- AER-102-ECH conductivity indicating controller (C5 option)
Sensor (conductivity controller) · Modbus register map
Shinko Technos AER-102-ECH conductivity indicating controller (C5 option) Modbus register map
Updated 17 November 2026
The AER-102-ECH measures electrical conductivity (or salinity/TDS) and temperature, and drives up to four event outputs and two transmission outputs. With the C5 option it speaks Shinko protocol or Modbus ASCII/RTU; every item is a signed 16-bit holding register. The map covers sensor and range setup, EVT1-EVT4 settings, temperature compensation, transmission outputs, calibration modes, user save area and the measured conductivity, temperature and status words.
This page lists 164 Modbus registers for the Shinko Technos AER-102-ECH conductivity indicating controller (C5 option) — 156 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Shinko Technos’s own free documentation (linked below) and checked against it.
- Manufacturer
- Shinko Technos
- Model
- AER-102-ECH conductivity indicating controller (C5 option)
- Equipment type
- Sensor (conductivity controller)
- Registers
- 164 (156 writable)
- Transport
- Modbus RTU, Modbus ASCII
- Default unit ID
- 0
- Default serial
- 9600 baud, 7E1
- Documented addressing
- hexadecimal, 0-based
- Also known as
- AER-102-ECH
Integration notes: Shinko Technos AER-102-ECH conductivity indicating controller (C5 option)
Select MODBUS RTU in the Basic Function Group and give the unit a non-zero instrument number; then read conductivity 0080H, temperature 0090H and the status words 0081H and 0091H.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 128 | Conductivity | INT16 | Conductivity / salinity / TDS value | Read |
| HR 144 | Temperature | INT16 | Temperature | Read |
| HR 129 | Status flag 1 | BITMAP16 | Sensor and range errors | Read |
| HR 145 | Status flag 2 | BITMAP16 | EVT output states | Read |
| HR 4 | Measurement range | INT16 | Measurement range (sets decimal point) | Read/write |
| HR 3 | Measurement unit | INT16 | Measurement unit | Read/write |
Enable Modbus control & writes
Requires the C5 option. In the Basic Function Group choose Communication protocol = MODBUS RTU (or ASCII), then instrument number, speed, data bit/parity and stop bit; these are keypad-only.
Byte order & addressing
- Instrument number 0 is the Modbus broadcast address; give each unit 1-95.
- Use Lock 3 for frequently written values so non-volatile memory is not worn out (about one million writes).
Network setup
- Factory defaults: Shinko protocol, instrument number 0, 9600 bps, 7 bits/even parity, 1 stop bit.
- For Modbus RTU choose an 8-bit data format.
- Do not fit a terminator; each unit has built-in pull-up/pull-down resistors.
Watch out for
- Changing any EVT type resets all four EVT values to 0; write types first.
- Writing transmission output 2 adjustment mode without the TA2 option returns exception 17 (11H).
Shinko Technos AER-102-ECH conductivity indicating controller (C5 option) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 1doc 0001H | Sensor cell constant | INT16 | Read/write | 0 = 1.0/cm; 1 = 10.0/cm | ||||
| HR | 2doc 0002H | Cell constant correction value | Decimal point ignored. | INT16 | Read/write | ||||
| HR | 3doc 0003H | Measurement unit | INT16 | Read/write | 0 = Conductivity (mS/cm, uS/cm); 1 = Conductivity (S/m, mS/m); 2 = Seawater salinity (%); 3 = NaCl salinity (%); 4 = TDS conversion (g/L, mg/L) | ||||
| HR | 4doc 0004H | Measurement range | Codes depend on cell constant and unit (p. 12); sets 0080H decimals. | INT16 | Read/write | ||||
| HR | 5doc 0005H | EVT1 type | Changing any EVT type resets EVT1-EVT4 values to 0. | INT16 | Read/write | 0 = No action; 1 = Conductivity input low limit action; 2 = Conductivity input high limit action; 3 = Temperature input low limit action; 4 = Temperature input high limit action; 5 = Error output; 6 = Fail output; 7 = Conductivity input error alarm output; 8 = Conductivity input High/Low limits independent action; 9 = Temperature input High/Low limits independent action | |||
| HR | 6doc 0006H | EVT1 value | Decimal point ignored. | INT16 | Read/write | ||||
| HR | 7doc 0007H | EVT1 ON side | Decimal point ignored. | INT16 | Read/write | ||||
| HR | 8doc 0008H | EVT1 ON delay time | INT16 | Read/write | |||||
| HR | 9doc 0009H | EVT1 OFF delay time | INT16 | Read/write | |||||
| HR | 10doc 000AH | Conductivity input filter time constant | Decimal point ignored. | INT16 | Read/write | ||||
| HR | 11doc 000BH | TDS conversion factor | Decimal point ignored. | INT16 | Read/write | ||||
| HR | 16doc 0010H | EVT1 proportional band | Decimal point ignored. | INT16 | Read/write | ||||
| HR | 17doc 0011H | EVT1 reset | Decimal point ignored. | INT16 | Read/write | ||||
| HR | 18doc 0012H | EVT1 proportional cycle | INT16 | Read/write | |||||
| HR | 19doc 0013H | EVT2 proportional band | Decimal point ignored. | INT16 | Read/write | ||||
| HR | 20doc 0014H | EVT2 reset | Decimal point ignored. | INT16 | Read/write | ||||
| HR | 21doc 0015H | EVT2 proportional cycle | INT16 | Read/write | |||||
| HR | 22doc 0016H | EVT3 proportional band | Decimal point ignored. | INT16 | Read/write | ||||
| HR | 23doc 0017H | EVT3 reset | Decimal point ignored. | INT16 | Read/write | ||||
| HR | 24doc 0018H | EVT3 proportional cycle | INT16 | Read/write | |||||
| HR | 25doc 0019H | EVT4 proportional band | Decimal point ignored. | INT16 | Read/write | ||||
| HR | 26doc 001AH | EVT4 reset | Decimal point ignored. | INT16 | Read/write | ||||
| HR | 27doc 001BH | EVT4 proportional cycle | INT16 | Read/write | |||||
| HR | 32doc 0020H | Temperature compensation method | INT16 | Read/write | 0 = Temperature characteristics of NaCl; 1 = Temperature coefficient (%/°C) and reference temperature; 2 = No temperature compensation | ||||
| HR | 33doc 0021H | Temperature coefficient | Decimal point ignored. | INT16 | Read/write | ||||
| HR | 34doc 0022H | Reference temperature | Decimal point ignored. | INT16 | Read/write | ||||
| HR | 35doc 0023H | Temperature input decimal point place | INT16 | Read/write | 0 = No decimal point; 1 = 1 digit after decimal point | ||||
| HR | 41doc 0029H | Temperature input filter time constant | Decimal point ignored. | INT16 | Read/write | ||||
| HR | 48doc 0030H | Set value lock | Lock 3 lets most values change over the bus without saving to memory. | INT16 | Read/write | 0 = Unlock; 1 = Lock 1; 2 = Lock 2; 3 = Lock 3 | |||
| HR | 49doc 0031H | Transmission output 1 type | INT16 | Read/write | 0 = Conductivity transmission; 1 = Temperature transmission; 2 = EVT1 MV transmission; 3 = EVT2 MV transmission; 4 = EVT3 MV transmission; 5 = EVT4 MV transmission | ||||
| HR | 50doc 0032H | Transmission output 1 high limit | Decimal point ignored. | INT16 | Read/write | ||||
| HR | 51doc 0033H | Transmission output 1 low limit | Decimal point ignored. | INT16 | Read/write | ||||
| HR | 55doc 0037H | Backlight time | INT16 | Read/write | |||||
| HR | 64doc 0040H | Temperature calibration mode | Write-only (function 06). | INT16 | Write | 0 = Conductivity/Temperature Display mode; 1 = Temperature calibration mode | |||
| HR | 65doc 0041H | Temperature calibration value | Decimal point ignored. | INT16 | Read/write | ||||
| HR | 66doc 0042H | Conductivity calibration mode | Write-only (function 06). | INT16 | Write | 0 = Conductivity/Temperature Display mode; 1 = Zero adjustment mode; 2 = Span adjustment mode | |||
| HR | 67doc 0043H | Conductivity zero adjustment value | Decimal point ignored. | INT16 | Read/write | ||||
| HR | 68doc 0044H | Conductivity span adjustment value | Decimal point ignored. | INT16 | Read/write | ||||
| HR | 69doc 0045H | EVT output on input error | INT16 | Read/write | 0 = Enabled; 1 = Disabled | ||||
| HR | 70doc 0046H | Cable length correction | Decimal point ignored. | INT16 | Read/write | ||||
| HR | 71doc 0047H | Cable cross-section area | Decimal point ignored. | INT16 | Read/write | ||||
| HR | 72doc 0048H | EVT1 output ON time while ON | INT16 | Read/write | |||||
| HR | 73doc 0049H | EVT1 output OFF time while ON | INT16 | Read/write | |||||
| HR | 74doc 004AH | EVT2 output ON time while ON | INT16 | Read/write | |||||
| HR | 75doc 004BH | EVT2 output OFF time while ON | INT16 | Read/write | |||||
| HR | 76doc 004CH | EVT3 output ON time while ON | INT16 | Read/write | |||||
| HR | 77doc 004DH | EVT3 output OFF time while ON | INT16 | Read/write | |||||
| HR | 78doc 004EH | EVT4 output ON time while ON | INT16 | Read/write | |||||
| HR | 79doc 004FH | EVT4 output OFF time while ON | INT16 | Read/write | |||||
| HR | 80doc 0050H | EVT2 type | Changing any EVT type resets EVT1-EVT4 values to 0. | INT16 | Read/write | 0 = No action; 1 = Conductivity input low limit action; 2 = Conductivity input high limit action; 3 = Temperature input low limit action; 4 = Temperature input high limit action; 5 = Error output; 6 = Fail output; 7 = Conductivity input error alarm output; 8 = Conductivity input High/Low limits independent action; 9 = Temperature input High/Low limits independent action | |||
| HR | 81doc 0051H | EVT3 type | Changing any EVT type resets EVT1-EVT4 values to 0. | INT16 | Read/write | 0 = No action; 1 = Conductivity input low limit action; 2 = Conductivity input high limit action; 3 = Temperature input low limit action; 4 = Temperature input high limit action; 5 = Error output; 6 = Fail output; 7 = Conductivity input error alarm output; 8 = Conductivity input High/Low limits independent action; 9 = Temperature input High/Low limits independent action | |||
| HR | 82doc 0052H | EVT4 type | Changing any EVT type resets EVT1-EVT4 values to 0. | INT16 | Read/write | 0 = No action; 1 = Conductivity input low limit action; 2 = Conductivity input high limit action; 3 = Temperature input low limit action; 4 = Temperature input high limit action; 5 = Error output; 6 = Fail output; 7 = Conductivity input error alarm output; 8 = Conductivity input High/Low limits independent action; 9 = Temperature input High/Low limits independent action | |||
| HR | 83doc 0053H | EVT2 value | Decimal point ignored. | INT16 | Read/write | ||||
| HR | 84doc 0054H | EVT3 value | Decimal point ignored. | INT16 | Read/write | ||||
| HR | 85doc 0055H | EVT4 value | Decimal point ignored. | INT16 | Read/write | ||||
| HR | 86doc 0056H | EVT2 ON side | Decimal point ignored. | INT16 | Read/write | ||||
| HR | 87doc 0057H | EVT3 ON side | Decimal point ignored. | INT16 | Read/write | ||||
| HR | 88doc 0058H | EVT4 ON side | Decimal point ignored. | INT16 | Read/write | ||||
| HR | 89doc 0059H | EVT2 ON delay time | INT16 | Read/write | |||||
| HR | 90doc 005AH | EVT3 ON delay time | INT16 | Read/write | |||||
| HR | 91doc 005BH | EVT4 ON delay time | INT16 | Read/write | |||||
| HR | 92doc 005CH | EVT2 OFF delay time | INT16 | Read/write | |||||
| HR | 93doc 005DH | EVT3 OFF delay time | INT16 | Read/write | |||||
| HR | 94doc 005EH | EVT4 OFF delay time | INT16 | Read/write | |||||
| HR | 99doc 0063H | Backlight selection | INT16 | Read/write | 0 = All backlit; 1 = Conductivity display; 2 = Temperature display; 3 = Action indicators; 4 = Conductivity display + temperature display; 5 = Conductivity display + action indicators; 6 = Temperature display + action indicators | ||||
| HR | 100doc 0064H | Conductivity color | INT16 | Read/write | 0 = Green; 1 = Red; 2 = Orange; 3 = Changes continuously | ||||
| HR | 101doc 0065H | Conductivity color range | Decimal point ignored. | INT16 | Read/write | ||||
| HR | 102doc 0066H | Bar graph indication | INT16 | Read/write | 0 = No indication; 1 = Transmission output 1; 2 = Transmission output 2 | ||||
| HR | 103doc 0067H | Conductivity color reference value | Decimal point ignored. | INT16 | Read/write | ||||
| HR | 104doc 0068H | Conductivity input sensor correction | Decimal point ignored. | INT16 | Read/write | ||||
| HR | 105doc 0069H | Temperature display without compensation | INT16 | Read/write | 0 = Unlit; 1 = Reference temperature; 2 = Measured value | ||||
| HR | 111doc 006FH | Pt100 input wire type | INT16 | Read/write | 0 = 2-wire; 1 = 3-wire | ||||
| HR | 112doc 0070H | EVT1 output high limit | INT16 | Read/write | |||||
| HR | 113doc 0071H | EVT1 output low limit | INT16 | Read/write | |||||
| HR | 114doc 0072H | EVT2 output high limit | INT16 | Read/write | |||||
| HR | 115doc 0073H | EVT2 output low limit | INT16 | Read/write | |||||
| HR | 116doc 0074H | EVT3 output high limit | INT16 | Read/write | |||||
| HR | 117doc 0075H | EVT3 output low limit | INT16 | Read/write | |||||
| HR | 118doc 0076H | EVT4 output high limit | INT16 | Read/write | |||||
| HR | 119doc 0077H | EVT4 output low limit | INT16 | Read/write | |||||
| HR | 127doc 007FH | Key operation change flag clearing | INT16 | Write | 1 = Clear change flag | ||||
| HR | 128doc 0080H | Conductivity | Measured value; decimal point set by measurement range (0004H). | INT16 | Read | ||||
| HR | 129doc 0081H | Status flag 1 | BITMAP16 | Read | bit 5 = Temperature sensor burnout; bit 6 = Temperature sensor short-circuited; bit 7 = Above temperature compensation range (110.0 °C); bit 8 = Below temperature compensation range (0.0 °C); bit 9 = Measured value above range; bit 10 = Measured value below range; bit 11 = Setting mode; bit 12 = Conductivity calibration zero adjustment; bit 13 = Conductivity calibration span adjustment; bit 15 = Changed by keypad | ||||
| HR | 132doc 0084H | EVT1 manipulated variable | Decimal point ignored. | INT16 | Read | ||||
| HR | 133doc 0085H | EVT2 manipulated variable | Decimal point ignored. | INT16 | Read | ||||
| HR | 134doc 0086H | EVT3 manipulated variable | Decimal point ignored. | INT16 | Read | ||||
| HR | 135doc 0087H | EVT4 manipulated variable | Decimal point ignored. | INT16 | Read | ||||
| HR | 144doc 0090H | Temperature | Decimal point per 0023H. | INT16 | Read | ||||
| HR | 145doc 0091H | Status flag 2 | BITMAP16 | Read | bit 0 = EVT1 output; bit 1 = EVT2 output; bit 2 = EVT3 output; bit 3 = EVT4 output; bit 4 = Transmission output 1 zero adjustment; bit 5 = Transmission output 1 span adjustment; bit 6 = Transmission output 2 zero adjustment; bit 7 = Transmission output 2 span adjustment; bit 12 = Temperature calibration | ||||
| HR | 256doc 0100H | EVT1 hysteresis type | INT16 | Read/write | 0 = Medium value; 1 = Reference value | ||||
| HR | 257doc 0101H | EVT2 hysteresis type | INT16 | Read/write | 0 = Medium value; 1 = Reference value | ||||
| HR | 258doc 0102H | EVT3 hysteresis type | INT16 | Read/write | 0 = Medium value; 1 = Reference value | ||||
| HR | 259doc 0103H | EVT4 hysteresis type | INT16 | Read/write | 0 = Medium value; 1 = Reference value | ||||
| HR | 260doc 0104H | EVT1 OFF side | Decimal point ignored. | INT16 | Read/write | ||||
| HR | 261doc 0105H | EVT2 OFF side | Decimal point ignored. | INT16 | Read/write | ||||
| HR | 262doc 0106H | EVT3 OFF side | Decimal point ignored. | INT16 | Read/write | ||||
| HR | 263doc 0107H | EVT4 OFF side | Decimal point ignored. | INT16 | Read/write | ||||
| HR | 271doc 010FH | Transmission output 1 status when calibrating | INT16 | Read/write | 0 = Last value HOLD; 1 = Set value HOLD; 2 = Measured value | ||||
| HR | 272doc 0110H | Transmission output 1 HOLD value when calibrating | Decimal point ignored. | INT16 | Read/write | ||||
| HR | 273doc 0111H | EVT1 conductivity error alarm EVT type | INT16 | Read/write | 0 = No action; 1 = EVT2 type; 2 = EVT3 type; 3 = EVT4 type | ||||
| HR | 274doc 0112H | EVT2 conductivity error alarm EVT type | INT16 | Read/write | 0 = EVT1 type; 1 = No action; 2 = EVT3 type; 3 = EVT4 type | ||||
| HR | 275doc 0113H | EVT3 conductivity error alarm EVT type | INT16 | Read/write | 0 = EVT1 type; 1 = EVT2 type; 2 = No action; 3 = EVT4 type | ||||
| HR | 276doc 0114H | EVT4 conductivity error alarm EVT type | INT16 | Read/write | 0 = EVT1 type; 1 = EVT2 type; 2 = EVT3 type; 3 = No action | ||||
| HR | 277doc 0115H | EVT1 error alarm band (output ON) | Decimal point ignored. | INT16 | Read/write | ||||
| HR | 278doc 0116H | EVT1 error alarm time (output ON) | INT16 | Read/write | |||||
| HR | 279doc 0117H | EVT1 error alarm band (output OFF) | Decimal point ignored. | INT16 | Read/write | ||||
| HR | 280doc 0118H | EVT1 error alarm time (output OFF) | INT16 | Read/write | |||||
| HR | 281doc 0119H | EVT2 error alarm band (output ON) | Decimal point ignored. | INT16 | Read/write | ||||
| HR | 282doc 011AH | EVT2 error alarm time (output ON) | INT16 | Read/write | |||||
| HR | 283doc 011BH | EVT2 error alarm band (output OFF) | Decimal point ignored. | INT16 | Read/write | ||||
| HR | 284doc 011CH | EVT2 error alarm time (output OFF) | INT16 | Read/write | |||||
| HR | 285doc 011DH | EVT3 error alarm band (output ON) | Decimal point ignored. | INT16 | Read/write | ||||
| HR | 286doc 011EH | EVT3 error alarm time (output ON) | INT16 | Read/write | |||||
| HR | 287doc 011FH | EVT3 error alarm band (output OFF) | Decimal point ignored. | INT16 | Read/write | ||||
| HR | 288doc 0120H | EVT3 error alarm time (output OFF) | INT16 | Read/write | |||||
| HR | 289doc 0121H | EVT4 error alarm band (output ON) | Decimal point ignored. | INT16 | Read/write | ||||
| HR | 290doc 0122H | EVT4 error alarm time (output ON) | INT16 | Read/write | |||||
| HR | 291doc 0123H | EVT4 error alarm band (output OFF) | Decimal point ignored. | INT16 | Read/write | ||||
| HR | 292doc 0124H | EVT4 error alarm time (output OFF) | INT16 | Read/write | |||||
| HR | 293doc 0125H | Conductivity error alarm time unit | INT16 | Read/write | 0 = Seconds; 1 = Minutes | ||||
| HR | 294doc 0126H | Transmission output 1 adjustment mode | INT16 | Read/write | 0 = Conductivity/Temperature Display mode; 1 = Zero adjustment mode; 2 = Span adjustment mode | ||||
| HR | 295doc 0127H | Transmission output 1 zero adjustment value | Decimal point ignored. | INT16 | Read/write | ||||
| HR | 296doc 0128H | Transmission output 1 span adjustment value | Decimal point ignored. | INT16 | Read/write | ||||
| HR | 297doc 0129H | EVT1 cycle variable range | Decimal point ignored. | INT16 | Read/write | ||||
| HR | 298doc 012AH | EVT2 cycle variable range | Decimal point ignored. | INT16 | Read/write | ||||
| HR | 299doc 012BH | EVT3 cycle variable range | Decimal point ignored. | INT16 | Read/write | ||||
| HR | 300doc 012CH | EVT4 cycle variable range | Decimal point ignored. | INT16 | Read/write | ||||
| HR | 301doc 012DH | EVT1 cycle extended time | INT16 | Read/write | |||||
| HR | 302doc 012EH | EVT2 cycle extended time | INT16 | Read/write | |||||
| HR | 303doc 012FH | EVT3 cycle extended time | INT16 | Read/write | |||||
| HR | 304doc 0130H | EVT4 cycle extended time | INT16 | Read/write | |||||
| HR | 305doc 0131H | 3-electrode sensor resistance | INT16 | Read/write | |||||
| HR | 313doc 0139H | EVT1 H/L independent lower value | Decimal point ignored. | INT16 | Read/write | ||||
| HR | 314doc 013AH | EVT2 H/L independent lower value | Decimal point ignored. | INT16 | Read/write | ||||
| HR | 315doc 013BH | EVT3 H/L independent lower value | Decimal point ignored. | INT16 | Read/write | ||||
| HR | 316doc 013CH | EVT4 H/L independent lower value | Decimal point ignored. | INT16 | Read/write | ||||
| HR | 317doc 013DH | EVT1 H/L independent upper value | Decimal point ignored. | INT16 | Read/write | ||||
| HR | 318doc 013EH | EVT2 H/L independent upper value | Decimal point ignored. | INT16 | Read/write | ||||
| HR | 319doc 013FH | EVT3 H/L independent upper value | Decimal point ignored. | INT16 | Read/write | ||||
| HR | 320doc 0140H | EVT4 H/L independent upper value | Decimal point ignored. | INT16 | Read/write | ||||
| HR | 321doc 0141H | EVT1 hysteresis | Decimal point ignored. | INT16 | Read/write | ||||
| HR | 322doc 0142H | EVT2 hysteresis | Decimal point ignored. | INT16 | Read/write | ||||
| HR | 323doc 0143H | EVT3 hysteresis | Decimal point ignored. | INT16 | Read/write | ||||
| HR | 324doc 0144H | EVT4 hysteresis | Decimal point ignored. | INT16 | Read/write | ||||
| HR | 327doc 0147H | Transmission output 2 type | INT16 | Read/write | 0 = Conductivity transmission; 1 = Temperature transmission; 2 = MV2 transmission; 3 = MV3 transmission; 4 = MV4 transmission | ||||
| HR | 328doc 0148H | Transmission output 2 high limit | Decimal point ignored. | INT16 | Read/write | ||||
| HR | 329doc 0149H | Transmission output 2 low limit | Decimal point ignored. | INT16 | Read/write | ||||
| HR | 330doc 014AH | Transmission output 2 adjustment mode | INT16 | Read/write | 0 = Conductivity/Temperature Display mode; 1 = Zero adjustment mode; 2 = Span adjustment mode | ||||
| HR | 331doc 014BH | Transmission output 2 zero adjustment value | Decimal point ignored. | INT16 | Read/write | ||||
| HR | 332doc 014CH | Transmission output 2 span adjustment value | Decimal point ignored. | INT16 | Read/write | ||||
| HR | 333doc 014DH | Transmission output 2 status when calibrating | INT16 | Read/write | 0 = Last value HOLD; 1 = Set value HOLD; 2 = Measured value | ||||
| HR | 334doc 014EH | Transmission output 2 HOLD value when calibrating | Decimal point ignored. | INT16 | Read/write | ||||
| HR | 337doc 0151H | Conductivity moving average inputs | INT16 | Read/write | |||||
| HR | 338doc 0152H | Temperature moving average inputs | INT16 | Read/write | |||||
| HR | 512doc 0200H | User save area 1 | Free 16-bit storage, -32768 to 32767. | INT16 | Read/write | ||||
| HR | 513doc 0201H | User save area 2 | Free 16-bit storage, -32768 to 32767. | INT16 | Read/write | ||||
| HR | 514doc 0202H | User save area 3 | Free 16-bit storage, -32768 to 32767. | INT16 | Read/write | ||||
| HR | 515doc 0203H | User save area 4 | Free 16-bit storage, -32768 to 32767. | INT16 | Read/write | ||||
| HR | 516doc 0204H | User save area 5 | Free 16-bit storage, -32768 to 32767. | INT16 | Read/write | ||||
| HR | 517doc 0205H | User save area 6 | Free 16-bit storage, -32768 to 32767. | INT16 | Read/write | ||||
| HR | 518doc 0206H | User save area 7 | Free 16-bit storage, -32768 to 32767. | INT16 | Read/write | ||||
| HR | 519doc 0207H | User save area 8 | Free 16-bit storage, -32768 to 32767. | INT16 | Read/write | ||||
| HR | 520doc 0208H | User save area 9 | Free 16-bit storage, -32768 to 32767. | INT16 | Read/write | ||||
| HR | 521doc 0209H | User save area 10 | Free 16-bit storage, -32768 to 32767. | INT16 | Read/write |
Notes on this map
- Function 03 reads and 06 writes; the manual's function column shows no multi-register write (10H).
- All data are 16-bit two's complement and are sent without the decimal point.
- Measurement range codes (0004H) are not listed: the list changes with sensor cell constant and unit.
- The status bit values in 0081H bits 12-13 and 0091H bits 4-7/12-13 are two-bit fields; only the codes listed in the manual are shown as single bits.
- EVT3/EVT4 and transmission output 2 items need their options; without them writes return exception 3 (some transmission output 2 items return exception 17).
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Shinko Technos AER-102-ECH conductivity indicating controller (C5 option)
What Modbus registers does the Shinko Technos AER-102-ECH conductivity indicating controller (C5 option) have?
This map lists 164 registers: 164 holding registers. 156 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Shinko Technos AER-102-ECH conductivity indicating controller (C5 option) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Registers are listed as hex data items (0001H) that go into the request unchanged. The manual adds that the matching Modicon holding-register number is the item in decimal plus 40001 (0001H = 40002). The manual's RTU example reads conductivity with data item 0080H (CRC 85E2H checked).
What are the minimum Modbus registers to integrate the Shinko Technos AER-102-ECH conductivity indicating controller (C5 option)?
Start with HR 128 Conductivity (Conductivity / salinity / TDS value); HR 144 Temperature (Temperature); HR 129 Status flag 1 (Sensor and range errors); HR 145 Status flag 2 (EVT output states); HR 4 Measurement range (Measurement range (sets decimal point)); HR 3 Measurement unit (Measurement unit).
How do I enable Modbus control of the Shinko Technos AER-102-ECH conductivity indicating controller (C5 option)?
Requires the C5 option. In the Basic Function Group choose Communication protocol = MODBUS RTU (or ASCII), then instrument number, speed, data bit/parity and stop bit; these are keypad-only.
Where is the official Shinko Technos AER-102-ECH conductivity indicating controller (C5 option) Modbus documentation?
The source is Communication Instruction Manual AER-102-ECH (C5) (No. AER11CECE5), revision 2019-06, published free by Shinko Technos at https://shinko-technos.co.jp/e/manual/english/AER11CECE5.pdf.
More Shinko Technos Modbus register maps
- Sensor (digital temperature controller)
Shinko Technos ACD-13A / ACR-13A / ACD-15A / ACR-15A digital indicating controller (C, C5 options)
Shinko ACD/ACR-13A (PID) and ACD/ACR-15A (valve positioning) with the C or C5 communication option; manual No.ACDR1CE8.
Also known as: ACD-13A, ACR-13A, ACD-15A, ACR-15A - Sensor (digital temperature controller)
Shinko Technos ACS-13A digital indicating controller (C5 option)
Shinko ACS-13A with the C5 serial communication option; communication manual No.ACS12CE5.
Also known as: ACS-13A-C5, ACS-13A C5 - Sensor (digital temperature controller)
Shinko Technos ACS2 digital indicating controller (C5, C5W options)
Shinko ACS2 with the C5 or C5W serial option, Shinko protocol / MODBUS RTU command set; manual No.ACS2CE3.
Also known as: ACS2-C5, ACS2-C5W - Sensor (digital temperature controller)
Shinko Technos BCS2 / BCR2 / BCD2 digital indicating controller (C5, C5W options)
Shinko BCx2 series (BCS2, BCR2, BCD2) with the C5 or C5W communication option, standard (not JC-allocated) command set; manual No.BCx2CE6.
Also known as: BCS2, BCR2, BCD2, BCx2 - Sensor (digital temperature controller)
Shinko Technos DCL-33A DC digital indicating controller (C5 option)
Shinko DCL-33A DC with the C5 option; communication manual No.DCL3CDCE2.
Also known as: DCL-33A DC, DCL-33A-DC-C5 - Sensor (digital temperature controller)
Shinko Technos DCL-33A digital indicating controller (C5 option)
Shinko DCL-33A with the C5 serial option, plain (non-block) Modbus protocol setting; manual No.DCL32CE3.
Also known as: DCL-33A-C5, DCL-33A C5 - Sensor (digital temperature controller)
Shinko Technos FC series digital indicating controller (C/C5 option, Modbus ASCII)
Shinko FCS-23A, FCR-13A, FCR-23A and FCD-13A with the C or C5 serial option; FCR-15A and FCD-15A have no Modbus (Shinko protocol only). Manual No.FC1CE11.
Also known as: FCS-23A, FCR-13A, FCR-23A, FCD-13A - Sensor (paperless recorder)
Shinko Technos GR200 paperless recorder (Modbus RTU / Modbus TCP)
Shinko GR200 paperless recorder with RS-485 Modbus RTU or Ethernet Modbus TCP; manual GR2CE1.
Also known as: GR200 - Sensor (chart recorder)
Shinko Technos HR-700 hybrid recorder (Modbus RTU, firmware 4.00+)
Shinko HR-700 hybrid recorders (multipoint and pen types), body version 4.00 or later, Modbus map version 01; manual No. HR7CE4.
Also known as: HR-700 - Sensor (digital temperature controller)
Shinko Technos JCL-33A digital indicating controller (C5 option)
Shinko JCL-33A with the C5 option, protocol set to plain 'Modbus RTU mode' or 'Modbus ASCII mode' (not the Block Read/Write modes, which use another layout); manual No.JCL3CE3.
Also known as: JCL-33A-C5, JCL-33A C5 - Sensor (digital temperature controller)
Shinko Technos JCS-33A / JCM-33A / JCR-33A / JCD-33A digital indicating controller (C5 option)
Shinko JCx-33A series (JCS, JCM, JCR, JCD-33A) with the C5 option; communication manual No.JC3CE11.
Also known as: JCS-33A, JCM-33A, JCR-33A, JCD-33A, JCx-33A - Sensor (digital temperature controller)
Shinko Technos JIR-301-M digital indicator (C5 option)
Shinko JIR-301-M with the C5 option, plain (non-block) Modbus protocol setting; manual No.JIR32CE4.
Also known as: JIR-301-M-C5, JIR-301-M C5 - Sensor (programmable temperature controller)
Shinko Technos PCA1 programmable controller (C/C5 option)
Shinko PCA1 programmable controllers with the C or C5 serial option; manual No. PCA1CE3.
Also known as: PCA1 - Sensor (programmable temperature controller)
Shinko Technos PCB1 programmable controller (C5W/C5 option)
Shinko PCB1 programmable controllers with the C5W or C5 RS-485 option, native PCB1 command set; manual No. PCB1CE3.
Also known as: PCB1 - Sensor (digital temperature controller)
Shinko Technos PCD-33A programmable controller (C5 option)
Shinko PCD-33A program controller with the C5 RS-485 option; manual printed No.PCD3CE1 2003.02 (file PCD3CE2).
Also known as: PCD-33A-R/M, PCD-33A-S/M - Sensor (signal conditioner)
Shinko Technos SGxL signal conditioner series (Modbus RTU)
Shinko SGxL signal conditioners (SGBL, SGCL, SGDL, SGIL, SGLL, SGML, SGPL, SGRL, SGSL, SGTL, SGUL); SGFL and SGJL are not covered. Manual No.SGxL1CE3.
Also known as: SGBL, SGCL, SGDL, SGIL, SGLL, SGML, SGPL, SGRL, SGSL, SGTL, SGUL - Sensor (digital temperature controller)
Shinko Technos WCL-13A 2-channel digital indicating controller (C5 option)
Shinko WCL-13A two-loop controller with the C5 option; communication manual No.WCL1CE3.
Also known as: WCL-13A-C5, WCL-13A C5
Other valves, actuators & sensors register maps
- Sensor (flow transmitter)
Siemens SITRANS F M MAG 6000 with USM II Modbus RTU module
SITRANS F M MAG 6000 / MAG 6000 I electromagnetic flow transmitters fitted with the USM II Modbus RTU RS-485 add-on module (operating instructions 03/2021).
Also known as: MAG 6000, MAG 6000 I, SITRANS FM MAG 6000 - Sensor (humidity / temperature)
Teracom TSH300v3 RS-485 humidity and temperature sensor
TSH300v3 per the Teracom TSH300v3 user manual Revision R1.17.
Also known as: TSH300, TSH300v3 - Sensor (gas density)
Trafag 8775 gas density sensor / 879x hybrid gas density monitor (legacy Modbus map)
Trafag 8775 and 879x (8791/8792/8793) running the 'Legacy' Modbus configuration of software description H73622a (10/2025).
Also known as: 8775, 8791, 8792, 8793, 879x, Trafag gas density monitor - Sensor (CO2 wall transmitter)
Vaisala GMW87 CO2 and temperature wall transmitter (Modbus RTU)
GMW87, the RS-485 Modbus RTU model of the GMW80 series (user guide M211748EN-H).
Also known as: GMW87, GMW80 series Modbus - Sensor (H2O2 / humidity probe)
Vaisala HPP272 hydrogen peroxide, humidity and temperature probe (Modbus RTU)
HPP272 vaporized hydrogen peroxide probe, Modbus RTU interface (user guide M211972EN-G).
Also known as: HPP272, PEROXCAP HPP272 - Sensor (humidity and temperature probe)
Vaisala XMP10 humidity and temperature probe (Modbus RTU)
XMP10 probes ordered with (or switched to) Modbus RTU output, user guide M213279EN-A.
Also known as: XMP10, HUMICAP XMP10, Vaisala XMP10
All valves, actuators & sensors Modbus register maps →
Source: Communication Instruction Manual AER-102-ECH (C5) · No. AER11CECE5 · rev. 2019-06. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.