Sensor (program temperature controller) · Modbus register map

Yokogawa UTAdvanced UP55A program controller Modbus register map

Updated 19 November 2026

Short answer

The UP55A is the UTAdvanced program (ramp/soak) controller with up to 30 patterns and two loops. Its D registers map one-to-one onto Modbus holding registers over RS-485 (Modbus RTU/ASCII) or Modbus/TCP on Ethernet models. This map covers process data, program status and events, the current PID group and the program operation commands.

This page lists 51 Modbus registers for the Yokogawa UTAdvanced UP55A program controller — 21 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Yokogawa’s own free documentation (linked below) and checked against it.

Manufacturer
Yokogawa
Model
UTAdvanced UP55A program controller
Equipment type
Sensor (program temperature controller)
Registers
51 (21 writable)
Transport
Modbus RTU, Modbus ASCII, Modbus TCP
Default unit ID
1
Default serial
19200 baud, 8E1
TCP port
502
Documented addressing
1-based (subtract 1 for the wire address)
Also known as
UP55A
Source document
UTAdvanced Series Communication Interface (RS-485, Ethernet) User's Manual · IM 05P07A01-01EN 13th Edition · rev. 2026-03
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Yokogawa UTAdvanced UP55A program controller

Integration in brief

Select a pattern with D2322 and start it with D2316 = 1 (PROG); stop with 0 (RESET). Poll D2003-D2008 for PV, SP, output and mode, D2015-D2017 for pattern, segment and remaining time, and D2040/D2041 for time events.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 2002PV_L1 loop-1 measured valueINT16Loop-1 PV (D2003)Read
HR 2003CSP_L1 loop-1 control setpointINT16Loop-1 SP (D2004)Read
HR 2007MOD_L1 loop-1 operation mode status (UP55A)BITMAP16Operation mode status (D2008)Read
HR 2015SEG.N current segment numberUINT16Current segment (D2016)Read
HR 2010ALM_L1 loop-1 alarm 1-8 statusBITMAP16Alarm status (D2011)Read
HR 2315MODE program operation modeUINT16Program MODE (D2316)Read/write
HR 2321PTNO. program pattern number selectionUINT16Pattern number (D2322)Read/write

Enable Modbus control & writes

Set the communication setup parameters (protocol MBRTU or MBASC, baud, parity, stop bits, data length, address) on the keypad. Ethernet models use Modbus/TCP on port 502 by default.

Byte order & addressing

Network setup

Watch out for

Yokogawa UTAdvanced UP55A program controller Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

51 of 51 shown
Yokogawa UTAdvanced UP55A program controller Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR2000doc D2001AD1.E A/D converter error status 1BITMAP16Readbit 0 = PV input A/D converter error; bit 1 = RSP input (E1) A/D converter error; bit 2 = AIN2 input (E2) A/D converter error; bit 4 = AIN4 input (E4) A/D converter error; bit 5 = PV input RJC error; bit 6 = RSP input RJC error; bit 8 = PV input burnout error; bit 9 = RSP input (E1) burnout error; bit 10 = AIN2 input (E2) burnout error; bit 12 = AIN4 input (E4) burnout error
HR2001doc D2002PV1.E_L1 loop-1 PV input error statusBITMAP16Readbit 0 = Loop-1 PV input burnout; bit 1 = Loop-1 RSP input burnout; bit 2 = Burnout of RSP input used for control; bit 4 = Loop-1 PV over-scale; bit 5 = Loop-1 PV under-scale; bit 14 = Loop-1 auto-tuning timeout error
HR2002doc D2003PV_L1 loop-1 measured valueEngineering value without decimal point; position set by the PV input decimal point.INT16Read
HR2003doc D2004CSP_L1 loop-1 control setpointEngineering value without decimal point; position set by the PV input decimal point.INT16Read
HR2004doc D2005OUT_L1 loop-1 control output-5.0 to 105.0 %.INT16× 0.1%Read
HR2005doc D2006H.OUT_L1 heating-side outputHeating/cooling control.INT16× 0.1%Read
HR2006doc D2007C.OUT_L1 cooling-side output0.0 to 105.0 %.INT16× 0.1%Read
HR2007doc D2008MOD_L1 loop-1 operation mode status (UP55A)BITMAP16Readbit 0 = A.M (0 AUTO, 1 MAN); bit 4 = Program reset; bit 5 = Program operation; bit 6 = Local operation; bit 8 = Remote-mode operation; bit 9 = Output tracking; bit 10 = Advance of segment; bit 12 = Pause (hold); bit 13 = Wait; bit 14 = Auto-tuning ON
HR2008doc D2009PID_L1 current PID number (loop 1)Bits 0-3 hold the PID number; reads 0 for reference PID.UINT16Read
HR2010doc D2011ALM_L1 loop-1 alarm 1-8 statusBITMAP16Readbit 0 = Alarm 1 ON (loop 1); bit 1 = Alarm 2 ON; bit 2 = Alarm 3 ON; bit 4 = Alarm 4 ON; bit 5 = Alarm 5 ON; bit 6 = Alarm 6 ON; bit 8 = Alarm 7 ON; bit 9 = Alarm 8 ON
HR2012doc D2013ALM_L2 loop-2 alarm 1-8 statusBITMAP16Readbit 0 = Alarm 1 ON (loop 2); bit 1 = Alarm 2 ON; bit 2 = Alarm 3 ON; bit 4 = Alarm 4 ON; bit 5 = Alarm 5 ON; bit 6 = Alarm 6 ON; bit 8 = Alarm 7 ON; bit 9 = Alarm 8 ON
HR2014doc D2015C.PTNO. current program pattern number0-30.UINT16Read
HR2015doc D2016SEG.N current segment number0 = not executing, 1-99.UINT16Read
HR2016doc D2017SEG_RTIME remaining segment time0-59999; elapsed time during wait. Unit (min or s) set by TMU.UINT16Read
HR2018doc D2019PV_L2 loop-2 measured valueEngineering value without decimal point; position set by the PV input decimal point.INT16Read
HR2019doc D2020CSP_L2 loop-2 control setpointEngineering value without decimal point; position set by the PV input decimal point.INT16Read
HR2020doc D2021OUT_L2 loop-2 control output-5.0 to 105.0 %.INT16× 0.1%Read
HR2023doc D2024MOD_L2 loop-2 operation mode status (UP55A)BITMAP16Readbit 0 = A.M_L2 (0 AUTO, 1 MAN); bit 8 = LC_L2 (0 cascade, 1 local LSP); bit 14 = Loop-2 auto-tuning ON
HR2032doc D2033CTSP_L1 loop-1 final target setpointEngineering value without decimal point; position set by the PV input decimal point.INT16Read
HR2033doc D2034CTSP_L2 loop-2 final target setpointEngineering value without decimal point; position set by the PV input decimal point.INT16Read
HR2034doc D2035DEV_L1 loop-1 deviationEngineering value of span without decimal point.INT16Read
HR2038doc D2039PV_EV PV event statusBITMAP16Readbit 0 = PV event 1 ON; bit 1 = PV event 2 ON; bit 2 = PV event 3 ON; bit 4 = PV event 4 ON; bit 5 = PV event 5 ON; bit 6 = PV event 6 ON; bit 8 = PV event 7 ON; bit 9 = PV event 8 ON
HR2039doc D2040TIME_EV_1 time event status 1Time events 1-8.BITMAP16Readbit 0 = Time event 1 ON; bit 1 = Time event 2 ON; bit 2 = Time event 3 ON; bit 4 = Time event 4 ON; bit 5 = Time event 5 ON; bit 6 = Time event 6 ON; bit 8 = Time event 7 ON; bit 9 = Time event 8 ON
HR2040doc D2041TIME_EV_2 time event status 2Time events 9-16.BITMAP16Readbit 0 = Time event 9 ON; bit 1 = Time event 10 ON; bit 2 = Time event 11 ON; bit 4 = Time event 12 ON; bit 5 = Time event 13 ON; bit 6 = Time event 14 ON; bit 8 = Time event 15 ON; bit 9 = Time event 16 ON
HR2043doc D2044SEG_USE segments in selected pattern0-99.UINT16Read
HR2047doc D2048NOW_RST repeat start segment1-99.UINT16Read
HR2048doc D2049NOW_REN repeat end segment1-99.UINT16Read
HR2060doc D2061HC1 heater break alarm-1 current0.0-360.0 A rms.INT16× 0.1ARead
HR2061doc D2062HC2 heater break alarm-2 current0.0-360.0 A rms.INT16× 0.1ARead
HR2067doc D2068PA.ER parameter error statusBITMAP16Readbit 0 = System data error; bit 1 = Calibration value error; bit 2 = User default value error; bit 4 = Setup parameter error; bit 5 = Operation parameter error; bit 6 = Program pattern error; bit 8 = Faulty FRAM; bit 10 = Control parameter error
HR2113doc D2114P_L1 proportional band0.0-999.9 %, current PID group.UINT16× 0.1%Read/write
HR2114doc D2115I_L1 integral time0 = off, 1-6000 s.UINT16sRead/write
HR2115doc D2116D_L1 derivative time0 = off, 1-6000 s.UINT16sRead/write
HR2116doc D2117OH_L1 control output high limitINT16× 0.1%Read/write
HR2117doc D2118OL_L1 control output low limitINT16× 0.1%Read/write
HR2123doc D2124DR_L1 direct/reverse actionUINT16Read/write0 = RVS reverse action; 1 = DIR direct action
HR2200doc D2201LSP_L1 loop-1 local target setpointSetpoint for local-mode operation. Engineering value without decimal point; position set by the PV input decimal point.INT16Read/write
HR2201doc D2202LSP_L2 loop-2 local target setpointINT16Read/write
HR2202doc D2203L.PID PID number for local-mode operation1-8.UINT16Read/write
HR2307doc D2308AT_L1 loop-1 auto-tuning switch0 = off, 1-8 = tune into that PID, 9 = reference PID.UINT16Read/write
HR2313doc D2314TRK_ON_L1 output trackingUINT16Read/write0 = OFF; 1 = ON
HR2315doc D2316MODE program operation modeStart/stop program, local or remote operation.UINT16Read/write0 = RESET (stop program); 1 = PROG (start program); 2 = LOCAL (start local-mode operation); 3 = REM (start remote-mode operation)
HR2316doc D2317HOLD program pauseUINT16Read/write0 = OFF (release pause); 1 = ON (pause)
HR2317doc D2318ADV advance segmentWrite 1 to jump to the next segment.UINT16Read/write1 = Advance
HR2318doc D2319A.M_L1 loop-1 AUTO/MAN switchUINT16Read/write0 = AUTO; 1 = MAN
HR2319doc D2320A.M_L2 loop-2 AUTO/MAN switchUINT16Read/write0 = AUTO; 1 = MAN
HR2320doc D2321L.C loop-2 local/cascade switchUINT16Read/write0 = CAS; 1 = LSP (local)
HR2321doc D2322PTNO. program pattern number selection0 = none, 1-30.UINT16Read/write
HR2330doc D2331C.RSP_L1 loop-1 communication remote setpointEngineering value without decimal point; position set by the PV input decimal point.INT16Read/write
HR2332doc D2333MOUT_L1 loop-1 manual outputOutput in MAN mode.INT16× 0.1%Read/write
HR2336doc D2337H.SP_L1 loop-1 SP for HOLD stateEngineering value without decimal point; position set by the PV input decimal point.INT16Read/write

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Yokogawa UTAdvanced UP55A program controller

What Modbus registers does the Yokogawa UTAdvanced UP55A program controller have?

This map lists 51 registers: 51 holding registers. 21 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Yokogawa UTAdvanced UP55A program controller Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual lists D register numbers (D2003). The Modbus reference number replaces the D with 4 (42003) and the wire address is that minus 40001, printed in the table's H No. column (D2003 = 07D2H).

What are the minimum Modbus registers to integrate the Yokogawa UTAdvanced UP55A program controller?

Start with HR 2002 PV_L1 loop-1 measured value (Loop-1 PV (D2003)); HR 2003 CSP_L1 loop-1 control setpoint (Loop-1 SP (D2004)); HR 2007 MOD_L1 loop-1 operation mode status (UP55A) (Operation mode status (D2008)); HR 2015 SEG.N current segment number (Current segment (D2016)); HR 2010 ALM_L1 loop-1 alarm 1-8 status (Alarm status (D2011)); HR 2315 MODE program operation mode (Program MODE (D2316)); HR 2321 PTNO. program pattern number selection (Pattern number (D2322)).

How do I enable Modbus control of the Yokogawa UTAdvanced UP55A program controller?

Set the communication setup parameters (protocol MBRTU or MBASC, baud, parity, stop bits, data length, address) on the keypad. Ethernet models use Modbus/TCP on port 502 by default.

Where is the official Yokogawa UTAdvanced UP55A program controller Modbus documentation?

The source is UTAdvanced Series Communication Interface (RS-485, Ethernet) User's Manual (IM 05P07A01-01EN 13th Edition), revision 2026-03, published free by Yokogawa at https://web-material3.yokogawa.com/IM05P07A01-01EN.pdf.

More Yokogawa Modbus register maps

Other temperature & process controllers register maps

All temperature & process controllers Modbus register maps →

Source: UTAdvanced Series Communication Interface (RS-485, Ethernet) User's Manual · IM 05P07A01-01EN 13th Edition · rev. 2026-03. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.