Sensor (digital temperature controller) · Modbus register map

Shinko Technos ACD-13A / ACR-13A / ACD-15A / ACR-15A digital indicating controller (C, C5 options) Modbus register map

Updated 17 November 2026

Short answer

The ACD/ACR-13A are PID temperature controllers and the ACD/ACR-15A are valve-positioning versions with open/close outputs and a feedback potentiometer input. With the serial option they speak Shinko protocol, Modbus ASCII or Modbus RTU. The map covers SV and alarm values for memory 1, PID zone 1, input, output and event settings, run/manual control, PV, MV, current SV and status flags.

This page lists 68 Modbus registers for the Shinko Technos ACD-13A / ACR-13A / ACD-15A / ACR-15A digital indicating controller (C, C5 options) — 60 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Shinko Technos’s own free documentation (linked below) and checked against it.

Manufacturer
Shinko Technos
Model
ACD-13A / ACR-13A / ACD-15A / ACR-15A digital indicating controller (C, C5 options)
Equipment type
Sensor (digital temperature controller)
Registers
68 (60 writable)
Transport
Modbus RTU, Modbus ASCII
Default unit ID
0
Default serial
9600 baud, 7E1
Documented addressing
hexadecimal, 0-based
Also known as
ACD-13A, ACR-13A, ACD-15A, ACR-15A
Source document
Communication Instruction Manual ACD/R-13A, ACD/R-15A (C, C5) · No. ACDR1CE8 · rev. 2020-03
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Shinko Technos ACD-13A / ACR-13A / ACD-15A / ACR-15A digital indicating controller (C, C5 options)

Integration in brief

Select MODBUS RTU in the Communication group, use an 8-bit data format and a non-zero instrument number, then read PV 0A00H, MV 0A01H and status 0A06H/0A07H; write SV at 0001H.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 2560PVINT16Process valueRead
HR 1SV (memory 1)INT16Set value (memory 1)Read/write
HR 2561OUT1 MV / output MVINT16Output MVRead
HR 2566Status flag 1BITMAP16Output and alarm statusRead
HR 209Control output OFF or RUN/STOPINT16Control output OFF or program RUN/STOPRead/write
HR 51Decimal point placeINT16Decimal point for scalingRead/write

Enable Modbus control & writes

Requires the C or C5 option. From the PV/SV display step through the Engineering and Input groups to the Communication group (key sequence on p. 3), then set Communication protocol to MODBUS RTU, instrument number, speed, data bit/parity and stop bit.

Byte order & addressing

Network setup

Watch out for

Shinko Technos ACD-13A / ACR-13A / ACD-15A / ACR-15A digital indicating controller (C, C5 options) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

68 of 68 shown
Shinko Technos ACD-13A / ACR-13A / ACD-15A / ACR-15A digital indicating controller (C, C5 options) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR1doc 0001HSV (memory 1)Set value, memory number SM1. Decimal point ignored: Raw integer; apply the decimal point setting.INT16Read/write
HR2doc 0002HEVT1 alarm value (SM1)Low side for independent alarms.INT16Read/write
HR3doc 0003HEVT1 high limit alarm value (SM1)High side for independent alarms.INT16Read/write
HR4doc 0004HEVT2 alarm value (SM1)Low side for independent alarms. (ACD/ACR-13A only)INT16Read/write
HR5doc 0005HEVT2 high limit alarm value (SM1)High side for independent alarms. (ACD/ACR-13A only)INT16Read/write
HR6doc 0006HEVT3 alarm value (SM1)Low side for independent alarms. (ACD/ACR-13A only)INT16Read/write
HR7doc 0007HEVT3 high limit alarm value (SM1)High side for independent alarms. (ACD/ACR-13A only)INT16Read/write
HR8doc 0008HEVT4 alarm value (SM1)Low side for independent alarms.INT16Read/write
HR9doc 0009HEVT4 high limit alarm value (SM1)High side for independent alarms.INT16Read/write
HR10doc 000AHEVT5 alarm value (SM1)Low side for independent alarms.INT16Read/write
HR11doc 000BHEVT5 high limit alarm value (SM1)High side for independent alarms.INT16Read/write
HR16doc 0010HAT/Auto-resetINT16Read/write0 = Cancel; 1 = Perform
HR17doc 0011HAT biasINT16Read/write
HR32doc 0020HOUT1 proportional band (zone 1)Decimal point ignored: Raw integer; apply the decimal point setting.INT16Read/write
HR33doc 0021HOUT2 proportional band (zone 1)Decimal point ignored: Raw integer; apply the decimal point setting. (ACD/ACR-13A only)INT16Read/write
HR34doc 0022HIntegral time (zone 1)INT16Read/write
HR35doc 0023HDerivative time (zone 1)INT16Read/write
HR36doc 0024HARW (zone 1)INT16Read/write
HR37doc 0025HManual reset (zone 1)Decimal point ignored: Raw integer; apply the decimal point setting.INT16Read/write
HR38doc 0026HOUT1 / MV rate-of-change (zone 1)INT16Read/write
HR48doc 0030HInput typeThe reply to this item takes about 2 s.INT16Read/write0 = K -200 to 1370 C; 1 = K -200.0 to 400.0 C; 2 = J -200 to 1000 C; 3 = R 0 to 1760 C; 4 = S 0 to 1760 C; 5 = B 0 to 1820 C; 6 = E -200 to 800 C; 7 = T -200.0 to 400.0 C; 8 = N -200 to 1300 C; 9 = PL-II 0 to 1390 C; 10 = C (W/Re5-26) 0 to 2315 C; 11 = Pt100 -200.0 to 850.0 C; 12 = JPt100 -200.0 to 500.0 C; 13 = Pt100 -200 to 850 C; 14 = JPt100 -200 to 500 C; 15 = Pt100 -100.0 to 100.0 C; 16 = JPt100 -100.0 to 500.0 C; 17 = K -328 to 2498 F; 18 = K -328.0 to 752.0 F; 19 = J -328 to 1832 F; 20 = R 32 to 3200 F; 21 = S 32 to 3200 F; 22 = B 32 to 3308 F; 23 = E -328 to 1472 F; 24 = T -328.0 to 752.0 F; 25 = N -328 to 2372 F; 26 = PL-II 32 to 2534 F; 27 = C (W/Re5-26) 32 to 4199 F; 28 = Pt100 -328.0 to 1562.0 F; 29 = JPt100 -328.0 to 932.0 F; 30 = Pt100 -328 to 1562 F; 31 = JPt100 -328 to 932 F; 32 = Pt100 -148.0 to 212.0 F; 33 = JPt100 -148.0 to 932.0 F; 34 = 4-20 mA DC; 35 = 0-20 mA DC; 36 = 0-10 mV DC; 37 = -10 to 10 mV DC; 38 = 0-50 mV DC; 39 = 0-100 mV DC; 40 = 0-1 V DC; 41 = 0-5 V DC; 42 = 1-5 V DC; 43 = 0-10 V DC
HR49doc 0031HScaling high limitDecimal point ignored: Raw integer; apply the decimal point setting.INT16Read/write
HR50doc 0032HScaling low limitDecimal point ignored: Raw integer; apply the decimal point setting.INT16Read/write
HR51doc 0033HDecimal point placeINT16Read/write0 = xxxxx; 1 = xxxx.x; 2 = xxx.xx; 3 = xx.xxx; 4 = x.xxxx
HR52doc 0034HPV filter time constantDecimal point ignored: Raw integer; apply the decimal point setting.INT16Read/write
HR53doc 0035HSensor correctionDecimal point ignored: Raw integer; apply the decimal point setting.INT16Read/write
HR64doc 0040HOUT1 proportional cycle(ACD/ACR-13A only)INT16Read/write
HR65doc 0041HOUT2 proportional cycle(ACD/ACR-13A only)INT16Read/write
HR66doc 0042HOUT1 / MV high limitINT16Read/write
HR67doc 0043HOUT1 / MV low limitINT16Read/write
HR68doc 0044HOUT1 ON/OFF hysteresisDecimal point ignored: Raw integer; apply the decimal point setting.INT16Read/write
HR69doc 0045HOUT2 cooling method(ACD/ACR-13A only)INT16Read/write0 = Air cooling; 1 = Oil cooling; 2 = Water cooling
HR70doc 0046HOUT2 high limit(ACD/ACR-13A only)INT16Read/write
HR71doc 0047HOUT2 low limit(ACD/ACR-13A only)INT16Read/write
HR72doc 0048HOverlap/dead bandDecimal point ignored: Raw integer; apply the decimal point setting. (ACD/ACR-13A only)INT16Read/write
HR73doc 0049HOUT2 ON/OFF hysteresisDecimal point ignored: Raw integer; apply the decimal point setting. (ACD/ACR-13A only)INT16Read/write
HR74doc 004AHDirect/reverse actionINT16Read/write0 = Reverse action; 1 = Direct action
HR75doc 004BHOUT1 MV preset outputDecimal point ignored: Raw integer; apply the decimal point setting. (ACD/ACR-13A only)INT16Read/write
HR76doc 004CHOUT2 MV preset outputDecimal point ignored: Raw integer; apply the decimal point setting. (ACD/ACR-13A only)INT16Read/write
HR80doc 0050HEvent input EVI1 allocationINT16Read/write0 = No event; 1 = Set value memory; 2 = Control ON/OFF; 3 = Direct/Reverse action; 4 = Timer start/stop; 5 = PV holding; 6 = PV peak value holding; 7 = Preset output 1; 8 = Auto/Manual control; 9 = Remote/Local; 10 = Program RUN/STOP; 11 = Program holding; 12 = Program advance; 13 = Integral action holding; 14 = Preset output 2
HR81doc 0051HEvent input EVI2 allocationINT16Read/write0 = No event; 1 = Set value memory; 2 = Control ON/OFF; 3 = Direct/Reverse action; 4 = Timer start/stop; 5 = PV holding; 6 = PV peak value holding; 7 = Preset output 1; 8 = Auto/Manual control; 9 = Remote/Local; 10 = Program RUN/STOP; 11 = Program holding; 12 = Program advance; 13 = Integral action holding; 14 = Preset output 2
HR82doc 0052HEvent input EVI3 allocationINT16Read/write0 = No event; 1 = Set value memory; 2 = Control ON/OFF; 3 = Direct/Reverse action; 4 = Timer start/stop; 5 = PV holding; 6 = PV peak value holding; 7 = Preset output 1; 8 = Auto/Manual control; 9 = Remote/Local; 10 = Program RUN/STOP; 11 = Program holding; 12 = Program advance; 13 = Integral action holding; 14 = Preset output 2
HR83doc 0053HEvent input EVI4 allocationINT16Read/write0 = No event; 1 = Set value memory; 2 = Control ON/OFF; 3 = Direct/Reverse action; 4 = Timer start/stop; 5 = PV holding; 6 = PV peak value holding; 7 = Preset output 1; 8 = Auto/Manual control; 9 = Remote/Local; 10 = Program RUN/STOP; 11 = Program holding; 12 = Program advance; 13 = Integral action holding; 14 = Preset output 2
HR198doc 00C6HPV colorINT16Read/write0 = Green; 1 = Red; 2 = Orange; 3 = EVT1-5 ON: green to red; 4 = EVT1-5 ON: orange to red; 5 = PV continuous change; 6 = PV continuous change + EVT1-5 ON red
HR199doc 00C7HPV color rangeDecimal point ignored: Raw integer; apply the decimal point setting.INT16Read/write
HR200doc 00C8HBacklight timeINT16Read/write
HR201doc 00C9HBar graphINT16Read/write0 = MV indication; 1 = DV indication; 2 = No indication; 3 = Valve opening (15A)
HR202doc 00CAHDeviation unitDecimal point ignored: Raw integer; apply the decimal point setting.INT16Read/write
HR208doc 00D0HSV of current set value memoryDecimal point ignored: Raw integer; apply the decimal point setting.INT16Read/write
HR209doc 00D1HControl output OFF or RUN/STOPFixed value control: 0 ON, 1 OFF. Program control: 0 STOP, 1 RUN.INT16Read/write
HR210doc 00D2HAuto/manual controlINT16Read/write0 = Automatic control; 1 = Manual control
HR211doc 00D3HManual MVINT16Read/write
HR212doc 00D4HKey operation allowed/prohibitedReturns to Allowed after a power cycle.INT16Read/write0 = Allowed; 1 = Prohibited
HR224doc 00E0HFBP yes/no (15A)Feedback potentiometer, ACD/ACR-15A valve control.INT16Read/write0 = FBP yes; 1 = FBP no
HR225doc 00E1HOpen/closed output dead band (15A)INT16Read/write
HR226doc 00E2HOpen/closed output hysteresis (15A)INT16Read/write
HR227doc 00E3HOpen output time (15A)INT16Read/write
HR228doc 00E4HClosed output time (15A)INT16Read/write
HR229doc 00E5HError detection during FBP adjustment (15A)INT16Read/write0 = Yes; 1 = No
HR240doc 00F0HKey operation change flag clearingINT16Write0 = No action; 1 = Clear all
HR2560doc 0A00HPVProcess value. Decimal point ignored: Raw integer; apply the decimal point setting.INT16Read
HR2561doc 0A01HOUT1 MV / output MVDecimal point ignored.INT16Read
HR2562doc 0A02HOUT2 MVDecimal point ignored. (ACD/ACR-13A only)INT16Read
HR2563doc 0A03HCurrent SVDecimal point ignored: Raw integer; apply the decimal point setting.INT16Read
HR2564doc 0A04HRemaining time (program)INT16Read
HR2565doc 0A05HProgram running stepINT16Read
HR2566doc 0A06HStatus flag 1BITMAP16Readbit 0 = OUT1 (13A) / open output (15A) on; bit 1 = OUT2 (13A) / closed output (15A) on; bit 2 = EVT1 output on; bit 3 = EVT2 output on (13A); bit 4 = EVT3 output on (13A); bit 5 = EVT4 output on; bit 6 = EVT5 output on; bit 7 = Heater burnout alarm (13A); bit 8 = Loop break alarm; bit 9 = Overscale; bit 10 = Underscale; bit 11 = Standby mode; bit 12 = Setting mode; bit 13 = AT/Auto-reset running; bit 14 = Warm-up; bit 15 = Settings changed by keypad
HR2567doc 0A07HStatus flag 2BITMAP16Readbit 0 = EVT1 input on; bit 1 = EVT2 input on; bit 2 = EVT3 input on; bit 3 = EVT4 input on; bit 11 = Manual control; bit 12 = Program control mode; bit 13 = Program control running; bit 14 = Wait active

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Shinko Technos ACD-13A / ACR-13A / ACD-15A / ACR-15A digital indicating controller (C, C5 options)

What Modbus registers does the Shinko Technos ACD-13A / ACR-13A / ACD-15A / ACR-15A digital indicating controller (C, C5 options) have?

This map lists 68 registers: 68 holding registers. 60 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Shinko Technos ACD-13A / ACR-13A / ACD-15A / ACR-15A digital indicating controller (C, C5 options) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Registers are listed as hex data items (0001H) that go into the request unchanged. The manual adds that the matching Modicon holding-register number is the item in decimal plus 40001 (0001H = 40002).

What are the minimum Modbus registers to integrate the Shinko Technos ACD-13A / ACR-13A / ACD-15A / ACR-15A digital indicating controller (C, C5 options)?

Start with HR 2560 PV (Process value); HR 1 SV (memory 1) (Set value (memory 1)); HR 2561 OUT1 MV / output MV (Output MV); HR 2566 Status flag 1 (Output and alarm status); HR 209 Control output OFF or RUN/STOP (Control output OFF or program RUN/STOP); HR 51 Decimal point place (Decimal point for scaling).

How do I enable Modbus control of the Shinko Technos ACD-13A / ACR-13A / ACD-15A / ACR-15A digital indicating controller (C, C5 options)?

Requires the C or C5 option. From the PV/SV display step through the Engineering and Input groups to the Communication group (key sequence on p. 3), then set Communication protocol to MODBUS RTU, instrument number, speed, data bit/parity and stop bit.

Where is the official Shinko Technos ACD-13A / ACR-13A / ACD-15A / ACR-15A digital indicating controller (C, C5 options) Modbus documentation?

The source is Communication Instruction Manual ACD/R-13A, ACD/R-15A (C, C5) (No. ACDR1CE8), revision 2020-03, published free by Shinko Technos at https://shinko-technos.co.jp/e/manual/english/ACDR1CE8.pdf.

More Shinko Technos Modbus register maps

Other temperature & process controllers register maps

All temperature & process controllers Modbus register maps →

Source: Communication Instruction Manual ACD/R-13A, ACD/R-15A (C, C5) · No. ACDR1CE8 · rev. 2020-03. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.