Sensor / controller (PID temperature controller) · Modbus register map

Autonics TK series PID temperature controller (Modbus RTU) Modbus register map

Updated 17 November 2026

Short answer

Panel-mount heating and cooling PID temperature controller with Modbus RTU. Coils start/stop control and auto-tuning; input registers report PV, active SV, decimal point, heating/cooling MV, heater current and indicator bits; holding registers carry setpoints, multi-SV, alarm limits, PID parameters, input and output setup and communication settings.

This page lists 62 Modbus registers for the Autonics TK series PID temperature controller (Modbus RTU) — 36 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Autonics’s own free documentation (linked below) and checked against it.

Manufacturer
Autonics
Model
TK series PID temperature controller (Modbus RTU)
Equipment type
Sensor / controller (PID temperature controller)
Registers
62 (36 writable)
Transport
Modbus RTU
Default unit ID
1
Default serial
9600 baud, 8N2
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
Also known as
TK4S, TK4M, TK4H, TK4W, TK4L, TK4S-14RR, TK4
Source document
TK Series Communication Manual (Simultaneous Heating & Cooling Output PID Temperature Controllers) · MCT-TKC1-V2.2-EN · unofficial copy
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Autonics TK series PID temperature controller (Modbus RTU)

Integration in brief

Read 301001-301008 with FC04 for PV, decimal point, SV and MV; write the setpoint to 400001 and use coil 0 for run/stop. Check 301002 to place the decimal point.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
IR 1000PV (present value)INT16Process valueRead
IR 1001Decimal point locationUINT16Decimal pointRead
IR 1003SV setting valueINT16Active setpointRead
IR 1004Heating side MVUINT16Heating output %Read
HR 0SV set valueINT16Write setpointRead/write
CO 0RUN/STOPBITRun/stopRead/write

Enable Modbus control & writes

Communication write (400224) must be Enabled (default) for Modbus writes.

Byte order & addressing

Network setup

Watch out for

Autonics TK series PID temperature controller (Modbus RTU) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

62 of 62 shown
Autonics TK series PID temperature controller (Modbus RTU) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
CO0doc 000001 (0000)RUN/STOPControl output run/stop.BITRead/write0 = RUN; 1 = STOP
CO1doc 000002 (0001)Auto-tuning executeBITRead/write0 = OFF; 1 = ON
DI0doc 100001 (0000)°C unit indicatorBITRead0 = OFF; 1 = ON
DI1doc 100002 (0001)°F unit indicatorBITRead0 = OFF; 1 = ON
DI2doc 100003 (0002)% unit indicatorBITRead0 = OFF; 1 = ON
DI3doc 100004 (0003)OUT1 indicatorBITRead0 = OFF; 1 = ON
DI4doc 100005 (0004)OUT2 indicatorBITRead0 = OFF; 1 = ON
DI5doc 100006 (0005)AT indicatorBITRead0 = OFF; 1 = ON
DI6doc 100007 (0006)SV1 indicatorBITRead0 = OFF; 1 = ON
DI7doc 100008 (0007)SV2 indicatorBITRead0 = OFF; 1 = ON
DI8doc 100009 (0008)SV3 indicatorBITRead0 = OFF; 1 = ON
DI9doc 100010 (0009)AL1 indicatorBITRead0 = OFF; 1 = ON
DI10doc 100011 (000A)AL2 indicatorBITRead0 = OFF; 1 = ON
DI11doc 100012 (000B)MAN indicatorBITRead0 = OFF; 1 = ON
DI12doc 100013 (000C)DI-1 inputBITRead0 = OFF; 1 = ON
DI13doc 100014 (000D)DI-2 inputBITRead0 = OFF; 1 = ON
IR100doc 300101 (0064)Product number HUINT16Read
IR101doc 300102 (0065)Product number LUINT16Read
IR102doc 300103 (0066)Hardware versionUINT16Read
IR103doc 300104 (0067)Software versionUINT16Read
IR104doc 300105-300114 (0068-0071)Model nameASCII model text, e.g. 'TK4 14RR'.STRING[20]Read
IR1000doc 301001 (03E8)PV (present value)-1999..9999; Raw count; decimal point from 301002.INT16Read30000 = HHHH (over range); 31000 = OPEN (sensor break); -30000 = LLLL (under range)
IR1001doc 301002 (03E9)Decimal point locationUINT16Read0 = 0; 1 = 0.0; 2 = 0.00; 3 = 0.000
IR1002doc 301003 (03EA)Indicator unitUINT16Read0 = °C; 1 = °F; 2 = %; 3 = OFF
IR1003doc 301004 (03EB)SV setting valueActive setpoint. Raw count; decimal point from 301002.INT16Read
IR1004doc 301005 (03EC)Heating side MV0..1000 = 0.0..100.0 %.UINT16× 0.1%Read
IR1005doc 301006 (03ED)Cooling side MV0..1000 = 0.0..100.0 %.UINT16× 0.1%Read
IR1006doc 301007 (03EE)Indicator / input status bitsBITMAP16Readbit 0 = °C unit indicator; bit 1 = °F unit indicator; bit 2 = % unit indicator; bit 3 = OUT1 indicator; bit 4 = OUT2 indicator; bit 5 = AT indicator; bit 6 = SV1 indicator; bit 7 = SV2 indicator; bit 8 = SV3 indicator; bit 9 = AL1 indicator; bit 10 = AL2 indicator; bit 11 = MAN indicator; bit 12 = DI-1 input; bit 13 = DI-2 input
HR0doc 400001 (0000)SV set valueWithin L-SV..H-SV. Raw count; decimal point from 301002.INT16Read/write
HR1doc 400002 (0001)Heating MV (manual)0..1000 = 0.0..100.0 %.UINT16× 0.1%Read/write
HR2doc 400003 (0002)Cooling MV (manual)0..1000 = 0.0..100.0 %.UINT16× 0.1%Read/write
HR3doc 400004 (0003)Auto/Manual controlUINT16Read/write0 = AUTO; 1 = MAN
HR50doc 400051 (0032)R-S control output run/stopUINT16Read/write0 = RUN; 1 = STOP
HR51doc 400052 (0033)SV-N multi SV numberUINT16Read/write0 = SV-0; 1 = SV-1; 2 = SV-2; 3 = SV-3
HR52doc 400053 (0034)CT-A heater current monitoring0..500 = 0.0..50.0 A.UINT16× 0.1ARead/write
HR53doc 400054 (0035)AL1.L alarm 1 low limitDeviation or absolute value per alarm mode. Raw count; decimal point from 301002.INT16Read/write
HR54doc 400055 (0036)AL1.H alarm 1 high limitDeviation or absolute value per alarm mode. Raw count; decimal point from 301002.INT16Read/write
HR55doc 400056 (0037)AL2.L alarm 2 low limitDeviation or absolute value per alarm mode. Raw count; decimal point from 301002.INT16Read/write
HR56doc 400057 (0038)AL2.H alarm 2 high limitDeviation or absolute value per alarm mode. Raw count; decimal point from 301002.INT16Read/write
HR57doc 400058 (0039)SV-0 set valueMulti-SV setpoint. Raw count; decimal point from 301002.INT16Read/write
HR58doc 400059 (003A)SV-1 set valueMulti-SV setpoint. Raw count; decimal point from 301002.INT16Read/write
HR59doc 400060 (003B)SV-2 set valueMulti-SV setpoint. Raw count; decimal point from 301002.INT16Read/write
HR60doc 400061 (003C)SV-3 set valueMulti-SV setpoint. Raw count; decimal point from 301002.INT16Read/write
HR61doc 400062 (003D)AL3.L alarm 3 low limitRaw count; decimal point from 301002.INT16Read/write
HR62doc 400063 (003E)AL3.H alarm 3 high limitRaw count; decimal point from 301002.INT16Read/write
HR100doc 400101 (0064)AT auto-tuning run/stopUINT16Read/write0 = OFF; 1 = ON
HR101doc 400102 (0065)H-P heating proportional band1..9999 = 0.1..999.9 (°C/°F or %).UINT16× 0.1Read/write
HR102doc 400103 (0066)C-P cooling proportional band1..9999 = 0.1..999.9.UINT16× 0.1Read/write
HR103doc 400104 (0067)H-I heating integral timeUINT16sRead/write
HR104doc 400105 (0068)C-I cooling integral timeUINT16sRead/write
HR105doc 400106 (0069)H-D heating derivative timeUINT16sRead/write
HR106doc 400107 (006A)C-D cooling derivative timeUINT16sRead/write
HR108doc 400109 (006C)REST manual reset0..1000 = 0.0..100.0 %.UINT16× 0.1%Read/write
HR151doc 400152 (0097)UNIT sensor temperature unitUINT16Read/write0 = °C; 1 = °F
HR157doc 400158 (009D)D.UNT display unitUINT16Read/write0 = °C; 1 = °F; 2 = %; 3 = OFF
HR163doc 400164 (00A3)C-MD control typeStandard: 0 PID, 1 ON/OFF. Heat&cool: 0 P.P, 1 P.ON, 2 ON.P, 3 ON.ON.UINT16Read/write
HR218doc 400219 (00DA)ADRS communication address1..99.UINT16Read/write
HR219doc 400220 (00DB)BPS communication speedUINT16Read/write0 = 2400; 1 = 4800; 2 = 9600; 3 = 19200; 4 = 38400
HR220doc 400221 (00DC)PRTY parityUINT16Read/write0 = None; 1 = Even; 2 = Odd
HR221doc 400222 (00DD)STP stop bitsUINT16Read/write0 = 1; 1 = 2
HR222doc 400223 (00DE)RSW.T response waiting time5..99 ms, default 20.UINT16msRead/write
HR223doc 400224 (00DF)COMW communication writeUINT16Read/write0 = Enabled; 1 = Disabled

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Autonics TK series PID temperature controller (Modbus RTU)

What Modbus registers does the Autonics TK series PID temperature controller (Modbus RTU) have?

This map lists 62 registers: 2 coils, 14 discrete inputs, 12 input registers, 34 holding registers. 36 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Autonics TK series PID temperature controller (Modbus RTU) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Rows print a 6-digit reference (000001/100001/300001/400001 style) and the hex protocol address in brackets, e.g. 301001 (03E8); the bracketed hex value is the wire address.

What are the minimum Modbus registers to integrate the Autonics TK series PID temperature controller (Modbus RTU)?

Start with IR 1000 PV (present value) (Process value); IR 1001 Decimal point location (Decimal point); IR 1003 SV setting value (Active setpoint); IR 1004 Heating side MV (Heating output %); HR 0 SV set value (Write setpoint); CO 0 RUN/STOP (Run/stop).

How do I enable Modbus control of the Autonics TK series PID temperature controller (Modbus RTU)?

Communication write (400224) must be Enabled (default) for Modbus writes.

Where is the official Autonics TK series PID temperature controller (Modbus RTU) Modbus documentation?

The source is TK Series Communication Manual (Simultaneous Heating & Cooling Output PID Temperature Controllers) (MCT-TKC1-V2.2-EN). Autonics doesn't publish it on its own website, so this map was re-typed from a free copy at https://cdn.automationdirect.com/static/manuals/autonics/autonicstkcommunicationsmanual.pdf. It may be an older revision, so check it against the live unit.

More Autonics Modbus register maps

Other temperature & process controllers register maps

All temperature & process controllers Modbus register maps →

Source: TK Series Communication Manual (Simultaneous Heating & Cooling Output PID Temperature Controllers) · MCT-TKC1-V2.2-EN · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.