- ACD-13A / ACR-13A / ACD-15A / ACR-15A digital indicating controller (C, C5 options)
Sensor (digital temperature controller) · Modbus register map
Shinko Technos ACD-13A / ACR-13A / ACD-15A / ACR-15A digital indicating controller (C, C5 options) Modbus register map
Updated 17 November 2026
The ACD/ACR-13A are PID temperature controllers and the ACD/ACR-15A are valve-positioning versions with open/close outputs and a feedback potentiometer input. With the serial option they speak Shinko protocol, Modbus ASCII or Modbus RTU. The map covers SV and alarm values for memory 1, PID zone 1, input, output and event settings, run/manual control, PV, MV, current SV and status flags.
This page lists 68 Modbus registers for the Shinko Technos ACD-13A / ACR-13A / ACD-15A / ACR-15A digital indicating controller (C, C5 options) — 60 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Shinko Technos’s own free documentation (linked below) and checked against it.
- Manufacturer
- Shinko Technos
- Model
- ACD-13A / ACR-13A / ACD-15A / ACR-15A digital indicating controller (C, C5 options)
- Equipment type
- Sensor (digital temperature controller)
- Registers
- 68 (60 writable)
- Transport
- Modbus RTU, Modbus ASCII
- Default unit ID
- 0
- Default serial
- 9600 baud, 7E1
- Documented addressing
- hexadecimal, 0-based
- Also known as
- ACD-13A, ACR-13A, ACD-15A, ACR-15A
Integration notes: Shinko Technos ACD-13A / ACR-13A / ACD-15A / ACR-15A digital indicating controller (C, C5 options)
Select MODBUS RTU in the Communication group, use an 8-bit data format and a non-zero instrument number, then read PV 0A00H, MV 0A01H and status 0A06H/0A07H; write SV at 0001H.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 2560 | PV | INT16 | Process value | Read |
| HR 1 | SV (memory 1) | INT16 | Set value (memory 1) | Read/write |
| HR 2561 | OUT1 MV / output MV | INT16 | Output MV | Read |
| HR 2566 | Status flag 1 | BITMAP16 | Output and alarm status | Read |
| HR 209 | Control output OFF or RUN/STOP | INT16 | Control output OFF or program RUN/STOP | Read/write |
| HR 51 | Decimal point place | INT16 | Decimal point for scaling | Read/write |
Enable Modbus control & writes
Requires the C or C5 option. From the PV/SV display step through the Engineering and Input groups to the Communication group (key sequence on p. 3), then set Communication protocol to MODBUS RTU, instrument number, speed, data bit/parity and stop bit.
Byte order & addressing
- Factory format is 7 bits/Even, suited to Shinko protocol; Modbus RTU needs an 8-bit choice.
- Instrument number defaults to 0, the Modbus broadcast address; set 1-95.
Network setup
- Factory defaults: Shinko protocol, instrument 0, 9600 bps, 7 bits/Even, 1 stop bit.
- Speeds 9600, 19200, 38400 bps.
Watch out for
- Key lock set to Prohibited (00D4H) reverts to Allowed after a power cycle.
Shinko Technos ACD-13A / ACR-13A / ACD-15A / ACR-15A digital indicating controller (C, C5 options) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 1doc 0001H | SV (memory 1) | Set value, memory number SM1. Decimal point ignored: Raw integer; apply the decimal point setting. | INT16 | Read/write | ||||
| HR | 2doc 0002H | EVT1 alarm value (SM1) | Low side for independent alarms. | INT16 | Read/write | ||||
| HR | 3doc 0003H | EVT1 high limit alarm value (SM1) | High side for independent alarms. | INT16 | Read/write | ||||
| HR | 4doc 0004H | EVT2 alarm value (SM1) | Low side for independent alarms. (ACD/ACR-13A only) | INT16 | Read/write | ||||
| HR | 5doc 0005H | EVT2 high limit alarm value (SM1) | High side for independent alarms. (ACD/ACR-13A only) | INT16 | Read/write | ||||
| HR | 6doc 0006H | EVT3 alarm value (SM1) | Low side for independent alarms. (ACD/ACR-13A only) | INT16 | Read/write | ||||
| HR | 7doc 0007H | EVT3 high limit alarm value (SM1) | High side for independent alarms. (ACD/ACR-13A only) | INT16 | Read/write | ||||
| HR | 8doc 0008H | EVT4 alarm value (SM1) | Low side for independent alarms. | INT16 | Read/write | ||||
| HR | 9doc 0009H | EVT4 high limit alarm value (SM1) | High side for independent alarms. | INT16 | Read/write | ||||
| HR | 10doc 000AH | EVT5 alarm value (SM1) | Low side for independent alarms. | INT16 | Read/write | ||||
| HR | 11doc 000BH | EVT5 high limit alarm value (SM1) | High side for independent alarms. | INT16 | Read/write | ||||
| HR | 16doc 0010H | AT/Auto-reset | INT16 | Read/write | 0 = Cancel; 1 = Perform | ||||
| HR | 17doc 0011H | AT bias | INT16 | Read/write | |||||
| HR | 32doc 0020H | OUT1 proportional band (zone 1) | Decimal point ignored: Raw integer; apply the decimal point setting. | INT16 | Read/write | ||||
| HR | 33doc 0021H | OUT2 proportional band (zone 1) | Decimal point ignored: Raw integer; apply the decimal point setting. (ACD/ACR-13A only) | INT16 | Read/write | ||||
| HR | 34doc 0022H | Integral time (zone 1) | INT16 | Read/write | |||||
| HR | 35doc 0023H | Derivative time (zone 1) | INT16 | Read/write | |||||
| HR | 36doc 0024H | ARW (zone 1) | INT16 | Read/write | |||||
| HR | 37doc 0025H | Manual reset (zone 1) | Decimal point ignored: Raw integer; apply the decimal point setting. | INT16 | Read/write | ||||
| HR | 38doc 0026H | OUT1 / MV rate-of-change (zone 1) | INT16 | Read/write | |||||
| HR | 48doc 0030H | Input type | The reply to this item takes about 2 s. | INT16 | Read/write | 0 = K -200 to 1370 C; 1 = K -200.0 to 400.0 C; 2 = J -200 to 1000 C; 3 = R 0 to 1760 C; 4 = S 0 to 1760 C; 5 = B 0 to 1820 C; 6 = E -200 to 800 C; 7 = T -200.0 to 400.0 C; 8 = N -200 to 1300 C; 9 = PL-II 0 to 1390 C; 10 = C (W/Re5-26) 0 to 2315 C; 11 = Pt100 -200.0 to 850.0 C; 12 = JPt100 -200.0 to 500.0 C; 13 = Pt100 -200 to 850 C; 14 = JPt100 -200 to 500 C; 15 = Pt100 -100.0 to 100.0 C; 16 = JPt100 -100.0 to 500.0 C; 17 = K -328 to 2498 F; 18 = K -328.0 to 752.0 F; 19 = J -328 to 1832 F; 20 = R 32 to 3200 F; 21 = S 32 to 3200 F; 22 = B 32 to 3308 F; 23 = E -328 to 1472 F; 24 = T -328.0 to 752.0 F; 25 = N -328 to 2372 F; 26 = PL-II 32 to 2534 F; 27 = C (W/Re5-26) 32 to 4199 F; 28 = Pt100 -328.0 to 1562.0 F; 29 = JPt100 -328.0 to 932.0 F; 30 = Pt100 -328 to 1562 F; 31 = JPt100 -328 to 932 F; 32 = Pt100 -148.0 to 212.0 F; 33 = JPt100 -148.0 to 932.0 F; 34 = 4-20 mA DC; 35 = 0-20 mA DC; 36 = 0-10 mV DC; 37 = -10 to 10 mV DC; 38 = 0-50 mV DC; 39 = 0-100 mV DC; 40 = 0-1 V DC; 41 = 0-5 V DC; 42 = 1-5 V DC; 43 = 0-10 V DC | |||
| HR | 49doc 0031H | Scaling high limit | Decimal point ignored: Raw integer; apply the decimal point setting. | INT16 | Read/write | ||||
| HR | 50doc 0032H | Scaling low limit | Decimal point ignored: Raw integer; apply the decimal point setting. | INT16 | Read/write | ||||
| HR | 51doc 0033H | Decimal point place | INT16 | Read/write | 0 = xxxxx; 1 = xxxx.x; 2 = xxx.xx; 3 = xx.xxx; 4 = x.xxxx | ||||
| HR | 52doc 0034H | PV filter time constant | Decimal point ignored: Raw integer; apply the decimal point setting. | INT16 | Read/write | ||||
| HR | 53doc 0035H | Sensor correction | Decimal point ignored: Raw integer; apply the decimal point setting. | INT16 | Read/write | ||||
| HR | 64doc 0040H | OUT1 proportional cycle | (ACD/ACR-13A only) | INT16 | Read/write | ||||
| HR | 65doc 0041H | OUT2 proportional cycle | (ACD/ACR-13A only) | INT16 | Read/write | ||||
| HR | 66doc 0042H | OUT1 / MV high limit | INT16 | Read/write | |||||
| HR | 67doc 0043H | OUT1 / MV low limit | INT16 | Read/write | |||||
| HR | 68doc 0044H | OUT1 ON/OFF hysteresis | Decimal point ignored: Raw integer; apply the decimal point setting. | INT16 | Read/write | ||||
| HR | 69doc 0045H | OUT2 cooling method | (ACD/ACR-13A only) | INT16 | Read/write | 0 = Air cooling; 1 = Oil cooling; 2 = Water cooling | |||
| HR | 70doc 0046H | OUT2 high limit | (ACD/ACR-13A only) | INT16 | Read/write | ||||
| HR | 71doc 0047H | OUT2 low limit | (ACD/ACR-13A only) | INT16 | Read/write | ||||
| HR | 72doc 0048H | Overlap/dead band | Decimal point ignored: Raw integer; apply the decimal point setting. (ACD/ACR-13A only) | INT16 | Read/write | ||||
| HR | 73doc 0049H | OUT2 ON/OFF hysteresis | Decimal point ignored: Raw integer; apply the decimal point setting. (ACD/ACR-13A only) | INT16 | Read/write | ||||
| HR | 74doc 004AH | Direct/reverse action | INT16 | Read/write | 0 = Reverse action; 1 = Direct action | ||||
| HR | 75doc 004BH | OUT1 MV preset output | Decimal point ignored: Raw integer; apply the decimal point setting. (ACD/ACR-13A only) | INT16 | Read/write | ||||
| HR | 76doc 004CH | OUT2 MV preset output | Decimal point ignored: Raw integer; apply the decimal point setting. (ACD/ACR-13A only) | INT16 | Read/write | ||||
| HR | 80doc 0050H | Event input EVI1 allocation | INT16 | Read/write | 0 = No event; 1 = Set value memory; 2 = Control ON/OFF; 3 = Direct/Reverse action; 4 = Timer start/stop; 5 = PV holding; 6 = PV peak value holding; 7 = Preset output 1; 8 = Auto/Manual control; 9 = Remote/Local; 10 = Program RUN/STOP; 11 = Program holding; 12 = Program advance; 13 = Integral action holding; 14 = Preset output 2 | ||||
| HR | 81doc 0051H | Event input EVI2 allocation | INT16 | Read/write | 0 = No event; 1 = Set value memory; 2 = Control ON/OFF; 3 = Direct/Reverse action; 4 = Timer start/stop; 5 = PV holding; 6 = PV peak value holding; 7 = Preset output 1; 8 = Auto/Manual control; 9 = Remote/Local; 10 = Program RUN/STOP; 11 = Program holding; 12 = Program advance; 13 = Integral action holding; 14 = Preset output 2 | ||||
| HR | 82doc 0052H | Event input EVI3 allocation | INT16 | Read/write | 0 = No event; 1 = Set value memory; 2 = Control ON/OFF; 3 = Direct/Reverse action; 4 = Timer start/stop; 5 = PV holding; 6 = PV peak value holding; 7 = Preset output 1; 8 = Auto/Manual control; 9 = Remote/Local; 10 = Program RUN/STOP; 11 = Program holding; 12 = Program advance; 13 = Integral action holding; 14 = Preset output 2 | ||||
| HR | 83doc 0053H | Event input EVI4 allocation | INT16 | Read/write | 0 = No event; 1 = Set value memory; 2 = Control ON/OFF; 3 = Direct/Reverse action; 4 = Timer start/stop; 5 = PV holding; 6 = PV peak value holding; 7 = Preset output 1; 8 = Auto/Manual control; 9 = Remote/Local; 10 = Program RUN/STOP; 11 = Program holding; 12 = Program advance; 13 = Integral action holding; 14 = Preset output 2 | ||||
| HR | 198doc 00C6H | PV color | INT16 | Read/write | 0 = Green; 1 = Red; 2 = Orange; 3 = EVT1-5 ON: green to red; 4 = EVT1-5 ON: orange to red; 5 = PV continuous change; 6 = PV continuous change + EVT1-5 ON red | ||||
| HR | 199doc 00C7H | PV color range | Decimal point ignored: Raw integer; apply the decimal point setting. | INT16 | Read/write | ||||
| HR | 200doc 00C8H | Backlight time | INT16 | Read/write | |||||
| HR | 201doc 00C9H | Bar graph | INT16 | Read/write | 0 = MV indication; 1 = DV indication; 2 = No indication; 3 = Valve opening (15A) | ||||
| HR | 202doc 00CAH | Deviation unit | Decimal point ignored: Raw integer; apply the decimal point setting. | INT16 | Read/write | ||||
| HR | 208doc 00D0H | SV of current set value memory | Decimal point ignored: Raw integer; apply the decimal point setting. | INT16 | Read/write | ||||
| HR | 209doc 00D1H | Control output OFF or RUN/STOP | Fixed value control: 0 ON, 1 OFF. Program control: 0 STOP, 1 RUN. | INT16 | Read/write | ||||
| HR | 210doc 00D2H | Auto/manual control | INT16 | Read/write | 0 = Automatic control; 1 = Manual control | ||||
| HR | 211doc 00D3H | Manual MV | INT16 | Read/write | |||||
| HR | 212doc 00D4H | Key operation allowed/prohibited | Returns to Allowed after a power cycle. | INT16 | Read/write | 0 = Allowed; 1 = Prohibited | |||
| HR | 224doc 00E0H | FBP yes/no (15A) | Feedback potentiometer, ACD/ACR-15A valve control. | INT16 | Read/write | 0 = FBP yes; 1 = FBP no | |||
| HR | 225doc 00E1H | Open/closed output dead band (15A) | INT16 | Read/write | |||||
| HR | 226doc 00E2H | Open/closed output hysteresis (15A) | INT16 | Read/write | |||||
| HR | 227doc 00E3H | Open output time (15A) | INT16 | Read/write | |||||
| HR | 228doc 00E4H | Closed output time (15A) | INT16 | Read/write | |||||
| HR | 229doc 00E5H | Error detection during FBP adjustment (15A) | INT16 | Read/write | 0 = Yes; 1 = No | ||||
| HR | 240doc 00F0H | Key operation change flag clearing | INT16 | Write | 0 = No action; 1 = Clear all | ||||
| HR | 2560doc 0A00H | PV | Process value. Decimal point ignored: Raw integer; apply the decimal point setting. | INT16 | Read | ||||
| HR | 2561doc 0A01H | OUT1 MV / output MV | Decimal point ignored. | INT16 | Read | ||||
| HR | 2562doc 0A02H | OUT2 MV | Decimal point ignored. (ACD/ACR-13A only) | INT16 | Read | ||||
| HR | 2563doc 0A03H | Current SV | Decimal point ignored: Raw integer; apply the decimal point setting. | INT16 | Read | ||||
| HR | 2564doc 0A04H | Remaining time (program) | INT16 | Read | |||||
| HR | 2565doc 0A05H | Program running step | INT16 | Read | |||||
| HR | 2566doc 0A06H | Status flag 1 | BITMAP16 | Read | bit 0 = OUT1 (13A) / open output (15A) on; bit 1 = OUT2 (13A) / closed output (15A) on; bit 2 = EVT1 output on; bit 3 = EVT2 output on (13A); bit 4 = EVT3 output on (13A); bit 5 = EVT4 output on; bit 6 = EVT5 output on; bit 7 = Heater burnout alarm (13A); bit 8 = Loop break alarm; bit 9 = Overscale; bit 10 = Underscale; bit 11 = Standby mode; bit 12 = Setting mode; bit 13 = AT/Auto-reset running; bit 14 = Warm-up; bit 15 = Settings changed by keypad | ||||
| HR | 2567doc 0A07H | Status flag 2 | BITMAP16 | Read | bit 0 = EVT1 input on; bit 1 = EVT2 input on; bit 2 = EVT3 input on; bit 3 = EVT4 input on; bit 11 = Manual control; bit 12 = Program control mode; bit 13 = Program control running; bit 14 = Wait active |
Notes on this map
- All data are 16-bit two's complement; items marked 'decimal point ignored' are whole numbers, so apply the decimal point place (0033H).
- Items marked 13A or 15A apply only to that model type, per the manual's tags.
- Left out: event output allocations and later settings on pp. 14-16, CT current and remaining read items on p. 19, program steps and PID zones 2-5 (separate command tables on pp. 19-21).
- SV memory 1 values at 0001H-000BH are shared with program step 1.
- Input type changes take about 2 s to answer; set the master timeout to 2 s or more.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Shinko Technos ACD-13A / ACR-13A / ACD-15A / ACR-15A digital indicating controller (C, C5 options)
What Modbus registers does the Shinko Technos ACD-13A / ACR-13A / ACD-15A / ACR-15A digital indicating controller (C, C5 options) have?
This map lists 68 registers: 68 holding registers. 60 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Shinko Technos ACD-13A / ACR-13A / ACD-15A / ACR-15A digital indicating controller (C, C5 options) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Registers are listed as hex data items (0001H) that go into the request unchanged. The manual adds that the matching Modicon holding-register number is the item in decimal plus 40001 (0001H = 40002).
What are the minimum Modbus registers to integrate the Shinko Technos ACD-13A / ACR-13A / ACD-15A / ACR-15A digital indicating controller (C, C5 options)?
Start with HR 2560 PV (Process value); HR 1 SV (memory 1) (Set value (memory 1)); HR 2561 OUT1 MV / output MV (Output MV); HR 2566 Status flag 1 (Output and alarm status); HR 209 Control output OFF or RUN/STOP (Control output OFF or program RUN/STOP); HR 51 Decimal point place (Decimal point for scaling).
How do I enable Modbus control of the Shinko Technos ACD-13A / ACR-13A / ACD-15A / ACR-15A digital indicating controller (C, C5 options)?
Requires the C or C5 option. From the PV/SV display step through the Engineering and Input groups to the Communication group (key sequence on p. 3), then set Communication protocol to MODBUS RTU, instrument number, speed, data bit/parity and stop bit.
Where is the official Shinko Technos ACD-13A / ACR-13A / ACD-15A / ACR-15A digital indicating controller (C, C5 options) Modbus documentation?
The source is Communication Instruction Manual ACD/R-13A, ACD/R-15A (C, C5) (No. ACDR1CE8), revision 2020-03, published free by Shinko Technos at https://shinko-technos.co.jp/e/manual/english/ACDR1CE8.pdf.
More Shinko Technos Modbus register maps
- Sensor (digital temperature controller)
Shinko Technos ACS-13A digital indicating controller (C5 option)
Shinko ACS-13A with the C5 serial communication option; communication manual No.ACS12CE5.
Also known as: ACS-13A-C5, ACS-13A C5 - Sensor (digital temperature controller)
Shinko Technos ACS2 digital indicating controller (C5, C5W options)
Shinko ACS2 with the C5 or C5W serial option, Shinko protocol / MODBUS RTU command set; manual No.ACS2CE3.
Also known as: ACS2-C5, ACS2-C5W - Sensor (conductivity controller)
Shinko Technos AER-102-ECH conductivity indicating controller (C5 option)
Shinko AER-102-ECH electrical conductivity controller with the C5 RS-485 option; manual No. AER11CECE5.
Also known as: AER-102-ECH - Sensor (digital temperature controller)
Shinko Technos BCS2 / BCR2 / BCD2 digital indicating controller (C5, C5W options)
Shinko BCx2 series (BCS2, BCR2, BCD2) with the C5 or C5W communication option, standard (not JC-allocated) command set; manual No.BCx2CE6.
Also known as: BCS2, BCR2, BCD2, BCx2 - Sensor (digital temperature controller)
Shinko Technos DCL-33A DC digital indicating controller (C5 option)
Shinko DCL-33A DC with the C5 option; communication manual No.DCL3CDCE2.
Also known as: DCL-33A DC, DCL-33A-DC-C5 - Sensor (digital temperature controller)
Shinko Technos DCL-33A digital indicating controller (C5 option)
Shinko DCL-33A with the C5 serial option, plain (non-block) Modbus protocol setting; manual No.DCL32CE3.
Also known as: DCL-33A-C5, DCL-33A C5 - Sensor (digital temperature controller)
Shinko Technos FC series digital indicating controller (C/C5 option, Modbus ASCII)
Shinko FCS-23A, FCR-13A, FCR-23A and FCD-13A with the C or C5 serial option; FCR-15A and FCD-15A have no Modbus (Shinko protocol only). Manual No.FC1CE11.
Also known as: FCS-23A, FCR-13A, FCR-23A, FCD-13A - Sensor (paperless recorder)
Shinko Technos GR200 paperless recorder (Modbus RTU / Modbus TCP)
Shinko GR200 paperless recorder with RS-485 Modbus RTU or Ethernet Modbus TCP; manual GR2CE1.
Also known as: GR200 - Sensor (chart recorder)
Shinko Technos HR-700 hybrid recorder (Modbus RTU, firmware 4.00+)
Shinko HR-700 hybrid recorders (multipoint and pen types), body version 4.00 or later, Modbus map version 01; manual No. HR7CE4.
Also known as: HR-700 - Sensor (digital temperature controller)
Shinko Technos JCL-33A digital indicating controller (C5 option)
Shinko JCL-33A with the C5 option, protocol set to plain 'Modbus RTU mode' or 'Modbus ASCII mode' (not the Block Read/Write modes, which use another layout); manual No.JCL3CE3.
Also known as: JCL-33A-C5, JCL-33A C5 - Sensor (digital temperature controller)
Shinko Technos JCS-33A / JCM-33A / JCR-33A / JCD-33A digital indicating controller (C5 option)
Shinko JCx-33A series (JCS, JCM, JCR, JCD-33A) with the C5 option; communication manual No.JC3CE11.
Also known as: JCS-33A, JCM-33A, JCR-33A, JCD-33A, JCx-33A - Sensor (digital temperature controller)
Shinko Technos JIR-301-M digital indicator (C5 option)
Shinko JIR-301-M with the C5 option, plain (non-block) Modbus protocol setting; manual No.JIR32CE4.
Also known as: JIR-301-M-C5, JIR-301-M C5 - Sensor (programmable temperature controller)
Shinko Technos PCA1 programmable controller (C/C5 option)
Shinko PCA1 programmable controllers with the C or C5 serial option; manual No. PCA1CE3.
Also known as: PCA1 - Sensor (programmable temperature controller)
Shinko Technos PCB1 programmable controller (C5W/C5 option)
Shinko PCB1 programmable controllers with the C5W or C5 RS-485 option, native PCB1 command set; manual No. PCB1CE3.
Also known as: PCB1 - Sensor (digital temperature controller)
Shinko Technos PCD-33A programmable controller (C5 option)
Shinko PCD-33A program controller with the C5 RS-485 option; manual printed No.PCD3CE1 2003.02 (file PCD3CE2).
Also known as: PCD-33A-R/M, PCD-33A-S/M - Sensor (signal conditioner)
Shinko Technos SGxL signal conditioner series (Modbus RTU)
Shinko SGxL signal conditioners (SGBL, SGCL, SGDL, SGIL, SGLL, SGML, SGPL, SGRL, SGSL, SGTL, SGUL); SGFL and SGJL are not covered. Manual No.SGxL1CE3.
Also known as: SGBL, SGCL, SGDL, SGIL, SGLL, SGML, SGPL, SGRL, SGSL, SGTL, SGUL - Sensor (digital temperature controller)
Shinko Technos WCL-13A 2-channel digital indicating controller (C5 option)
Shinko WCL-13A two-loop controller with the C5 option; communication manual No.WCL1CE3.
Also known as: WCL-13A-C5, WCL-13A C5
Other temperature & process controllers register maps
- Sensor (program temperature controller)
Yokogawa UTAdvanced UP35A / UP32A program controller
Yokogawa UP35A and UP32A single-loop program controllers with RS-485 or Ethernet communication; D-register map from IM 05P07A01-01EN chapter 8 (UP35A/UP32A columns).
Also known as: UP35A, UP32A - Sensor / controller (PID temperature controller)
Autonics TK series PID temperature controller (Modbus RTU)
Autonics TK series heating/cooling PID temperature controllers with RS-485, communication manual MCT-TKC1-V2.2-EN.
Also known as: TK4S, TK4M, TK4H, TK4W, TK4L, TK4S-14RR, TK4 - Sensor (modular temperature controller)
RKC Instrument SRX module type controller, TIO temperature control module (Modbus RTU)
RKC SRX two-channel temperature control (TIO) modules, basic type X-TIO-A and extension type X-TIO-B, with Modbus selected; DI and DO module maps are not included.
Also known as: SRX, X-TIO-A, X-TIO-B, SRX TIO module, RKC SRX - Sensor / counter-timer (programmable counter and timer)
Autonics CT series programmable counter / timer (Modbus RTU)
Autonics CT series counters/timers with RS-485 communication, communication manual MCC-CTC1-V1.3-EN.
Also known as: CT4S, CT6, CT6S, CT6M, CT6Y, CT6M-2P, CT6S-1P4 - Sensor (modular temperature controller)
RKC Instrument SRV module type controller, TIO temperature control module (Modbus RTU)
RKC SRV two-channel temperature control (TIO) modules, basic and extension type, with Modbus selected.
Also known as: SRV, SRV TIO module, RKC SRV - Process controller (sensor / PID controller)
ABB Protronic 100/500/550 and Digitric 500 process controllers (Modbus RTU)
ABB Protronic 100/500/550 and Digitric 500 universal process controllers with the RS-485/RS-232 Modbus interface module, interface description 42/62-50040 EN Rev. 04.
Also known as: Protronic 100, Protronic 500, Protronic 550, Digitric 500
All temperature & process controllers Modbus register maps →
Source: Communication Instruction Manual ACD/R-13A, ACD/R-15A (C, C5) · No. ACDR1CE8 · rev. 2020-03. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.