Sensor (digital temperature controller) · Modbus register map

Shinko Technos JIR-301-M digital indicator (C5 option) Modbus register map

Updated 17 November 2026

Short answer

The JIR-301-M is a digital indicator with up to three alarm outputs and an optional retransmission output; it measures thermocouple, RTD, current or voltage inputs. With the C5 option it speaks Shinko protocol, Modbus ASCII or Modbus RTU on RS485. The map covers PV, alarm settings and states, input and scaling settings.

This page lists 28 Modbus registers for the Shinko Technos JIR-301-M digital indicator (C5 option) — 25 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Shinko Technos’s own free documentation (linked below) and checked against it.

Manufacturer
Shinko Technos
Model
JIR-301-M digital indicator (C5 option)
Equipment type
Sensor (digital temperature controller)
Registers
28 (25 writable)
Transport
Modbus RTU, Modbus ASCII
Default unit ID
0
Default serial
9600 baud, 8E1
Documented addressing
hexadecimal, 0-based
Also known as
JIR-301-M-C5, JIR-301-M C5
Source document
Communication Instruction Manual JIR-301-M (C5) · No.JIR32CE4 · rev. 2023-11
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Shinko Technos JIR-301-M digital indicator (C5 option)

Integration in brief

Choose MODBUS RTU and a non-zero instrument number on the keypad, then read PV at 0080H and status at 0081H with function 03.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 128PVINT16Process valueRead
HR 129Status flagBITMAP16Alarm and over/underscale statusRead
HR 8Decimal point placeINT16Decimal point for scalingRead/write
HR 1A1 valueINT16Alarm 1 valueRead/write

Enable Modbus control & writes

Requires the C5 option. In the keypad setup, step with the MODE key to Communication protocol and pick MODBUS RTU mode, then set instrument number, speed, parity and stop bit.

Byte order & addressing

Network setup

Watch out for

Shinko Technos JIR-301-M digital indicator (C5 option) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

28 of 28 shown
Shinko Technos JIR-301-M digital indicator (C5 option) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR1doc 0001HA1 valueDecimal point ignored: Raw integer; apply the decimal point setting.INT16Read/write
HR2doc 0002HA2 valueDecimal point ignored: Raw integer; apply the decimal point setting.INT16Read/write
HR3doc 0003HA3 valueDecimal point ignored: Raw integer; apply the decimal point setting.INT16Read/write
HR4doc 0004HSet value lockINT16Read/write0 = Unlock; 1 = Lock 1; 2 = Lock 2; 3 = Lock 3
HR5doc 0005HSensor correctionDecimal point ignored: Raw integer; apply the decimal point setting.INT16Read/write
HR6doc 0006HScaling high limitINT16Read/write
HR7doc 0007HScaling low limitINT16Read/write
HR8doc 0008HDecimal point placeINT16Read/write0 = XXXX; 1 = XXX.X; 2 = XX.XX; 3 = X.XXX
HR9doc 0009HPV filter time constantDecimal point ignored: Raw integer; apply the decimal point setting.INT16Read/write
HR10doc 000AHA1 hysteresisDecimal point ignored: Raw integer; apply the decimal point setting.INT16Read/write
HR11doc 000BHA2 hysteresisDecimal point ignored: Raw integer; apply the decimal point setting.INT16Read/write
HR12doc 000CHA3 hysteresisDecimal point ignored: Raw integer; apply the decimal point setting.INT16Read/write
HR13doc 000DHA1 typeINT16Read/write0 = No alarm action; 1 = High limit alarm; 2 = Low limit alarm; 3 = High limit with standby; 4 = Low limit with standby
HR14doc 000EHA2 typeINT16Read/write0 = No alarm action; 1 = High limit alarm; 2 = Low limit alarm; 3 = High limit with standby; 4 = Low limit with standby
HR15doc 000FHA3 typeINT16Read/write0 = No alarm action; 1 = High limit alarm; 2 = Low limit alarm; 3 = High limit with standby; 4 = Low limit with standby; 5 = High/Low limit range alarm
HR16doc 0010HTransmission output 1 high limitINT16Read/write
HR17doc 0011HTransmission output 1 low limitINT16Read/write
HR18doc 0012HA1 energized/de-energizedINT16Read/write0 = Energized; 1 = De-energized
HR19doc 0013HA2 energized/de-energizedINT16Read/write0 = Energized; 1 = De-energized
HR20doc 0014HA3 energized/de-energizedINT16Read/write0 = Energized; 1 = De-energized
HR21doc 0015HA1 delay timeINT16Read/write
HR22doc 0016HA2 delay timeINT16Read/write
HR23doc 0017HA3 delay timeINT16Read/write
HR25doc 0019HInput typeINT16Read/write0 = K -200 to 1370 C; 1 = K -200.0 to 400.0 C; 2 = J -200 to 1000 C; 3 = R 0 to 1760 C; 4 = S 0 to 1760 C; 5 = B 0 to 1820 C; 6 = E -200 to 800 C; 7 = T -200.0 to 400.0 C; 8 = N -200 to 1300 C; 9 = PL-II 0 to 1390 C; 10 = C (W/Re5-26) 0 to 2315 C; 11 = Pt100 -200.0 to 850.0 C; 12 = JPt100 -200.0 to 500.0 C; 13 = Pt100 -200 to 850 C; 14 = JPt100 -200 to 500 C; 15 = K -320 to 2500 F; 16 = K -200.0 to 750.0 F; 17 = J -320 to 1800 F; 18 = R 0 to 3200 F; 19 = S 0 to 3200 F; 20 = B 0 to 3300 F; 21 = E -320 to 1500 F; 22 = T -200.0 to 750.0 F; 23 = N -320 to 2300 F; 24 = PL-II 0 to 2500 F; 25 = C (W/Re5-26) 0 to 4200 F; 26 = Pt100 -200.0 to 1000.0 F; 27 = JPt100 -200.0 to 900.0 F; 28 = Pt100 -300 to 1500 F; 29 = JPt100 -300 to 900 F; 30 = 4-20 mA DC (external shunt); 31 = 0-20 mA DC (external shunt); 32 = 0-1 V DC; 33 = 0-5 V DC; 34 = 1-5 V DC; 35 = 0-10 V DC; 36 = 4-20 mA DC (built-in shunt); 37 = 0-20 mA DC (built-in shunt)
HR112doc 0070HKey operation change flag clearingINT16Write0 = No action; 1 = Clear the flag
HR128doc 0080HPVProcess value. Decimal point ignored: Raw integer; apply the decimal point setting.INT16Read
HR129doc 0081HStatus flagBITMAP16Readbit 0 = A1 output on; bit 1 = A2 output on; bit 2 = A3 output on; bit 3 = Overscale; bit 4 = Underscale; bit 15 = Settings changed by keypad
HR161doc 00A1HUnit specification flagBITMAP16Readbit 0 = A1 available; bit 1 = A2 available; bit 2 = A3 available; bit 3 = Communication available; bit 4 = Transmission output 1 available

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Shinko Technos JIR-301-M digital indicator (C5 option)

What Modbus registers does the Shinko Technos JIR-301-M digital indicator (C5 option) have?

This map lists 28 registers: 28 holding registers. 25 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Shinko Technos JIR-301-M digital indicator (C5 option) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Registers are listed as hex data items (0001H) that go into the request unchanged. The manual adds that the matching Modicon holding-register number is the item in decimal plus 40001 (0001H = 40002).

What are the minimum Modbus registers to integrate the Shinko Technos JIR-301-M digital indicator (C5 option)?

Start with HR 128 PV (Process value); HR 129 Status flag (Alarm and over/underscale status); HR 8 Decimal point place (Decimal point for scaling); HR 1 A1 value (Alarm 1 value).

How do I enable Modbus control of the Shinko Technos JIR-301-M digital indicator (C5 option)?

Requires the C5 option. In the keypad setup, step with the MODE key to Communication protocol and pick MODBUS RTU mode, then set instrument number, speed, parity and stop bit.

Where is the official Shinko Technos JIR-301-M digital indicator (C5 option) Modbus documentation?

The source is Communication Instruction Manual JIR-301-M (C5) (No.JIR32CE4), revision 2023-11, published free by Shinko Technos at https://shinko-technos.co.jp/e/manual/english/JIR32CE4.pdf.

More Shinko Technos Modbus register maps

Other temperature & process controllers register maps

All temperature & process controllers Modbus register maps →

Source: Communication Instruction Manual JIR-301-M (C5) · No.JIR32CE4 · rev. 2023-11. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.