Sensor (program temperature controller) · Modbus register map
Yokogawa UTAdvanced UP55A program controller Modbus register map
Updated 19 November 2026
The UP55A is the UTAdvanced program (ramp/soak) controller with up to 30 patterns and two loops. Its D registers map one-to-one onto Modbus holding registers over RS-485 (Modbus RTU/ASCII) or Modbus/TCP on Ethernet models. This map covers process data, program status and events, the current PID group and the program operation commands.
This page lists 51 Modbus registers for the Yokogawa UTAdvanced UP55A program controller — 21 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Yokogawa’s own free documentation (linked below) and checked against it.
- Manufacturer
- Yokogawa
- Model
- UTAdvanced UP55A program controller
- Equipment type
- Sensor (program temperature controller)
- Registers
- 51 (21 writable)
- Transport
- Modbus RTU, Modbus ASCII, Modbus TCP
- Default unit ID
- 1
- Default serial
- 19200 baud, 8E1
- TCP port
- 502
- Documented addressing
- 1-based (subtract 1 for the wire address)
- Also known as
- UP55A
Integration notes: Yokogawa UTAdvanced UP55A program controller
Select a pattern with D2322 and start it with D2316 = 1 (PROG); stop with 0 (RESET). Poll D2003-D2008 for PV, SP, output and mode, D2015-D2017 for pattern, segment and remaining time, and D2040/D2041 for time events.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 2002 | PV_L1 loop-1 measured value | INT16 | Loop-1 PV (D2003) | Read |
| HR 2003 | CSP_L1 loop-1 control setpoint | INT16 | Loop-1 SP (D2004) | Read |
| HR 2007 | MOD_L1 loop-1 operation mode status (UP55A) | BITMAP16 | Operation mode status (D2008) | Read |
| HR 2015 | SEG.N current segment number | UINT16 | Current segment (D2016) | Read |
| HR 2010 | ALM_L1 loop-1 alarm 1-8 status | BITMAP16 | Alarm status (D2011) | Read |
| HR 2315 | MODE program operation mode | UINT16 | Program MODE (D2316) | Read/write |
| HR 2321 | PTNO. program pattern number selection | UINT16 | Pattern number (D2322) | Read/write |
Enable Modbus control & writes
Set the communication setup parameters (protocol MBRTU or MBASC, baud, parity, stop bits, data length, address) on the keypad. Ethernet models use Modbus/TCP on port 502 by default.
Byte order & addressing
- Address D register n at wire address n-1.
- Write values without the decimal point (50.0 with one decimal place = 500).
Network setup
- Factory defaults: Modbus RTU, 19200 bps, even parity, 1 stop bit, 8 data bits, address 1.
Watch out for
- HOLD (D2317) and ADV (D2318) are program-operation items: write them while a program is running.
Yokogawa UTAdvanced UP55A program controller Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 2000doc D2001 | AD1.E A/D converter error status 1 | BITMAP16 | Read | bit 0 = PV input A/D converter error; bit 1 = RSP input (E1) A/D converter error; bit 2 = AIN2 input (E2) A/D converter error; bit 4 = AIN4 input (E4) A/D converter error; bit 5 = PV input RJC error; bit 6 = RSP input RJC error; bit 8 = PV input burnout error; bit 9 = RSP input (E1) burnout error; bit 10 = AIN2 input (E2) burnout error; bit 12 = AIN4 input (E4) burnout error | ||||
| HR | 2001doc D2002 | PV1.E_L1 loop-1 PV input error status | BITMAP16 | Read | bit 0 = Loop-1 PV input burnout; bit 1 = Loop-1 RSP input burnout; bit 2 = Burnout of RSP input used for control; bit 4 = Loop-1 PV over-scale; bit 5 = Loop-1 PV under-scale; bit 14 = Loop-1 auto-tuning timeout error | ||||
| HR | 2002doc D2003 | PV_L1 loop-1 measured value | Engineering value without decimal point; position set by the PV input decimal point. | INT16 | Read | ||||
| HR | 2003doc D2004 | CSP_L1 loop-1 control setpoint | Engineering value without decimal point; position set by the PV input decimal point. | INT16 | Read | ||||
| HR | 2004doc D2005 | OUT_L1 loop-1 control output | -5.0 to 105.0 %. | INT16 | × 0.1 | % | Read | ||
| HR | 2005doc D2006 | H.OUT_L1 heating-side output | Heating/cooling control. | INT16 | × 0.1 | % | Read | ||
| HR | 2006doc D2007 | C.OUT_L1 cooling-side output | 0.0 to 105.0 %. | INT16 | × 0.1 | % | Read | ||
| HR | 2007doc D2008 | MOD_L1 loop-1 operation mode status (UP55A) | BITMAP16 | Read | bit 0 = A.M (0 AUTO, 1 MAN); bit 4 = Program reset; bit 5 = Program operation; bit 6 = Local operation; bit 8 = Remote-mode operation; bit 9 = Output tracking; bit 10 = Advance of segment; bit 12 = Pause (hold); bit 13 = Wait; bit 14 = Auto-tuning ON | ||||
| HR | 2008doc D2009 | PID_L1 current PID number (loop 1) | Bits 0-3 hold the PID number; reads 0 for reference PID. | UINT16 | Read | ||||
| HR | 2010doc D2011 | ALM_L1 loop-1 alarm 1-8 status | BITMAP16 | Read | bit 0 = Alarm 1 ON (loop 1); bit 1 = Alarm 2 ON; bit 2 = Alarm 3 ON; bit 4 = Alarm 4 ON; bit 5 = Alarm 5 ON; bit 6 = Alarm 6 ON; bit 8 = Alarm 7 ON; bit 9 = Alarm 8 ON | ||||
| HR | 2012doc D2013 | ALM_L2 loop-2 alarm 1-8 status | BITMAP16 | Read | bit 0 = Alarm 1 ON (loop 2); bit 1 = Alarm 2 ON; bit 2 = Alarm 3 ON; bit 4 = Alarm 4 ON; bit 5 = Alarm 5 ON; bit 6 = Alarm 6 ON; bit 8 = Alarm 7 ON; bit 9 = Alarm 8 ON | ||||
| HR | 2014doc D2015 | C.PTNO. current program pattern number | 0-30. | UINT16 | Read | ||||
| HR | 2015doc D2016 | SEG.N current segment number | 0 = not executing, 1-99. | UINT16 | Read | ||||
| HR | 2016doc D2017 | SEG_RTIME remaining segment time | 0-59999; elapsed time during wait. Unit (min or s) set by TMU. | UINT16 | Read | ||||
| HR | 2018doc D2019 | PV_L2 loop-2 measured value | Engineering value without decimal point; position set by the PV input decimal point. | INT16 | Read | ||||
| HR | 2019doc D2020 | CSP_L2 loop-2 control setpoint | Engineering value without decimal point; position set by the PV input decimal point. | INT16 | Read | ||||
| HR | 2020doc D2021 | OUT_L2 loop-2 control output | -5.0 to 105.0 %. | INT16 | × 0.1 | % | Read | ||
| HR | 2023doc D2024 | MOD_L2 loop-2 operation mode status (UP55A) | BITMAP16 | Read | bit 0 = A.M_L2 (0 AUTO, 1 MAN); bit 8 = LC_L2 (0 cascade, 1 local LSP); bit 14 = Loop-2 auto-tuning ON | ||||
| HR | 2032doc D2033 | CTSP_L1 loop-1 final target setpoint | Engineering value without decimal point; position set by the PV input decimal point. | INT16 | Read | ||||
| HR | 2033doc D2034 | CTSP_L2 loop-2 final target setpoint | Engineering value without decimal point; position set by the PV input decimal point. | INT16 | Read | ||||
| HR | 2034doc D2035 | DEV_L1 loop-1 deviation | Engineering value of span without decimal point. | INT16 | Read | ||||
| HR | 2038doc D2039 | PV_EV PV event status | BITMAP16 | Read | bit 0 = PV event 1 ON; bit 1 = PV event 2 ON; bit 2 = PV event 3 ON; bit 4 = PV event 4 ON; bit 5 = PV event 5 ON; bit 6 = PV event 6 ON; bit 8 = PV event 7 ON; bit 9 = PV event 8 ON | ||||
| HR | 2039doc D2040 | TIME_EV_1 time event status 1 | Time events 1-8. | BITMAP16 | Read | bit 0 = Time event 1 ON; bit 1 = Time event 2 ON; bit 2 = Time event 3 ON; bit 4 = Time event 4 ON; bit 5 = Time event 5 ON; bit 6 = Time event 6 ON; bit 8 = Time event 7 ON; bit 9 = Time event 8 ON | |||
| HR | 2040doc D2041 | TIME_EV_2 time event status 2 | Time events 9-16. | BITMAP16 | Read | bit 0 = Time event 9 ON; bit 1 = Time event 10 ON; bit 2 = Time event 11 ON; bit 4 = Time event 12 ON; bit 5 = Time event 13 ON; bit 6 = Time event 14 ON; bit 8 = Time event 15 ON; bit 9 = Time event 16 ON | |||
| HR | 2043doc D2044 | SEG_USE segments in selected pattern | 0-99. | UINT16 | Read | ||||
| HR | 2047doc D2048 | NOW_RST repeat start segment | 1-99. | UINT16 | Read | ||||
| HR | 2048doc D2049 | NOW_REN repeat end segment | 1-99. | UINT16 | Read | ||||
| HR | 2060doc D2061 | HC1 heater break alarm-1 current | 0.0-360.0 A rms. | INT16 | × 0.1 | A | Read | ||
| HR | 2061doc D2062 | HC2 heater break alarm-2 current | 0.0-360.0 A rms. | INT16 | × 0.1 | A | Read | ||
| HR | 2067doc D2068 | PA.ER parameter error status | BITMAP16 | Read | bit 0 = System data error; bit 1 = Calibration value error; bit 2 = User default value error; bit 4 = Setup parameter error; bit 5 = Operation parameter error; bit 6 = Program pattern error; bit 8 = Faulty FRAM; bit 10 = Control parameter error | ||||
| HR | 2113doc D2114 | P_L1 proportional band | 0.0-999.9 %, current PID group. | UINT16 | × 0.1 | % | Read/write | ||
| HR | 2114doc D2115 | I_L1 integral time | 0 = off, 1-6000 s. | UINT16 | s | Read/write | |||
| HR | 2115doc D2116 | D_L1 derivative time | 0 = off, 1-6000 s. | UINT16 | s | Read/write | |||
| HR | 2116doc D2117 | OH_L1 control output high limit | INT16 | × 0.1 | % | Read/write | |||
| HR | 2117doc D2118 | OL_L1 control output low limit | INT16 | × 0.1 | % | Read/write | |||
| HR | 2123doc D2124 | DR_L1 direct/reverse action | UINT16 | Read/write | 0 = RVS reverse action; 1 = DIR direct action | ||||
| HR | 2200doc D2201 | LSP_L1 loop-1 local target setpoint | Setpoint for local-mode operation. Engineering value without decimal point; position set by the PV input decimal point. | INT16 | Read/write | ||||
| HR | 2201doc D2202 | LSP_L2 loop-2 local target setpoint | INT16 | Read/write | |||||
| HR | 2202doc D2203 | L.PID PID number for local-mode operation | 1-8. | UINT16 | Read/write | ||||
| HR | 2307doc D2308 | AT_L1 loop-1 auto-tuning switch | 0 = off, 1-8 = tune into that PID, 9 = reference PID. | UINT16 | Read/write | ||||
| HR | 2313doc D2314 | TRK_ON_L1 output tracking | UINT16 | Read/write | 0 = OFF; 1 = ON | ||||
| HR | 2315doc D2316 | MODE program operation mode | Start/stop program, local or remote operation. | UINT16 | Read/write | 0 = RESET (stop program); 1 = PROG (start program); 2 = LOCAL (start local-mode operation); 3 = REM (start remote-mode operation) | |||
| HR | 2316doc D2317 | HOLD program pause | UINT16 | Read/write | 0 = OFF (release pause); 1 = ON (pause) | ||||
| HR | 2317doc D2318 | ADV advance segment | Write 1 to jump to the next segment. | UINT16 | Read/write | 1 = Advance | |||
| HR | 2318doc D2319 | A.M_L1 loop-1 AUTO/MAN switch | UINT16 | Read/write | 0 = AUTO; 1 = MAN | ||||
| HR | 2319doc D2320 | A.M_L2 loop-2 AUTO/MAN switch | UINT16 | Read/write | 0 = AUTO; 1 = MAN | ||||
| HR | 2320doc D2321 | L.C loop-2 local/cascade switch | UINT16 | Read/write | 0 = CAS; 1 = LSP (local) | ||||
| HR | 2321doc D2322 | PTNO. program pattern number selection | 0 = none, 1-30. | UINT16 | Read/write | ||||
| HR | 2330doc D2331 | C.RSP_L1 loop-1 communication remote setpoint | Engineering value without decimal point; position set by the PV input decimal point. | INT16 | Read/write | ||||
| HR | 2332doc D2333 | MOUT_L1 loop-1 manual output | Output in MAN mode. | INT16 | × 0.1 | % | Read/write | ||
| HR | 2336doc D2337 | H.SP_L1 loop-1 SP for HOLD state | Engineering value without decimal point; position set by the PV input decimal point. | INT16 | Read/write |
Notes on this map
- All registers are 16-bit. Values are sent without their decimal point: PV/SP-type values follow the input's decimal point setting, percentages carry one decimal (scale 0.1).
- Only registers whose UP55A column shows R or R/W are listed. D2001-D2100 are read-only.
- D2045-D2047 (pattern repeat counters) are left out because the source gives two of them the same description.
- Program pattern data (D8001-D9000), the GREEN-series compatible area (D0001-D2000) and setup parameters (D2501 onward) are not included.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Yokogawa UTAdvanced UP55A program controller
What Modbus registers does the Yokogawa UTAdvanced UP55A program controller have?
This map lists 51 registers: 51 holding registers. 21 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Yokogawa UTAdvanced UP55A program controller Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual lists D register numbers (D2003). The Modbus reference number replaces the D with 4 (42003) and the wire address is that minus 40001, printed in the table's H No. column (D2003 = 07D2H).
What are the minimum Modbus registers to integrate the Yokogawa UTAdvanced UP55A program controller?
Start with HR 2002 PV_L1 loop-1 measured value (Loop-1 PV (D2003)); HR 2003 CSP_L1 loop-1 control setpoint (Loop-1 SP (D2004)); HR 2007 MOD_L1 loop-1 operation mode status (UP55A) (Operation mode status (D2008)); HR 2015 SEG.N current segment number (Current segment (D2016)); HR 2010 ALM_L1 loop-1 alarm 1-8 status (Alarm status (D2011)); HR 2315 MODE program operation mode (Program MODE (D2316)); HR 2321 PTNO. program pattern number selection (Pattern number (D2322)).
How do I enable Modbus control of the Yokogawa UTAdvanced UP55A program controller?
Set the communication setup parameters (protocol MBRTU or MBASC, baud, parity, stop bits, data length, address) on the keypad. Ethernet models use Modbus/TCP on port 502 by default.
Where is the official Yokogawa UTAdvanced UP55A program controller Modbus documentation?
The source is UTAdvanced Series Communication Interface (RS-485, Ethernet) User's Manual (IM 05P07A01-01EN 13th Edition), revision 2026-03, published free by Yokogawa at https://web-material3.yokogawa.com/IM05P07A01-01EN.pdf.
More Yokogawa Modbus register maps
- Sensor (digital indicator with alarms)
Yokogawa UTAdvanced UM33A digital indicator with alarms
Yokogawa UM33A indicators with RS-485 (Modbus RTU/ASCII); process monitoring D registers from IM 05P07A01-01EN chapter 10.
Also known as: UM33A - Sensor (program temperature controller)
Yokogawa UTAdvanced UP35A / UP32A program controller
Yokogawa UP35A and UP32A single-loop program controllers with RS-485 or Ethernet communication; D-register map from IM 05P07A01-01EN chapter 8 (UP35A/UP32A columns).
Also known as: UP35A, UP32A - Sensor (digital indicating temperature controller)
Yokogawa UTAdvanced UT35A / UT32A digital indicating controller
Yokogawa UT35A and UT32A single-loop controllers with RS-485 or Ethernet communication; D-register map from IM 05P07A01-01EN chapter 8 (UT32A-D loop 2 and UP35A/UP32A program items excluded).
Also known as: UT35A, UT32A, UT35A/MDL, UT32A/MDL - Sensor (limit controller)
Yokogawa UTAdvanced UT35A-L limit controller
Yokogawa UT35A-L limit controllers with RS-485 (Modbus RTU/ASCII); process monitoring D registers from IM 05P07A01-01EN chapter 12.
Also known as: UT35A-L - Sensor (digital indicating temperature controller)
Yokogawa UTAdvanced UT55A / UT52A digital indicating controller
Yokogawa UT55A and UT52A one- or two-loop controllers with RS-485 or Ethernet communication; D-register map from IM 05P07A01-01EN chapter 6 (UP55A program items excluded).
Also known as: UT55A, UT52A - Sensor (digital indicating temperature controller)
Yokogawa UTAdvanced UT75A digital indicating controller
Yokogawa UT75A one- or two-loop controller with RS-485 or Ethernet communication; D-register map from IM 05P07A01-01EN chapter 14.
Also known as: UT75A
Other temperature & process controllers register maps
- Sensor (digital process controller)
Fuji Electric PXH digital controller (Modbus RTU, monitoring map)
Fuji Electric PXH digital controllers on the RS-485 Modbus port; read-only monitoring registers from manual INP-TN514207c-E.
Also known as: PXH - Sensor (digital temperature controller)
Shinko Technos ACD-13A / ACR-13A / ACD-15A / ACR-15A digital indicating controller (C, C5 options)
Shinko ACD/ACR-13A (PID) and ACD/ACR-15A (valve positioning) with the C or C5 communication option; manual No.ACDR1CE8.
Also known as: ACD-13A, ACR-13A, ACD-15A, ACR-15A - Sensor (digital temperature controller)
Shinko Technos JCL-33A digital indicating controller (C5 option)
Shinko JCL-33A with the C5 option, protocol set to plain 'Modbus RTU mode' or 'Modbus ASCII mode' (not the Block Read/Write modes, which use another layout); manual No.JCL3CE3.
Also known as: JCL-33A-C5, JCL-33A C5 - Sensor / controller (PID temperature controller)
Autonics TK series PID temperature controller (Modbus RTU)
Autonics TK series heating/cooling PID temperature controllers with RS-485, communication manual MCT-TKC1-V2.2-EN.
Also known as: TK4S, TK4M, TK4H, TK4W, TK4L, TK4S-14RR, TK4 - Sensor (modular temperature controller)
RKC Instrument SRX module type controller, TIO temperature control module (Modbus RTU)
RKC SRX two-channel temperature control (TIO) modules, basic type X-TIO-A and extension type X-TIO-B, with Modbus selected; DI and DO module maps are not included.
Also known as: SRX, X-TIO-A, X-TIO-B, SRX TIO module, RKC SRX - Sensor (digital temperature controller)
Shinko Technos FC series digital indicating controller (C/C5 option, Modbus ASCII)
Shinko FCS-23A, FCR-13A, FCR-23A and FCD-13A with the C or C5 serial option; FCR-15A and FCD-15A have no Modbus (Shinko protocol only). Manual No.FC1CE11.
Also known as: FCS-23A, FCR-13A, FCR-23A, FCD-13A
All temperature & process controllers Modbus register maps →
Source: UTAdvanced Series Communication Interface (RS-485, Ethernet) User's Manual · IM 05P07A01-01EN 13th Edition · rev. 2026-03. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.