- PCD-33A programmable controller (C5 option)
Sensor (digital temperature controller) · Modbus register map
Shinko Technos PCD-33A programmable controller (C5 option) Modbus register map
Updated 17 November 2026
The PCD-33A is a 9-pattern, 9-step ramp/soak temperature controller. With the C5 option it speaks Shinko protocol or Modbus ASCII/RTU on RS-485, one 16-bit holding register per request. The map covers every pattern/step SV, time and wait flag, per-pattern wait, alarm and time-signal values, PID and alarm settings, run/stop and advance commands, PV, MV, current SV, running pattern/step and status.
This page lists 329 Modbus registers for the Shinko Technos PCD-33A programmable controller (C5 option) — 321 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Shinko Technos’s own free documentation (linked below) and checked against it.
- Manufacturer
- Shinko Technos
- Model
- PCD-33A programmable controller (C5 option)
- Equipment type
- Sensor (digital temperature controller)
- Registers
- 329 (321 writable)
- Transport
- Modbus RTU, Modbus ASCII
- Default unit ID
- Not stated
- Default serial
- 9600 baud
- Documented addressing
- hexadecimal, 0-based
- Also known as
- PCD-33A-R/M, PCD-33A-S/M
Integration notes: Shinko Technos PCD-33A programmable controller (C5 option)
Select Modbus RTU (or ASCII) in Auxiliary function setting mode 1, set instrument number and speed, then read PV 0080H, current SV 0083H, running pattern/step 0085H and status 0086H; start and stop the program with 0042H.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 128 | PV | INT16 | Process value | Read |
| HR 131 | Current SV | INT16 | Current program SV | Read |
| HR 133 | Running pattern and step | INT16 | Running pattern and step | Read |
| HR 134 | Instrument status | BITMAP16 | Run, alarm and error status | Read |
| HR 66 | Program run Perform/Stop | INT16 | Run/stop the program | Write |
| HR 63 | Running pattern number | INT16 | Select pattern to run | Read/write |
| HR 4368 | P1 step 1 SV | INT16 | Pattern 1 step 1 SV | Read/write |
Enable Modbus control & writes
Requires the C5 option. Choose the Modbus protocol, instrument number and speed in Auxiliary function setting mode 1 on the keypad.
Byte order & addressing
- Modbus is not available through Shinko's IF-300-C5 converter; use a generic RS-232C/RS-485 converter.
- Slave address range 0-95; address 0 is broadcast (no reply).
Network setup
- Speeds 2400, 4800, 9600 (default) or 19200 bps; data 7 or 8 bits, parity even/odd/none, 1 or 2 stop bits.
- Do not add a terminator: the unit has built-in pull-up/pull-down resistors.
Watch out for
- Changing an alarm action type resets that alarm's values; send the type first.
- Exception 17 (11H) means the item cannot be set in the present state; 18 (12H) means the keypad is in setting mode.
Shinko Technos PCD-33A programmable controller (C5 option) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 2doc 0002H | Proportional band | INT16 | Read/write | |||||
| HR | 3doc 0003H | Integral time | INT16 | Read/write | |||||
| HR | 4doc 0004H | Derivative time | INT16 | Read/write | |||||
| HR | 5doc 0005H | Anti-reset windup (ARW) | INT16 | Read/write | |||||
| HR | 14doc 000EH | PID auto-tuning Perform/Cancel | INT16 | Read/write | 0 = Cancel; 1 = Perform | ||||
| HR | 15doc 000FH | A1 action selection | Changing it resets the A1 values. | INT16 | Read/write | 0 = No alarm action; 1 = High limit alarm; 2 = Low limit alarm; 3 = High/Low limits alarm; 4 = High/Low limit range alarm; 5 = Process high alarm; 6 = Process low alarm; 7 = High limit alarm with standby; 8 = Low limit alarm with standby; 9 = High/Low limits alarm with standby | |||
| HR | 16doc 0010H | A2 action selection | Changing it resets the A2 values. | INT16 | Read/write | 0 = No alarm action; 1 = High limit alarm; 2 = Low limit alarm; 3 = High/Low limits alarm; 4 = High/Low limit range alarm; 5 = Process high alarm; 6 = Process low alarm; 7 = High limit alarm with standby; 8 = Low limit alarm with standby; 9 = High/Low limits alarm with standby | |||
| HR | 17doc 0011H | A1 hysteresis | INT16 | Read/write | |||||
| HR | 18doc 0012H | A2 hysteresis | INT16 | Read/write | |||||
| HR | 21doc 0015H | A1 action delay timer | INT16 | Read/write | |||||
| HR | 22doc 0016H | A2 action delay timer | INT16 | Read/write | |||||
| HR | 27doc 001BH | Proportional cycle | INT16 | Read/write | |||||
| HR | 28doc 001CH | Control output high limit | INT16 | Read/write | |||||
| HR | 29doc 001DH | Control output low limit | INT16 | Read/write | |||||
| HR | 30doc 001EH | Control output ON/OFF hysteresis | INT16 | Read/write | |||||
| HR | 39doc 0027H | SV high limit | Raw integer; apply the decimal point (keypad setting). | INT16 | Read/write | ||||
| HR | 40doc 0028H | SV low limit | Raw integer; apply the decimal point (keypad setting). | INT16 | Read/write | ||||
| HR | 47doc 002FH | Sensor correction | INT16 | Read/write | |||||
| HR | 48doc 0030H | PV filter time constant | INT16 | Read/write | |||||
| HR | 49doc 0031H | Set value lock | INT16 | Read/write | 0 = Unlock; 1 = Lock | ||||
| HR | 50doc 0032H | Step SV when control starts | Raw integer; apply the decimal point (keypad setting). | INT16 | Read/write | ||||
| HR | 51doc 0033H | Program control start form | INT16 | Read/write | 0 = PV start; 1 = SV start | ||||
| HR | 53doc 0035H | Step time unit | INT16 | Read/write | 0 = Hour:Minute; 1 = Minute:Second | ||||
| HR | 56doc 0038H | Pattern end output time | INT16 | Read/write | |||||
| HR | 59doc 003BH | Event output function | INT16 | Read/write | 0 = Time signal output; 1 = Pattern end output; 2 = Run output | ||||
| HR | 63doc 003FH | Running pattern number | Pattern 1 to 9. | INT16 | Read/write | ||||
| HR | 66doc 0042H | Program run Perform/Stop | Write-only (function 06). | INT16 | Write | 0 = Stop; 1 = Perform | |||
| HR | 67doc 0043H | Advance function Perform | Write-only; skips to the next step. | INT16 | Write | 1 = Perform | |||
| HR | 68doc 0044H | Input type | INT16 | Read/write | 0 = K -200 to 1370 C; 1 = K -199.9 to 400.0 C; 2 = J -200 to 1000 C; 3 = R 0 to 1760 C; 4 = S 0 to 1760 C; 5 = B 0 to 1820 C; 6 = E -200 to 800 C; 7 = T -199.9 to 400.0 C; 8 = N -200 to 1300 C; 9 = PL-II 0 to 1390 C; 10 = C (W/Re5-26) 0 to 2315 C; 11 = Pt100 -199.9 to 850.0 C; 12 = JPt100 -199.9 to 500.0 C; 13 = Pt100 -200 to 850 C; 14 = JPt100 -200 to 500 C; 15 = K -320 to 2500 F; 16 = K -199.9 to 750.0 F; 17 = J -320 to 1800 F; 18 = R 0 to 3200 F; 19 = S 0 to 3200 F; 20 = B 0 to 3300 F; 21 = E -320 to 1500 F; 22 = T -199.9 to 750.0 F; 23 = N -320 to 2300 F; 24 = PL-II 0 to 2500 F; 25 = C (W/Re5-26) 0 to 4200 F; 26 = Pt100 -199.9 to 999.9 F; 27 = JPt100 -199.9 to 900.0 F; 28 = Pt100 -300 to 1500 F; 29 = JPt100 -300 to 900 F; 30 = 4-20 mA DC (-1999 to 9999); 31 = 0-20 mA DC (-1999 to 9999); 32 = 0-1 V DC (-1999 to 9999); 33 = 0-5 V DC (-1999 to 9999); 34 = 1-5 V DC (-1999 to 9999); 35 = 0-10 V DC (-1999 to 9999) | ||||
| HR | 69doc 0045H | Direct/Reverse action | INT16 | Read/write | 0 = Heating (reverse); 1 = Cooling (direct) | ||||
| HR | 72doc 0048H | A1 energized/de-energized | INT16 | Read/write | 0 = Energized; 1 = De-energized | ||||
| HR | 73doc 0049H | A2 energized/de-energized | INT16 | Read/write | 0 = Energized; 1 = De-energized | ||||
| HR | 112doc 0070H | Key operation change flag clearing | INT16 | Write | 0 = No action; 1 = Clear all | ||||
| HR | 128doc 0080H | PV | Process value. Raw integer; apply the decimal point (keypad setting). | INT16 | Read | ||||
| HR | 129doc 0081H | Control output MV | INT16 | Read | |||||
| HR | 131doc 0083H | Current SV | Raw integer; apply the decimal point (keypad setting). | INT16 | Read | ||||
| HR | 132doc 0084H | Running step remaining time | INT16 | Read | |||||
| HR | 133doc 0085H | Running pattern and step | Lowest hex digit = pattern number; next hex digit = step number. | INT16 | Read | ||||
| HR | 134doc 0086H | Instrument status | BITMAP16 | Read | bit 0 = Control output on; bit 2 = A1 output on; bit 3 = A2 output on; bit 4 = Event output on; bit 7 = Overscale; bit 8 = Underscale; bit 9 = Running; bit 10 = Waiting; bit 11 = Auto-tuning; bit 12 = Hold; bit 15 = Changed by keypad | ||||
| HR | 161doc 00A1H | Instrument information | BITMAP16 | Read | bit 1 = A2 function fitted; bit 2 = Communication function fitted | ||||
| HR | 163doc 00A3H | Keypad changed item | Data item code changed by keypad operation, if any. | INT16 | Read | ||||
| HR | 4368doc 1110H | P1 step 1 SV | Raw integer; apply the decimal point (keypad setting). | INT16 | Read/write | ||||
| HR | 4369doc 1111H | P1 step 1 time | Unit per step time unit selection (0035H). | INT16 | Read/write | ||||
| HR | 4370doc 1112H | P1 step 1 wait used | INT16 | Read/write | 0 = Not used; 1 = Used | ||||
| HR | 4371doc 1113H | P1 wait value | Raw integer; apply the decimal point (keypad setting). | INT16 | Read/write | ||||
| HR | 4372doc 1114H | P1 A1 action point | Raw integer; apply the decimal point (keypad setting). | INT16 | Read/write | ||||
| HR | 4373doc 1115H | P1 A2 action point | Raw integer; apply the decimal point (keypad setting). | INT16 | Read/write | ||||
| HR | 4374doc 1116H | P1 time signal OFF time | INT16 | Read/write | |||||
| HR | 4375doc 1117H | P1 time signal ON time | INT16 | Read/write | |||||
| HR | 4384doc 1120H | P1 step 2 SV | Raw integer; apply the decimal point (keypad setting). | INT16 | Read/write | ||||
| HR | 4385doc 1121H | P1 step 2 time | Unit per step time unit selection (0035H). | INT16 | Read/write | ||||
| HR | 4386doc 1122H | P1 step 2 wait used | INT16 | Read/write | 0 = Not used; 1 = Used | ||||
| HR | 4400doc 1130H | P1 step 3 SV | Raw integer; apply the decimal point (keypad setting). | INT16 | Read/write | ||||
| HR | 4401doc 1131H | P1 step 3 time | Unit per step time unit selection (0035H). | INT16 | Read/write | ||||
| HR | 4402doc 1132H | P1 step 3 wait used | INT16 | Read/write | 0 = Not used; 1 = Used | ||||
| HR | 4416doc 1140H | P1 step 4 SV | Raw integer; apply the decimal point (keypad setting). | INT16 | Read/write | ||||
| HR | 4417doc 1141H | P1 step 4 time | Unit per step time unit selection (0035H). | INT16 | Read/write | ||||
| HR | 4418doc 1142H | P1 step 4 wait used | INT16 | Read/write | 0 = Not used; 1 = Used | ||||
| HR | 4432doc 1150H | P1 step 5 SV | Raw integer; apply the decimal point (keypad setting). | INT16 | Read/write | ||||
| HR | 4433doc 1151H | P1 step 5 time | Unit per step time unit selection (0035H). | INT16 | Read/write | ||||
| HR | 4434doc 1152H | P1 step 5 wait used | INT16 | Read/write | 0 = Not used; 1 = Used | ||||
| HR | 4448doc 1160H | P1 step 6 SV | Raw integer; apply the decimal point (keypad setting). | INT16 | Read/write | ||||
| HR | 4449doc 1161H | P1 step 6 time | Unit per step time unit selection (0035H). | INT16 | Read/write | ||||
| HR | 4450doc 1162H | P1 step 6 wait used | INT16 | Read/write | 0 = Not used; 1 = Used | ||||
| HR | 4464doc 1170H | P1 step 7 SV | Raw integer; apply the decimal point (keypad setting). | INT16 | Read/write | ||||
| HR | 4465doc 1171H | P1 step 7 time | Unit per step time unit selection (0035H). | INT16 | Read/write | ||||
| HR | 4466doc 1172H | P1 step 7 wait used | INT16 | Read/write | 0 = Not used; 1 = Used | ||||
| HR | 4480doc 1180H | P1 step 8 SV | Raw integer; apply the decimal point (keypad setting). | INT16 | Read/write | ||||
| HR | 4481doc 1181H | P1 step 8 time | Unit per step time unit selection (0035H). | INT16 | Read/write | ||||
| HR | 4482doc 1182H | P1 step 8 wait used | INT16 | Read/write | 0 = Not used; 1 = Used | ||||
| HR | 4496doc 1190H | P1 step 9 SV | Raw integer; apply the decimal point (keypad setting). | INT16 | Read/write | ||||
| HR | 4497doc 1191H | P1 step 9 time | Unit per step time unit selection (0035H). | INT16 | Read/write | ||||
| HR | 4498doc 1192H | P1 step 9 wait used | INT16 | Read/write | 0 = Not used; 1 = Used | ||||
| HR | 4624doc 1210H | P2 step 1 SV | Raw integer; apply the decimal point (keypad setting). | INT16 | Read/write | ||||
| HR | 4625doc 1211H | P2 step 1 time | Unit per step time unit selection (0035H). | INT16 | Read/write | ||||
| HR | 4626doc 1212H | P2 step 1 wait used | INT16 | Read/write | 0 = Not used; 1 = Used | ||||
| HR | 4627doc 1213H | P2 wait value | Raw integer; apply the decimal point (keypad setting). | INT16 | Read/write | ||||
| HR | 4628doc 1214H | P2 A1 action point | Raw integer; apply the decimal point (keypad setting). | INT16 | Read/write | ||||
| HR | 4629doc 1215H | P2 A2 action point | Raw integer; apply the decimal point (keypad setting). | INT16 | Read/write | ||||
| HR | 4630doc 1216H | P2 time signal OFF time | INT16 | Read/write | |||||
| HR | 4631doc 1217H | P2 time signal ON time | INT16 | Read/write | |||||
| HR | 4640doc 1220H | P2 step 2 SV | Raw integer; apply the decimal point (keypad setting). | INT16 | Read/write | ||||
| HR | 4641doc 1221H | P2 step 2 time | Unit per step time unit selection (0035H). | INT16 | Read/write | ||||
| HR | 4642doc 1222H | P2 step 2 wait used | INT16 | Read/write | 0 = Not used; 1 = Used | ||||
| HR | 4656doc 1230H | P2 step 3 SV | Raw integer; apply the decimal point (keypad setting). | INT16 | Read/write | ||||
| HR | 4657doc 1231H | P2 step 3 time | Unit per step time unit selection (0035H). | INT16 | Read/write | ||||
| HR | 4658doc 1232H | P2 step 3 wait used | INT16 | Read/write | 0 = Not used; 1 = Used | ||||
| HR | 4672doc 1240H | P2 step 4 SV | Raw integer; apply the decimal point (keypad setting). | INT16 | Read/write | ||||
| HR | 4673doc 1241H | P2 step 4 time | Unit per step time unit selection (0035H). | INT16 | Read/write | ||||
| HR | 4674doc 1242H | P2 step 4 wait used | INT16 | Read/write | 0 = Not used; 1 = Used | ||||
| HR | 4688doc 1250H | P2 step 5 SV | Raw integer; apply the decimal point (keypad setting). | INT16 | Read/write | ||||
| HR | 4689doc 1251H | P2 step 5 time | Unit per step time unit selection (0035H). | INT16 | Read/write | ||||
| HR | 4690doc 1252H | P2 step 5 wait used | INT16 | Read/write | 0 = Not used; 1 = Used | ||||
| HR | 4704doc 1260H | P2 step 6 SV | Raw integer; apply the decimal point (keypad setting). | INT16 | Read/write | ||||
| HR | 4705doc 1261H | P2 step 6 time | Unit per step time unit selection (0035H). | INT16 | Read/write | ||||
| HR | 4706doc 1262H | P2 step 6 wait used | INT16 | Read/write | 0 = Not used; 1 = Used | ||||
| HR | 4720doc 1270H | P2 step 7 SV | Raw integer; apply the decimal point (keypad setting). | INT16 | Read/write | ||||
| HR | 4721doc 1271H | P2 step 7 time | Unit per step time unit selection (0035H). | INT16 | Read/write | ||||
| HR | 4722doc 1272H | P2 step 7 wait used | INT16 | Read/write | 0 = Not used; 1 = Used | ||||
| HR | 4736doc 1280H | P2 step 8 SV | Raw integer; apply the decimal point (keypad setting). | INT16 | Read/write | ||||
| HR | 4737doc 1281H | P2 step 8 time | Unit per step time unit selection (0035H). | INT16 | Read/write | ||||
| HR | 4738doc 1282H | P2 step 8 wait used | INT16 | Read/write | 0 = Not used; 1 = Used | ||||
| HR | 4752doc 1290H | P2 step 9 SV | Raw integer; apply the decimal point (keypad setting). | INT16 | Read/write | ||||
| HR | 4753doc 1291H | P2 step 9 time | Unit per step time unit selection (0035H). | INT16 | Read/write | ||||
| HR | 4754doc 1292H | P2 step 9 wait used | INT16 | Read/write | 0 = Not used; 1 = Used | ||||
| HR | 4880doc 1310H | P3 step 1 SV | Raw integer; apply the decimal point (keypad setting). | INT16 | Read/write | ||||
| HR | 4881doc 1311H | P3 step 1 time | Unit per step time unit selection (0035H). | INT16 | Read/write | ||||
| HR | 4882doc 1312H | P3 step 1 wait used | INT16 | Read/write | 0 = Not used; 1 = Used | ||||
| HR | 4883doc 1313H | P3 wait value | Raw integer; apply the decimal point (keypad setting). | INT16 | Read/write | ||||
| HR | 4884doc 1314H | P3 A1 action point | Raw integer; apply the decimal point (keypad setting). | INT16 | Read/write | ||||
| HR | 4885doc 1315H | P3 A2 action point | Raw integer; apply the decimal point (keypad setting). | INT16 | Read/write | ||||
| HR | 4886doc 1316H | P3 time signal OFF time | INT16 | Read/write | |||||
| HR | 4887doc 1317H | P3 time signal ON time | INT16 | Read/write | |||||
| HR | 4896doc 1320H | P3 step 2 SV | Raw integer; apply the decimal point (keypad setting). | INT16 | Read/write | ||||
| HR | 4897doc 1321H | P3 step 2 time | Unit per step time unit selection (0035H). | INT16 | Read/write | ||||
| HR | 4898doc 1322H | P3 step 2 wait used | INT16 | Read/write | 0 = Not used; 1 = Used | ||||
| HR | 4912doc 1330H | P3 step 3 SV | Raw integer; apply the decimal point (keypad setting). | INT16 | Read/write | ||||
| HR | 4913doc 1331H | P3 step 3 time | Unit per step time unit selection (0035H). | INT16 | Read/write | ||||
| HR | 4914doc 1332H | P3 step 3 wait used | INT16 | Read/write | 0 = Not used; 1 = Used | ||||
| HR | 4928doc 1340H | P3 step 4 SV | Raw integer; apply the decimal point (keypad setting). | INT16 | Read/write | ||||
| HR | 4929doc 1341H | P3 step 4 time | Unit per step time unit selection (0035H). | INT16 | Read/write | ||||
| HR | 4930doc 1342H | P3 step 4 wait used | INT16 | Read/write | 0 = Not used; 1 = Used | ||||
| HR | 4944doc 1350H | P3 step 5 SV | Raw integer; apply the decimal point (keypad setting). | INT16 | Read/write | ||||
| HR | 4945doc 1351H | P3 step 5 time | Unit per step time unit selection (0035H). | INT16 | Read/write | ||||
| HR | 4946doc 1352H | P3 step 5 wait used | INT16 | Read/write | 0 = Not used; 1 = Used | ||||
| HR | 4960doc 1360H | P3 step 6 SV | Raw integer; apply the decimal point (keypad setting). | INT16 | Read/write | ||||
| HR | 4961doc 1361H | P3 step 6 time | Unit per step time unit selection (0035H). | INT16 | Read/write | ||||
| HR | 4962doc 1362H | P3 step 6 wait used | INT16 | Read/write | 0 = Not used; 1 = Used | ||||
| HR | 4976doc 1370H | P3 step 7 SV | Raw integer; apply the decimal point (keypad setting). | INT16 | Read/write | ||||
| HR | 4977doc 1371H | P3 step 7 time | Unit per step time unit selection (0035H). | INT16 | Read/write | ||||
| HR | 4978doc 1372H | P3 step 7 wait used | INT16 | Read/write | 0 = Not used; 1 = Used | ||||
| HR | 4992doc 1380H | P3 step 8 SV | Raw integer; apply the decimal point (keypad setting). | INT16 | Read/write | ||||
| HR | 4993doc 1381H | P3 step 8 time | Unit per step time unit selection (0035H). | INT16 | Read/write | ||||
| HR | 4994doc 1382H | P3 step 8 wait used | INT16 | Read/write | 0 = Not used; 1 = Used | ||||
| HR | 5008doc 1390H | P3 step 9 SV | Raw integer; apply the decimal point (keypad setting). | INT16 | Read/write | ||||
| HR | 5009doc 1391H | P3 step 9 time | Unit per step time unit selection (0035H). | INT16 | Read/write | ||||
| HR | 5010doc 1392H | P3 step 9 wait used | INT16 | Read/write | 0 = Not used; 1 = Used | ||||
| HR | 5136doc 1410H | P4 step 1 SV | Raw integer; apply the decimal point (keypad setting). | INT16 | Read/write | ||||
| HR | 5137doc 1411H | P4 step 1 time | Unit per step time unit selection (0035H). | INT16 | Read/write | ||||
| HR | 5138doc 1412H | P4 step 1 wait used | INT16 | Read/write | 0 = Not used; 1 = Used | ||||
| HR | 5139doc 1413H | P4 wait value | Raw integer; apply the decimal point (keypad setting). | INT16 | Read/write | ||||
| HR | 5140doc 1414H | P4 A1 action point | Raw integer; apply the decimal point (keypad setting). | INT16 | Read/write | ||||
| HR | 5141doc 1415H | P4 A2 action point | Raw integer; apply the decimal point (keypad setting). | INT16 | Read/write | ||||
| HR | 5142doc 1416H | P4 time signal OFF time | INT16 | Read/write | |||||
| HR | 5143doc 1417H | P4 time signal ON time | INT16 | Read/write | |||||
| HR | 5152doc 1420H | P4 step 2 SV | Raw integer; apply the decimal point (keypad setting). | INT16 | Read/write | ||||
| HR | 5153doc 1421H | P4 step 2 time | Unit per step time unit selection (0035H). | INT16 | Read/write | ||||
| HR | 5154doc 1422H | P4 step 2 wait used | INT16 | Read/write | 0 = Not used; 1 = Used | ||||
| HR | 5168doc 1430H | P4 step 3 SV | Raw integer; apply the decimal point (keypad setting). | INT16 | Read/write | ||||
| HR | 5169doc 1431H | P4 step 3 time | Unit per step time unit selection (0035H). | INT16 | Read/write | ||||
| HR | 5170doc 1432H | P4 step 3 wait used | INT16 | Read/write | 0 = Not used; 1 = Used | ||||
| HR | 5184doc 1440H | P4 step 4 SV | Raw integer; apply the decimal point (keypad setting). | INT16 | Read/write | ||||
| HR | 5185doc 1441H | P4 step 4 time | Unit per step time unit selection (0035H). | INT16 | Read/write | ||||
| HR | 5186doc 1442H | P4 step 4 wait used | INT16 | Read/write | 0 = Not used; 1 = Used | ||||
| HR | 5200doc 1450H | P4 step 5 SV | Raw integer; apply the decimal point (keypad setting). | INT16 | Read/write | ||||
| HR | 5201doc 1451H | P4 step 5 time | Unit per step time unit selection (0035H). | INT16 | Read/write | ||||
| HR | 5202doc 1452H | P4 step 5 wait used | INT16 | Read/write | 0 = Not used; 1 = Used | ||||
| HR | 5216doc 1460H | P4 step 6 SV | Raw integer; apply the decimal point (keypad setting). | INT16 | Read/write | ||||
| HR | 5217doc 1461H | P4 step 6 time | Unit per step time unit selection (0035H). | INT16 | Read/write | ||||
| HR | 5218doc 1462H | P4 step 6 wait used | INT16 | Read/write | 0 = Not used; 1 = Used | ||||
| HR | 5232doc 1470H | P4 step 7 SV | Raw integer; apply the decimal point (keypad setting). | INT16 | Read/write | ||||
| HR | 5233doc 1471H | P4 step 7 time | Unit per step time unit selection (0035H). | INT16 | Read/write | ||||
| HR | 5234doc 1472H | P4 step 7 wait used | INT16 | Read/write | 0 = Not used; 1 = Used | ||||
| HR | 5248doc 1480H | P4 step 8 SV | Raw integer; apply the decimal point (keypad setting). | INT16 | Read/write | ||||
| HR | 5249doc 1481H | P4 step 8 time | Unit per step time unit selection (0035H). | INT16 | Read/write | ||||
| HR | 5250doc 1482H | P4 step 8 wait used | INT16 | Read/write | 0 = Not used; 1 = Used | ||||
| HR | 5264doc 1490H | P4 step 9 SV | Raw integer; apply the decimal point (keypad setting). | INT16 | Read/write | ||||
| HR | 5265doc 1491H | P4 step 9 time | Unit per step time unit selection (0035H). | INT16 | Read/write | ||||
| HR | 5266doc 1492H | P4 step 9 wait used | INT16 | Read/write | 0 = Not used; 1 = Used | ||||
| HR | 5392doc 1510H | P5 step 1 SV | Raw integer; apply the decimal point (keypad setting). | INT16 | Read/write | ||||
| HR | 5393doc 1511H | P5 step 1 time | Unit per step time unit selection (0035H). | INT16 | Read/write | ||||
| HR | 5394doc 1512H | P5 step 1 wait used | INT16 | Read/write | 0 = Not used; 1 = Used | ||||
| HR | 5395doc 1513H | P5 wait value | Raw integer; apply the decimal point (keypad setting). | INT16 | Read/write | ||||
| HR | 5396doc 1514H | P5 A1 action point | Raw integer; apply the decimal point (keypad setting). | INT16 | Read/write | ||||
| HR | 5397doc 1515H | P5 A2 action point | Raw integer; apply the decimal point (keypad setting). | INT16 | Read/write | ||||
| HR | 5398doc 1516H | P5 time signal OFF time | INT16 | Read/write | |||||
| HR | 5399doc 1517H | P5 time signal ON time | INT16 | Read/write | |||||
| HR | 5408doc 1520H | P5 step 2 SV | Raw integer; apply the decimal point (keypad setting). | INT16 | Read/write | ||||
| HR | 5409doc 1521H | P5 step 2 time | Unit per step time unit selection (0035H). | INT16 | Read/write | ||||
| HR | 5410doc 1522H | P5 step 2 wait used | INT16 | Read/write | 0 = Not used; 1 = Used | ||||
| HR | 5424doc 1530H | P5 step 3 SV | Raw integer; apply the decimal point (keypad setting). | INT16 | Read/write | ||||
| HR | 5425doc 1531H | P5 step 3 time | Unit per step time unit selection (0035H). | INT16 | Read/write | ||||
| HR | 5426doc 1532H | P5 step 3 wait used | INT16 | Read/write | 0 = Not used; 1 = Used | ||||
| HR | 5440doc 1540H | P5 step 4 SV | Raw integer; apply the decimal point (keypad setting). | INT16 | Read/write | ||||
| HR | 5441doc 1541H | P5 step 4 time | Unit per step time unit selection (0035H). | INT16 | Read/write | ||||
| HR | 5442doc 1542H | P5 step 4 wait used | INT16 | Read/write | 0 = Not used; 1 = Used | ||||
| HR | 5456doc 1550H | P5 step 5 SV | Raw integer; apply the decimal point (keypad setting). | INT16 | Read/write | ||||
| HR | 5457doc 1551H | P5 step 5 time | Unit per step time unit selection (0035H). | INT16 | Read/write | ||||
| HR | 5458doc 1552H | P5 step 5 wait used | INT16 | Read/write | 0 = Not used; 1 = Used | ||||
| HR | 5472doc 1560H | P5 step 6 SV | Raw integer; apply the decimal point (keypad setting). | INT16 | Read/write | ||||
| HR | 5473doc 1561H | P5 step 6 time | Unit per step time unit selection (0035H). | INT16 | Read/write | ||||
| HR | 5474doc 1562H | P5 step 6 wait used | INT16 | Read/write | 0 = Not used; 1 = Used | ||||
| HR | 5488doc 1570H | P5 step 7 SV | Raw integer; apply the decimal point (keypad setting). | INT16 | Read/write | ||||
| HR | 5489doc 1571H | P5 step 7 time | Unit per step time unit selection (0035H). | INT16 | Read/write | ||||
| HR | 5490doc 1572H | P5 step 7 wait used | INT16 | Read/write | 0 = Not used; 1 = Used | ||||
| HR | 5504doc 1580H | P5 step 8 SV | Raw integer; apply the decimal point (keypad setting). | INT16 | Read/write | ||||
| HR | 5505doc 1581H | P5 step 8 time | Unit per step time unit selection (0035H). | INT16 | Read/write | ||||
| HR | 5506doc 1582H | P5 step 8 wait used | INT16 | Read/write | 0 = Not used; 1 = Used | ||||
| HR | 5520doc 1590H | P5 step 9 SV | Raw integer; apply the decimal point (keypad setting). | INT16 | Read/write | ||||
| HR | 5521doc 1591H | P5 step 9 time | Unit per step time unit selection (0035H). | INT16 | Read/write | ||||
| HR | 5522doc 1592H | P5 step 9 wait used | INT16 | Read/write | 0 = Not used; 1 = Used | ||||
| HR | 5648doc 1610H | P6 step 1 SV | Raw integer; apply the decimal point (keypad setting). | INT16 | Read/write | ||||
| HR | 5649doc 1611H | P6 step 1 time | Unit per step time unit selection (0035H). | INT16 | Read/write | ||||
| HR | 5650doc 1612H | P6 step 1 wait used | INT16 | Read/write | 0 = Not used; 1 = Used | ||||
| HR | 5651doc 1613H | P6 wait value | Raw integer; apply the decimal point (keypad setting). | INT16 | Read/write | ||||
| HR | 5652doc 1614H | P6 A1 action point | Raw integer; apply the decimal point (keypad setting). | INT16 | Read/write | ||||
| HR | 5653doc 1615H | P6 A2 action point | Raw integer; apply the decimal point (keypad setting). | INT16 | Read/write | ||||
| HR | 5654doc 1616H | P6 time signal OFF time | INT16 | Read/write | |||||
| HR | 5655doc 1617H | P6 time signal ON time | INT16 | Read/write | |||||
| HR | 5664doc 1620H | P6 step 2 SV | Raw integer; apply the decimal point (keypad setting). | INT16 | Read/write | ||||
| HR | 5665doc 1621H | P6 step 2 time | Unit per step time unit selection (0035H). | INT16 | Read/write | ||||
| HR | 5666doc 1622H | P6 step 2 wait used | INT16 | Read/write | 0 = Not used; 1 = Used | ||||
| HR | 5680doc 1630H | P6 step 3 SV | Raw integer; apply the decimal point (keypad setting). | INT16 | Read/write | ||||
| HR | 5681doc 1631H | P6 step 3 time | Unit per step time unit selection (0035H). | INT16 | Read/write | ||||
| HR | 5682doc 1632H | P6 step 3 wait used | INT16 | Read/write | 0 = Not used; 1 = Used | ||||
| HR | 5696doc 1640H | P6 step 4 SV | Raw integer; apply the decimal point (keypad setting). | INT16 | Read/write | ||||
| HR | 5697doc 1641H | P6 step 4 time | Unit per step time unit selection (0035H). | INT16 | Read/write | ||||
| HR | 5698doc 1642H | P6 step 4 wait used | INT16 | Read/write | 0 = Not used; 1 = Used | ||||
| HR | 5712doc 1650H | P6 step 5 SV | Raw integer; apply the decimal point (keypad setting). | INT16 | Read/write | ||||
| HR | 5713doc 1651H | P6 step 5 time | Unit per step time unit selection (0035H). | INT16 | Read/write | ||||
| HR | 5714doc 1652H | P6 step 5 wait used | INT16 | Read/write | 0 = Not used; 1 = Used | ||||
| HR | 5728doc 1660H | P6 step 6 SV | Raw integer; apply the decimal point (keypad setting). | INT16 | Read/write | ||||
| HR | 5729doc 1661H | P6 step 6 time | Unit per step time unit selection (0035H). | INT16 | Read/write | ||||
| HR | 5730doc 1662H | P6 step 6 wait used | INT16 | Read/write | 0 = Not used; 1 = Used | ||||
| HR | 5744doc 1670H | P6 step 7 SV | Raw integer; apply the decimal point (keypad setting). | INT16 | Read/write | ||||
| HR | 5745doc 1671H | P6 step 7 time | Unit per step time unit selection (0035H). | INT16 | Read/write | ||||
| HR | 5746doc 1672H | P6 step 7 wait used | INT16 | Read/write | 0 = Not used; 1 = Used | ||||
| HR | 5760doc 1680H | P6 step 8 SV | Raw integer; apply the decimal point (keypad setting). | INT16 | Read/write | ||||
| HR | 5761doc 1681H | P6 step 8 time | Unit per step time unit selection (0035H). | INT16 | Read/write | ||||
| HR | 5762doc 1682H | P6 step 8 wait used | INT16 | Read/write | 0 = Not used; 1 = Used | ||||
| HR | 5776doc 1690H | P6 step 9 SV | Raw integer; apply the decimal point (keypad setting). | INT16 | Read/write | ||||
| HR | 5777doc 1691H | P6 step 9 time | Unit per step time unit selection (0035H). | INT16 | Read/write | ||||
| HR | 5778doc 1692H | P6 step 9 wait used | INT16 | Read/write | 0 = Not used; 1 = Used | ||||
| HR | 5904doc 1710H | P7 step 1 SV | Raw integer; apply the decimal point (keypad setting). | INT16 | Read/write | ||||
| HR | 5905doc 1711H | P7 step 1 time | Unit per step time unit selection (0035H). | INT16 | Read/write | ||||
| HR | 5906doc 1712H | P7 step 1 wait used | INT16 | Read/write | 0 = Not used; 1 = Used | ||||
| HR | 5907doc 1713H | P7 wait value | Raw integer; apply the decimal point (keypad setting). | INT16 | Read/write | ||||
| HR | 5908doc 1714H | P7 A1 action point | Raw integer; apply the decimal point (keypad setting). | INT16 | Read/write | ||||
| HR | 5909doc 1715H | P7 A2 action point | Raw integer; apply the decimal point (keypad setting). | INT16 | Read/write | ||||
| HR | 5910doc 1716H | P7 time signal OFF time | INT16 | Read/write | |||||
| HR | 5911doc 1717H | P7 time signal ON time | INT16 | Read/write | |||||
| HR | 5920doc 1720H | P7 step 2 SV | Raw integer; apply the decimal point (keypad setting). | INT16 | Read/write | ||||
| HR | 5921doc 1721H | P7 step 2 time | Unit per step time unit selection (0035H). | INT16 | Read/write | ||||
| HR | 5922doc 1722H | P7 step 2 wait used | INT16 | Read/write | 0 = Not used; 1 = Used | ||||
| HR | 5936doc 1730H | P7 step 3 SV | Raw integer; apply the decimal point (keypad setting). | INT16 | Read/write | ||||
| HR | 5937doc 1731H | P7 step 3 time | Unit per step time unit selection (0035H). | INT16 | Read/write | ||||
| HR | 5938doc 1732H | P7 step 3 wait used | INT16 | Read/write | 0 = Not used; 1 = Used | ||||
| HR | 5952doc 1740H | P7 step 4 SV | Raw integer; apply the decimal point (keypad setting). | INT16 | Read/write | ||||
| HR | 5953doc 1741H | P7 step 4 time | Unit per step time unit selection (0035H). | INT16 | Read/write | ||||
| HR | 5954doc 1742H | P7 step 4 wait used | INT16 | Read/write | 0 = Not used; 1 = Used | ||||
| HR | 5968doc 1750H | P7 step 5 SV | Raw integer; apply the decimal point (keypad setting). | INT16 | Read/write | ||||
| HR | 5969doc 1751H | P7 step 5 time | Unit per step time unit selection (0035H). | INT16 | Read/write | ||||
| HR | 5970doc 1752H | P7 step 5 wait used | INT16 | Read/write | 0 = Not used; 1 = Used | ||||
| HR | 5984doc 1760H | P7 step 6 SV | Raw integer; apply the decimal point (keypad setting). | INT16 | Read/write | ||||
| HR | 5985doc 1761H | P7 step 6 time | Unit per step time unit selection (0035H). | INT16 | Read/write | ||||
| HR | 5986doc 1762H | P7 step 6 wait used | INT16 | Read/write | 0 = Not used; 1 = Used | ||||
| HR | 6000doc 1770H | P7 step 7 SV | Raw integer; apply the decimal point (keypad setting). | INT16 | Read/write | ||||
| HR | 6001doc 1771H | P7 step 7 time | Unit per step time unit selection (0035H). | INT16 | Read/write | ||||
| HR | 6002doc 1772H | P7 step 7 wait used | INT16 | Read/write | 0 = Not used; 1 = Used | ||||
| HR | 6016doc 1780H | P7 step 8 SV | Raw integer; apply the decimal point (keypad setting). | INT16 | Read/write | ||||
| HR | 6017doc 1781H | P7 step 8 time | Unit per step time unit selection (0035H). | INT16 | Read/write | ||||
| HR | 6018doc 1782H | P7 step 8 wait used | INT16 | Read/write | 0 = Not used; 1 = Used | ||||
| HR | 6032doc 1790H | P7 step 9 SV | Raw integer; apply the decimal point (keypad setting). | INT16 | Read/write | ||||
| HR | 6033doc 1791H | P7 step 9 time | Unit per step time unit selection (0035H). | INT16 | Read/write | ||||
| HR | 6034doc 1792H | P7 step 9 wait used | INT16 | Read/write | 0 = Not used; 1 = Used | ||||
| HR | 6160doc 1810H | P8 step 1 SV | Raw integer; apply the decimal point (keypad setting). | INT16 | Read/write | ||||
| HR | 6161doc 1811H | P8 step 1 time | Unit per step time unit selection (0035H). | INT16 | Read/write | ||||
| HR | 6162doc 1812H | P8 step 1 wait used | INT16 | Read/write | 0 = Not used; 1 = Used | ||||
| HR | 6163doc 1813H | P8 wait value | Raw integer; apply the decimal point (keypad setting). | INT16 | Read/write | ||||
| HR | 6164doc 1814H | P8 A1 action point | Raw integer; apply the decimal point (keypad setting). | INT16 | Read/write | ||||
| HR | 6165doc 1815H | P8 A2 action point | Raw integer; apply the decimal point (keypad setting). | INT16 | Read/write | ||||
| HR | 6166doc 1816H | P8 time signal OFF time | INT16 | Read/write | |||||
| HR | 6167doc 1817H | P8 time signal ON time | INT16 | Read/write | |||||
| HR | 6176doc 1820H | P8 step 2 SV | Raw integer; apply the decimal point (keypad setting). | INT16 | Read/write | ||||
| HR | 6177doc 1821H | P8 step 2 time | Unit per step time unit selection (0035H). | INT16 | Read/write | ||||
| HR | 6178doc 1822H | P8 step 2 wait used | INT16 | Read/write | 0 = Not used; 1 = Used | ||||
| HR | 6192doc 1830H | P8 step 3 SV | Raw integer; apply the decimal point (keypad setting). | INT16 | Read/write | ||||
| HR | 6193doc 1831H | P8 step 3 time | Unit per step time unit selection (0035H). | INT16 | Read/write | ||||
| HR | 6194doc 1832H | P8 step 3 wait used | INT16 | Read/write | 0 = Not used; 1 = Used | ||||
| HR | 6208doc 1840H | P8 step 4 SV | Raw integer; apply the decimal point (keypad setting). | INT16 | Read/write | ||||
| HR | 6209doc 1841H | P8 step 4 time | Unit per step time unit selection (0035H). | INT16 | Read/write | ||||
| HR | 6210doc 1842H | P8 step 4 wait used | INT16 | Read/write | 0 = Not used; 1 = Used | ||||
| HR | 6224doc 1850H | P8 step 5 SV | Raw integer; apply the decimal point (keypad setting). | INT16 | Read/write | ||||
| HR | 6225doc 1851H | P8 step 5 time | Unit per step time unit selection (0035H). | INT16 | Read/write | ||||
| HR | 6226doc 1852H | P8 step 5 wait used | INT16 | Read/write | 0 = Not used; 1 = Used | ||||
| HR | 6240doc 1860H | P8 step 6 SV | Raw integer; apply the decimal point (keypad setting). | INT16 | Read/write | ||||
| HR | 6241doc 1861H | P8 step 6 time | Unit per step time unit selection (0035H). | INT16 | Read/write | ||||
| HR | 6242doc 1862H | P8 step 6 wait used | INT16 | Read/write | 0 = Not used; 1 = Used | ||||
| HR | 6256doc 1870H | P8 step 7 SV | Raw integer; apply the decimal point (keypad setting). | INT16 | Read/write | ||||
| HR | 6257doc 1871H | P8 step 7 time | Unit per step time unit selection (0035H). | INT16 | Read/write | ||||
| HR | 6258doc 1872H | P8 step 7 wait used | INT16 | Read/write | 0 = Not used; 1 = Used | ||||
| HR | 6272doc 1880H | P8 step 8 SV | Raw integer; apply the decimal point (keypad setting). | INT16 | Read/write | ||||
| HR | 6273doc 1881H | P8 step 8 time | Unit per step time unit selection (0035H). | INT16 | Read/write | ||||
| HR | 6274doc 1882H | P8 step 8 wait used | INT16 | Read/write | 0 = Not used; 1 = Used | ||||
| HR | 6288doc 1890H | P8 step 9 SV | Raw integer; apply the decimal point (keypad setting). | INT16 | Read/write | ||||
| HR | 6289doc 1891H | P8 step 9 time | Unit per step time unit selection (0035H). | INT16 | Read/write | ||||
| HR | 6290doc 1892H | P8 step 9 wait used | INT16 | Read/write | 0 = Not used; 1 = Used | ||||
| HR | 6416doc 1910H | P9 step 1 SV | Raw integer; apply the decimal point (keypad setting). | INT16 | Read/write | ||||
| HR | 6417doc 1911H | P9 step 1 time | Unit per step time unit selection (0035H). | INT16 | Read/write | ||||
| HR | 6418doc 1912H | P9 step 1 wait used | INT16 | Read/write | 0 = Not used; 1 = Used | ||||
| HR | 6419doc 1913H | P9 wait value | Raw integer; apply the decimal point (keypad setting). | INT16 | Read/write | ||||
| HR | 6420doc 1914H | P9 A1 action point | Raw integer; apply the decimal point (keypad setting). | INT16 | Read/write | ||||
| HR | 6421doc 1915H | P9 A2 action point | Raw integer; apply the decimal point (keypad setting). | INT16 | Read/write | ||||
| HR | 6422doc 1916H | P9 time signal OFF time | INT16 | Read/write | |||||
| HR | 6423doc 1917H | P9 time signal ON time | INT16 | Read/write | |||||
| HR | 6432doc 1920H | P9 step 2 SV | Raw integer; apply the decimal point (keypad setting). | INT16 | Read/write | ||||
| HR | 6433doc 1921H | P9 step 2 time | Unit per step time unit selection (0035H). | INT16 | Read/write | ||||
| HR | 6434doc 1922H | P9 step 2 wait used | INT16 | Read/write | 0 = Not used; 1 = Used | ||||
| HR | 6448doc 1930H | P9 step 3 SV | Raw integer; apply the decimal point (keypad setting). | INT16 | Read/write | ||||
| HR | 6449doc 1931H | P9 step 3 time | Unit per step time unit selection (0035H). | INT16 | Read/write | ||||
| HR | 6450doc 1932H | P9 step 3 wait used | INT16 | Read/write | 0 = Not used; 1 = Used | ||||
| HR | 6464doc 1940H | P9 step 4 SV | Raw integer; apply the decimal point (keypad setting). | INT16 | Read/write | ||||
| HR | 6465doc 1941H | P9 step 4 time | Unit per step time unit selection (0035H). | INT16 | Read/write | ||||
| HR | 6466doc 1942H | P9 step 4 wait used | INT16 | Read/write | 0 = Not used; 1 = Used | ||||
| HR | 6480doc 1950H | P9 step 5 SV | Raw integer; apply the decimal point (keypad setting). | INT16 | Read/write | ||||
| HR | 6481doc 1951H | P9 step 5 time | Unit per step time unit selection (0035H). | INT16 | Read/write | ||||
| HR | 6482doc 1952H | P9 step 5 wait used | INT16 | Read/write | 0 = Not used; 1 = Used | ||||
| HR | 6496doc 1960H | P9 step 6 SV | Raw integer; apply the decimal point (keypad setting). | INT16 | Read/write | ||||
| HR | 6497doc 1961H | P9 step 6 time | Unit per step time unit selection (0035H). | INT16 | Read/write | ||||
| HR | 6498doc 1962H | P9 step 6 wait used | INT16 | Read/write | 0 = Not used; 1 = Used | ||||
| HR | 6512doc 1970H | P9 step 7 SV | Raw integer; apply the decimal point (keypad setting). | INT16 | Read/write | ||||
| HR | 6513doc 1971H | P9 step 7 time | Unit per step time unit selection (0035H). | INT16 | Read/write | ||||
| HR | 6514doc 1972H | P9 step 7 wait used | INT16 | Read/write | 0 = Not used; 1 = Used | ||||
| HR | 6528doc 1980H | P9 step 8 SV | Raw integer; apply the decimal point (keypad setting). | INT16 | Read/write | ||||
| HR | 6529doc 1981H | P9 step 8 time | Unit per step time unit selection (0035H). | INT16 | Read/write | ||||
| HR | 6530doc 1982H | P9 step 8 wait used | INT16 | Read/write | 0 = Not used; 1 = Used | ||||
| HR | 6544doc 1990H | P9 step 9 SV | Raw integer; apply the decimal point (keypad setting). | INT16 | Read/write | ||||
| HR | 6545doc 1991H | P9 step 9 time | Unit per step time unit selection (0035H). | INT16 | Read/write | ||||
| HR | 6546doc 1992H | P9 step 9 wait used | INT16 | Read/write | 0 = Not used; 1 = Used |
Notes on this map
- Pattern/step addresses follow the manual's 1xx0H scheme: 1000H + pattern x 100H + step x 10H + item (SV 0, time 1, wait 2); per-pattern items are 1p13H-1p17H. The RTU example reads pattern 1 step 1 SV at 1110H.
- Scaling high/low limit (002CH, 002DH) and decimal point place (002EH) are listed without a Shinko or Modbus command code in the table, so they are left out; set the decimal point on the keypad.
- Function 03 reads one register and 06 writes one; the number of data is fixed at 1.
- Values with a decimal point are sent as whole numbers. Units of PID times, step times and MV are not printed in the table.
- A value changed over the bus does not drag related values with it (e.g. lowering SV high limit leaves step SVs as they were).
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Shinko Technos PCD-33A programmable controller (C5 option)
What Modbus registers does the Shinko Technos PCD-33A programmable controller (C5 option) have?
This map lists 329 registers: 329 holding registers. 321 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Shinko Technos PCD-33A programmable controller (C5 option) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Data items are printed as hex (0080H, 1110H) and go into the request unchanged, as the manual's RTU example frames show (PV read at 0080H). The RTU example reads pattern 1 step 1 SV at 1110H (CRC 80F3H checked).
What are the minimum Modbus registers to integrate the Shinko Technos PCD-33A programmable controller (C5 option)?
Start with HR 128 PV (Process value); HR 131 Current SV (Current program SV); HR 133 Running pattern and step (Running pattern and step); HR 134 Instrument status (Run, alarm and error status); HR 66 Program run Perform/Stop (Run/stop the program); HR 63 Running pattern number (Select pattern to run); HR 4368 P1 step 1 SV (Pattern 1 step 1 SV).
How do I enable Modbus control of the Shinko Technos PCD-33A programmable controller (C5 option)?
Requires the C5 option. Choose the Modbus protocol, instrument number and speed in Auxiliary function setting mode 1 on the keypad.
Where is the official Shinko Technos PCD-33A programmable controller (C5 option) Modbus documentation?
The source is Communication Instruction Manual PCD-33A (C5, SVTC) (No.PCD3CE1), revision 2003-02, published free by Shinko Technos at https://shinko-technos.co.jp/e/manual/english/PCD3CE2.pdf.
More Shinko Technos Modbus register maps
- Sensor (digital temperature controller)
Shinko Technos ACD-13A / ACR-13A / ACD-15A / ACR-15A digital indicating controller (C, C5 options)
Shinko ACD/ACR-13A (PID) and ACD/ACR-15A (valve positioning) with the C or C5 communication option; manual No.ACDR1CE8.
Also known as: ACD-13A, ACR-13A, ACD-15A, ACR-15A - Sensor (digital temperature controller)
Shinko Technos ACS-13A digital indicating controller (C5 option)
Shinko ACS-13A with the C5 serial communication option; communication manual No.ACS12CE5.
Also known as: ACS-13A-C5, ACS-13A C5 - Sensor (digital temperature controller)
Shinko Technos ACS2 digital indicating controller (C5, C5W options)
Shinko ACS2 with the C5 or C5W serial option, Shinko protocol / MODBUS RTU command set; manual No.ACS2CE3.
Also known as: ACS2-C5, ACS2-C5W - Sensor (conductivity controller)
Shinko Technos AER-102-ECH conductivity indicating controller (C5 option)
Shinko AER-102-ECH electrical conductivity controller with the C5 RS-485 option; manual No. AER11CECE5.
Also known as: AER-102-ECH - Sensor (digital temperature controller)
Shinko Technos BCS2 / BCR2 / BCD2 digital indicating controller (C5, C5W options)
Shinko BCx2 series (BCS2, BCR2, BCD2) with the C5 or C5W communication option, standard (not JC-allocated) command set; manual No.BCx2CE6.
Also known as: BCS2, BCR2, BCD2, BCx2 - Sensor (digital temperature controller)
Shinko Technos DCL-33A DC digital indicating controller (C5 option)
Shinko DCL-33A DC with the C5 option; communication manual No.DCL3CDCE2.
Also known as: DCL-33A DC, DCL-33A-DC-C5 - Sensor (digital temperature controller)
Shinko Technos DCL-33A digital indicating controller (C5 option)
Shinko DCL-33A with the C5 serial option, plain (non-block) Modbus protocol setting; manual No.DCL32CE3.
Also known as: DCL-33A-C5, DCL-33A C5 - Sensor (digital temperature controller)
Shinko Technos FC series digital indicating controller (C/C5 option, Modbus ASCII)
Shinko FCS-23A, FCR-13A, FCR-23A and FCD-13A with the C or C5 serial option; FCR-15A and FCD-15A have no Modbus (Shinko protocol only). Manual No.FC1CE11.
Also known as: FCS-23A, FCR-13A, FCR-23A, FCD-13A - Sensor (paperless recorder)
Shinko Technos GR200 paperless recorder (Modbus RTU / Modbus TCP)
Shinko GR200 paperless recorder with RS-485 Modbus RTU or Ethernet Modbus TCP; manual GR2CE1.
Also known as: GR200 - Sensor (chart recorder)
Shinko Technos HR-700 hybrid recorder (Modbus RTU, firmware 4.00+)
Shinko HR-700 hybrid recorders (multipoint and pen types), body version 4.00 or later, Modbus map version 01; manual No. HR7CE4.
Also known as: HR-700 - Sensor (digital temperature controller)
Shinko Technos JCL-33A digital indicating controller (C5 option)
Shinko JCL-33A with the C5 option, protocol set to plain 'Modbus RTU mode' or 'Modbus ASCII mode' (not the Block Read/Write modes, which use another layout); manual No.JCL3CE3.
Also known as: JCL-33A-C5, JCL-33A C5 - Sensor (digital temperature controller)
Shinko Technos JCS-33A / JCM-33A / JCR-33A / JCD-33A digital indicating controller (C5 option)
Shinko JCx-33A series (JCS, JCM, JCR, JCD-33A) with the C5 option; communication manual No.JC3CE11.
Also known as: JCS-33A, JCM-33A, JCR-33A, JCD-33A, JCx-33A - Sensor (digital temperature controller)
Shinko Technos JIR-301-M digital indicator (C5 option)
Shinko JIR-301-M with the C5 option, plain (non-block) Modbus protocol setting; manual No.JIR32CE4.
Also known as: JIR-301-M-C5, JIR-301-M C5 - Sensor (programmable temperature controller)
Shinko Technos PCA1 programmable controller (C/C5 option)
Shinko PCA1 programmable controllers with the C or C5 serial option; manual No. PCA1CE3.
Also known as: PCA1 - Sensor (programmable temperature controller)
Shinko Technos PCB1 programmable controller (C5W/C5 option)
Shinko PCB1 programmable controllers with the C5W or C5 RS-485 option, native PCB1 command set; manual No. PCB1CE3.
Also known as: PCB1 - Sensor (signal conditioner)
Shinko Technos SGxL signal conditioner series (Modbus RTU)
Shinko SGxL signal conditioners (SGBL, SGCL, SGDL, SGIL, SGLL, SGML, SGPL, SGRL, SGSL, SGTL, SGUL); SGFL and SGJL are not covered. Manual No.SGxL1CE3.
Also known as: SGBL, SGCL, SGDL, SGIL, SGLL, SGML, SGPL, SGRL, SGSL, SGTL, SGUL - Sensor (digital temperature controller)
Shinko Technos WCL-13A 2-channel digital indicating controller (C5 option)
Shinko WCL-13A two-loop controller with the C5 option; communication manual No.WCL1CE3.
Also known as: WCL-13A-C5, WCL-13A C5
Other temperature & process controllers register maps
- Process controller (sensor / PID controller)
ABB Protronic 100/500/550 and Digitric 500 process controllers (Modbus RTU)
ABB Protronic 100/500/550 and Digitric 500 universal process controllers with the RS-485/RS-232 Modbus interface module, interface description 42/62-50040 EN Rev. 04.
Also known as: Protronic 100, Protronic 500, Protronic 550, Digitric 500 - Sensor / multi-input controller
ProMinent DULCOMETER AEGIS II controller (Modbus RTU slave)
AEGIS II controllers fitted with the COM module (Modbus RTU slave on XB21/XB22), per manual BA DM 229 08/18.
Also known as: AEGIS II, Aegis II, DULCOMETER AEGIS II, AEGIS II COM module - Sensor (digital indicating temperature controller)
Yokogawa UTAdvanced UT75A digital indicating controller
Yokogawa UT75A one- or two-loop controller with RS-485 or Ethernet communication; D-register map from IM 05P07A01-01EN chapter 14.
Also known as: UT75A - Sensor (digital temperature controller)
Omron E5CC / E5EC / E5AC / E5DC digital temperature controllers (E5_C series)
Omron E5CC, E5EC, E5AC, E5DC and E5CC-U controllers with RS-485, per the E5_C Communications Manual H175; registers present depend on model and options.
Also known as: E5CC, E5EC, E5AC, E5DC, E5CC-U, E5@C, E5_C - Sensor (digital indicating temperature controller)
Yokogawa UTAdvanced UT55A / UT52A digital indicating controller
Yokogawa UT55A and UT52A one- or two-loop controllers with RS-485 or Ethernet communication; D-register map from IM 05P07A01-01EN chapter 6 (UP55A program items excluded).
Also known as: UT55A, UT52A - Sensor (process / temperature controller)
Novus N20K48 modular process controller (Modbus RTU)
N20K48 controllers with the optional RS-485 interface, communication protocol V1.0x.
Also known as: Novus N20K48, N20K48 modular controller
All temperature & process controllers Modbus register maps →
Source: Communication Instruction Manual PCD-33A (C5, SVTC) · No.PCD3CE1 · rev. 2003-02. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.