Sensor (digital temperature controller) · Modbus register map

Shinko Technos ACS-13A digital indicating controller (C5 option) Modbus register map

Updated 17 November 2026

Short answer

The ACS-13A is a digital indicating PID temperature controller. With the C5 option it speaks Shinko protocol, Modbus ASCII or Modbus RTU on RS485, and every item is a signed 16-bit holding register. The map covers SV, PID, alarm, heater-burnout and display settings, auto/manual and output-off control, PV, MV, heater current and status flags.

This page lists 58 Modbus registers for the Shinko Technos ACS-13A digital indicating controller (C5 option) — 50 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Shinko Technos’s own free documentation (linked below) and checked against it.

Manufacturer
Shinko Technos
Model
ACS-13A digital indicating controller (C5 option)
Equipment type
Sensor (digital temperature controller)
Registers
58 (50 writable)
Transport
Modbus RTU, Modbus ASCII
Default unit ID
0
Default serial
9600 baud, 7E1
Documented addressing
hexadecimal, 0-based
Also known as
ACS-13A-C5, ACS-13A C5
Source document
Communication Instruction Manual ACS-13A (C5) · No. ACS12CE5 · rev. 2019-08
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Shinko Technos ACS-13A digital indicating controller (C5 option)

Integration in brief

Select MODBUS RTU and an 8-bit data format on the keypad, set a non-zero instrument number, then poll PV 0080H, OUT1 MV 0081H and status 0085H with function 03. Write SV at 0001H with function 06.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 128PVINT16Process valueRead
HR 1SVINT16Set valueRead/write
HR 129OUT1 MVINT16OUT1 manipulated valueRead
HR 133Status flagBITMAP16Output, alarm and error statusRead
HR 55Control output OFF functionINT16Control output on/offRead/write
HR 26Decimal point placeINT16Decimal point for scalingRead/write

Enable Modbus control & writes

Requires the C5 option. In the communication settings choose MODBUS RTU, an instrument number, speed, Data bit/Parity (use an 8-bit choice for RTU) and stop bit.

Byte order & addressing

Network setup

Watch out for

Shinko Technos ACS-13A digital indicating controller (C5 option) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

58 of 58 shown
Shinko Technos ACS-13A digital indicating controller (C5 option) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR1doc 0001HSVSet value. Raw integer; apply the decimal point setting.INT16Read/write
HR3doc 0003HAT/Auto-resetINT16Read/write0 = Cancel; 1 = Perform
HR4doc 0004HOUT1 proportional bandRaw integer; apply the decimal point setting.INT16Read/write
HR5doc 0005HOUT2 proportional bandRaw integer; apply the decimal point setting.INT16Read/write
HR6doc 0006HIntegral timeINT16Read/write
HR7doc 0007HDerivative timeINT16Read/write
HR8doc 0008HOUT1 proportional cycleINT16Read/write
HR9doc 0009HOUT2 proportional cycleINT16Read/write
HR11doc 000BHAlarm 1 valueRaw integer; apply the decimal point setting.INT16Read/write
HR12doc 000CHAlarm 2 valueRaw integer; apply the decimal point setting.INT16Read/write
HR15doc 000FHHeater burnout alarm valueRaw integer; apply the decimal point setting.INT16Read/write
HR18doc 0012HSet value lockINT16Read/write0 = Unlock; 1 = Lock 1; 2 = Lock 2; 3 = Lock 3
HR21doc 0015HSensor correctionRaw integer; apply the decimal point setting.INT16Read/write
HR22doc 0016HOverlap/dead bandINT16Read/write
HR24doc 0018HScaling high limitRaw integer; apply the decimal point setting.INT16Read/write
HR25doc 0019HScaling low limitRaw integer; apply the decimal point setting.INT16Read/write
HR26doc 001AHDecimal point placeINT16Read/write0 = xxxx; 1 = xxx.x; 2 = xx.xx; 3 = x.xxx
HR27doc 001BHPV filter time constantRaw integer; apply the decimal point setting.INT16Read/write
HR28doc 001CHOUT1 high limitINT16Read/write
HR29doc 001DHOUT1 low limitINT16Read/write
HR30doc 001EHOUT1 ON/OFF hysteresisRaw integer; apply the decimal point setting.INT16Read/write
HR31doc 001FHOUT2 cooling methodINT16Read/write0 = Air cooling; 1 = Oil cooling; 2 = Water cooling
HR32doc 0020HOUT2 high limitINT16Read/write
HR33doc 0021HOUT2 low limitINT16Read/write
HR34doc 0022HOUT2 ON/OFF hysteresisRaw integer; apply the decimal point setting.INT16Read/write
HR35doc 0023HAlarm 1 typeChanging the type resets the alarm value to 0.INT16Read/write0 = No alarm action; 1 = High limit alarm; 2 = Low limit alarm; 3 = High/Low limits alarm; 4 = High/Low limit range alarm; 5 = Process high alarm; 6 = Process low alarm; 7 = High limit with standby; 8 = Low limit with standby; 9 = High/Low limits with standby
HR36doc 0024HAlarm 2 typeChanging the type resets the alarm value to 0.INT16Read/write0 = No alarm action; 1 = High limit alarm; 2 = Low limit alarm; 3 = High/Low limits alarm; 4 = High/Low limit range alarm; 5 = Process high alarm; 6 = Process low alarm; 7 = High limit with standby; 8 = Low limit with standby; 9 = High/Low limits with standby
HR37doc 0025HAlarm 1 hysteresisRaw integer; apply the decimal point setting.INT16Read/write
HR38doc 0026HAlarm 2 hysteresisRaw integer; apply the decimal point setting.INT16Read/write
HR41doc 0029HAlarm 1 delay timeINT16Read/write
HR42doc 002AHAlarm 2 delay timeINT16Read/write
HR50doc 0032HIndication when output OFFINT16Read/write0 = OFF indication; 1 = No indication; 2 = PV indication; 3 = PV + active alarm outputs
HR51doc 0033HSV rise rateRaw integer; apply the decimal point setting.INT16Read/write
HR52doc 0034HSV fall rateRaw integer; apply the decimal point setting.INT16Read/write
HR55doc 0037HControl output OFF functionINT16Read/write0 = Control output ON; 1 = Control output OFF
HR56doc 0038HAuto/manual controlINT16Read/write0 = Automatic control; 1 = Manual control
HR57doc 0039HManual control MVAccepted only in manual control.INT16Read/write
HR64doc 0040HAlarm 1 energized/de-energizedINT16Read/write0 = Energized; 1 = De-energized
HR65doc 0041HAlarm 2 energized/de-energizedINT16Read/write0 = Energized; 1 = De-energized
HR68doc 0044HInput typeINT16Read/write0 = K -200 to 1370; 1 = K -200.0 to 400.0; 2 = J -200 to 1000; 3 = R 0 to 1760; 4 = S 0 to 1760; 5 = B 0 to 1820; 6 = E -200 to 800; 7 = T -200.0 to 400.0; 8 = N -200 to 1300; 9 = PL-II 0 to 1390; 10 = C (W/Re5-26) 0 to 2315; 11 = Pt100 -200.0 to 850.0; 12 = JPt100 -200.0 to 500.0; 13 = Pt100 -200 to 850; 14 = JPt100 -200 to 500; 15 = K -320 to 2500; 16 = K -320.0 to 750.0; 17 = J -320 to 1800; 18 = R 0 to 3200; 19 = S 0 to 3200; 20 = B 0 to 3300; 21 = E -320 to 1500; 22 = T -320.0 to 750.0; 23 = N -320 to 2300; 24 = PL-II 0 to 2500; 25 = C (W/Re5-26) 0 to 4200; 26 = Pt100 -320.0 to 1500.0; 27 = JPt100 -320.0 to 900.0; 28 = Pt100 -320 to 1500; 29 = JPt100 -320 to 900; 30 = 4-20 mA -2000 to 10000; 31 = 0-20 mA -2000 to 10000; 32 = 0-1 V -2000 to 10000; 33 = 0-5 V -2000 to 10000; 34 = 1-5 V -2000 to 10000; 35 = 0-10 V -2000 to 10000
HR69doc 0045HDirect/reverse control actionINT16Read/write0 = Reverse (heating); 1 = Direct (cooling)
HR71doc 0047HAT biasINT16Read/write
HR72doc 0048HARWAnti-reset windup.INT16Read/write
HR73doc 0049HHeater burnout alarm 2 valueRaw integer; apply the decimal point setting.INT16Read/write
HR74doc 004AHOUT1 rate-of-changeINT16Read/write
HR80doc 0050HBacklight selectionINT16Read/write0 = All; 1 = PV display; 2 = SV display; 3 = Action indicators; 4 = PV + SV displays; 5 = PV + action indicators; 6 = SV + action indicators
HR81doc 0051HPV colorINT16Read/write0 = Green; 1 = Red; 2 = Orange; 3 = Alarm ON: green to red; 4 = Alarm ON: orange to red; 5 = Changes continuously; 6 = Changes continuously + alarm ON red
HR82doc 0052HPV color rangeRaw integer; apply the decimal point setting.INT16Read/write
HR83doc 0053HBacklight timeINT16Read/write
HR112doc 0070HKey operation change flag clearingINT16Write0 = No action; 1 = Clear all
HR128doc 0080HPVProcess value. Raw integer; apply the decimal point setting.INT16Read
HR129doc 0081HOUT1 MVDecimal point ignored.INT16Read
HR130doc 0082HOUT2 MVDecimal point ignored.INT16Read
HR131doc 0083HSV in use (ramping)SV while it rises or falls. Raw integer; apply the decimal point setting.INT16Read
HR133doc 0085HStatus flagBITMAP16Readbit 0 = OUT1 on; bit 1 = OUT2 on; bit 2 = Alarm 1 output on; bit 3 = Alarm 2 output on; bit 6 = Heater burnout alarm output on; bit 8 = Overscale; bit 9 = Underscale; bit 10 = Control output OFF; bit 11 = AT/Auto-reset running; bit 12 = OUT/OFF key = Auto/Manual (0 = output OFF function); bit 14 = Manual control; bit 15 = Settings changed by keypad
HR134doc 0086HCT1 current valueHeater current, decimal point ignored.INT16Read
HR135doc 0087HCT2 current valueHeater current, decimal point ignored.INT16Read
HR161doc 00A1HUnit specification flagBITMAP16Readbit 0 = Set value memory external selection; bit 1 = Serial communication; bit 2 = Heater burnout function; bit 3 = HB rated current 50 A (0 = 20 A); bit 4 = HB 3-phase (0 = single phase); bit 5 = Alarm 2 output; bit 6 = Heat/cool output

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Shinko Technos ACS-13A digital indicating controller (C5 option)

What Modbus registers does the Shinko Technos ACS-13A digital indicating controller (C5 option) have?

This map lists 58 registers: 58 holding registers. 50 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Shinko Technos ACS-13A digital indicating controller (C5 option) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Registers are listed as hex data items (0001H) that go into the request unchanged. The manual adds that the matching Modicon holding-register number is the item in decimal plus 40001 (0001H = 40002).

What are the minimum Modbus registers to integrate the Shinko Technos ACS-13A digital indicating controller (C5 option)?

Start with HR 128 PV (Process value); HR 1 SV (Set value); HR 129 OUT1 MV (OUT1 manipulated value); HR 133 Status flag (Output, alarm and error status); HR 55 Control output OFF function (Control output on/off); HR 26 Decimal point place (Decimal point for scaling).

How do I enable Modbus control of the Shinko Technos ACS-13A digital indicating controller (C5 option)?

Requires the C5 option. In the communication settings choose MODBUS RTU, an instrument number, speed, Data bit/Parity (use an 8-bit choice for RTU) and stop bit.

Where is the official Shinko Technos ACS-13A digital indicating controller (C5 option) Modbus documentation?

The source is Communication Instruction Manual ACS-13A (C5) (No. ACS12CE5), revision 2019-08, published free by Shinko Technos at https://shinko-technos.co.jp/e/manual/english/ACS12CE5.pdf.

More Shinko Technos Modbus register maps

Other temperature & process controllers register maps

All temperature & process controllers Modbus register maps →

Source: Communication Instruction Manual ACS-13A (C5) · No. ACS12CE5 · rev. 2019-08. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.