Yokogawa UTAdvanced UT55A / UT52A digital indicating controller Modbus register map

Updated 19 November 2026

Short answer

The UT55A and UT52A are UTAdvanced PID controllers with up to two loops, heater-break and valve-position functions. Their data live in D registers that map one-to-one onto Modbus holding registers over RS-485 (Modbus RTU/ASCII) or Modbus/TCP on Ethernet models. This map covers the process data block, the current SP/PID group for both loops and the operation-mode switches.

This page lists 63 Modbus registers for the Yokogawa UTAdvanced UT55A / UT52A digital indicating controller — 32 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Yokogawa’s own free documentation (linked below) and checked against it.

Manufacturer
Yokogawa
Model
UTAdvanced UT55A / UT52A digital indicating controller
Equipment type
Sensor (digital indicating temperature controller)
Registers
63 (32 writable)
Transport
Modbus RTU, Modbus ASCII, Modbus TCP
Default unit ID
1
Default serial
19200 baud, 8E1
TCP port
502
Documented addressing
1-based (subtract 1 for the wire address)
Also known as
UT55A, UT52A
Source document
UTAdvanced Series Communication Interface (RS-485, Ethernet) User's Manual · IM 05P07A01-01EN 13th Edition · rev. 2026-03
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Yokogawa UTAdvanced UT55A / UT52A digital indicating controller

Integration in brief

Read D2001-D2013 in one block for errors, PV, SP, output and alarms; write the target setpoint to D2101 (loop 2: D2151) and switch AUTO/MAN, RUN/STOP and REMOTE/LOCAL with D2301, D2304 and D2306.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 2002PV_L1 loop-1 measured valueINT16Loop-1 PV (D2003)Read
HR 2003CSP_L1 loop-1 control setpointINT16Loop-1 control setpoint (D2004)Read
HR 2004OUT_L1 loop-1 control outputINT16Loop-1 output (D2005)Read
HR 2007MOD_L1 loop-1 operation mode status (UT55A/UT52A)BITMAP16Operation mode status (D2008)Read
HR 2010ALM_L1 loop-1 alarm 1-8 statusBITMAP16Loop-1 alarm status (D2011)Read
HR 2100SP_L1 loop-1 target setpointINT16Loop-1 target setpoint (D2101)Read/write
HR 2300A.M AUTO/MAN switchUINT16AUTO/MAN (D2301)Read/write
HR 2303S.R STOP/RUN switchUINT16RUN/STOP (D2304)Read/write

Enable Modbus control & writes

Set the communication setup parameters (protocol MBRTU or MBASC, baud, parity, stop bits, data length, address) on the keypad. Ethernet models use Modbus/TCP on port 502 by default.

Byte order & addressing

Network setup

Watch out for

Yokogawa UTAdvanced UT55A / UT52A digital indicating controller Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

63 of 63 shown
Yokogawa UTAdvanced UT55A / UT52A digital indicating controller Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR2000doc D2001AD1.E A/D converter error status 1BITMAP16Readbit 0 = PV input A/D converter error; bit 1 = RSP input (E1) A/D converter error; bit 2 = AIN2 input (E2) A/D converter error; bit 4 = AIN4 input (E4) A/D converter error; bit 5 = PV input RJC error; bit 6 = RSP input RJC error; bit 8 = PV input burnout error; bit 9 = RSP input (E1) burnout error; bit 10 = AIN2 input (E2) burnout error; bit 12 = AIN4 input (E4) burnout error
HR2001doc D2002PV1.E_L1 loop-1 PV input error statusBITMAP16Readbit 0 = Loop-1 PV input burnout; bit 1 = Loop-1 RSP input burnout; bit 2 = Burnout of RSP input used for control; bit 4 = Loop-1 PV over-scale; bit 5 = Loop-1 PV under-scale; bit 14 = Loop-1 auto-tuning timeout error
HR2002doc D2003PV_L1 loop-1 measured valueEngineering value without decimal point; position set by the PV input decimal point.INT16Read
HR2003doc D2004CSP_L1 loop-1 control setpointEngineering value without decimal point; position set by the PV input decimal point.INT16Read
HR2004doc D2005OUT_L1 loop-1 control output-5.0 to 105.0 %; valve opening in position-proportional control.INT16× 0.1%Read
HR2005doc D2006H.OUT_L1 heating-side outputHeating/cooling control.INT16× 0.1%Read
HR2006doc D2007C.OUT_L1 cooling-side output0.0 to 105.0 %.INT16× 0.1%Read
HR2007doc D2008MOD_L1 loop-1 operation mode status (UT55A/UT52A)BITMAP16Readbit 0 = A.M (0 AUTO, 1 MAN); bit 1 = R.L (0 local, 1 remote); bit 2 = S.R (0 run, 1 stop); bit 4 = CAS (cascade modes); bit 5 = AUTO (cascade modes); bit 6 = MAN (cascade modes); bit 8 = Output tracking; bit 14 = Auto-tuning ON
HR2008doc D2009PID_L1 current PID number (loop 1)Bits 0-3 hold the PID number; reads 0 for reference PID.UINT16Read
HR2009doc D2010CSPNO. current control setpoint numberBits 0-3 hold the SP number.UINT16Read
HR2010doc D2011ALM_L1 loop-1 alarm 1-8 statusBITMAP16Readbit 0 = Alarm 1 ON (loop 1); bit 1 = Alarm 2 ON; bit 2 = Alarm 3 ON; bit 4 = Alarm 4 ON; bit 5 = Alarm 5 ON; bit 6 = Alarm 6 ON; bit 8 = Alarm 7 ON; bit 9 = Alarm 8 ON
HR2011doc D2012LA.ER ladder error statusBITMAP16Readbit 0 = Corrupted ladder program; bit 1 = Ladder calculation overflow; bit 2 = Ladder program error; bit 4 = Load factor over 100 %; bit 5 = Load factor over 200 % (forced end)
HR2012doc D2013ALM_L2 loop-2 alarm 1-8 statusBITMAP16Readbit 0 = Alarm 1 ON (loop 2); bit 1 = Alarm 2 ON; bit 2 = Alarm 3 ON; bit 4 = Alarm 4 ON; bit 5 = Alarm 5 ON; bit 6 = Alarm 6 ON; bit 8 = Alarm 7 ON; bit 9 = Alarm 8 ON
HR2017doc D2018PV2.E_L2 loop-2 PV input error statusBITMAP16Readbit 0 = Loop-2 PV input burnout; bit 1 = Loop-2 RSP input burnout; bit 2 = Burnout of loop-2 RSP input used for control; bit 4 = Loop-2 PV over-scale; bit 5 = Loop-2 PV under-scale; bit 14 = Loop-2 auto-tuning timeout error
HR2018doc D2019PV_L2 loop-2 measured valueEngineering value without decimal point; position set by the PV input decimal point.INT16Read
HR2019doc D2020CSP_L2 loop-2 control setpointEngineering value without decimal point; position set by the PV input decimal point.INT16Read
HR2020doc D2021OUT_L2 loop-2 control output-5.0 to 105.0 %.INT16× 0.1%Read
HR2021doc D2022H.OUT_L2 loop-2 heating-side outputINT16× 0.1%Read
HR2022doc D2023C.OUT_L2 loop-2 cooling-side outputINT16× 0.1%Read
HR2023doc D2024MOD_L2 loop-2 operation mode status (UT55A/UT52A)BITMAP16Readbit 1 = R.L_L2 (0 local, 1 remote); bit 14 = Loop-2 auto-tuning ON
HR2034doc D2035DEV_L1 loop-1 deviation-105.0 to 105.0 % of span, sent as engineering value without decimal point.INT16Read
HR2035doc D2036DEV_L2 loop-2 deviationSame format as DEV_L1.INT16Read
HR2036doc D2037ALO_L1 loop-1 alarm output 1-8 status1 = relay contact closed.BITMAP16Readbit 0 = Alarm output 1 contact closed (loop 1); bit 1 = Alarm output 2 contact closed; bit 2 = Alarm output 3 contact closed; bit 4 = Alarm output 4 contact closed; bit 5 = Alarm output 5 contact closed; bit 6 = Alarm output 6 contact closed; bit 8 = Alarm output 7 contact closed; bit 9 = Alarm output 8 contact closed
HR2037doc D2038ALO_L2 loop-2 alarm output 1-8 status1 = relay contact closed.BITMAP16Readbit 0 = Alarm output 1 contact closed (loop 2); bit 1 = Alarm output 2 contact closed; bit 2 = Alarm output 3 contact closed; bit 4 = Alarm output 4 contact closed; bit 5 = Alarm output 5 contact closed; bit 6 = Alarm output 6 contact closed; bit 8 = Alarm output 7 contact closed; bit 9 = Alarm output 8 contact closed
HR2060doc D2061HC1 heater break alarm-1 current0.0-360.0 A rms.INT16× 0.1ARead
HR2061doc D2062HC2 heater break alarm-2 current0.0-360.0 A rms.INT16× 0.1ARead
HR2062doc D2063CT_AL heater break alarm statusBITMAP16Readbit 0 = Heater break alarm 1 ON; bit 1 = Heater break alarm 2 ON
HR2063doc D2064VALV valve statusPosition-proportional control.BITMAP16Readbit 0 = Estimating-type operation (0 = feedback input); bit 1 = Open output on; bit 2 = Close output on; bit 3 = Automatic valve position adjustment running
HR2064doc D2065AD2.E A/D converter error status 2BITMAP16Readbit 0 = Feedback input resistor/current burnout; bit 1 = Valve position automatic adjustment error
HR2067doc D2068PA.ER parameter error statusBITMAP16Readbit 0 = System data error; bit 1 = Calibration value error; bit 2 = User default value error; bit 4 = Setup parameter error; bit 5 = Operation parameter error; bit 8 = Faulty FRAM; bit 10 = Control parameter error
HR2069doc D2070OP.ER option error statusBITMAP16Readbit 0 = E1 terminal hardware not responding; bit 1 = E2 terminal hardware not responding; bit 2 = E3 terminal hardware not responding; bit 4 = E4 terminal hardware not responding; bit 8 = E1 communication error (UT52A); bit 10 = E3 communication error (UT55A); bit 12 = E4 communication error (UT55A)
HR2100doc D2101SP_L1 loop-1 target setpointCurrent SP group. Engineering value without decimal point; position set by the PV input decimal point.INT16Read/write
HR2101doc D2102SUB sub-target setpointOffset from SP in two-position two-level control.INT16Read/write
HR2102doc D2103PIDN_L1 loop-1 PID number selection1-8.UINT16Read/write
HR2103doc D2104A1_L1 loop-1 alarm-1 setpoint-19999 to 30000, decimal point per input.INT16Read/write
HR2104doc D2105A2_L1 loop-1 alarm-2 setpointINT16Read/write
HR2105doc D2106A3_L1 loop-1 alarm-3 setpointINT16Read/write
HR2106doc D2107A4_L1 loop-1 alarm-4 setpointINT16Read/write
HR2113doc D2114P_L1 proportional band0.0-999.9 % (heating side in heating/cooling).UINT16× 0.1%Read/write
HR2114doc D2115I_L1 integral time0 = off, 1-6000 s.UINT16sRead/write
HR2115doc D2116D_L1 derivative time0 = off, 1-6000 s.UINT16sRead/write
HR2116doc D2117OH_L1 control output high limitINT16× 0.1%Read/write
HR2117doc D2118OL_L1 control output low limitINT16× 0.1%Read/write
HR2118doc D2119MR_L1 manual resetUsed when integral time is off.INT16× 0.1%Read/write
HR2123doc D2124DR_L1 direct/reverse actionUINT16Read/write0 = RVS reverse action; 1 = DIR direct action
HR2132doc D2133PO_L1 preset outputOutput used in STOP mode, -5.0 to 105.0 %.INT16× 0.1%Read/write
HR2150doc D2151SP_L2 loop-2 target setpointSame as D2101 for loop 2.INT16Read/write
HR2163doc D2164P_L2 loop-2 proportional bandUINT16× 0.1%Read/write
HR2164doc D2165I_L2 loop-2 integral timeUINT16sRead/write
HR2165doc D2166D_L2 loop-2 derivative timeUINT16sRead/write
HR2300doc D2301A.M AUTO/MAN switchNot for cascade modes.UINT16Read/write0 = AUTO; 1 = MAN
HR2302doc D2303C.A.M CAS/AUTO/MAN switchCascade control modes.UINT16Read/write0 = AUTO; 1 = MAN; 2 = CAS
HR2303doc D2304S.R STOP/RUN switchPreset output is used in STOP.UINT16Read/write0 = RUN; 1 = STOP
HR2305doc D2306R.L_L1 loop-1 REMOTE/LOCAL switchUINT16Read/write0 = LCL (local); 1 = REM (remote)
HR2306doc D2307R.L_L2 loop-2 REMOTE/LOCAL switchUINT16Read/write0 = LCL (local); 1 = REM (remote)
HR2307doc D2308AT_L1 loop-1 auto-tuning switch0 = off, 1-8 = tune into that PID, 9 = reference PID.UINT16Read/write
HR2308doc D2309AT_L2 loop-2 auto-tuning switchSame as AT_L1.UINT16Read/write
HR2311doc D2312SPNO. SP number selection1-8.UINT16Read/write
HR2313doc D2314TRK_ON_L1 output trackingUINT16Read/write0 = OFF; 1 = ON
HR2330doc D2331C.RSP_L1 loop-1 communication remote setpointUsed when remote mode takes SP from comms. Engineering value without decimal point; position set by the PV input decimal point.INT16Read/write
HR2331doc D2332C.RSP_L2 loop-2 communication remote setpointINT16Read/write
HR2332doc D2333MOUT_L1 loop-1 manual outputHeating-side output in MAN mode.INT16× 0.1%Read/write
HR2334doc D2335MOUT_L2 loop-2 manual outputHeating-side output in MAN mode.INT16× 0.1%Read/write

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Yokogawa UTAdvanced UT55A / UT52A digital indicating controller

What Modbus registers does the Yokogawa UTAdvanced UT55A / UT52A digital indicating controller have?

This map lists 63 registers: 63 holding registers. 32 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Yokogawa UTAdvanced UT55A / UT52A digital indicating controller Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual lists D register numbers (D2003). The Modbus reference number replaces the D with 4 (42003) and the wire address is that minus 40001, printed in the table's H No. column (D2003 = 07D2H).

What are the minimum Modbus registers to integrate the Yokogawa UTAdvanced UT55A / UT52A digital indicating controller?

Start with HR 2002 PV_L1 loop-1 measured value (Loop-1 PV (D2003)); HR 2003 CSP_L1 loop-1 control setpoint (Loop-1 control setpoint (D2004)); HR 2004 OUT_L1 loop-1 control output (Loop-1 output (D2005)); HR 2007 MOD_L1 loop-1 operation mode status (UT55A/UT52A) (Operation mode status (D2008)); HR 2010 ALM_L1 loop-1 alarm 1-8 status (Loop-1 alarm status (D2011)); HR 2100 SP_L1 loop-1 target setpoint (Loop-1 target setpoint (D2101)); HR 2300 A.M AUTO/MAN switch (AUTO/MAN (D2301)); HR 2303 S.R STOP/RUN switch (RUN/STOP (D2304)).

How do I enable Modbus control of the Yokogawa UTAdvanced UT55A / UT52A digital indicating controller?

Set the communication setup parameters (protocol MBRTU or MBASC, baud, parity, stop bits, data length, address) on the keypad. Ethernet models use Modbus/TCP on port 502 by default.

Where is the official Yokogawa UTAdvanced UT55A / UT52A digital indicating controller Modbus documentation?

The source is UTAdvanced Series Communication Interface (RS-485, Ethernet) User's Manual (IM 05P07A01-01EN 13th Edition), revision 2026-03, published free by Yokogawa at https://web-material3.yokogawa.com/IM05P07A01-01EN.pdf.

More Yokogawa Modbus register maps

Other temperature & process controllers register maps

All temperature & process controllers Modbus register maps →

Source: UTAdvanced Series Communication Interface (RS-485, Ethernet) User's Manual · IM 05P07A01-01EN 13th Edition · rev. 2026-03. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.