Sensor (digital temperature controller) · Modbus register map
Shinko Technos JIR-301-M digital indicator (C5 option) Modbus register map
Updated 17 November 2026
The JIR-301-M is a digital indicator with up to three alarm outputs and an optional retransmission output; it measures thermocouple, RTD, current or voltage inputs. With the C5 option it speaks Shinko protocol, Modbus ASCII or Modbus RTU on RS485. The map covers PV, alarm settings and states, input and scaling settings.
This page lists 28 Modbus registers for the Shinko Technos JIR-301-M digital indicator (C5 option) — 25 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Shinko Technos’s own free documentation (linked below) and checked against it.
- Manufacturer
- Shinko Technos
- Model
- JIR-301-M digital indicator (C5 option)
- Equipment type
- Sensor (digital temperature controller)
- Registers
- 28 (25 writable)
- Transport
- Modbus RTU, Modbus ASCII
- Default unit ID
- 0
- Default serial
- 9600 baud, 8E1
- Documented addressing
- hexadecimal, 0-based
- Also known as
- JIR-301-M-C5, JIR-301-M C5
Integration notes: Shinko Technos JIR-301-M digital indicator (C5 option)
Choose MODBUS RTU and a non-zero instrument number on the keypad, then read PV at 0080H and status at 0081H with function 03.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 128 | PV | INT16 | Process value | Read |
| HR 129 | Status flag | BITMAP16 | Alarm and over/underscale status | Read |
| HR 8 | Decimal point place | INT16 | Decimal point for scaling | Read/write |
| HR 1 | A1 value | INT16 | Alarm 1 value | Read/write |
Enable Modbus control & writes
Requires the C5 option. In the keypad setup, step with the MODE key to Communication protocol and pick MODBUS RTU mode, then set instrument number, speed, parity and stop bit.
Byte order & addressing
- Instrument number defaults to 0, the Modbus broadcast address; set 1-95.
- Parity and stop bit only apply to the Modbus settings.
Network setup
- Factory defaults: Shinko protocol, instrument 0, 9600 bps, even parity, 1 stop bit.
- Speeds 2400-38400 bps.
Watch out for
- Settings are stored in non-volatile memory; avoid cyclic writes.
Shinko Technos JIR-301-M digital indicator (C5 option) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 1doc 0001H | A1 value | Decimal point ignored: Raw integer; apply the decimal point setting. | INT16 | Read/write | ||||
| HR | 2doc 0002H | A2 value | Decimal point ignored: Raw integer; apply the decimal point setting. | INT16 | Read/write | ||||
| HR | 3doc 0003H | A3 value | Decimal point ignored: Raw integer; apply the decimal point setting. | INT16 | Read/write | ||||
| HR | 4doc 0004H | Set value lock | INT16 | Read/write | 0 = Unlock; 1 = Lock 1; 2 = Lock 2; 3 = Lock 3 | ||||
| HR | 5doc 0005H | Sensor correction | Decimal point ignored: Raw integer; apply the decimal point setting. | INT16 | Read/write | ||||
| HR | 6doc 0006H | Scaling high limit | INT16 | Read/write | |||||
| HR | 7doc 0007H | Scaling low limit | INT16 | Read/write | |||||
| HR | 8doc 0008H | Decimal point place | INT16 | Read/write | 0 = XXXX; 1 = XXX.X; 2 = XX.XX; 3 = X.XXX | ||||
| HR | 9doc 0009H | PV filter time constant | Decimal point ignored: Raw integer; apply the decimal point setting. | INT16 | Read/write | ||||
| HR | 10doc 000AH | A1 hysteresis | Decimal point ignored: Raw integer; apply the decimal point setting. | INT16 | Read/write | ||||
| HR | 11doc 000BH | A2 hysteresis | Decimal point ignored: Raw integer; apply the decimal point setting. | INT16 | Read/write | ||||
| HR | 12doc 000CH | A3 hysteresis | Decimal point ignored: Raw integer; apply the decimal point setting. | INT16 | Read/write | ||||
| HR | 13doc 000DH | A1 type | INT16 | Read/write | 0 = No alarm action; 1 = High limit alarm; 2 = Low limit alarm; 3 = High limit with standby; 4 = Low limit with standby | ||||
| HR | 14doc 000EH | A2 type | INT16 | Read/write | 0 = No alarm action; 1 = High limit alarm; 2 = Low limit alarm; 3 = High limit with standby; 4 = Low limit with standby | ||||
| HR | 15doc 000FH | A3 type | INT16 | Read/write | 0 = No alarm action; 1 = High limit alarm; 2 = Low limit alarm; 3 = High limit with standby; 4 = Low limit with standby; 5 = High/Low limit range alarm | ||||
| HR | 16doc 0010H | Transmission output 1 high limit | INT16 | Read/write | |||||
| HR | 17doc 0011H | Transmission output 1 low limit | INT16 | Read/write | |||||
| HR | 18doc 0012H | A1 energized/de-energized | INT16 | Read/write | 0 = Energized; 1 = De-energized | ||||
| HR | 19doc 0013H | A2 energized/de-energized | INT16 | Read/write | 0 = Energized; 1 = De-energized | ||||
| HR | 20doc 0014H | A3 energized/de-energized | INT16 | Read/write | 0 = Energized; 1 = De-energized | ||||
| HR | 21doc 0015H | A1 delay time | INT16 | Read/write | |||||
| HR | 22doc 0016H | A2 delay time | INT16 | Read/write | |||||
| HR | 23doc 0017H | A3 delay time | INT16 | Read/write | |||||
| HR | 25doc 0019H | Input type | INT16 | Read/write | 0 = K -200 to 1370 C; 1 = K -200.0 to 400.0 C; 2 = J -200 to 1000 C; 3 = R 0 to 1760 C; 4 = S 0 to 1760 C; 5 = B 0 to 1820 C; 6 = E -200 to 800 C; 7 = T -200.0 to 400.0 C; 8 = N -200 to 1300 C; 9 = PL-II 0 to 1390 C; 10 = C (W/Re5-26) 0 to 2315 C; 11 = Pt100 -200.0 to 850.0 C; 12 = JPt100 -200.0 to 500.0 C; 13 = Pt100 -200 to 850 C; 14 = JPt100 -200 to 500 C; 15 = K -320 to 2500 F; 16 = K -200.0 to 750.0 F; 17 = J -320 to 1800 F; 18 = R 0 to 3200 F; 19 = S 0 to 3200 F; 20 = B 0 to 3300 F; 21 = E -320 to 1500 F; 22 = T -200.0 to 750.0 F; 23 = N -320 to 2300 F; 24 = PL-II 0 to 2500 F; 25 = C (W/Re5-26) 0 to 4200 F; 26 = Pt100 -200.0 to 1000.0 F; 27 = JPt100 -200.0 to 900.0 F; 28 = Pt100 -300 to 1500 F; 29 = JPt100 -300 to 900 F; 30 = 4-20 mA DC (external shunt); 31 = 0-20 mA DC (external shunt); 32 = 0-1 V DC; 33 = 0-5 V DC; 34 = 1-5 V DC; 35 = 0-10 V DC; 36 = 4-20 mA DC (built-in shunt); 37 = 0-20 mA DC (built-in shunt) | ||||
| HR | 112doc 0070H | Key operation change flag clearing | INT16 | Write | 0 = No action; 1 = Clear the flag | ||||
| HR | 128doc 0080H | PV | Process value. Decimal point ignored: Raw integer; apply the decimal point setting. | INT16 | Read | ||||
| HR | 129doc 0081H | Status flag | BITMAP16 | Read | bit 0 = A1 output on; bit 1 = A2 output on; bit 2 = A3 output on; bit 3 = Overscale; bit 4 = Underscale; bit 15 = Settings changed by keypad | ||||
| HR | 161doc 00A1H | Unit specification flag | BITMAP16 | Read | bit 0 = A1 available; bit 1 = A2 available; bit 2 = A3 available; bit 3 = Communication available; bit 4 = Transmission output 1 available |
Notes on this map
- This map is for the plain 'MODBUS RTU mode' / 'MODBUS ASCII mode' settings. The 'Block Read/Write available' settings use the different layout of section 7.2 and are not covered.
- All data are 16-bit two's complement. Items marked 'decimal point ignored' are whole numbers; apply the decimal point place (0008H).
- Item 0018H is not listed in the single-item table and is left out.
- Protocol, instrument number, speed, parity and stop bit are keypad-only settings.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Shinko Technos JIR-301-M digital indicator (C5 option)
What Modbus registers does the Shinko Technos JIR-301-M digital indicator (C5 option) have?
This map lists 28 registers: 28 holding registers. 25 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Shinko Technos JIR-301-M digital indicator (C5 option) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Registers are listed as hex data items (0001H) that go into the request unchanged. The manual adds that the matching Modicon holding-register number is the item in decimal plus 40001 (0001H = 40002).
What are the minimum Modbus registers to integrate the Shinko Technos JIR-301-M digital indicator (C5 option)?
Start with HR 128 PV (Process value); HR 129 Status flag (Alarm and over/underscale status); HR 8 Decimal point place (Decimal point for scaling); HR 1 A1 value (Alarm 1 value).
How do I enable Modbus control of the Shinko Technos JIR-301-M digital indicator (C5 option)?
Requires the C5 option. In the keypad setup, step with the MODE key to Communication protocol and pick MODBUS RTU mode, then set instrument number, speed, parity and stop bit.
Where is the official Shinko Technos JIR-301-M digital indicator (C5 option) Modbus documentation?
The source is Communication Instruction Manual JIR-301-M (C5) (No.JIR32CE4), revision 2023-11, published free by Shinko Technos at https://shinko-technos.co.jp/e/manual/english/JIR32CE4.pdf.
More Shinko Technos Modbus register maps
- Sensor (digital temperature controller)
Shinko Technos ACD-13A / ACR-13A / ACD-15A / ACR-15A digital indicating controller (C, C5 options)
Shinko ACD/ACR-13A (PID) and ACD/ACR-15A (valve positioning) with the C or C5 communication option; manual No.ACDR1CE8.
Also known as: ACD-13A, ACR-13A, ACD-15A, ACR-15A - Sensor (digital temperature controller)
Shinko Technos ACS-13A digital indicating controller (C5 option)
Shinko ACS-13A with the C5 serial communication option; communication manual No.ACS12CE5.
Also known as: ACS-13A-C5, ACS-13A C5 - Sensor (digital temperature controller)
Shinko Technos ACS2 digital indicating controller (C5, C5W options)
Shinko ACS2 with the C5 or C5W serial option, Shinko protocol / MODBUS RTU command set; manual No.ACS2CE3.
Also known as: ACS2-C5, ACS2-C5W - Sensor (conductivity controller)
Shinko Technos AER-102-ECH conductivity indicating controller (C5 option)
Shinko AER-102-ECH electrical conductivity controller with the C5 RS-485 option; manual No. AER11CECE5.
Also known as: AER-102-ECH - Sensor (digital temperature controller)
Shinko Technos BCS2 / BCR2 / BCD2 digital indicating controller (C5, C5W options)
Shinko BCx2 series (BCS2, BCR2, BCD2) with the C5 or C5W communication option, standard (not JC-allocated) command set; manual No.BCx2CE6.
Also known as: BCS2, BCR2, BCD2, BCx2 - Sensor (digital temperature controller)
Shinko Technos DCL-33A DC digital indicating controller (C5 option)
Shinko DCL-33A DC with the C5 option; communication manual No.DCL3CDCE2.
Also known as: DCL-33A DC, DCL-33A-DC-C5 - Sensor (digital temperature controller)
Shinko Technos DCL-33A digital indicating controller (C5 option)
Shinko DCL-33A with the C5 serial option, plain (non-block) Modbus protocol setting; manual No.DCL32CE3.
Also known as: DCL-33A-C5, DCL-33A C5 - Sensor (digital temperature controller)
Shinko Technos FC series digital indicating controller (C/C5 option, Modbus ASCII)
Shinko FCS-23A, FCR-13A, FCR-23A and FCD-13A with the C or C5 serial option; FCR-15A and FCD-15A have no Modbus (Shinko protocol only). Manual No.FC1CE11.
Also known as: FCS-23A, FCR-13A, FCR-23A, FCD-13A - Sensor (paperless recorder)
Shinko Technos GR200 paperless recorder (Modbus RTU / Modbus TCP)
Shinko GR200 paperless recorder with RS-485 Modbus RTU or Ethernet Modbus TCP; manual GR2CE1.
Also known as: GR200 - Sensor (chart recorder)
Shinko Technos HR-700 hybrid recorder (Modbus RTU, firmware 4.00+)
Shinko HR-700 hybrid recorders (multipoint and pen types), body version 4.00 or later, Modbus map version 01; manual No. HR7CE4.
Also known as: HR-700 - Sensor (digital temperature controller)
Shinko Technos JCL-33A digital indicating controller (C5 option)
Shinko JCL-33A with the C5 option, protocol set to plain 'Modbus RTU mode' or 'Modbus ASCII mode' (not the Block Read/Write modes, which use another layout); manual No.JCL3CE3.
Also known as: JCL-33A-C5, JCL-33A C5 - Sensor (digital temperature controller)
Shinko Technos JCS-33A / JCM-33A / JCR-33A / JCD-33A digital indicating controller (C5 option)
Shinko JCx-33A series (JCS, JCM, JCR, JCD-33A) with the C5 option; communication manual No.JC3CE11.
Also known as: JCS-33A, JCM-33A, JCR-33A, JCD-33A, JCx-33A - Sensor (programmable temperature controller)
Shinko Technos PCA1 programmable controller (C/C5 option)
Shinko PCA1 programmable controllers with the C or C5 serial option; manual No. PCA1CE3.
Also known as: PCA1 - Sensor (programmable temperature controller)
Shinko Technos PCB1 programmable controller (C5W/C5 option)
Shinko PCB1 programmable controllers with the C5W or C5 RS-485 option, native PCB1 command set; manual No. PCB1CE3.
Also known as: PCB1 - Sensor (digital temperature controller)
Shinko Technos PCD-33A programmable controller (C5 option)
Shinko PCD-33A program controller with the C5 RS-485 option; manual printed No.PCD3CE1 2003.02 (file PCD3CE2).
Also known as: PCD-33A-R/M, PCD-33A-S/M - Sensor (signal conditioner)
Shinko Technos SGxL signal conditioner series (Modbus RTU)
Shinko SGxL signal conditioners (SGBL, SGCL, SGDL, SGIL, SGLL, SGML, SGPL, SGRL, SGSL, SGTL, SGUL); SGFL and SGJL are not covered. Manual No.SGxL1CE3.
Also known as: SGBL, SGCL, SGDL, SGIL, SGLL, SGML, SGPL, SGRL, SGSL, SGTL, SGUL - Sensor (digital temperature controller)
Shinko Technos WCL-13A 2-channel digital indicating controller (C5 option)
Shinko WCL-13A two-loop controller with the C5 option; communication manual No.WCL1CE3.
Also known as: WCL-13A-C5, WCL-13A C5
Other temperature & process controllers register maps
- Sensor (digital indicating temperature controller)
Yokogawa UTAdvanced UT35A / UT32A digital indicating controller
Yokogawa UT35A and UT32A single-loop controllers with RS-485 or Ethernet communication; D-register map from IM 05P07A01-01EN chapter 8 (UT32A-D loop 2 and UP35A/UP32A program items excluded).
Also known as: UT35A, UT32A, UT35A/MDL, UT32A/MDL - Sensor (digital temperature controller)
Fuji Electric PXR micro controller X (RS-485 Modbus option)
Fuji Electric PXR series controllers with the RS-485 Modbus communication option; manual INP-TN512642d-E.
Also known as: PXR3, PXR4, PXR5, PXR9 - Sensor (program temperature controller)
Yokogawa UTAdvanced UP55A program controller
Yokogawa UP55A program controller with RS-485 or Ethernet communication; D-register map from IM 05P07A01-01EN chapter 6 (UP55A column).
Also known as: UP55A - Sensor (digital process controller)
Fuji Electric PXH digital controller (Modbus RTU, monitoring map)
Fuji Electric PXH digital controllers on the RS-485 Modbus port; read-only monitoring registers from manual INP-TN514207c-E.
Also known as: PXH - Sensor (program temperature controller)
Yokogawa UTAdvanced UP35A / UP32A program controller
Yokogawa UP35A and UP32A single-loop program controllers with RS-485 or Ethernet communication; D-register map from IM 05P07A01-01EN chapter 8 (UP35A/UP32A columns).
Also known as: UP35A, UP32A - Sensor / controller (PID temperature controller)
Autonics TK series PID temperature controller (Modbus RTU)
Autonics TK series heating/cooling PID temperature controllers with RS-485, communication manual MCT-TKC1-V2.2-EN.
Also known as: TK4S, TK4M, TK4H, TK4W, TK4L, TK4S-14RR, TK4
All temperature & process controllers Modbus register maps →
Source: Communication Instruction Manual JIR-301-M (C5) · No.JIR32CE4 · rev. 2023-11. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.