- SRV module type controller, TIO temperature control module (Modbus RTU)
Sensor (modular temperature controller) · Modbus register map
RKC Instrument SRV module type controller, TIO temperature control module (Modbus RTU) Modbus register map
Updated 19 November 2026
The SRV is a DIN-rail modular controller whose TIO modules each run two heat or heat/cool PID loops; extension modules share the bus of a basic module. With DIP switch 6 set to Modbus, each module answers Modbus RTU on RS-485 with channel 1 data at 0000H and channel 2 data at 1000H. This map covers measured values, events, setpoints, PID, manual output, module DI/DO and the key input setup items.
This page lists 98 Modbus registers for the RKC Instrument SRV module type controller, TIO temperature control module (Modbus RTU) — 72 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from RKC Instrument’s own free documentation (linked below) and checked against it.
- Manufacturer
- RKC Instrument
- Model
- SRV module type controller, TIO temperature control module (Modbus RTU)
- Equipment type
- Sensor (modular temperature controller)
- Registers
- 98 (72 writable)
- Transport
- Modbus RTU
- Default unit ID
- 1
- Default serial
- 38400 baud, 8N1
- Documented addressing
- hexadecimal, 0-based
- Also known as
- SRV, SRV TIO module, RKC SRV
Integration notes: RKC Instrument SRV module type controller, TIO temperature control module (Modbus RTU)
Set DIP switch 6 ON (Modbus) and the rotary address, then read 0000H-0006H for CH1 PV, event state, outputs and SV monitor (1000H onward for CH2). Write the setpoint to 0010H/1010H and start control with 0030H = 1.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 0 | Measured value (PV) (CH1) | INT16 | CH1 measured value | Read |
| HR 1 | Comprehensive event state (CH1) | BITMAP16 | CH1 event state | Read |
| HR 2 | Heat-side manipulated output value (CH1) | INT16 | CH1 heat-side output | Read |
| HR 16 | Set value (SV) (CH1) | INT16 | CH1 set value | Read/write |
| HR 48 | Control RUN/STOP transfer (module) | UINT16 | Control RUN/STOP | Read/write |
| HR 4096 | Measured value (PV) (CH2) | INT16 | CH2 measured value | Read |
| HR 4112 | Set value (SV) (CH2) | INT16 | CH2 set value | Read/write |
Enable Modbus control & writes
The protocol is set when ordering but can be changed with DIP switch 6 (ON = Modbus). Speed is set by DIP switches 1-2, data/parity by 3-5; changes apply after power-up or a RUN/STOP change.
Byte order & addressing
- The Modbus slave address is the rotary switch setting plus 1 (switch 00 = slave 1).
- Each module (slave address) carries at most two channels.
- With a data error part-way through a multi-write, the values before the error still take effect.
Network setup
- Factory DIP settings for Modbus: 38400 bps, 8 data bits, no parity, 1 stop bit (fixed). Speeds 2400-38400 bps.
- Give the basic TIO module the lowest address when extension modules share its bus. DIP switches 7 and 8 stay OFF.
Watch out for
- Wait 30 bit times after a response before the next request.
- Do not write to addresses not in the data map; items for functions that are not fitted return no error response.
RKC Instrument SRV module type controller, TIO temperature control module (Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0doc 0000 | Measured value (PV) (CH1) | Raw integer; decimals follow the input range (0873H for voltage/current inputs). | INT16 | Read | ||||
| HR | 1doc 0001 | Comprehensive event state (CH1) | BITMAP16 | Read | bit 0 = Burnout; bit 1 = Event 1; bit 2 = Event 2; bit 3 = Heater break alarm; bit 4 = Control loop break alarm (LBA) | ||||
| HR | 2doc 0002 | Heat-side manipulated output value (CH1) | -5.0 to +105.0 %. | INT16 | × 0.1 | % | Read | ||
| HR | 3doc 0003 | Set value monitor (CH1) | Raw integer; decimals follow the input range (0873H for voltage/current inputs). | INT16 | Read | ||||
| HR | 4doc 0004 | Error code (module) | BITMAP16 | Read | bit 0 = Memory backup error; bit 2 = Internal communication error; bit 3 = Adjustment data error; bit 4 = Input error; bit 5 = Current transformer input error; bit 6 = Temperature compensation error | ||||
| HR | 5doc 0005 | Cool-side manipulated output value (CH1) | -5.0 to +105.0 %. | INT16 | × 0.1 | % | Read | ||
| HR | 6doc 0006 | Current transformer input measured value (CH1) | 0.0 to 30.0 A or 0.0 to 100.0 A depending on CT. | INT16 | × 0.1 | A | Read | ||
| HR | 8doc 0008 | Burnout state (CH1) | UINT16 | Read | 0 = OFF; 1 = ON | ||||
| HR | 9doc 0009 | Event 1 state (CH1) | UINT16 | Read | 0 = OFF; 1 = ON | ||||
| HR | 10doc 000A | Event 2 state (CH1) | UINT16 | Read | 0 = OFF; 1 = ON | ||||
| HR | 11doc 000B | Heater break alarm (HBA) state (CH1) | UINT16 | Read | 0 = OFF; 1 = Heater break; 2 = Relay welding | ||||
| HR | 12doc 000C | Control loop break alarm (LBA) state (CH1) | UINT16 | Read | 0 = OFF; 1 = ON | ||||
| HR | 13doc 000D | Temperature rise completion state (CH1) | UINT16 | Read | 0 = Not complete; 1 = Temperature rise complete | ||||
| HR | 15doc 000F | Operation mode (CH1) | UINT16 | Read/write | 0 = Unused; 1 = Monitor 1; 2 = Monitor 2; 3 = Control | ||||
| HR | 16doc 0010 | Set value (SV) (CH1) | Raw integer; decimals follow the input range (0873H for voltage/current inputs). | INT16 | Read/write | ||||
| HR | 17doc 0011 | Heat-side proportional band (CH1) | 0 = ON/OFF action. Decimal places follow the input range; V/I inputs are in % of span. | INT16 | Read/write | ||||
| HR | 18doc 0012 | Integral time (CH1) | 1 to 3600 s. | UINT16 | s | Read/write | |||
| HR | 19doc 0013 | Derivative time (CH1) | 0 to 3600 s; 0 = PI action. | UINT16 | s | Read/write | |||
| HR | 20doc 0014 | Control response parameters (CH1) | UINT16 | Read/write | 0 = Slow; 1 = Medium; 2 = Fast | ||||
| HR | 21doc 0015 | PV bias (CH1) | Raw integer; decimals follow the input range (0873H for voltage/current inputs). | INT16 | Read/write | ||||
| HR | 22doc 0016 | Event 1 set value (CH1) | Raw integer; decimals follow the input range (0873H for voltage/current inputs). | INT16 | Read/write | ||||
| HR | 23doc 0017 | Event 2 set value (CH1) | Raw integer; decimals follow the input range (0873H for voltage/current inputs). | INT16 | Read/write | ||||
| HR | 28doc 001C | Cool-side proportional band (CH1) | Decimal places follow the input range; V/I inputs are in % of span. | INT16 | Read/write | ||||
| HR | 30doc 001E | Overlap/Deadband (CH1) | Raw integer; decimals follow the input range (0873H for voltage/current inputs). | INT16 | Read/write | ||||
| HR | 31doc 001F | Setting change rate limiter (CH1) | Input span per minute, 0 = off; decimal places follow the input range. | INT16 | Read/write | ||||
| HR | 32doc 0020 | PID/AT transfer (CH1) | UINT16 | Read/write | 0 = PID control; 1 = Autotuning (AT) | ||||
| HR | 33doc 0021 | Auto/Manual transfer (CH1) | UINT16 | Read/write | 0 = Auto; 1 = Manual | ||||
| HR | 34doc 0022 | Manual output value (CH1) | -5.0 to +105.0 %. | INT16 | × 0.1 | % | Read/write | ||
| HR | 35doc 0023 | Output limiter (high) (CH1) | Output limiter (low) to 105.0 %. | INT16 | × 0.1 | % | Read/write | ||
| HR | 36doc 0024 | Output limiter (low) (CH1) | -5.0 % to output limiter (high). | INT16 | × 0.1 | % | Read/write | ||
| HR | 37doc 0025 | Heat-side proportional cycle time (CH1) | 1 to 100 s. | UINT16 | s | Read/write | |||
| HR | 38doc 0026 | Cool-side proportional cycle time (CH1) | 1 to 100 s. | UINT16 | s | Read/write | |||
| HR | 39doc 0027 | Digital filter (CH1) | 0 to 100 s; 0 = off. | UINT16 | s | Read/write | |||
| HR | 40doc 0028 | Heater break alarm (HBA) set value (CH1) | 0.0 to 30.0 A or 0.0 to 100.0 A. | UINT16 | × 0.1 | A | Read/write | ||
| HR | 48doc 0030 | Control RUN/STOP transfer (module) | UINT16 | Read/write | 0 = Control STOP; 1 = Control RUN | ||||
| HR | 53doc 0035 | Manipulated output value at input error (CH1) | -105.0 to +105.0 %. | INT16 | × 0.1 | % | Read/write | ||
| HR | 62doc 003E | DI state (module) | UINT16 | Read | 0 = Contact open (OFF); 1 = Contact closed (ON) | ||||
| HR | 65doc 0041 | DO state (module) | Writable only when DO1 and DO2 settings are 0. | UINT16 | Read/write | 0 = DO1 open, DO2 open; 1 = DO1 closed, DO2 open; 2 = DO1 open, DO2 closed; 3 = DO1 closed, DO2 closed | |||
| HR | 66doc 0042 | Event interlock release (module) | UINT16 | Read/write | 0 = Normal state; 1 = Execute interlock release | ||||
| HR | 67doc 0043 | Temperature rise completion zone (CH1) | 0 = unused. Raw integer; decimals follow the input range (0873H for voltage/current inputs). | INT16 | Read/write | ||||
| HR | 68doc 0044 | Temperature rise completion soak time (CH1) | 0 to 360 min. | UINT16 | min | Read/write | |||
| HR | 2137doc 0859 | Control loop break alarm (LBA) use selection (CH1) | UINT16 | Read/write | 0 = Unused; 1 = Used | ||||
| HR | 2138doc 085A | Control loop break alarm (LBA) time (CH1) | 1 to 7200 s. | UINT16 | s | Read/write | |||
| HR | 2144doc 0860 | Initial setting mode (module) | Stop control before entering initial setting mode. | UINT16 | Read/write | 0 = Normal setting mode; 1 = Initial setting mode | |||
| HR | 2160doc 0870 | Input range number (CH1) | Input type code 0-37, e.g. 0 = type K, 23 = Pt100, 37 = 4-20 mA. | UINT16 | Read/write | ||||
| HR | 2161doc 0871 | Input scale high limit (CH1) | Voltage/current input only. Raw integer; decimals follow the input range (0873H for voltage/current inputs). | INT16 | Read/write | ||||
| HR | 2162doc 0872 | Input scale low limit (CH1) | Voltage/current input only. Raw integer; decimals follow the input range (0873H for voltage/current inputs). | INT16 | Read/write | ||||
| HR | 2163doc 0873 | Input range decimal point position (CH1) | Voltage/current input only. | UINT16 | Read/write | 0 = No decimal place; 1 = One decimal place; 2 = Two decimal places; 3 = Three decimal places | |||
| HR | 2164doc 0874 | Temperature unit selection (CH1) | UINT16 | Read/write | 0 = °C; 1 = °F | ||||
| HR | 2165doc 0875 | Control type selection (CH1) | UINT16 | Read/write | 0 = Heat control, direct action; 1 = Heat control, reverse action; 2 = Heat/cool control, water cooling; 3 = Heat/cool control, air cooling | ||||
| HR | 2170doc 087A | Event 1 type selection (CH1) | UINT16 | Read/write | 0 = Not provided; 1 = Process high; 2 = Process low; 3 = Deviation high; 4 = Deviation low; 5 = Deviation high/low; 6 = Band | ||||
| HR | 2171doc 087B | Event 2 type selection (CH1) | UINT16 | Read/write | 0 = Not provided; 1 = Process high; 2 = Process low; 3 = Deviation high; 4 = Deviation low; 5 = Deviation high/low; 6 = Band | ||||
| HR | 4096doc 1000 | Measured value (PV) (CH2) | Raw integer; decimals follow the input range (0873H for voltage/current inputs). | INT16 | Read | ||||
| HR | 4097doc 1001 | Comprehensive event state (CH2) | BITMAP16 | Read | bit 0 = Burnout; bit 1 = Event 1; bit 2 = Event 2; bit 3 = Heater break alarm; bit 4 = Control loop break alarm (LBA) | ||||
| HR | 4098doc 1002 | Heat-side manipulated output value (CH2) | -5.0 to +105.0 %. | INT16 | × 0.1 | % | Read | ||
| HR | 4099doc 1003 | Set value monitor (CH2) | Raw integer; decimals follow the input range (0873H for voltage/current inputs). | INT16 | Read | ||||
| HR | 4101doc 1005 | Cool-side manipulated output value (CH2) | -5.0 to +105.0 %. | INT16 | × 0.1 | % | Read | ||
| HR | 4102doc 1006 | Current transformer input measured value (CH2) | 0.0 to 30.0 A or 0.0 to 100.0 A depending on CT. | INT16 | × 0.1 | A | Read | ||
| HR | 4104doc 1008 | Burnout state (CH2) | UINT16 | Read | 0 = OFF; 1 = ON | ||||
| HR | 4105doc 1009 | Event 1 state (CH2) | UINT16 | Read | 0 = OFF; 1 = ON | ||||
| HR | 4106doc 100A | Event 2 state (CH2) | UINT16 | Read | 0 = OFF; 1 = ON | ||||
| HR | 4107doc 100B | Heater break alarm (HBA) state (CH2) | UINT16 | Read | 0 = OFF; 1 = Heater break; 2 = Relay welding | ||||
| HR | 4108doc 100C | Control loop break alarm (LBA) state (CH2) | UINT16 | Read | 0 = OFF; 1 = ON | ||||
| HR | 4109doc 100D | Temperature rise completion state (CH2) | UINT16 | Read | 0 = Not complete; 1 = Temperature rise complete | ||||
| HR | 4111doc 100F | Operation mode (CH2) | UINT16 | Read/write | 0 = Unused; 1 = Monitor 1; 2 = Monitor 2; 3 = Control | ||||
| HR | 4112doc 1010 | Set value (SV) (CH2) | Raw integer; decimals follow the input range (0873H for voltage/current inputs). | INT16 | Read/write | ||||
| HR | 4113doc 1011 | Heat-side proportional band (CH2) | 0 = ON/OFF action. Decimal places follow the input range; V/I inputs are in % of span. | INT16 | Read/write | ||||
| HR | 4114doc 1012 | Integral time (CH2) | 1 to 3600 s. | UINT16 | s | Read/write | |||
| HR | 4115doc 1013 | Derivative time (CH2) | 0 to 3600 s; 0 = PI action. | UINT16 | s | Read/write | |||
| HR | 4116doc 1014 | Control response parameters (CH2) | UINT16 | Read/write | 0 = Slow; 1 = Medium; 2 = Fast | ||||
| HR | 4117doc 1015 | PV bias (CH2) | Raw integer; decimals follow the input range (0873H for voltage/current inputs). | INT16 | Read/write | ||||
| HR | 4118doc 1016 | Event 1 set value (CH2) | Raw integer; decimals follow the input range (0873H for voltage/current inputs). | INT16 | Read/write | ||||
| HR | 4119doc 1017 | Event 2 set value (CH2) | Raw integer; decimals follow the input range (0873H for voltage/current inputs). | INT16 | Read/write | ||||
| HR | 4124doc 101C | Cool-side proportional band (CH2) | Decimal places follow the input range; V/I inputs are in % of span. | INT16 | Read/write | ||||
| HR | 4126doc 101E | Overlap/Deadband (CH2) | Raw integer; decimals follow the input range (0873H for voltage/current inputs). | INT16 | Read/write | ||||
| HR | 4127doc 101F | Setting change rate limiter (CH2) | Input span per minute, 0 = off; decimal places follow the input range. | INT16 | Read/write | ||||
| HR | 4128doc 1020 | PID/AT transfer (CH2) | UINT16 | Read/write | 0 = PID control; 1 = Autotuning (AT) | ||||
| HR | 4129doc 1021 | Auto/Manual transfer (CH2) | UINT16 | Read/write | 0 = Auto; 1 = Manual | ||||
| HR | 4130doc 1022 | Manual output value (CH2) | -5.0 to +105.0 %. | INT16 | × 0.1 | % | Read/write | ||
| HR | 4131doc 1023 | Output limiter (high) (CH2) | Output limiter (low) to 105.0 %. | INT16 | × 0.1 | % | Read/write | ||
| HR | 4132doc 1024 | Output limiter (low) (CH2) | -5.0 % to output limiter (high). | INT16 | × 0.1 | % | Read/write | ||
| HR | 4133doc 1025 | Heat-side proportional cycle time (CH2) | 1 to 100 s. | UINT16 | s | Read/write | |||
| HR | 4134doc 1026 | Cool-side proportional cycle time (CH2) | 1 to 100 s. | UINT16 | s | Read/write | |||
| HR | 4135doc 1027 | Digital filter (CH2) | 0 to 100 s; 0 = off. | UINT16 | s | Read/write | |||
| HR | 4136doc 1028 | Heater break alarm (HBA) set value (CH2) | 0.0 to 30.0 A or 0.0 to 100.0 A. | UINT16 | × 0.1 | A | Read/write | ||
| HR | 4149doc 1035 | Manipulated output value at input error (CH2) | -105.0 to +105.0 %. | INT16 | × 0.1 | % | Read/write | ||
| HR | 4163doc 1043 | Temperature rise completion zone (CH2) | 0 = unused. Raw integer; decimals follow the input range (0873H for voltage/current inputs). | INT16 | Read/write | ||||
| HR | 4164doc 1044 | Temperature rise completion soak time (CH2) | 0 to 360 min. | UINT16 | min | Read/write | |||
| HR | 6233doc 1859 | Control loop break alarm (LBA) use selection (CH2) | UINT16 | Read/write | 0 = Unused; 1 = Used | ||||
| HR | 6234doc 185A | Control loop break alarm (LBA) time (CH2) | 1 to 7200 s. | UINT16 | s | Read/write | |||
| HR | 6256doc 1870 | Input range number (CH2) | Input type code 0-37, e.g. 0 = type K, 23 = Pt100, 37 = 4-20 mA. | UINT16 | Read/write | ||||
| HR | 6257doc 1871 | Input scale high limit (CH2) | Voltage/current input only. Raw integer; decimals follow the input range (0873H for voltage/current inputs). | INT16 | Read/write | ||||
| HR | 6258doc 1872 | Input scale low limit (CH2) | Voltage/current input only. Raw integer; decimals follow the input range (0873H for voltage/current inputs). | INT16 | Read/write | ||||
| HR | 6259doc 1873 | Input range decimal point position (CH2) | Voltage/current input only. | UINT16 | Read/write | 0 = No decimal place; 1 = One decimal place; 2 = Two decimal places; 3 = Three decimal places | |||
| HR | 6260doc 1874 | Temperature unit selection (CH2) | UINT16 | Read/write | 0 = °C; 1 = °F | ||||
| HR | 6261doc 1875 | Control type selection (CH2) | UINT16 | Read/write | 0 = Heat control, direct action; 1 = Heat control, reverse action; 2 = Heat/cool control, water cooling; 3 = Heat/cool control, air cooling | ||||
| HR | 6266doc 187A | Event 1 type selection (CH2) | UINT16 | Read/write | 0 = Not provided; 1 = Process high; 2 = Process low; 3 = Deviation high; 4 = Deviation low; 5 = Deviation high/low; 6 = Band | ||||
| HR | 6267doc 187B | Event 2 type selection (CH2) | UINT16 | Read/write | 0 = Not provided; 1 = Process high; 2 = Process low; 3 = Deviation high; 4 = Deviation low; 5 = Deviation high/low; 6 = Band |
Notes on this map
- RKC's own download center does not offer this manual publicly; the linked copy is the unaltered RKC manual hosted by a US distributor (a distributor stamp on the cover only).
- All registers are 16-bit; FFFFH is -1. Values are sent without a decimal point: PV/SV-type items follow the input range (temperature ranges with or without one decimal, or the 0873H setting for voltage/current inputs); other items have the fixed decimals shown (scale).
- Items marked (module) exist once per module (channel 1 address only); all others repeat for channel 2 at +1000H.
- DI/DO function settings, input error actions, AT bias, differential gaps and event action bits are left out.
- Initial-setting items (0870H onward) can only be written in initial setting mode (0860H = 1), which needs control stopped (0030H = 0).
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the RKC Instrument SRV module type controller, TIO temperature control module (Modbus RTU)
What Modbus registers does the RKC Instrument SRV module type controller, TIO temperature control module (Modbus RTU) have?
This map lists 98 registers: 98 holding registers. 72 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the RKC Instrument SRV module type controller, TIO temperature control module (Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The data map prints each register in hex and decimal; the value is the address sent on the wire. The manual's read example asks for 0000H-0002H, so 0000H is a real register (CH1 measured value).
What are the minimum Modbus registers to integrate the RKC Instrument SRV module type controller, TIO temperature control module (Modbus RTU)?
Start with HR 0 Measured value (PV) (CH1) (CH1 measured value); HR 1 Comprehensive event state (CH1) (CH1 event state); HR 2 Heat-side manipulated output value (CH1) (CH1 heat-side output); HR 16 Set value (SV) (CH1) (CH1 set value); HR 48 Control RUN/STOP transfer (module) (Control RUN/STOP); HR 4096 Measured value (PV) (CH2) (CH2 measured value); HR 4112 Set value (SV) (CH2) (CH2 set value).
How do I enable Modbus control of the RKC Instrument SRV module type controller, TIO temperature control module (Modbus RTU)?
The protocol is set when ordering but can be changed with DIP switch 6 (ON = Modbus). Speed is set by DIP switches 1-2, data/parity by 3-5; changes apply after power-up or a RUN/STOP change.
Where is the official RKC Instrument SRV module type controller, TIO temperature control module (Modbus RTU) Modbus documentation?
The source is SRV Communication Instruction Manual (Module Type Controller) (IMS01P01-E7). RKC Instrument doesn't publish it on its own website, so this map was re-typed from a free copy at https://flw.com/rkc/pdf/ims01p01e7.pdf. It may be an older revision, so check it against the live unit.
More RKC Instrument Modbus register maps
Other temperature & process controllers register maps
- Sensor (digital temperature controller)
Shinko Technos DCL-33A digital indicating controller (C5 option)
Shinko DCL-33A with the C5 serial option, plain (non-block) Modbus protocol setting; manual No.DCL32CE3.
Also known as: DCL-33A-C5, DCL-33A C5 - Sensor (digital temperature controller)
Shinko Technos PCD-33A programmable controller (C5 option)
Shinko PCD-33A program controller with the C5 RS-485 option; manual printed No.PCD3CE1 2003.02 (file PCD3CE2).
Also known as: PCD-33A-R/M, PCD-33A-S/M - Process controller (sensor / PID controller)
ABB Protronic 100/500/550 and Digitric 500 process controllers (Modbus RTU)
ABB Protronic 100/500/550 and Digitric 500 universal process controllers with the RS-485/RS-232 Modbus interface module, interface description 42/62-50040 EN Rev. 04.
Also known as: Protronic 100, Protronic 500, Protronic 550, Digitric 500 - Sensor / multi-input controller
ProMinent DULCOMETER AEGIS II controller (Modbus RTU slave)
AEGIS II controllers fitted with the COM module (Modbus RTU slave on XB21/XB22), per manual BA DM 229 08/18.
Also known as: AEGIS II, Aegis II, DULCOMETER AEGIS II, AEGIS II COM module - Sensor (digital temperature controller)
Shinko Technos DCL-33A DC digital indicating controller (C5 option)
Shinko DCL-33A DC with the C5 option; communication manual No.DCL3CDCE2.
Also known as: DCL-33A DC, DCL-33A-DC-C5 - Sensor (programmable temperature controller)
Shinko Technos PCB1 programmable controller (C5W/C5 option)
Shinko PCB1 programmable controllers with the C5W or C5 RS-485 option, native PCB1 command set; manual No. PCB1CE3.
Also known as: PCB1
All temperature & process controllers Modbus register maps →
Source: SRV Communication Instruction Manual (Module Type Controller) · IMS01P01-E7 · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.