Sensor / controller (PID temperature controller) · Modbus register map
Autonics TK series PID temperature controller (Modbus RTU) Modbus register map
Updated 17 November 2026
Panel-mount heating and cooling PID temperature controller with Modbus RTU. Coils start/stop control and auto-tuning; input registers report PV, active SV, decimal point, heating/cooling MV, heater current and indicator bits; holding registers carry setpoints, multi-SV, alarm limits, PID parameters, input and output setup and communication settings.
This page lists 62 Modbus registers for the Autonics TK series PID temperature controller (Modbus RTU) — 36 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Autonics’s own free documentation (linked below) and checked against it.
- Manufacturer
- Autonics
- Model
- TK series PID temperature controller (Modbus RTU)
- Equipment type
- Sensor / controller (PID temperature controller)
- Registers
- 62 (36 writable)
- Transport
- Modbus RTU
- Default unit ID
- 1
- Default serial
- 9600 baud, 8N2
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- Also known as
- TK4S, TK4M, TK4H, TK4W, TK4L, TK4S-14RR, TK4
Integration notes: Autonics TK series PID temperature controller (Modbus RTU)
Read 301001-301008 with FC04 for PV, decimal point, SV and MV; write the setpoint to 400001 and use coil 0 for run/stop. Check 301002 to place the decimal point.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| IR 1000 | PV (present value) | INT16 | Process value | Read |
| IR 1001 | Decimal point location | UINT16 | Decimal point | Read |
| IR 1003 | SV setting value | INT16 | Active setpoint | Read |
| IR 1004 | Heating side MV | UINT16 | Heating output % | Read |
| HR 0 | SV set value | INT16 | Write setpoint | Read/write |
| CO 0 | RUN/STOP | BIT | Run/stop | Read/write |
Enable Modbus control & writes
Communication write (400224) must be Enabled (default) for Modbus writes.
Byte order & addressing
- PV reports 31000 for sensor open, 30000 / -30000 for over/under range.
- The bracketed hex is the wire address.
Network setup
- Address 1..99 (default 1), 2400-38400 bps (default 9600), parity none, 2 stop bits.
Watch out for
- Display values carry no fixed scale; Temp.L input types report one decimal place, so always apply the decimal point from 301002.
Autonics TK series PID temperature controller (Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| CO | 0doc 000001 (0000) | RUN/STOP | Control output run/stop. | BIT | Read/write | 0 = RUN; 1 = STOP | |||
| CO | 1doc 000002 (0001) | Auto-tuning execute | BIT | Read/write | 0 = OFF; 1 = ON | ||||
| DI | 0doc 100001 (0000) | °C unit indicator | BIT | Read | 0 = OFF; 1 = ON | ||||
| DI | 1doc 100002 (0001) | °F unit indicator | BIT | Read | 0 = OFF; 1 = ON | ||||
| DI | 2doc 100003 (0002) | % unit indicator | BIT | Read | 0 = OFF; 1 = ON | ||||
| DI | 3doc 100004 (0003) | OUT1 indicator | BIT | Read | 0 = OFF; 1 = ON | ||||
| DI | 4doc 100005 (0004) | OUT2 indicator | BIT | Read | 0 = OFF; 1 = ON | ||||
| DI | 5doc 100006 (0005) | AT indicator | BIT | Read | 0 = OFF; 1 = ON | ||||
| DI | 6doc 100007 (0006) | SV1 indicator | BIT | Read | 0 = OFF; 1 = ON | ||||
| DI | 7doc 100008 (0007) | SV2 indicator | BIT | Read | 0 = OFF; 1 = ON | ||||
| DI | 8doc 100009 (0008) | SV3 indicator | BIT | Read | 0 = OFF; 1 = ON | ||||
| DI | 9doc 100010 (0009) | AL1 indicator | BIT | Read | 0 = OFF; 1 = ON | ||||
| DI | 10doc 100011 (000A) | AL2 indicator | BIT | Read | 0 = OFF; 1 = ON | ||||
| DI | 11doc 100012 (000B) | MAN indicator | BIT | Read | 0 = OFF; 1 = ON | ||||
| DI | 12doc 100013 (000C) | DI-1 input | BIT | Read | 0 = OFF; 1 = ON | ||||
| DI | 13doc 100014 (000D) | DI-2 input | BIT | Read | 0 = OFF; 1 = ON | ||||
| IR | 100doc 300101 (0064) | Product number H | UINT16 | Read | |||||
| IR | 101doc 300102 (0065) | Product number L | UINT16 | Read | |||||
| IR | 102doc 300103 (0066) | Hardware version | UINT16 | Read | |||||
| IR | 103doc 300104 (0067) | Software version | UINT16 | Read | |||||
| IR | 104doc 300105-300114 (0068-0071) | Model name | ASCII model text, e.g. 'TK4 14RR'. | STRING[20] | Read | ||||
| IR | 1000doc 301001 (03E8) | PV (present value) | -1999..9999; Raw count; decimal point from 301002. | INT16 | Read | 30000 = HHHH (over range); 31000 = OPEN (sensor break); -30000 = LLLL (under range) | |||
| IR | 1001doc 301002 (03E9) | Decimal point location | UINT16 | Read | 0 = 0; 1 = 0.0; 2 = 0.00; 3 = 0.000 | ||||
| IR | 1002doc 301003 (03EA) | Indicator unit | UINT16 | Read | 0 = °C; 1 = °F; 2 = %; 3 = OFF | ||||
| IR | 1003doc 301004 (03EB) | SV setting value | Active setpoint. Raw count; decimal point from 301002. | INT16 | Read | ||||
| IR | 1004doc 301005 (03EC) | Heating side MV | 0..1000 = 0.0..100.0 %. | UINT16 | × 0.1 | % | Read | ||
| IR | 1005doc 301006 (03ED) | Cooling side MV | 0..1000 = 0.0..100.0 %. | UINT16 | × 0.1 | % | Read | ||
| IR | 1006doc 301007 (03EE) | Indicator / input status bits | BITMAP16 | Read | bit 0 = °C unit indicator; bit 1 = °F unit indicator; bit 2 = % unit indicator; bit 3 = OUT1 indicator; bit 4 = OUT2 indicator; bit 5 = AT indicator; bit 6 = SV1 indicator; bit 7 = SV2 indicator; bit 8 = SV3 indicator; bit 9 = AL1 indicator; bit 10 = AL2 indicator; bit 11 = MAN indicator; bit 12 = DI-1 input; bit 13 = DI-2 input | ||||
| HR | 0doc 400001 (0000) | SV set value | Within L-SV..H-SV. Raw count; decimal point from 301002. | INT16 | Read/write | ||||
| HR | 1doc 400002 (0001) | Heating MV (manual) | 0..1000 = 0.0..100.0 %. | UINT16 | × 0.1 | % | Read/write | ||
| HR | 2doc 400003 (0002) | Cooling MV (manual) | 0..1000 = 0.0..100.0 %. | UINT16 | × 0.1 | % | Read/write | ||
| HR | 3doc 400004 (0003) | Auto/Manual control | UINT16 | Read/write | 0 = AUTO; 1 = MAN | ||||
| HR | 50doc 400051 (0032) | R-S control output run/stop | UINT16 | Read/write | 0 = RUN; 1 = STOP | ||||
| HR | 51doc 400052 (0033) | SV-N multi SV number | UINT16 | Read/write | 0 = SV-0; 1 = SV-1; 2 = SV-2; 3 = SV-3 | ||||
| HR | 52doc 400053 (0034) | CT-A heater current monitoring | 0..500 = 0.0..50.0 A. | UINT16 | × 0.1 | A | Read/write | ||
| HR | 53doc 400054 (0035) | AL1.L alarm 1 low limit | Deviation or absolute value per alarm mode. Raw count; decimal point from 301002. | INT16 | Read/write | ||||
| HR | 54doc 400055 (0036) | AL1.H alarm 1 high limit | Deviation or absolute value per alarm mode. Raw count; decimal point from 301002. | INT16 | Read/write | ||||
| HR | 55doc 400056 (0037) | AL2.L alarm 2 low limit | Deviation or absolute value per alarm mode. Raw count; decimal point from 301002. | INT16 | Read/write | ||||
| HR | 56doc 400057 (0038) | AL2.H alarm 2 high limit | Deviation or absolute value per alarm mode. Raw count; decimal point from 301002. | INT16 | Read/write | ||||
| HR | 57doc 400058 (0039) | SV-0 set value | Multi-SV setpoint. Raw count; decimal point from 301002. | INT16 | Read/write | ||||
| HR | 58doc 400059 (003A) | SV-1 set value | Multi-SV setpoint. Raw count; decimal point from 301002. | INT16 | Read/write | ||||
| HR | 59doc 400060 (003B) | SV-2 set value | Multi-SV setpoint. Raw count; decimal point from 301002. | INT16 | Read/write | ||||
| HR | 60doc 400061 (003C) | SV-3 set value | Multi-SV setpoint. Raw count; decimal point from 301002. | INT16 | Read/write | ||||
| HR | 61doc 400062 (003D) | AL3.L alarm 3 low limit | Raw count; decimal point from 301002. | INT16 | Read/write | ||||
| HR | 62doc 400063 (003E) | AL3.H alarm 3 high limit | Raw count; decimal point from 301002. | INT16 | Read/write | ||||
| HR | 100doc 400101 (0064) | AT auto-tuning run/stop | UINT16 | Read/write | 0 = OFF; 1 = ON | ||||
| HR | 101doc 400102 (0065) | H-P heating proportional band | 1..9999 = 0.1..999.9 (°C/°F or %). | UINT16 | × 0.1 | Read/write | |||
| HR | 102doc 400103 (0066) | C-P cooling proportional band | 1..9999 = 0.1..999.9. | UINT16 | × 0.1 | Read/write | |||
| HR | 103doc 400104 (0067) | H-I heating integral time | UINT16 | s | Read/write | ||||
| HR | 104doc 400105 (0068) | C-I cooling integral time | UINT16 | s | Read/write | ||||
| HR | 105doc 400106 (0069) | H-D heating derivative time | UINT16 | s | Read/write | ||||
| HR | 106doc 400107 (006A) | C-D cooling derivative time | UINT16 | s | Read/write | ||||
| HR | 108doc 400109 (006C) | REST manual reset | 0..1000 = 0.0..100.0 %. | UINT16 | × 0.1 | % | Read/write | ||
| HR | 151doc 400152 (0097) | UNIT sensor temperature unit | UINT16 | Read/write | 0 = °C; 1 = °F | ||||
| HR | 157doc 400158 (009D) | D.UNT display unit | UINT16 | Read/write | 0 = °C; 1 = °F; 2 = %; 3 = OFF | ||||
| HR | 163doc 400164 (00A3) | C-MD control type | Standard: 0 PID, 1 ON/OFF. Heat&cool: 0 P.P, 1 P.ON, 2 ON.P, 3 ON.ON. | UINT16 | Read/write | ||||
| HR | 218doc 400219 (00DA) | ADRS communication address | 1..99. | UINT16 | Read/write | ||||
| HR | 219doc 400220 (00DB) | BPS communication speed | UINT16 | Read/write | 0 = 2400; 1 = 4800; 2 = 9600; 3 = 19200; 4 = 38400 | ||||
| HR | 220doc 400221 (00DC) | PRTY parity | UINT16 | Read/write | 0 = None; 1 = Even; 2 = Odd | ||||
| HR | 221doc 400222 (00DD) | STP stop bits | UINT16 | Read/write | 0 = 1; 1 = 2 | ||||
| HR | 222doc 400223 (00DE) | RSW.T response waiting time | 5..99 ms, default 20. | UINT16 | ms | Read/write | |||
| HR | 223doc 400224 (00DF) | COMW communication write | UINT16 | Read/write | 0 = Enabled; 1 = Disabled |
Notes on this map
- Autonics does not publish a static public link to this manual; this is the unaltered Autonics document hosted by distributor AutomationDirect.
- PV, SV, alarm limits and multi-SV values are signed display counts whose decimal point depends on the input type; read 301002 (decimal point) and scale accordingly. They are listed with scale 1.
- Default communication settings (address 1, 9600 bps, no parity, 2 stop bits, writes enabled) are the defaults printed in the communication parameter rows.
- Left out: hysteresis, dead band, OFF offset, input correction, scaling and alarm-mode registers whose scale depends on the input range, plus the input-type code table.
- Registers 400301-400330 are the user-parameter group (copies of chosen parameters).
- Left out: heater current monitoring input register 301008, because the manual prints only the display range 0.0..50.0 and not the raw value scaling.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Autonics TK series PID temperature controller (Modbus RTU)
What Modbus registers does the Autonics TK series PID temperature controller (Modbus RTU) have?
This map lists 62 registers: 2 coils, 14 discrete inputs, 12 input registers, 34 holding registers. 36 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Autonics TK series PID temperature controller (Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Rows print a 6-digit reference (000001/100001/300001/400001 style) and the hex protocol address in brackets, e.g. 301001 (03E8); the bracketed hex value is the wire address.
What are the minimum Modbus registers to integrate the Autonics TK series PID temperature controller (Modbus RTU)?
Start with IR 1000 PV (present value) (Process value); IR 1001 Decimal point location (Decimal point); IR 1003 SV setting value (Active setpoint); IR 1004 Heating side MV (Heating output %); HR 0 SV set value (Write setpoint); CO 0 RUN/STOP (Run/stop).
How do I enable Modbus control of the Autonics TK series PID temperature controller (Modbus RTU)?
Communication write (400224) must be Enabled (default) for Modbus writes.
Where is the official Autonics TK series PID temperature controller (Modbus RTU) Modbus documentation?
The source is TK Series Communication Manual (Simultaneous Heating & Cooling Output PID Temperature Controllers) (MCT-TKC1-V2.2-EN). Autonics doesn't publish it on its own website, so this map was re-typed from a free copy at https://cdn.automationdirect.com/static/manuals/autonics/autonicstkcommunicationsmanual.pdf. It may be an older revision, so check it against the live unit.
More Autonics Modbus register maps
Other temperature & process controllers register maps
- Sensor (modular temperature controller)
RKC Instrument SRX module type controller, TIO temperature control module (Modbus RTU)
RKC SRX two-channel temperature control (TIO) modules, basic type X-TIO-A and extension type X-TIO-B, with Modbus selected; DI and DO module maps are not included.
Also known as: SRX, X-TIO-A, X-TIO-B, SRX TIO module, RKC SRX - Sensor (digital temperature controller)
Shinko Technos FC series digital indicating controller (C/C5 option, Modbus ASCII)
Shinko FCS-23A, FCR-13A, FCR-23A and FCD-13A with the C or C5 serial option; FCR-15A and FCD-15A have no Modbus (Shinko protocol only). Manual No.FC1CE11.
Also known as: FCS-23A, FCR-13A, FCR-23A, FCD-13A - Sensor (digital temperature controller)
Shinko Technos WCL-13A 2-channel digital indicating controller (C5 option)
Shinko WCL-13A two-loop controller with the C5 option; communication manual No.WCL1CE3.
Also known as: WCL-13A-C5, WCL-13A C5 - Sensor (modular temperature controller)
RKC Instrument SRV module type controller, TIO temperature control module (Modbus RTU)
RKC SRV two-channel temperature control (TIO) modules, basic and extension type, with Modbus selected.
Also known as: SRV, SRV TIO module, RKC SRV - Sensor (digital temperature controller)
Shinko Technos DCL-33A digital indicating controller (C5 option)
Shinko DCL-33A with the C5 serial option, plain (non-block) Modbus protocol setting; manual No.DCL32CE3.
Also known as: DCL-33A-C5, DCL-33A C5 - Sensor (digital temperature controller)
Shinko Technos PCD-33A programmable controller (C5 option)
Shinko PCD-33A program controller with the C5 RS-485 option; manual printed No.PCD3CE1 2003.02 (file PCD3CE2).
Also known as: PCD-33A-R/M, PCD-33A-S/M
All temperature & process controllers Modbus register maps →
Source: TK Series Communication Manual (Simultaneous Heating & Cooling Output PID Temperature Controllers) · MCT-TKC1-V2.2-EN · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.