Sensor (conductivity controller) · Modbus register map

Shinko Technos AER-102-ECH conductivity indicating controller (C5 option) Modbus register map

Updated 17 November 2026

Short answer

The AER-102-ECH measures electrical conductivity (or salinity/TDS) and temperature, and drives up to four event outputs and two transmission outputs. With the C5 option it speaks Shinko protocol or Modbus ASCII/RTU; every item is a signed 16-bit holding register. The map covers sensor and range setup, EVT1-EVT4 settings, temperature compensation, transmission outputs, calibration modes, user save area and the measured conductivity, temperature and status words.

This page lists 164 Modbus registers for the Shinko Technos AER-102-ECH conductivity indicating controller (C5 option) — 156 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Shinko Technos’s own free documentation (linked below) and checked against it.

Manufacturer
Shinko Technos
Model
AER-102-ECH conductivity indicating controller (C5 option)
Equipment type
Sensor (conductivity controller)
Registers
164 (156 writable)
Transport
Modbus RTU, Modbus ASCII
Default unit ID
0
Default serial
9600 baud, 7E1
Documented addressing
hexadecimal, 0-based
Also known as
AER-102-ECH
Source document
Communication Instruction Manual AER-102-ECH (C5) · No. AER11CECE5 · rev. 2019-06
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Shinko Technos AER-102-ECH conductivity indicating controller (C5 option)

Integration in brief

Select MODBUS RTU in the Basic Function Group and give the unit a non-zero instrument number; then read conductivity 0080H, temperature 0090H and the status words 0081H and 0091H.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 128ConductivityINT16Conductivity / salinity / TDS valueRead
HR 144TemperatureINT16TemperatureRead
HR 129Status flag 1BITMAP16Sensor and range errorsRead
HR 145Status flag 2BITMAP16EVT output statesRead
HR 4Measurement rangeINT16Measurement range (sets decimal point)Read/write
HR 3Measurement unitINT16Measurement unitRead/write

Enable Modbus control & writes

Requires the C5 option. In the Basic Function Group choose Communication protocol = MODBUS RTU (or ASCII), then instrument number, speed, data bit/parity and stop bit; these are keypad-only.

Byte order & addressing

Network setup

Watch out for

Shinko Technos AER-102-ECH conductivity indicating controller (C5 option) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

164 of 164 shown
Shinko Technos AER-102-ECH conductivity indicating controller (C5 option) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR1doc 0001HSensor cell constantINT16Read/write0 = 1.0/cm; 1 = 10.0/cm
HR2doc 0002HCell constant correction valueDecimal point ignored.INT16Read/write
HR3doc 0003HMeasurement unitINT16Read/write0 = Conductivity (mS/cm, uS/cm); 1 = Conductivity (S/m, mS/m); 2 = Seawater salinity (%); 3 = NaCl salinity (%); 4 = TDS conversion (g/L, mg/L)
HR4doc 0004HMeasurement rangeCodes depend on cell constant and unit (p. 12); sets 0080H decimals.INT16Read/write
HR5doc 0005HEVT1 typeChanging any EVT type resets EVT1-EVT4 values to 0.INT16Read/write0 = No action; 1 = Conductivity input low limit action; 2 = Conductivity input high limit action; 3 = Temperature input low limit action; 4 = Temperature input high limit action; 5 = Error output; 6 = Fail output; 7 = Conductivity input error alarm output; 8 = Conductivity input High/Low limits independent action; 9 = Temperature input High/Low limits independent action
HR6doc 0006HEVT1 valueDecimal point ignored.INT16Read/write
HR7doc 0007HEVT1 ON sideDecimal point ignored.INT16Read/write
HR8doc 0008HEVT1 ON delay timeINT16Read/write
HR9doc 0009HEVT1 OFF delay timeINT16Read/write
HR10doc 000AHConductivity input filter time constantDecimal point ignored.INT16Read/write
HR11doc 000BHTDS conversion factorDecimal point ignored.INT16Read/write
HR16doc 0010HEVT1 proportional bandDecimal point ignored.INT16Read/write
HR17doc 0011HEVT1 resetDecimal point ignored.INT16Read/write
HR18doc 0012HEVT1 proportional cycleINT16Read/write
HR19doc 0013HEVT2 proportional bandDecimal point ignored.INT16Read/write
HR20doc 0014HEVT2 resetDecimal point ignored.INT16Read/write
HR21doc 0015HEVT2 proportional cycleINT16Read/write
HR22doc 0016HEVT3 proportional bandDecimal point ignored.INT16Read/write
HR23doc 0017HEVT3 resetDecimal point ignored.INT16Read/write
HR24doc 0018HEVT3 proportional cycleINT16Read/write
HR25doc 0019HEVT4 proportional bandDecimal point ignored.INT16Read/write
HR26doc 001AHEVT4 resetDecimal point ignored.INT16Read/write
HR27doc 001BHEVT4 proportional cycleINT16Read/write
HR32doc 0020HTemperature compensation methodINT16Read/write0 = Temperature characteristics of NaCl; 1 = Temperature coefficient (%/°C) and reference temperature; 2 = No temperature compensation
HR33doc 0021HTemperature coefficientDecimal point ignored.INT16Read/write
HR34doc 0022HReference temperatureDecimal point ignored.INT16Read/write
HR35doc 0023HTemperature input decimal point placeINT16Read/write0 = No decimal point; 1 = 1 digit after decimal point
HR41doc 0029HTemperature input filter time constantDecimal point ignored.INT16Read/write
HR48doc 0030HSet value lockLock 3 lets most values change over the bus without saving to memory.INT16Read/write0 = Unlock; 1 = Lock 1; 2 = Lock 2; 3 = Lock 3
HR49doc 0031HTransmission output 1 typeINT16Read/write0 = Conductivity transmission; 1 = Temperature transmission; 2 = EVT1 MV transmission; 3 = EVT2 MV transmission; 4 = EVT3 MV transmission; 5 = EVT4 MV transmission
HR50doc 0032HTransmission output 1 high limitDecimal point ignored.INT16Read/write
HR51doc 0033HTransmission output 1 low limitDecimal point ignored.INT16Read/write
HR55doc 0037HBacklight timeINT16Read/write
HR64doc 0040HTemperature calibration modeWrite-only (function 06).INT16Write0 = Conductivity/Temperature Display mode; 1 = Temperature calibration mode
HR65doc 0041HTemperature calibration valueDecimal point ignored.INT16Read/write
HR66doc 0042HConductivity calibration modeWrite-only (function 06).INT16Write0 = Conductivity/Temperature Display mode; 1 = Zero adjustment mode; 2 = Span adjustment mode
HR67doc 0043HConductivity zero adjustment valueDecimal point ignored.INT16Read/write
HR68doc 0044HConductivity span adjustment valueDecimal point ignored.INT16Read/write
HR69doc 0045HEVT output on input errorINT16Read/write0 = Enabled; 1 = Disabled
HR70doc 0046HCable length correctionDecimal point ignored.INT16Read/write
HR71doc 0047HCable cross-section areaDecimal point ignored.INT16Read/write
HR72doc 0048HEVT1 output ON time while ONINT16Read/write
HR73doc 0049HEVT1 output OFF time while ONINT16Read/write
HR74doc 004AHEVT2 output ON time while ONINT16Read/write
HR75doc 004BHEVT2 output OFF time while ONINT16Read/write
HR76doc 004CHEVT3 output ON time while ONINT16Read/write
HR77doc 004DHEVT3 output OFF time while ONINT16Read/write
HR78doc 004EHEVT4 output ON time while ONINT16Read/write
HR79doc 004FHEVT4 output OFF time while ONINT16Read/write
HR80doc 0050HEVT2 typeChanging any EVT type resets EVT1-EVT4 values to 0.INT16Read/write0 = No action; 1 = Conductivity input low limit action; 2 = Conductivity input high limit action; 3 = Temperature input low limit action; 4 = Temperature input high limit action; 5 = Error output; 6 = Fail output; 7 = Conductivity input error alarm output; 8 = Conductivity input High/Low limits independent action; 9 = Temperature input High/Low limits independent action
HR81doc 0051HEVT3 typeChanging any EVT type resets EVT1-EVT4 values to 0.INT16Read/write0 = No action; 1 = Conductivity input low limit action; 2 = Conductivity input high limit action; 3 = Temperature input low limit action; 4 = Temperature input high limit action; 5 = Error output; 6 = Fail output; 7 = Conductivity input error alarm output; 8 = Conductivity input High/Low limits independent action; 9 = Temperature input High/Low limits independent action
HR82doc 0052HEVT4 typeChanging any EVT type resets EVT1-EVT4 values to 0.INT16Read/write0 = No action; 1 = Conductivity input low limit action; 2 = Conductivity input high limit action; 3 = Temperature input low limit action; 4 = Temperature input high limit action; 5 = Error output; 6 = Fail output; 7 = Conductivity input error alarm output; 8 = Conductivity input High/Low limits independent action; 9 = Temperature input High/Low limits independent action
HR83doc 0053HEVT2 valueDecimal point ignored.INT16Read/write
HR84doc 0054HEVT3 valueDecimal point ignored.INT16Read/write
HR85doc 0055HEVT4 valueDecimal point ignored.INT16Read/write
HR86doc 0056HEVT2 ON sideDecimal point ignored.INT16Read/write
HR87doc 0057HEVT3 ON sideDecimal point ignored.INT16Read/write
HR88doc 0058HEVT4 ON sideDecimal point ignored.INT16Read/write
HR89doc 0059HEVT2 ON delay timeINT16Read/write
HR90doc 005AHEVT3 ON delay timeINT16Read/write
HR91doc 005BHEVT4 ON delay timeINT16Read/write
HR92doc 005CHEVT2 OFF delay timeINT16Read/write
HR93doc 005DHEVT3 OFF delay timeINT16Read/write
HR94doc 005EHEVT4 OFF delay timeINT16Read/write
HR99doc 0063HBacklight selectionINT16Read/write0 = All backlit; 1 = Conductivity display; 2 = Temperature display; 3 = Action indicators; 4 = Conductivity display + temperature display; 5 = Conductivity display + action indicators; 6 = Temperature display + action indicators
HR100doc 0064HConductivity colorINT16Read/write0 = Green; 1 = Red; 2 = Orange; 3 = Changes continuously
HR101doc 0065HConductivity color rangeDecimal point ignored.INT16Read/write
HR102doc 0066HBar graph indicationINT16Read/write0 = No indication; 1 = Transmission output 1; 2 = Transmission output 2
HR103doc 0067HConductivity color reference valueDecimal point ignored.INT16Read/write
HR104doc 0068HConductivity input sensor correctionDecimal point ignored.INT16Read/write
HR105doc 0069HTemperature display without compensationINT16Read/write0 = Unlit; 1 = Reference temperature; 2 = Measured value
HR111doc 006FHPt100 input wire typeINT16Read/write0 = 2-wire; 1 = 3-wire
HR112doc 0070HEVT1 output high limitINT16Read/write
HR113doc 0071HEVT1 output low limitINT16Read/write
HR114doc 0072HEVT2 output high limitINT16Read/write
HR115doc 0073HEVT2 output low limitINT16Read/write
HR116doc 0074HEVT3 output high limitINT16Read/write
HR117doc 0075HEVT3 output low limitINT16Read/write
HR118doc 0076HEVT4 output high limitINT16Read/write
HR119doc 0077HEVT4 output low limitINT16Read/write
HR127doc 007FHKey operation change flag clearingINT16Write1 = Clear change flag
HR128doc 0080HConductivityMeasured value; decimal point set by measurement range (0004H).INT16Read
HR129doc 0081HStatus flag 1BITMAP16Readbit 5 = Temperature sensor burnout; bit 6 = Temperature sensor short-circuited; bit 7 = Above temperature compensation range (110.0 °C); bit 8 = Below temperature compensation range (0.0 °C); bit 9 = Measured value above range; bit 10 = Measured value below range; bit 11 = Setting mode; bit 12 = Conductivity calibration zero adjustment; bit 13 = Conductivity calibration span adjustment; bit 15 = Changed by keypad
HR132doc 0084HEVT1 manipulated variableDecimal point ignored.INT16Read
HR133doc 0085HEVT2 manipulated variableDecimal point ignored.INT16Read
HR134doc 0086HEVT3 manipulated variableDecimal point ignored.INT16Read
HR135doc 0087HEVT4 manipulated variableDecimal point ignored.INT16Read
HR144doc 0090HTemperatureDecimal point per 0023H.INT16Read
HR145doc 0091HStatus flag 2BITMAP16Readbit 0 = EVT1 output; bit 1 = EVT2 output; bit 2 = EVT3 output; bit 3 = EVT4 output; bit 4 = Transmission output 1 zero adjustment; bit 5 = Transmission output 1 span adjustment; bit 6 = Transmission output 2 zero adjustment; bit 7 = Transmission output 2 span adjustment; bit 12 = Temperature calibration
HR256doc 0100HEVT1 hysteresis typeINT16Read/write0 = Medium value; 1 = Reference value
HR257doc 0101HEVT2 hysteresis typeINT16Read/write0 = Medium value; 1 = Reference value
HR258doc 0102HEVT3 hysteresis typeINT16Read/write0 = Medium value; 1 = Reference value
HR259doc 0103HEVT4 hysteresis typeINT16Read/write0 = Medium value; 1 = Reference value
HR260doc 0104HEVT1 OFF sideDecimal point ignored.INT16Read/write
HR261doc 0105HEVT2 OFF sideDecimal point ignored.INT16Read/write
HR262doc 0106HEVT3 OFF sideDecimal point ignored.INT16Read/write
HR263doc 0107HEVT4 OFF sideDecimal point ignored.INT16Read/write
HR271doc 010FHTransmission output 1 status when calibratingINT16Read/write0 = Last value HOLD; 1 = Set value HOLD; 2 = Measured value
HR272doc 0110HTransmission output 1 HOLD value when calibratingDecimal point ignored.INT16Read/write
HR273doc 0111HEVT1 conductivity error alarm EVT typeINT16Read/write0 = No action; 1 = EVT2 type; 2 = EVT3 type; 3 = EVT4 type
HR274doc 0112HEVT2 conductivity error alarm EVT typeINT16Read/write0 = EVT1 type; 1 = No action; 2 = EVT3 type; 3 = EVT4 type
HR275doc 0113HEVT3 conductivity error alarm EVT typeINT16Read/write0 = EVT1 type; 1 = EVT2 type; 2 = No action; 3 = EVT4 type
HR276doc 0114HEVT4 conductivity error alarm EVT typeINT16Read/write0 = EVT1 type; 1 = EVT2 type; 2 = EVT3 type; 3 = No action
HR277doc 0115HEVT1 error alarm band (output ON)Decimal point ignored.INT16Read/write
HR278doc 0116HEVT1 error alarm time (output ON)INT16Read/write
HR279doc 0117HEVT1 error alarm band (output OFF)Decimal point ignored.INT16Read/write
HR280doc 0118HEVT1 error alarm time (output OFF)INT16Read/write
HR281doc 0119HEVT2 error alarm band (output ON)Decimal point ignored.INT16Read/write
HR282doc 011AHEVT2 error alarm time (output ON)INT16Read/write
HR283doc 011BHEVT2 error alarm band (output OFF)Decimal point ignored.INT16Read/write
HR284doc 011CHEVT2 error alarm time (output OFF)INT16Read/write
HR285doc 011DHEVT3 error alarm band (output ON)Decimal point ignored.INT16Read/write
HR286doc 011EHEVT3 error alarm time (output ON)INT16Read/write
HR287doc 011FHEVT3 error alarm band (output OFF)Decimal point ignored.INT16Read/write
HR288doc 0120HEVT3 error alarm time (output OFF)INT16Read/write
HR289doc 0121HEVT4 error alarm band (output ON)Decimal point ignored.INT16Read/write
HR290doc 0122HEVT4 error alarm time (output ON)INT16Read/write
HR291doc 0123HEVT4 error alarm band (output OFF)Decimal point ignored.INT16Read/write
HR292doc 0124HEVT4 error alarm time (output OFF)INT16Read/write
HR293doc 0125HConductivity error alarm time unitINT16Read/write0 = Seconds; 1 = Minutes
HR294doc 0126HTransmission output 1 adjustment modeINT16Read/write0 = Conductivity/Temperature Display mode; 1 = Zero adjustment mode; 2 = Span adjustment mode
HR295doc 0127HTransmission output 1 zero adjustment valueDecimal point ignored.INT16Read/write
HR296doc 0128HTransmission output 1 span adjustment valueDecimal point ignored.INT16Read/write
HR297doc 0129HEVT1 cycle variable rangeDecimal point ignored.INT16Read/write
HR298doc 012AHEVT2 cycle variable rangeDecimal point ignored.INT16Read/write
HR299doc 012BHEVT3 cycle variable rangeDecimal point ignored.INT16Read/write
HR300doc 012CHEVT4 cycle variable rangeDecimal point ignored.INT16Read/write
HR301doc 012DHEVT1 cycle extended timeINT16Read/write
HR302doc 012EHEVT2 cycle extended timeINT16Read/write
HR303doc 012FHEVT3 cycle extended timeINT16Read/write
HR304doc 0130HEVT4 cycle extended timeINT16Read/write
HR305doc 0131H3-electrode sensor resistanceINT16Read/write
HR313doc 0139HEVT1 H/L independent lower valueDecimal point ignored.INT16Read/write
HR314doc 013AHEVT2 H/L independent lower valueDecimal point ignored.INT16Read/write
HR315doc 013BHEVT3 H/L independent lower valueDecimal point ignored.INT16Read/write
HR316doc 013CHEVT4 H/L independent lower valueDecimal point ignored.INT16Read/write
HR317doc 013DHEVT1 H/L independent upper valueDecimal point ignored.INT16Read/write
HR318doc 013EHEVT2 H/L independent upper valueDecimal point ignored.INT16Read/write
HR319doc 013FHEVT3 H/L independent upper valueDecimal point ignored.INT16Read/write
HR320doc 0140HEVT4 H/L independent upper valueDecimal point ignored.INT16Read/write
HR321doc 0141HEVT1 hysteresisDecimal point ignored.INT16Read/write
HR322doc 0142HEVT2 hysteresisDecimal point ignored.INT16Read/write
HR323doc 0143HEVT3 hysteresisDecimal point ignored.INT16Read/write
HR324doc 0144HEVT4 hysteresisDecimal point ignored.INT16Read/write
HR327doc 0147HTransmission output 2 typeINT16Read/write0 = Conductivity transmission; 1 = Temperature transmission; 2 = MV2 transmission; 3 = MV3 transmission; 4 = MV4 transmission
HR328doc 0148HTransmission output 2 high limitDecimal point ignored.INT16Read/write
HR329doc 0149HTransmission output 2 low limitDecimal point ignored.INT16Read/write
HR330doc 014AHTransmission output 2 adjustment modeINT16Read/write0 = Conductivity/Temperature Display mode; 1 = Zero adjustment mode; 2 = Span adjustment mode
HR331doc 014BHTransmission output 2 zero adjustment valueDecimal point ignored.INT16Read/write
HR332doc 014CHTransmission output 2 span adjustment valueDecimal point ignored.INT16Read/write
HR333doc 014DHTransmission output 2 status when calibratingINT16Read/write0 = Last value HOLD; 1 = Set value HOLD; 2 = Measured value
HR334doc 014EHTransmission output 2 HOLD value when calibratingDecimal point ignored.INT16Read/write
HR337doc 0151HConductivity moving average inputsINT16Read/write
HR338doc 0152HTemperature moving average inputsINT16Read/write
HR512doc 0200HUser save area 1Free 16-bit storage, -32768 to 32767.INT16Read/write
HR513doc 0201HUser save area 2Free 16-bit storage, -32768 to 32767.INT16Read/write
HR514doc 0202HUser save area 3Free 16-bit storage, -32768 to 32767.INT16Read/write
HR515doc 0203HUser save area 4Free 16-bit storage, -32768 to 32767.INT16Read/write
HR516doc 0204HUser save area 5Free 16-bit storage, -32768 to 32767.INT16Read/write
HR517doc 0205HUser save area 6Free 16-bit storage, -32768 to 32767.INT16Read/write
HR518doc 0206HUser save area 7Free 16-bit storage, -32768 to 32767.INT16Read/write
HR519doc 0207HUser save area 8Free 16-bit storage, -32768 to 32767.INT16Read/write
HR520doc 0208HUser save area 9Free 16-bit storage, -32768 to 32767.INT16Read/write
HR521doc 0209HUser save area 10Free 16-bit storage, -32768 to 32767.INT16Read/write

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Shinko Technos AER-102-ECH conductivity indicating controller (C5 option)

What Modbus registers does the Shinko Technos AER-102-ECH conductivity indicating controller (C5 option) have?

This map lists 164 registers: 164 holding registers. 156 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Shinko Technos AER-102-ECH conductivity indicating controller (C5 option) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Registers are listed as hex data items (0001H) that go into the request unchanged. The manual adds that the matching Modicon holding-register number is the item in decimal plus 40001 (0001H = 40002). The manual's RTU example reads conductivity with data item 0080H (CRC 85E2H checked).

What are the minimum Modbus registers to integrate the Shinko Technos AER-102-ECH conductivity indicating controller (C5 option)?

Start with HR 128 Conductivity (Conductivity / salinity / TDS value); HR 144 Temperature (Temperature); HR 129 Status flag 1 (Sensor and range errors); HR 145 Status flag 2 (EVT output states); HR 4 Measurement range (Measurement range (sets decimal point)); HR 3 Measurement unit (Measurement unit).

How do I enable Modbus control of the Shinko Technos AER-102-ECH conductivity indicating controller (C5 option)?

Requires the C5 option. In the Basic Function Group choose Communication protocol = MODBUS RTU (or ASCII), then instrument number, speed, data bit/parity and stop bit; these are keypad-only.

Where is the official Shinko Technos AER-102-ECH conductivity indicating controller (C5 option) Modbus documentation?

The source is Communication Instruction Manual AER-102-ECH (C5) (No. AER11CECE5), revision 2019-06, published free by Shinko Technos at https://shinko-technos.co.jp/e/manual/english/AER11CECE5.pdf.