocked; 12 = Output Forced On; 13 = Output Timeout; 14 = Output Input Error; 15 = Output Error; 16 = Output Hold; 17 = Output HOA: Auto On; 18 = Output HOA: Auto Off; 19 = Output HOA: Hand; 20 = Output HOA: Off; 21 = Output Deadband; 22 = Relay Timeout; 23 = Relay OK; 24 = Daily Max Timeout; 25 = Biocide: Prebleed; 26 = Biocide: Hold; 27 = Biocide: Add; 28 = Time Proportional: Off; 29 = Bleed & Feed: Bleeding; 30 = Bleed & Feed: Timeout; 31 = Intermittent Sampling: Wait; 32 = Intermittent Sampling: Sample; 33 = Intermittent Sampling: Hold; 34 = Intermittent Sampling: Bleed; 35 = Probe Wash: On; 36 = Probe Wash: Hold | |||
| HR | 1187doc x1188 | Sensor 1-1 alarm bitfield | BITMAP16 | Read | bit 0 = Low; bit 1 = High; bit 2 = Low Low; bit 3 = High High; bit 4 = Type-specific (replace electrode / total / PV2 low); bit 5 = PV2 high (digital sensors only); bit 6 = Input failure; bit 7 = Calibration required | ||||
| HR | 1188doc x1189 | Sensor 1-2 primary value | Measured value in the sensor's configured units. | FLOAT32 | CDAB | Read | |||
| HR | 1222doc x1223 | Sensor 1-2 status | Status code. | UINT16 | Read | 0 = Error; 1 = None; 2 = Sensor: Auto Cal; 3 = Sensor: User Cal; 4 = DI State: Open; 5 = DI State: Closed; 6 = DI Interlock: Active; 7 = DI Interlock: Inactive; 8 = Relay: On; 9 = Relay: Off; 11 = Output Interlocked; 12 = Output Forced On; 13 = Output Timeout; 14 = Output Input Error; 15 = Output Error; 16 = Output Hold; 17 = Output HOA: Auto On; 18 = Output HOA: Auto Off; 19 = Output HOA: Hand; 20 = Output HOA: Off; 21 = Output Deadband; 22 = Relay Timeout; 23 = Relay OK; 24 = Daily Max Timeout; 25 = Biocide: Prebleed; 26 = Biocide: Hold; 27 = Biocide: Add; 28 = Time Proportional: Off; 29 = Bleed & Feed: Bleeding; 30 = Bleed & Feed: Timeout; 31 = Intermittent Sampling: Wait; 32 = Intermittent Sampling: Sample; 33 = Intermittent Sampling: Hold; 34 = Intermittent Sampling: Bleed; 35 = Probe Wash: On; 36 = Probe Wash: Hold | |||
| HR | 1223doc x1224 | Sensor 1-2 alarm bitfield | BITMAP16 | Read | bit 0 = Low; bit 1 = High; bit 2 = Low Low; bit 3 = High High; bit 4 = Type-specific (replace electrode / total / PV2 low); bit 5 = PV2 high (digital sensors only); bit 6 = Input failure; bit 7 = Calibration required | ||||
| HR | 1224doc x1225 | Sensor 1-3 primary value | Measured value in the sensor's configured units. | FLOAT32 | CDAB | Read | |||
| HR | 1258doc x1259 | Sensor 1-3 status | Status code. | UINT16 | Read | 0 = Error; 1 = None; 2 = Sensor: Auto Cal; 3 = Sensor: User Cal; 4 = DI State: Open; 5 = DI State: Closed; 6 = DI Interlock: Active; 7 = DI Interlock: Inactive; 8 = Relay: On; 9 = Relay: Off; 11 = Output Interlocked; 12 = Output Forced On; 13 = Output Timeout; 14 = Output Input Error; 15 = Output Error; 16 = Output Hold; 17 = Output HOA: Auto On; 18 = Output HOA: Auto Off; 19 = Output HOA: Hand; 20 = Output HOA: Off; 21 = Output Deadband; 22 = Relay Timeout; 23 = Relay OK; 24 = Daily Max Timeout; 25 = Biocide: Prebleed; 26 = Biocide: Hold; 27 = Biocide: Add; 28 = Time Proportional: Off; 29 = Bleed & Feed: Bleeding; 30 = Bleed & Feed: Timeout; 31 = Intermittent Sampling: Wait; 32 = Intermittent Sampling: Sample; 33 = Intermittent Sampling: Hold; 34 = Intermittent Sampling: Bleed; 35 = Probe Wash: On; 36 = Probe Wash: Hold | |||
| HR | 1259doc x1260 | Sensor 1-3 alarm bitfield | BITMAP16 | Read | bit 0 = Low; bit 1 = High; bit 2 = Low Low; bit 3 = High High; bit 4 = Type-specific (replace electrode / total / PV2 low); bit 5 = PV2 high (digital sensors only); bit 6 = Input failure; bit 7 = Calibration required | ||||
| HR | 1260doc x1261 | Sensor 1-4 primary value | Measured value in the sensor's configured units. | FLOAT32 | CDAB | Read | |||
| HR | 1294doc x1295 | Sensor 1-4 status | Status code. | UINT16 | Read | 0 = Error; 1 = None; 2 = Sensor: Auto Cal; 3 = Sensor: User Cal; 4 = DI State: Open; 5 = DI State: Closed; 6 = DI Interlock: Active; 7 = DI Interlock: Inactive; 8 = Relay: On; 9 = Relay: Off; 11 = Output Interlocked; 12 = Output Forced On; 13 = Output Timeout; 14 = Output Input Error; 15 = Output Error; 16 = Output Hold; 17 = Output HOA: Auto On; 18 = Output HOA: Auto Off; 19 = Output HOA: Hand; 20 = Output HOA: Off; 21 = Output Deadband; 22 = Relay Timeout; 23 = Relay OK; 24 = Daily Max Timeout; 25 = Biocide: Prebleed; 26 = Biocide: Hold; 27 = Biocide: Add; 28 = Time Proportional: Off; 29 = Bleed & Feed: Bleeding; 30 = Bleed & Feed: Timeout; 31 = Intermittent Sampling: Wait; 32 = Intermittent Sampling: Sample; 33 = Intermittent Sampling: Hold; 34 = Intermittent Sampling: Bleed; 35 = Probe Wash: On; 36 = Probe Wash: Hold | |||
| HR | 1295doc x1296 | Sensor 1-4 alarm bitfield | BITMAP16 | Read | bit 0 = Low; bit 1 = High; bit 2 = Low Low; bit 3 = High High; bit 4 = Type-specific (replace electrode / total / PV2 low); bit 5 = PV2 high (digital sensors only); bit 6 = Input failure; bit 7 = Calibration required | ||||
| HR | 1296doc x1297 | Sensor 1-5 primary value | Measured value in the sensor's configured units. | FLOAT32 | CDAB | Read | |||
| HR | 1330doc x1331 | Sensor 1-5 status | Status code. | UINT16 | Read | 0 = Error; 1 = None; 2 = Sensor: Auto Cal; 3 = Sensor: User Cal; 4 = DI State: Open; 5 = DI State: Closed; 6 = DI Interlock: Active; 7 = DI Interlock: Inactive; 8 = Relay: On; 9 = Relay: Off; 11 = Output Interlocked; 12 = Output Forced On; 13 = Output Timeout; 14 = Output Input Error; 15 = Output Error; 16 = Output Hold; 17 = Output HOA: Auto On; 18 = Output HOA: Auto Off; 19 = Output HOA: Hand; 20 = Output HOA: Off; 21 = Output Deadband; 22 = Relay Timeout; 23 = Relay OK; 24 = Daily Max Timeout; 25 = Biocide: Prebleed; 26 = Biocide: Hold; 27 = Biocide: Add; 28 = Time Proportional: Off; 29 = Bleed & Feed: Bleeding; 30 = Bleed & Feed: Timeout; 31 = Intermittent Sampling: Wait; 32 = Intermittent Sampling: Sample; 33 = Intermittent Sampling: Hold; 34 = Intermittent Sampling: Bleed; 35 = Probe Wash: On; 36 = Probe Wash: Hold | |||
| HR | 1331doc x1332 | Sensor 1-5 alarm bitfield | BITMAP16 | Read | bit 0 = Low; bit 1 = High; bit 2 = Low Low; bit 3 = High High; bit 4 = Type-specific (replace electrode / total / PV2 low); bit 5 = PV2 high (digital sensors only); bit 6 = Input failure; bit 7 = Calibration required | ||||
| HR | 1332doc x1333 | Sensor 1-6 primary value | Measured value in the sensor's configured units. | FLOAT32 | CDAB | Read | |||
| HR | 1366doc x1367 | Sensor 1-6 status | Status code. | UINT16 | Read | 0 = Error; 1 = None; 2 = Sensor: Auto Cal; 3 = Sensor: User Cal; 4 = DI State: Open; 5 = DI State: Closed; 6 = DI Interlock: Active; 7 = DI Interlock: Inactive; 8 = Relay: On; 9 = Relay: Off; 11 = Output Interlocked; 12 = Output Forced On; 13 = Output Timeout; 14 = Output Input Error; 15 = Output Error; 16 = Output Hold; 17 = Output HOA: Auto On; 18 = Output HOA: Auto Off; 19 = Output HOA: Hand; 20 = Output HOA: Off; 21 = Output Deadband; 22 = Relay Timeout; 23 = Relay OK; 24 = Daily Max Timeout; 25 = Biocide: Prebleed; 26 = Biocide: Hold; 27 = Biocide: Add; 28 = Time Proportional: Off; 29 = Bleed & Feed: Bleeding; 30 = Bleed & Feed: Timeout; 31 = Intermittent Sampling: Wait; 32 = Intermittent Sampling: Sample; 33 = Intermittent Sampling: Hold; 34 = Intermittent Sampling: Bleed; 35 = Probe Wash: On; 36 = Probe Wash: Hold | |||
| HR | 1367doc x1368 | Sensor 1-6 alarm bitfield | BITMAP16 | Read | bit 0 = Low; bit 1 = High; bit 2 = Low Low; bit 3 = High High; bit 4 = Type-specific (replace electrode / total / PV2 low); bit 5 = PV2 high (digital sensors only); bit 6 = Input failure; bit 7 = Calibration required | ||||
| HR | 1728doc x1729 | Sensor 2-1 primary value | Measured value in the sensor's configured units. | FLOAT32 | CDAB | Read | |||
| HR | 1762doc x1763 | Sensor 2-1 status | Status code. | UINT16 | Read | 0 = Error; 1 = None; 2 = Sensor: Auto Cal; 3 = Sensor: User Cal; 4 = DI State: Open; 5 = DI State: Closed; 6 = DI Interlock: Active; 7 = DI Interlock: Inactive; 8 = Relay: On; 9 = Relay: Off; 11 = Output Interlocked; 12 = Output Forced On; 13 = Output Timeout; 14 = Output Input Error; 15 = Output Error; 16 = Output Hold; 17 = Output HOA: Auto On; 18 = Output HOA: Auto Off; 19 = Output HOA: Hand; 20 = Output HOA: Off; 21 = Output Deadband; 22 = Relay Timeout; 23 = Relay OK; 24 = Daily Max Timeout; 25 = Biocide: Prebleed; 26 = Biocide: Hold; 27 = Biocide: Add; 28 = Time Proportional: Off; 29 = Bleed & Feed: Bleeding; 30 = Bleed & Feed: Timeout; 31 = Intermittent Sampling: Wait; 32 = Intermittent Sampling: Sample; 33 = Intermittent Sampling: Hold; 34 = Intermittent Sampling: Bleed; 35 = Probe Wash: On; 36 = Probe Wash: Hold | |||
| HR | 1763doc x1764 | Sensor 2-1 alarm bitfield | BITMAP16 | Read | bit 0 = Low; bit 1 = High; bit 2 = Low Low; bit 3 = High High; bit 4 = Type-specific (replace electrode / total / PV2 low); bit 5 = PV2 high (digital sensors only); bit 6 = Input failure; bit 7 = Calibration required | ||||
| HR | 1764doc x1765 | Sensor 2-2 primary value | Measured value in the sensor's configured units. | FLOAT32 | CDAB | Read | |||
| HR | 1798doc x1799 | Sensor 2-2 status | Status code. | UINT16 | Read | 0 = Error; 1 = None; 2 = Sensor: Auto Cal; 3 = Sensor: User Cal; 4 = DI State: Open; 5 = DI State: Closed; 6 = DI Interlock: Active; 7 = DI Interlock: Inactive; 8 = Relay: On; 9 = Relay: Off; 11 = Output Interlocked; 12 = Output Forced On; 13 = Output Timeout; 14 = Output Input Error; 15 = Output Error; 16 = Output Hold; 17 = Output HOA: Auto On; 18 = Output HOA: Auto Off; 19 = Output HOA: Hand; 20 = Output HOA: Off; 21 = Output Deadband; 22 = Relay Timeout; 23 = Relay OK; 24 = Daily Max Timeout; 25 = Biocide: Prebleed; 26 = Biocide: Hold; 27 = Biocide: Add; 28 = Time Proportional: Off; 29 = Bleed & Feed: Bleeding; 30 = Bleed & Feed: Timeout; 31 = Intermittent Sampling: Wait; 32 = Intermittent Sampling: Sample; 33 = Intermittent Sampling: Hold; 34 = Intermittent Sampling: Bleed; 35 = Probe Wash: On; 36 = Probe Wash: Hold | |||
| HR | 1799doc x1800 | Sensor 2-2 alarm bitfield | BITMAP16 | Read | bit 0 = Low; bit 1 = High; bit 2 = Low Low; bit 3 = High High; bit 4 = Type-specific (replace electrode / total / PV2 low); bit 5 = PV2 high (digital sensors only); bit 6 = Input failure; bit 7 = Calibration required | ||||
| HR | 1800doc x1801 | Sensor 2-3 primary value | Measured value in the sensor's configured units. | FLOAT32 | CDAB | Read | |||
| HR | 1834doc x1835 | Sensor 2-3 status | Status code. | UINT16 | Read | 0 = Error; 1 = None; 2 = Sensor: Auto Cal; 3 = Sensor: User Cal; 4 = DI State: Open; 5 = DI State: Closed; 6 = DI Interlock: Active; 7 = DI Interlock: Inactive; 8 = Relay: On; 9 = Relay: Off; 11 = Output Interlocked; 12 = Output Forced On; 13 = Output Timeout; 14 = Output Input Error; 15 = Output Error; 16 = Output Hold; 17 = Output HOA: Auto On; 18 = Output HOA: Auto Off; 19 = Output HOA: Hand; 20 = Output HOA: Off; 21 = Output Deadband; 22 = Relay Timeout; 23 = Relay OK; 24 = Daily Max Timeout; 25 = Biocide: Prebleed; 26 = Biocide: Hold; 27 = Biocide: Add; 28 = Time Proportional: Off; 29 = Bleed & Feed: Bleeding; 30 = Bleed & Feed: Timeout; 31 = Intermittent Sampling: Wait; 32 = Intermittent Sampling: Sample; 33 = Intermittent Sampling: Hold; 34 = Intermittent Sampling: Bleed; 35 = Probe Wash: On; 36 = Probe Wash: Hold | |||
| HR | 1835doc x1836 | Sensor 2-3 alarm bitfield | BITMAP16 | Read | bit 0 = Low; bit 1 = High; bit 2 = Low Low; bit 3 = High High; bit 4 = Type-specific (replace electrode / total / PV2 low); bit 5 = PV2 high (digital sensors only); bit 6 = Input failure; bit 7 = Calibration required | ||||
| HR | 1836doc x1837 | Sensor 2-4 primary value | Measured value in the sensor's configured units. | FLOAT32 | CDAB | Read | |||
| HR | 1870doc x1871 | Sensor 2-4 status | Status code. | UINT16 | Read | 0 = Error; 1 = None; 2 = Sensor: Auto Cal; 3 = Sensor: User Cal; 4 = DI State: Open; 5 = DI State: Closed; 6 = DI Interlock: Active; 7 = DI Interlock: Inactive; 8 = Relay: On; 9 = Relay: Off; 11 = Output Interlocked; 12 = Output Forced On; 13 = Output Timeout; 14 = Output Input Error; 15 = Output Error; 16 = Output Hold; 17 = Output HOA: Auto On; 18 = Output HOA: Auto Off; 19 = Output HOA: Hand; 20 = Output HOA: Off; 21 = Output Deadband; 22 = Relay Timeout; 23 = Relay OK; 24 = Daily Max Timeout; 25 = Biocide: Prebleed; 26 = Biocide: Hold; 27 = Biocide: Add; 28 = Time Proportional: Off; 29 = Bleed & Feed: Bleeding; 30 = Bleed & Feed: Timeout; 31 = Intermittent Sampling: Wait; 32 = Intermittent Sampling: Sample; 33 = Intermittent Sampling: Hold; 34 = Intermittent Sampling: Bleed; 35 = Probe Wash: On; 36 = Probe Wash: Hold | |||
| HR | 1871doc x1872 | Sensor 2-4 alarm bitfield | BITMAP16 | Read | bit 0 = Low; bit 1 = High; bit 2 = Low Low; bit 3 = High High; bit 4 = Type-specific (replace electrode / total / PV2 low); bit 5 = PV2 high (digital sensors only); bit 6 = Input failure; bit 7 = Calibration required | ||||
| HR | 1872doc x1873 | Sensor 2-5 primary value | Measured value in the sensor's configured units. | FLOAT32 | CDAB | Read | |||
| HR | 1906doc x1907 | Sensor 2-5 status | Status code. | UINT16 | Read | 0 = Error; 1 = None; 2 = Sensor: Auto Cal; 3 = Sensor: User Cal; 4 = DI State: Open; 5 = DI State: Closed; 6 = DI Interlock: Active; 7 = DI Interlock: Inactive; 8 = Relay: On; 9 = Relay: Off; 11 = Output Interlocked; 12 = Output Forced On; 13 = Output Timeout; 14 = Output Input Error; 15 = Output Error; 16 = Output Hold; 17 = Output HOA: Auto On; 18 = Output HOA: Auto Off; 19 = Output HOA: Hand; 20 = Output HOA: Off; 21 = Output Deadband; 22 = Relay Timeout; 23 = Relay OK; 24 = Daily Max Timeout; 25 = Biocide: Prebleed; 26 = Biocide: Hold; 27 = Biocide: Add; 28 = Time Proportional: Off; 29 = Bleed & Feed: Bleeding; 30 = Bleed & Feed: Timeout; 31 = Intermittent Sampling: Wait; 32 = Intermittent Sampling: Sample; 33 = Intermittent Sampling: Hold; 34 = Intermittent Sampling: Bleed; 35 = Probe Wash: On; 36 = Probe Wash: Hold | |||
| HR | 1907doc x1908 | Sensor 2-5 alarm bitfield | BITMAP16 | Read | bit 0 = Low; bit 1 = High; bit 2 = Low Low; bit 3 = High High; bit 4 = Type-specific (replace electrode / total / PV2 low); bit 5 = PV2 high (digital sensors only); bit 6 = Input failure; bit 7 = Calibration required | ||||
| HR | 1908doc x1909 | Sensor 2-6 primary value | Measured value in the sensor's configured units. | FLOAT32 | CDAB | Read | |||
| HR | 1942doc x1943 | Sensor 2-6 status | Status code. | UINT16 | Read | 0 = Error; 1 = None; 2 = Sensor: Auto Cal; 3 = Sensor: User Cal; 4 = DI State: Open; 5 = DI State: Closed; 6 = DI Interlock: Active; 7 = DI Interlock: Inactive; 8 = Relay: On; 9 = Relay: Off; 11 = Output Interlocked; 12 = Output Forced On; 13 = Output Timeout; 14 = Output Input Error; 15 = Output Error; 16 = Output Hold; 17 = Output HOA: Auto On; 18 = Output HOA: Auto Off; 19 = Output HOA: Hand; 20 = Output HOA: Off; 21 = Output Deadband; 22 = Relay Timeout; 23 = Relay OK; 24 = Daily Max Timeout; 25 = Biocide: Prebleed; 26 = Biocide: Hold; 27 = Biocide: Add; 28 = Time Proportional: Off; 29 = Bleed & Feed: Bleeding; 30 = Bleed & Feed: Timeout; 31 = Intermittent Sampling: Wait; 32 = Intermittent Sampling: Sample; 33 = Intermittent Sampling: Hold; 34 = Intermittent Sampling: Bleed; 35 = Probe Wash: On; 36 = Probe Wash: Hold | |||
| HR | 1943doc x1944 | Sensor 2-6 alarm bitfield | BITMAP16 | Read | bit 0 = Low; bit 1 = High; bit 2 = Low Low; bit 3 = High High; bit 4 = Type-specific (replace electrode / total / PV2 low); bit 5 = PV2 high (digital sensors only); bit 6 = Input failure; bit 7 = Calibration required | ||||
| HR | 8928doc x8929 | Relay 1 time on | Current on time. | UINT32 | CDAB | s | Read | ||
| HR | 8930doc x8931 | Relay 1 total time | Accumulated on time. | UINT32 | CDAB | s | Read | ||
| HR | 8959doc x8960 | Relay 1 state | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 8960doc x8961 | Relay 1 reset time total | Write 1 to reset. | UINT16 | Read/write | ||||
| HR | 8961doc x8962 | Relay 1 HOA setting | Hand / Off / Auto. | UINT16 | Read/write | 0 = Hand; 1 = Off; 2 = Auto | |||
| HR | 8962doc x8963 | Relay 1 status | Status code. | UINT16 | Read | 0 = Error; 1 = None; 2 = Sensor: Auto Cal; 3 = Sensor: User Cal; 4 = DI State: Open; 5 = DI State: Closed; 6 = DI Interlock: Active; 7 = DI Interlock: Inactive; 8 = Relay: On; 9 = Relay: Off; 11 = Output Interlocked; 12 = Output Forced On; 13 = Output Timeout; 14 = Output Input Error; 15 = Output Error; 16 = Output Hold; 17 = Output HOA: Auto On; 18 = Output HOA: Auto Off; 19 = Output HOA: Hand; 20 = Output HOA: Off; 21 = Output Deadband; 22 = Relay Timeout; 23 = Relay OK; 24 = Daily Max Timeout; 25 = Biocide: Prebleed; 26 = Biocide: Hold; 27 = Biocide: Add; 28 = Time Proportional: Off; 29 = Bleed & Feed: Bleeding; 30 = Bleed & Feed: Timeout; 31 = Intermittent Sampling: Wait; 32 = Intermittent Sampling: Sample; 33 = Intermittent Sampling: Hold; 34 = Intermittent Sampling: Bleed; 35 = Probe Wash: On; 36 = Probe Wash: Hold | |||
| HR | 8963doc x8964 | Relay 1 alarm bitfield | BITMAP16 | Read | bit 0 = Output timeout; bit 1 = Relay event skipped / turnover limit; bit 2 = Control failure; bit 3 = State alarm; bit 4 = Daily max timeout | ||||
| HR | 8995doc x8996 | Relay 2 state | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 8997doc x8998 | Relay 2 HOA setting | Hand / Off / Auto. | UINT16 | Read/write | 0 = Hand; 1 = Off; 2 = Auto | |||
| HR | 8998doc x8999 | Relay 2 status | Status code. | UINT16 | Read | 0 = Error; 1 = None; 2 = Sensor: Auto Cal; 3 = Sensor: User Cal; 4 = DI State: Open; 5 = DI State: Closed; 6 = DI Interlock: Active; 7 = DI Interlock: Inactive; 8 = Relay: On; 9 = Relay: Off; 11 = Output Interlocked; 12 = Output Forced On; 13 = Output Timeout; 14 = Output Input Error; 15 = Output Error; 16 = Output Hold; 17 = Output HOA: Auto On; 18 = Output HOA: Auto Off; 19 = Output HOA: Hand; 20 = Output HOA: Off; 21 = Output Deadband; 22 = Relay Timeout; 23 = Relay OK; 24 = Daily Max Timeout; 25 = Biocide: Prebleed; 26 = Biocide: Hold; 27 = Biocide: Add; 28 = Time Proportional: Off; 29 = Bleed & Feed: Bleeding; 30 = Bleed & Feed: Timeout; 31 = Intermittent Sampling: Wait; 32 = Intermittent Sampling: Sample; 33 = Intermittent Sampling: Hold; 34 = Intermittent Sampling: Bleed; 35 = Probe Wash: On; 36 = Probe Wash: Hold | |||
| HR | 8999doc x9000 | Relay 2 alarm bitfield | BITMAP16 | Read | bit 0 = Output timeout; bit 1 = Relay event skipped / turnover limit; bit 2 = Control failure; bit 3 = State alarm; bit 4 = Daily max timeout | ||||
| HR | 9031doc x9032 | Relay 3 state | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 9033doc x9034 | Relay 3 HOA setting | Hand / Off / Auto. | UINT16 | Read/write | 0 = Hand; 1 = Off; 2 = Auto | |||
| HR | 9034doc x9035 | Relay 3 status | Status code. | UINT16 | Read | 0 = Error; 1 = None; 2 = Sensor: Auto Cal; 3 = Sensor: User Cal; 4 = DI State: Open; 5 = DI State: Closed; 6 = DI Interlock: Active; 7 = DI Interlock: Inactive; 8 = Relay: On; 9 = Relay: Off; 11 = Output Interlocked; 12 = Output Forced On; 13 = Output Timeout; 14 = Output Input Error; 15 = Output Error; 16 = Output Hold; 17 = Output HOA: Auto On; 18 = Output HOA: Auto Off; 19 = Output HOA: Hand; 20 = Output HOA: Off; 21 = Output Deadband; 22 = Relay Timeout; 23 = Relay OK; 24 = Daily Max Timeout; 25 = Biocide: Prebleed; 26 = Biocide: Hold; 27 = Biocide: Add; 28 = Time Proportional: Off; 29 = Bleed & Feed: Bleeding; 30 = Bleed & Feed: Timeout; 31 = Intermittent Sampling: Wait; 32 = Intermittent Sampling: Sample; 33 = Intermittent Sampling: Hold; 34 = Intermittent Sampling: Bleed; 35 = Probe Wash: On; 36 = Probe Wash: Hold | |||
| HR | 9035doc x9036 | Relay 3 alarm bitfield | BITMAP16 | Read | bit 0 = Output timeout; bit 1 = Relay event skipped / turnover limit; bit 2 = Control failure; bit 3 = State alarm; bit 4 = Daily max timeout | ||||
| HR | 9067doc x9068 | Relay 4 state | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 9069doc x9070 | Relay 4 HOA setting | Hand / Off / Auto. | UINT16 | Read/write | 0 = Hand; 1 = Off; 2 = Auto | |||
| HR | 9070doc x9071 | Relay 4 status | Status code. | UINT16 | Read | 0 = Error; 1 = None; 2 = Sensor: Auto Cal; 3 = Sensor: User Cal; 4 = DI State: Open; 5 = DI State: Closed; 6 = DI Interlock: Active; 7 = DI Interlock: Inactive; 8 = Relay: On; 9 = Relay: Off; 11 = Output Interlocked; 12 = Output Forced On; 13 = Output Timeout; 14 = Output Input Error; 15 = Output Error; 16 = Output Hold; 17 = Output HOA: Auto On; 18 = Output HOA: Auto Off; 19 = Output HOA: Hand; 20 = Output HOA: Off; 21 = Output Deadband; 22 = Relay Timeout; 23 = Relay OK; 24 = Daily Max Timeout; 25 = Biocide: Prebleed; 26 = Biocide: Hold; 27 = Biocide: Add; 28 = Time Proportional: Off; 29 = Bleed & Feed: Bleeding; 30 = Bleed & Feed: Timeout; 31 = Intermittent Sampling: Wait; 32 = Intermittent Sampling: Sample; 33 = Intermittent Sampling: Hold; 34 = Intermittent Sampling: Bleed; 35 = Probe Wash: On; 36 = Probe Wash: Hold | |||
| HR | 9071doc x9072 | Relay 4 alarm bitfield | BITMAP16 | Read | bit 0 = Output timeout; bit 1 = Relay event skipped / turnover limit; bit 2 = Control failure; bit 3 = State alarm; bit 4 = Daily max timeout | ||||
| HR | 9103doc x9104 | Relay 5 state | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 9105doc x9106 | Relay 5 HOA setting | Hand / Off / Auto. | UINT16 | Read/write | 0 = Hand; 1 = Off; 2 = Auto | |||
| HR | 9106doc x9107 | Relay 5 status | Status code. | UINT16 | Read | 0 = Error; 1 = None; 2 = Sensor: Auto Cal; 3 = Sensor: User Cal; 4 = DI State: Open; 5 = DI State: Closed; 6 = DI Interlock: Active; 7 = DI Interlock: Inactive; 8 = Relay: On; 9 = Relay: Off; 11 = Output Interlocked; 12 = Output Forced On; 13 = Output Timeout; 14 = Output Input Error; 15 = Output Error; 16 = Output Hold; 17 = Output HOA: Auto On; 18 = Output HOA: Auto Off; 19 = Output HOA: Hand; 20 = Output HOA: Off; 21 = Output Deadband; 22 = Relay Timeout; 23 = Relay OK; 24 = Daily Max Timeout; 25 = Biocide: Prebleed; 26 = Biocide: Hold; 27 = Biocide: Add; 28 = Time Proportional: Off; 29 = Bleed & Feed: Bleeding; 30 = Bleed & Feed: Timeout; 31 = Intermittent Sampling: Wait; 32 = Intermittent Sampling: Sample; 33 = Intermittent Sampling: Hold; 34 = Intermittent Sampling: Bleed; 35 = Probe Wash: On; 36 = Probe Wash: Hold | |||
| HR | 9107doc x9108 | Relay 5 alarm bitfield | BITMAP16 | Read | bit 0 = Output timeout; bit 1 = Relay event skipped / turnover limit; bit 2 = Control failure; bit 3 = State alarm; bit 4 = Daily max timeout | ||||
| HR | 9139doc x9140 | Relay 6 state | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 9141doc x9142 | Relay 6 HOA setting | Hand / Off / Auto. | UINT16 | Read/write | 0 = Hand; 1 = Off; 2 = Auto | |||
| HR | 9142doc x9143 | Relay 6 status | Status code. | UINT16 | Read | 0 = Error; 1 = None; 2 = Sensor: Auto Cal; 3 = Sensor: User Cal; 4 = DI State: Open; 5 = DI State: Closed; 6 = DI Interlock: Active; 7 = DI Interlock: Inactive; 8 = Relay: On; 9 = Relay: Off; 11 = Output Interlocked; 12 = Output Forced On; 13 = Output Timeout; 14 = Output Input Error; 15 = Output Error; 16 = Output Hold; 17 = Output HOA: Auto On; 18 = Output HOA: Auto Off; 19 = Output HOA: Hand; 20 = Output HOA: Off; 21 = Output Deadband; 22 = Relay Timeout; 23 = Relay OK; 24 = Daily Max Timeout; 25 = Biocide: Prebleed; 26 = Biocide: Hold; 27 = Biocide: Add; 28 = Time Proportional: Off; 29 = Bleed & Feed: Bleeding; 30 = Bleed & Feed: Timeout; 31 = Intermittent Sampling: Wait; 32 = Intermittent Sampling: Sample; 33 = Intermittent Sampling: Hold; 34 = Intermittent Sampling: Bleed; 35 = Probe Wash: On; 36 = Probe Wash: Hold | |||
| HR | 9143doc x9144 | Relay 6 alarm bitfield | BITMAP16 | Read | bit 0 = Output timeout; bit 1 = Relay event skipped / turnover limit; bit 2 = Control failure; bit 3 = State alarm; bit 4 = Daily max timeout | ||||
| HR | 9175doc x9176 | Relay 7 state | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 9177doc x9178 | Relay 7 HOA setting | Hand / Off / Auto. | UINT16 | Read/write | 0 = Hand; 1 = Off; 2 = Auto | |||
| HR | 9178doc x9179 | Relay 7 status | Status code. | UINT16 | Read | 0 = Error; 1 = None; 2 = Sensor: Auto Cal; 3 = Sensor: User Cal; 4 = DI State: Open; 5 = DI State: Closed; 6 = DI Interlock: Active; 7 = DI Interlock: Inactive; 8 = Relay: On; 9 = Relay: Off; 11 = Output Interlocked; 12 = Output Forced On; 13 = Output Timeout; 14 = Output Input Error; 15 = Output Error; 16 = Output Hold; 17 = Output HOA: Auto On; 18 = Output HOA: Auto Off; 19 = Output HOA: Hand; 20 = Output HOA: Off; 21 = Output Deadband; 22 = Relay Timeout; 23 = Relay OK; 24 = Daily Max Timeout; 25 = Biocide: Prebleed; 26 = Biocide: Hold; 27 = Biocide: Add; 28 = Time Proportional: Off; 29 = Bleed & Feed: Bleeding; 30 = Bleed & Feed: Timeout; 31 = Intermittent Sampling: Wait; 32 = Intermittent Sampling: Sample; 33 = Intermittent Sampling: Hold; 34 = Intermittent Sampling: Bleed; 35 = Probe Wash: On; 36 = Probe Wash: Hold | |||
| HR | 9179doc x9180 | Relay 7 alarm bitfield | BITMAP16 | Read | bit 0 = Output timeout; bit 1 = Relay event skipped / turnover limit; bit 2 = Control failure; bit 3 = State alarm; bit 4 = Daily max timeout | ||||
| HR | 9211doc x9212 | Relay 8 state | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 9213doc x9214 | Relay 8 HOA setting | Hand / Off / Auto. | UINT16 | Read/write | 0 = Hand; 1 = Off; 2 = Auto | |||
| HR | 9214doc x9215 | Relay 8 status | Status code. | UINT16 | Read | 0 = Error; 1 = None; 2 = Sensor: Auto Cal; 3 = Sensor: User Cal; 4 = DI State: Open; 5 = DI State: Closed; 6 = DI Interlock: Active; 7 = DI Interlock: Inactive; 8 = Relay: On; 9 = Relay: Off; 11 = Output Interlocked; 12 = Output Forced On; 13 = Output Timeout; 14 = Output Input Error; 15 = Output Error; 16 = Output Hold; 17 = Output HOA: Auto On; 18 = Output HOA: Auto Off; 19 = Output HOA: Hand; 20 = Output HOA: Off; 21 = Output Deadband; 22 = Relay Timeout; 23 = Relay OK; 24 = Daily Max Timeout; 25 = Biocide: Prebleed; 26 = Biocide: Hold; 27 = Biocide: Add; 28 = Time Proportional: Off; 29 = Bleed & Feed: Bleeding; 30 = Bleed & Feed: Timeout; 31 = Intermittent Sampling: Wait; 32 = Intermittent Sampling: Sample; 33 = Intermittent Sampling: Hold; 34 = Intermittent Sampling: Bleed; 35 = Probe Wash: On; 36 = Probe Wash: Hold | |||
| HR | 9215doc x9216 | Relay 8 alarm bitfield | BITMAP16 | Read | bit 0 = Output timeout; bit 1 = Relay event skipped / turnover limit; bit 2 = Control failure; bit 3 = State alarm; bit 4 = Daily max timeout |
Notes on this map
- 32-bit integers and floats are sent least significant word first (CDAB) by default. The Remote Communications menu has an 'inverse' data format that swaps to high word first (ABCD); if values look wrong, check that setting.
- All 32-bit integers are unsigned; times are Unix seconds since 1970-01-01.
- Every address can be read as a holding register (FC3) or input register (FC4); this map lists them as holding registers. Booleans (the bold rows in the manual) can also be read as coils/discrete inputs at the same number.
- Sensor blocks use the general sensor map (all sensor types except Digital Sensor and Analog Input Flowmeter, which have their own maps). The full block is listed for the first sensor only; for the others only primary value, status and alarm bitfield are listed - the same indices apply to every sensor block.
- Digital input blocks are shown for the DI State type. Flow meter, counter, flow monitor and remote Modbus DI types use different maps (section 5.3.4).
- Relay entries use the indices common to every relay control mode (time on, total time, state, reset, HOA, status, alarm bitfield). Mode-specific set points live at other indices in section 5.3.6. Pulse relay maps (section 5.3.7) differ and are not included.
- Status register codes 37 and above are not listed in the values here; see section 5.4. Alarm bit 5 meanings vary by sensor or DI type.
- Analog outputs and virtual inputs are left out.
- Block start addresses are from the W900 I/O channel map (pp. 13-14): sensors in I/O slot 1 start at x1153 and slot 2 at x1729, with 36 addresses per sensor; slot 3 starts at x2305 and slot 4 at x2881 (not listed here, same layout). Digital inputs 1-12 start at x0577, relays 1-8 at x8929, control outputs 1-8 at x6913 (relay maps).
- Analog output cards reuse the same slot address ranges as sensor cards. With the 2 AI + 4 AO card (P/N 191918) the two sensor inputs move to channels 5 and 6 of that slot.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Walchem W900 water treatment controller (Modbus/TCP)
What Modbus registers does the Walchem W900 water treatment controller (Modbus/TCP) have?
This map lists 138 registers: 138 holding registers. 17 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Walchem W900 water treatment controller (Modbus/TCP) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Section 5.1 says the published addresses are 1-based while the packet is 0-based, so subtract 1 on the wire. Each object's address = its block start (xNNNN in the I/O channel map) + the index in its type-specific map; e.g. firmware version is block x0037 + index 2 = 30039/40039, wire address 38. The 'x' prefix stands for the table digit: the same address can be read as a holding register (FC3) or input register (FC4).
What byte order does the Walchem W900 water treatment controller (Modbus/TCP) use for 32-bit values?
Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Walchem W900 water treatment controller (Modbus/TCP)?
Start with HR 36 Controller time (Controller time (proves comms)); HR 1152 Sensor 1-1 primary value (Sensor primary value); HR 1186 Sensor 1-1 status (Sensor status code); HR 1187 Sensor 1-1 alarm bitfield (Sensor alarm bitfield); HR 609 Digital input 1 state (Digital input 1 state); HR 8959 Relay 1 state (Relay 1 state); HR 8961 Relay 1 HOA setting (Relay 1 HOA setting); HR 71 System alarm bitfield (System alarm bitfield).
How do I enable Modbus control of the Walchem W900 water treatment controller (Modbus/TCP)?
Modbus/TCP is a feature of the controller; enable it and set the port and data format (normal or inverse word order) in the Remote Communications menu. A 'Verbose Logging' option there logs every message for commissioning and turns itself off at restart.
Where is the official Walchem W900 water treatment controller (Modbus/TCP) Modbus documentation?
The source is Modbus Manual - Intuition-9 / Intuition-6 / W900 / W600 (180676.K), revision 2026-06, published free by Walchem at https://www.walchem.com/Literature/Controllers/Intuition/180676_W600_W900_Intuition_Modbus_Manual.pdf.
More Walchem Modbus register maps
- Water treatment controller (Sensor / controller)
Walchem W600 water treatment controller (Modbus/TCP)
Walchem W600 controllers (software 3.01 and up) with the Modbus/TCP feature, per Modbus manual 180676.K. W900, Intuition-6 and Intuition-9 use the same type maps but different block start addresses.
Also known as: W600 series - Water treatment controller (Sensor / controller)
Walchem WebMaster / WebMaster ONE (WM1) Modbus TCP/IP option
Walchem WebMaster and WebMaster ONE controllers with the Modbus TCP/IP option, software s800/s801/s802/s811/s830 v017 and higher, per manual 180422 Rev G.
Also known as: WebMaster, WebMaster ONE, WM1, s800, s801, s802, s811, s830 - Water treatment controller (Sensor / controller)
Walchem WebMaster WIND series Modbus TCP/IP option (s825)
Walchem WebMaster WIND-series controllers with the Modbus TCP/IP option, software s825v008 and higher, per manual 180413 Rev A1.
Also known as: WIND, WebMaster WIND, s825
Other valves, actuators & sensors register maps
- Sensor (Ethernet analog output module)
Acromag BusWorks XT1531-000 4-channel current output + 4 digital I/O (Modbus TCP)
BusWorks XT1531-000 per its user's manual (file revision H, 18 Nov 2022).
Also known as: XT1531-000, XT1531, BusWorks XT1531 - Sensor (humidity / temperature transmitter)
Dwyer Series RHPX communicating humidity/temperature transmitter
Dwyer Series RHPX humidity and temperature transmitters with the BACnet MS/TP / Modbus RTU communication board, set to Modbus with DIP switch 9 (bulletin AQ-RHPX-C).
Also known as: RHPX, Dwyer RHPX BACnet/Modbus, 607xxx - Sensor (turbidity)
JUMO ecoLine NTU digital turbidity sensor (Modbus RTU)
JUMO ecoLine NTU type 202670 with RS-485 Modbus RTU (interface description V1.01).
Also known as: 202670, JUMO ecoLine NTU, ecoLine NTU type 202670 - Sensor (vibration / temperature)
Machine Saver TriVibe vibration and temperature sensor (Modbus RTU)
Machine Saver TriVibe triaxial vibration sensors on RS-485 Modbus RTU, per the 'Modbus Registers Map' page of the Machine Saver online library (revision #12).
Also known as: TriVibe, Machine Saver TriVibe - Sensor (conductivity controller)
Shinko Technos AER-102-ECH conductivity indicating controller (C5 option)
Shinko AER-102-ECH electrical conductivity controller with the C5 RS-485 option; manual No. AER11CECE5.
Also known as: AER-102-ECH - Sensor (flow transmitter)
Siemens SITRANS F M MAG 6000 with USM II Modbus RTU module
SITRANS F M MAG 6000 / MAG 6000 I electromagnetic flow transmitters fitted with the USM II Modbus RTU RS-485 add-on module (operating instructions 03/2021).
Also known as: MAG 6000, MAG 6000 I, SITRANS FM MAG 6000
All valves, actuators & sensors Modbus register maps →
Source: Modbus Manual - Intuition-9 / Intuition-6 / W900 / W600 · 180676.K · rev. 2026-06. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.