- ACS-13A digital indicating controller (C5 option)
Sensor (digital temperature controller) · Modbus register map
Shinko Technos ACS-13A digital indicating controller (C5 option) Modbus register map
Updated 17 November 2026
The ACS-13A is a digital indicating PID temperature controller. With the C5 option it speaks Shinko protocol, Modbus ASCII or Modbus RTU on RS485, and every item is a signed 16-bit holding register. The map covers SV, PID, alarm, heater-burnout and display settings, auto/manual and output-off control, PV, MV, heater current and status flags.
This page lists 58 Modbus registers for the Shinko Technos ACS-13A digital indicating controller (C5 option) — 50 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Shinko Technos’s own free documentation (linked below) and checked against it.
- Manufacturer
- Shinko Technos
- Model
- ACS-13A digital indicating controller (C5 option)
- Equipment type
- Sensor (digital temperature controller)
- Registers
- 58 (50 writable)
- Transport
- Modbus RTU, Modbus ASCII
- Default unit ID
- 0
- Default serial
- 9600 baud, 7E1
- Documented addressing
- hexadecimal, 0-based
- Also known as
- ACS-13A-C5, ACS-13A C5
Integration notes: Shinko Technos ACS-13A digital indicating controller (C5 option)
Select MODBUS RTU and an 8-bit data format on the keypad, set a non-zero instrument number, then poll PV 0080H, OUT1 MV 0081H and status 0085H with function 03. Write SV at 0001H with function 06.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 128 | PV | INT16 | Process value | Read |
| HR 1 | SV | INT16 | Set value | Read/write |
| HR 129 | OUT1 MV | INT16 | OUT1 manipulated value | Read |
| HR 133 | Status flag | BITMAP16 | Output, alarm and error status | Read |
| HR 55 | Control output OFF function | INT16 | Control output on/off | Read/write |
| HR 26 | Decimal point place | INT16 | Decimal point for scaling | Read/write |
Enable Modbus control & writes
Requires the C5 option. In the communication settings choose MODBUS RTU, an instrument number, speed, Data bit/Parity (use an 8-bit choice for RTU) and stop bit.
Byte order & addressing
- Factory data format is 7 bits/Even, which suits Shinko protocol; RTU needs 8 bits.
- Instrument number 0 is the default but is the Modbus broadcast address; set 1-95.
- Writes over Modbus work even when the keypad set value lock is on.
Network setup
- Factory defaults: Shinko protocol, instrument 0, 9600 bps, 7 bits/Even, 1 stop bit.
- Speeds 2400, 4800, 9600, 19200 bps.
Watch out for
- Non-volatile memory is rated about 1,000,000 writes; writing an unchanged value does not use a write.
- The manual suggests polling only PV, OUT1 MV and status, and re-reading settings when status bit 15 shows a keypad change.
Shinko Technos ACS-13A digital indicating controller (C5 option) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 1doc 0001H | SV | Set value. Raw integer; apply the decimal point setting. | INT16 | Read/write | ||||
| HR | 3doc 0003H | AT/Auto-reset | INT16 | Read/write | 0 = Cancel; 1 = Perform | ||||
| HR | 4doc 0004H | OUT1 proportional band | Raw integer; apply the decimal point setting. | INT16 | Read/write | ||||
| HR | 5doc 0005H | OUT2 proportional band | Raw integer; apply the decimal point setting. | INT16 | Read/write | ||||
| HR | 6doc 0006H | Integral time | INT16 | Read/write | |||||
| HR | 7doc 0007H | Derivative time | INT16 | Read/write | |||||
| HR | 8doc 0008H | OUT1 proportional cycle | INT16 | Read/write | |||||
| HR | 9doc 0009H | OUT2 proportional cycle | INT16 | Read/write | |||||
| HR | 11doc 000BH | Alarm 1 value | Raw integer; apply the decimal point setting. | INT16 | Read/write | ||||
| HR | 12doc 000CH | Alarm 2 value | Raw integer; apply the decimal point setting. | INT16 | Read/write | ||||
| HR | 15doc 000FH | Heater burnout alarm value | Raw integer; apply the decimal point setting. | INT16 | Read/write | ||||
| HR | 18doc 0012H | Set value lock | INT16 | Read/write | 0 = Unlock; 1 = Lock 1; 2 = Lock 2; 3 = Lock 3 | ||||
| HR | 21doc 0015H | Sensor correction | Raw integer; apply the decimal point setting. | INT16 | Read/write | ||||
| HR | 22doc 0016H | Overlap/dead band | INT16 | Read/write | |||||
| HR | 24doc 0018H | Scaling high limit | Raw integer; apply the decimal point setting. | INT16 | Read/write | ||||
| HR | 25doc 0019H | Scaling low limit | Raw integer; apply the decimal point setting. | INT16 | Read/write | ||||
| HR | 26doc 001AH | Decimal point place | INT16 | Read/write | 0 = xxxx; 1 = xxx.x; 2 = xx.xx; 3 = x.xxx | ||||
| HR | 27doc 001BH | PV filter time constant | Raw integer; apply the decimal point setting. | INT16 | Read/write | ||||
| HR | 28doc 001CH | OUT1 high limit | INT16 | Read/write | |||||
| HR | 29doc 001DH | OUT1 low limit | INT16 | Read/write | |||||
| HR | 30doc 001EH | OUT1 ON/OFF hysteresis | Raw integer; apply the decimal point setting. | INT16 | Read/write | ||||
| HR | 31doc 001FH | OUT2 cooling method | INT16 | Read/write | 0 = Air cooling; 1 = Oil cooling; 2 = Water cooling | ||||
| HR | 32doc 0020H | OUT2 high limit | INT16 | Read/write | |||||
| HR | 33doc 0021H | OUT2 low limit | INT16 | Read/write | |||||
| HR | 34doc 0022H | OUT2 ON/OFF hysteresis | Raw integer; apply the decimal point setting. | INT16 | Read/write | ||||
| HR | 35doc 0023H | Alarm 1 type | Changing the type resets the alarm value to 0. | INT16 | Read/write | 0 = No alarm action; 1 = High limit alarm; 2 = Low limit alarm; 3 = High/Low limits alarm; 4 = High/Low limit range alarm; 5 = Process high alarm; 6 = Process low alarm; 7 = High limit with standby; 8 = Low limit with standby; 9 = High/Low limits with standby | |||
| HR | 36doc 0024H | Alarm 2 type | Changing the type resets the alarm value to 0. | INT16 | Read/write | 0 = No alarm action; 1 = High limit alarm; 2 = Low limit alarm; 3 = High/Low limits alarm; 4 = High/Low limit range alarm; 5 = Process high alarm; 6 = Process low alarm; 7 = High limit with standby; 8 = Low limit with standby; 9 = High/Low limits with standby | |||
| HR | 37doc 0025H | Alarm 1 hysteresis | Raw integer; apply the decimal point setting. | INT16 | Read/write | ||||
| HR | 38doc 0026H | Alarm 2 hysteresis | Raw integer; apply the decimal point setting. | INT16 | Read/write | ||||
| HR | 41doc 0029H | Alarm 1 delay time | INT16 | Read/write | |||||
| HR | 42doc 002AH | Alarm 2 delay time | INT16 | Read/write | |||||
| HR | 50doc 0032H | Indication when output OFF | INT16 | Read/write | 0 = OFF indication; 1 = No indication; 2 = PV indication; 3 = PV + active alarm outputs | ||||
| HR | 51doc 0033H | SV rise rate | Raw integer; apply the decimal point setting. | INT16 | Read/write | ||||
| HR | 52doc 0034H | SV fall rate | Raw integer; apply the decimal point setting. | INT16 | Read/write | ||||
| HR | 55doc 0037H | Control output OFF function | INT16 | Read/write | 0 = Control output ON; 1 = Control output OFF | ||||
| HR | 56doc 0038H | Auto/manual control | INT16 | Read/write | 0 = Automatic control; 1 = Manual control | ||||
| HR | 57doc 0039H | Manual control MV | Accepted only in manual control. | INT16 | Read/write | ||||
| HR | 64doc 0040H | Alarm 1 energized/de-energized | INT16 | Read/write | 0 = Energized; 1 = De-energized | ||||
| HR | 65doc 0041H | Alarm 2 energized/de-energized | INT16 | Read/write | 0 = Energized; 1 = De-energized | ||||
| HR | 68doc 0044H | Input type | INT16 | Read/write | 0 = K -200 to 1370; 1 = K -200.0 to 400.0; 2 = J -200 to 1000; 3 = R 0 to 1760; 4 = S 0 to 1760; 5 = B 0 to 1820; 6 = E -200 to 800; 7 = T -200.0 to 400.0; 8 = N -200 to 1300; 9 = PL-II 0 to 1390; 10 = C (W/Re5-26) 0 to 2315; 11 = Pt100 -200.0 to 850.0; 12 = JPt100 -200.0 to 500.0; 13 = Pt100 -200 to 850; 14 = JPt100 -200 to 500; 15 = K -320 to 2500; 16 = K -320.0 to 750.0; 17 = J -320 to 1800; 18 = R 0 to 3200; 19 = S 0 to 3200; 20 = B 0 to 3300; 21 = E -320 to 1500; 22 = T -320.0 to 750.0; 23 = N -320 to 2300; 24 = PL-II 0 to 2500; 25 = C (W/Re5-26) 0 to 4200; 26 = Pt100 -320.0 to 1500.0; 27 = JPt100 -320.0 to 900.0; 28 = Pt100 -320 to 1500; 29 = JPt100 -320 to 900; 30 = 4-20 mA -2000 to 10000; 31 = 0-20 mA -2000 to 10000; 32 = 0-1 V -2000 to 10000; 33 = 0-5 V -2000 to 10000; 34 = 1-5 V -2000 to 10000; 35 = 0-10 V -2000 to 10000 | ||||
| HR | 69doc 0045H | Direct/reverse control action | INT16 | Read/write | 0 = Reverse (heating); 1 = Direct (cooling) | ||||
| HR | 71doc 0047H | AT bias | INT16 | Read/write | |||||
| HR | 72doc 0048H | ARW | Anti-reset windup. | INT16 | Read/write | ||||
| HR | 73doc 0049H | Heater burnout alarm 2 value | Raw integer; apply the decimal point setting. | INT16 | Read/write | ||||
| HR | 74doc 004AH | OUT1 rate-of-change | INT16 | Read/write | |||||
| HR | 80doc 0050H | Backlight selection | INT16 | Read/write | 0 = All; 1 = PV display; 2 = SV display; 3 = Action indicators; 4 = PV + SV displays; 5 = PV + action indicators; 6 = SV + action indicators | ||||
| HR | 81doc 0051H | PV color | INT16 | Read/write | 0 = Green; 1 = Red; 2 = Orange; 3 = Alarm ON: green to red; 4 = Alarm ON: orange to red; 5 = Changes continuously; 6 = Changes continuously + alarm ON red | ||||
| HR | 82doc 0052H | PV color range | Raw integer; apply the decimal point setting. | INT16 | Read/write | ||||
| HR | 83doc 0053H | Backlight time | INT16 | Read/write | |||||
| HR | 112doc 0070H | Key operation change flag clearing | INT16 | Write | 0 = No action; 1 = Clear all | ||||
| HR | 128doc 0080H | PV | Process value. Raw integer; apply the decimal point setting. | INT16 | Read | ||||
| HR | 129doc 0081H | OUT1 MV | Decimal point ignored. | INT16 | Read | ||||
| HR | 130doc 0082H | OUT2 MV | Decimal point ignored. | INT16 | Read | ||||
| HR | 131doc 0083H | SV in use (ramping) | SV while it rises or falls. Raw integer; apply the decimal point setting. | INT16 | Read | ||||
| HR | 133doc 0085H | Status flag | BITMAP16 | Read | bit 0 = OUT1 on; bit 1 = OUT2 on; bit 2 = Alarm 1 output on; bit 3 = Alarm 2 output on; bit 6 = Heater burnout alarm output on; bit 8 = Overscale; bit 9 = Underscale; bit 10 = Control output OFF; bit 11 = AT/Auto-reset running; bit 12 = OUT/OFF key = Auto/Manual (0 = output OFF function); bit 14 = Manual control; bit 15 = Settings changed by keypad | ||||
| HR | 134doc 0086H | CT1 current value | Heater current, decimal point ignored. | INT16 | Read | ||||
| HR | 135doc 0087H | CT2 current value | Heater current, decimal point ignored. | INT16 | Read | ||||
| HR | 161doc 00A1H | Unit specification flag | BITMAP16 | Read | bit 0 = Set value memory external selection; bit 1 = Serial communication; bit 2 = Heater burnout function; bit 3 = HB rated current 50 A (0 = 20 A); bit 4 = HB 3-phase (0 = single phase); bit 5 = Alarm 2 output; bit 6 = Heat/cool output |
Notes on this map
- All data are 16-bit; negatives are two's complement. Items marked 'decimal point ignored' are sent as whole numbers, so apply the decimal point place (001AH).
- Units of PID times, cycles, rates and MV are not printed in the command table; they match the keypad settings in the main instruction manual.
- Some writes are refused with exception 1: output-OFF (0037H) when the OUT/OFF key is set for auto/manual, auto/manual (0038H) when it is set for output OFF, manual MV (0039H) in automatic mode, and AT (0003H) under PI or ON/OFF control.
- Instrument number and communication speed can only be set from the keypad, not over Modbus.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Shinko Technos ACS-13A digital indicating controller (C5 option)
What Modbus registers does the Shinko Technos ACS-13A digital indicating controller (C5 option) have?
This map lists 58 registers: 58 holding registers. 50 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Shinko Technos ACS-13A digital indicating controller (C5 option) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Registers are listed as hex data items (0001H) that go into the request unchanged. The manual adds that the matching Modicon holding-register number is the item in decimal plus 40001 (0001H = 40002).
What are the minimum Modbus registers to integrate the Shinko Technos ACS-13A digital indicating controller (C5 option)?
Start with HR 128 PV (Process value); HR 1 SV (Set value); HR 129 OUT1 MV (OUT1 manipulated value); HR 133 Status flag (Output, alarm and error status); HR 55 Control output OFF function (Control output on/off); HR 26 Decimal point place (Decimal point for scaling).
How do I enable Modbus control of the Shinko Technos ACS-13A digital indicating controller (C5 option)?
Requires the C5 option. In the communication settings choose MODBUS RTU, an instrument number, speed, Data bit/Parity (use an 8-bit choice for RTU) and stop bit.
Where is the official Shinko Technos ACS-13A digital indicating controller (C5 option) Modbus documentation?
The source is Communication Instruction Manual ACS-13A (C5) (No. ACS12CE5), revision 2019-08, published free by Shinko Technos at https://shinko-technos.co.jp/e/manual/english/ACS12CE5.pdf.
More Shinko Technos Modbus register maps
- Sensor (digital temperature controller)
Shinko Technos ACD-13A / ACR-13A / ACD-15A / ACR-15A digital indicating controller (C, C5 options)
Shinko ACD/ACR-13A (PID) and ACD/ACR-15A (valve positioning) with the C or C5 communication option; manual No.ACDR1CE8.
Also known as: ACD-13A, ACR-13A, ACD-15A, ACR-15A - Sensor (digital temperature controller)
Shinko Technos ACS2 digital indicating controller (C5, C5W options)
Shinko ACS2 with the C5 or C5W serial option, Shinko protocol / MODBUS RTU command set; manual No.ACS2CE3.
Also known as: ACS2-C5, ACS2-C5W - Sensor (conductivity controller)
Shinko Technos AER-102-ECH conductivity indicating controller (C5 option)
Shinko AER-102-ECH electrical conductivity controller with the C5 RS-485 option; manual No. AER11CECE5.
Also known as: AER-102-ECH - Sensor (digital temperature controller)
Shinko Technos BCS2 / BCR2 / BCD2 digital indicating controller (C5, C5W options)
Shinko BCx2 series (BCS2, BCR2, BCD2) with the C5 or C5W communication option, standard (not JC-allocated) command set; manual No.BCx2CE6.
Also known as: BCS2, BCR2, BCD2, BCx2 - Sensor (digital temperature controller)
Shinko Technos DCL-33A DC digital indicating controller (C5 option)
Shinko DCL-33A DC with the C5 option; communication manual No.DCL3CDCE2.
Also known as: DCL-33A DC, DCL-33A-DC-C5 - Sensor (digital temperature controller)
Shinko Technos DCL-33A digital indicating controller (C5 option)
Shinko DCL-33A with the C5 serial option, plain (non-block) Modbus protocol setting; manual No.DCL32CE3.
Also known as: DCL-33A-C5, DCL-33A C5 - Sensor (digital temperature controller)
Shinko Technos FC series digital indicating controller (C/C5 option, Modbus ASCII)
Shinko FCS-23A, FCR-13A, FCR-23A and FCD-13A with the C or C5 serial option; FCR-15A and FCD-15A have no Modbus (Shinko protocol only). Manual No.FC1CE11.
Also known as: FCS-23A, FCR-13A, FCR-23A, FCD-13A - Sensor (paperless recorder)
Shinko Technos GR200 paperless recorder (Modbus RTU / Modbus TCP)
Shinko GR200 paperless recorder with RS-485 Modbus RTU or Ethernet Modbus TCP; manual GR2CE1.
Also known as: GR200 - Sensor (chart recorder)
Shinko Technos HR-700 hybrid recorder (Modbus RTU, firmware 4.00+)
Shinko HR-700 hybrid recorders (multipoint and pen types), body version 4.00 or later, Modbus map version 01; manual No. HR7CE4.
Also known as: HR-700 - Sensor (digital temperature controller)
Shinko Technos JCL-33A digital indicating controller (C5 option)
Shinko JCL-33A with the C5 option, protocol set to plain 'Modbus RTU mode' or 'Modbus ASCII mode' (not the Block Read/Write modes, which use another layout); manual No.JCL3CE3.
Also known as: JCL-33A-C5, JCL-33A C5 - Sensor (digital temperature controller)
Shinko Technos JCS-33A / JCM-33A / JCR-33A / JCD-33A digital indicating controller (C5 option)
Shinko JCx-33A series (JCS, JCM, JCR, JCD-33A) with the C5 option; communication manual No.JC3CE11.
Also known as: JCS-33A, JCM-33A, JCR-33A, JCD-33A, JCx-33A - Sensor (digital temperature controller)
Shinko Technos JIR-301-M digital indicator (C5 option)
Shinko JIR-301-M with the C5 option, plain (non-block) Modbus protocol setting; manual No.JIR32CE4.
Also known as: JIR-301-M-C5, JIR-301-M C5 - Sensor (programmable temperature controller)
Shinko Technos PCA1 programmable controller (C/C5 option)
Shinko PCA1 programmable controllers with the C or C5 serial option; manual No. PCA1CE3.
Also known as: PCA1 - Sensor (programmable temperature controller)
Shinko Technos PCB1 programmable controller (C5W/C5 option)
Shinko PCB1 programmable controllers with the C5W or C5 RS-485 option, native PCB1 command set; manual No. PCB1CE3.
Also known as: PCB1 - Sensor (digital temperature controller)
Shinko Technos PCD-33A programmable controller (C5 option)
Shinko PCD-33A program controller with the C5 RS-485 option; manual printed No.PCD3CE1 2003.02 (file PCD3CE2).
Also known as: PCD-33A-R/M, PCD-33A-S/M - Sensor (signal conditioner)
Shinko Technos SGxL signal conditioner series (Modbus RTU)
Shinko SGxL signal conditioners (SGBL, SGCL, SGDL, SGIL, SGLL, SGML, SGPL, SGRL, SGSL, SGTL, SGUL); SGFL and SGJL are not covered. Manual No.SGxL1CE3.
Also known as: SGBL, SGCL, SGDL, SGIL, SGLL, SGML, SGPL, SGRL, SGSL, SGTL, SGUL - Sensor (digital temperature controller)
Shinko Technos WCL-13A 2-channel digital indicating controller (C5 option)
Shinko WCL-13A two-loop controller with the C5 option; communication manual No.WCL1CE3.
Also known as: WCL-13A-C5, WCL-13A C5
Other temperature & process controllers register maps
- Sensor (program temperature controller)
Yokogawa UTAdvanced UP55A program controller
Yokogawa UP55A program controller with RS-485 or Ethernet communication; D-register map from IM 05P07A01-01EN chapter 6 (UP55A column).
Also known as: UP55A - Sensor (digital process controller)
Fuji Electric PXH digital controller (Modbus RTU, monitoring map)
Fuji Electric PXH digital controllers on the RS-485 Modbus port; read-only monitoring registers from manual INP-TN514207c-E.
Also known as: PXH - Sensor (program temperature controller)
Yokogawa UTAdvanced UP35A / UP32A program controller
Yokogawa UP35A and UP32A single-loop program controllers with RS-485 or Ethernet communication; D-register map from IM 05P07A01-01EN chapter 8 (UP35A/UP32A columns).
Also known as: UP35A, UP32A - Sensor / controller (PID temperature controller)
Autonics TK series PID temperature controller (Modbus RTU)
Autonics TK series heating/cooling PID temperature controllers with RS-485, communication manual MCT-TKC1-V2.2-EN.
Also known as: TK4S, TK4M, TK4H, TK4W, TK4L, TK4S-14RR, TK4 - Sensor (modular temperature controller)
RKC Instrument SRX module type controller, TIO temperature control module (Modbus RTU)
RKC SRX two-channel temperature control (TIO) modules, basic type X-TIO-A and extension type X-TIO-B, with Modbus selected; DI and DO module maps are not included.
Also known as: SRX, X-TIO-A, X-TIO-B, SRX TIO module, RKC SRX - Sensor / counter-timer (programmable counter and timer)
Autonics CT series programmable counter / timer (Modbus RTU)
Autonics CT series counters/timers with RS-485 communication, communication manual MCC-CTC1-V1.3-EN.
Also known as: CT4S, CT6, CT6S, CT6M, CT6Y, CT6M-2P, CT6S-1P4
All temperature & process controllers Modbus register maps →
Source: Communication Instruction Manual ACS-13A (C5) · No. ACS12CE5 · rev. 2019-08. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.