- N20K48 modular process controller (Modbus RTU)
Sensor (process / temperature controller) · Modbus register map
Novus N20K48 modular process controller (Modbus RTU) Modbus register map
Updated 17 November 2026
The Novus N20K48 is a modular PID temperature and process controller with optional RS-485 Modbus RTU. All registers are 16-bit holding registers covering identity, input configuration, control, tuning, timers, alarms and ramp/soak programs. This map covers the setpoint, process variable, output, run/auto modes, input setup, tuning and alarm setpoints.
This page lists 38 Modbus registers for the Novus N20K48 modular process controller (Modbus RTU) — 33 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Novus’s own free documentation (linked below) and checked against it.
- Manufacturer
- Novus
- Model
- N20K48 modular process controller (Modbus RTU)
- Equipment type
- Sensor (process / temperature controller)
- Registers
- 38 (33 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Documented addressing
- 0-based (the number printed is the address on the wire)
- Firmware
- Protocol V1.0x
- Also known as
- Novus N20K48, N20K48 modular controller
Integration notes: Novus N20K48 modular process controller (Modbus RTU)
Poll 200-202 for setpoint, PV and output power. Write 200 to change the setpoint, 214 to run/stop control and 213 for manual/automatic.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 201 | CTRL_PV1 process variable | INT16 | Process variable | Read/write |
| HR 200 | CTRL_SP control setpoint | INT16 | Setpoint | Read/write |
| HR 202 | CTRL_MV1 control output power | INT16 | Output power 0.1 % | Read/write |
| HR 214 | CTRL_RUN run | UINT16 | Run control | Read/write |
| HR 213 | CTRL_AUTO control mode | UINT16 | Manual/automatic | Read/write |
| HR 279 | INPUT_DPPO decimal point position | UINT16 | Decimal point position | Read/write |
Enable Modbus control & writes
Fit the RS-485 option and set address and serial parameters on the controller.
Byte order & addressing
- Addresses are 0-based.
- Temperature PV is x10 regardless of the decimal-point setting.
Network setup
- Up to 247 controllers on one RS-485 line; terminals 3 (D1/D+/B), 2 (D0/D-/A), 1 (GND).
Watch out for
- Setpoint writes are limited to SPLL/SPHL (220/221).
Novus N20K48 modular process controller (Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0 | INFO_ID device ID | UINT16 | Read | |||||
| HR | 1 | INFO_FW_VERSION firmware version | UINT16 | Read | |||||
| HR | 2 | INFO_FW_RELEASE firmware release | UINT16 | Read | |||||
| HR | 74 | AI_ENABLE analog input enable | UINT16 | Read/write | 0 = No; 1 = Yes | ||||
| HR | 75 | AI_TYPE input sensor type | UINT16 | Read/write | 0 = T/C J; 1 = T/C K; 2 = T/C T; 3 = T/C N; 4 = T/C R; 5 = T/C S; 6 = T/C B; 7 = T/C E; 8 = Pt100; 9 = 0-20 mA; 10 = 4-20 mA; 11 = 0-50 mV; 12 = 0-5 V; 13 = 0-10 V | ||||
| HR | 76 | AI_FILTER input filter | One decimal place. | UINT16 | × 0.1 | s | Read/write | ||
| HR | 77 | AI_UNIT temperature unit | UINT16 | Read/write | 0 = °C; 1 = °F | ||||
| HR | 87 | AI_GRID_FREQ mains frequency | UINT16 | Read/write | 0 = 50 Hz; 1 = 60 Hz | ||||
| HR | 110 | PULSE_ENABLE pulse output enable | UINT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 111 | RELAY_ENABLE relay output enable | UINT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 112 | PULSE_STATE pulse output status | UINT16 | Read/write | |||||
| HR | 113 | RELAY_STATE relay output status | UINT16 | Read/write | |||||
| HR | 200 | CTRL_SP control setpoint | Main setpoint, between SPLL and SPHL; decimal point per INPUT_DPPO (279). | INT16 | Read/write | ||||
| HR | 201 | CTRL_PV1 process variable | Temperature inputs: always value x 10. Linear inputs: decimals per INPUT_DPPO. | INT16 | Read/write | ||||
| HR | 202 | CTRL_MV1 control output power | 0-1000 = 0.0-100.0 %, manual or automatic. | INT16 | × 0.1 | % | Read/write | ||
| HR | 210 | CTRL_REMOTE_SP_EN remote setpoint enable | UINT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 211 | CTRL_REMOTE_SP remote setpoint | Between SPLL and SPHL; decimal point per INPUT_DPPO. | INT16 | Read/write | ||||
| HR | 212 | CTRL_ACT control action | UINT16 | Read/write | 0 = Inverse; 1 = Direct | ||||
| HR | 213 | CTRL_AUTO control mode | UINT16 | Read/write | 0 = Manual; 1 = Automatic | ||||
| HR | 214 | CTRL_RUN run | UINT16 | Read/write | 0 = No; 1 = Yes | ||||
| HR | 215 | CTRL_IE_MV_ONOFF on/off output on input error | UINT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 226 | CTRL_SFST soft start time | 0-9999 s. | UINT16 | s | Read/write | |||
| HR | 257 | TUNE_AUTO auto-tuning mode | UINT16 | Read/write | 0 = Off; 1 = Fast auto-tune; 2 = Precise auto-tune; 3 = Self-adaptive + precise; 4 = Force new precise + self-adaptive; 5 = Force new precise when RUN or at power-up | ||||
| HR | 258 | TUNE_PB proportional band | Range 0-5000. | UINT16 | Read/write | ||||
| HR | 259 | TUNE_IR integral rate | Range 0-2400. | UINT16 | rep/min | Read/write | |||
| HR | 260 | TUNE_DT derivative time | Range 0-2400. | UINT16 | s | Read/write | |||
| HR | 261 | TUNE_CT PWM cycle time | Range 5-1000. | UINT16 | s | Read/write | |||
| HR | 279 | INPUT_DPPO decimal point position | UINT16 | Read/write | 0 = XXXX; 1 = XXX.X; 2 = XX.XX; 3 = X.XXX | ||||
| HR | 280 | INPUT_LL_PV1 sensor lower limit | INT16 | Read | |||||
| HR | 281 | INPUT_HL_PV1 sensor upper limit | INT16 | Read | |||||
| HR | 310 | FUA1 alarm 1 function | UINT16 | Read/write | 0 = Off; 1 = Lo; 2 = Hi; 3 = DiF; 4 = DIf.L; 5 = DIF.H; 6 = i.Err; 7 = rS; 8 = End.t; 9 = Lbd | ||||
| HR | 311 | SPA1 alarm 1 setpoint | INT16 | Read/write | |||||
| HR | 319 | FUA2 alarm 2 function | UINT16 | Read/write | 0 = Off; 1 = Lo; 2 = Hi; 3 = DiF; 4 = DIf.L; 5 = DIF.H; 6 = i.Err; 7 = rS; 8 = End.t; 9 = Lbd | ||||
| HR | 320 | SPA2 alarm 2 setpoint | INT16 | Read/write | |||||
| HR | 328 | FUA3 alarm 3 function | UINT16 | Read/write | 0 = Off; 1 = Lo; 2 = Hi; 3 = DiF; 4 = DIf.L; 5 = DIF.H; 6 = i.Err; 7 = rS; 8 = End.t; 9 = Lbd | ||||
| HR | 329 | SPA3 alarm 3 setpoint | INT16 | Read/write | |||||
| HR | 337 | FUA4 alarm 4 function | UINT16 | Read/write | 0 = Off; 1 = Lo; 2 = Hi; 3 = DiF; 4 = DIf.L; 5 = DIF.H; 6 = i.Err; 7 = rS; 8 = End.t; 9 = Lbd | ||||
| HR | 338 | SPA4 alarm 4 setpoint | INT16 | Read/write |
Notes on this map
- This copy is hosted on a reseller's Shopify store; it is the Novus N20K48 Communication Protocol V1.0x document.
- Function codes 03, 05, 06 and 16 are supported; the manual says all registers are 16-bit integers. Signed types are used where a published range goes negative.
- Scaling: the PV of a temperature input is always the value times 10, whatever INPUT_DPPO says; for linear inputs, PV and setpoint decimals follow INPUT_DPPO (279). Setpoint-type registers are listed unscaled because the manual does not say whether the x10 rule also applies to them.
- Left out: AI_DIAG (88) and the status words, whose bit numbering (printed from bit 1) is not tied to bit 0 in the text; serial-number, Bluetooth name and ramp/soak program registers; dual-word input limits 78-81 and 103-106, whose word order is not stated.
- Serial settings are made at the controller; the protocol document gives no defaults.
- Addressing rests on the register table starting at address 0 with a real register (INFO_ID); the document has no request-frame example.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Novus N20K48 modular process controller (Modbus RTU)
What Modbus registers does the Novus N20K48 modular process controller (Modbus RTU) have?
This map lists 38 registers: 38 holding registers. 33 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Novus N20K48 modular process controller (Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The register table lists addresses from 0 (INFO_ID), which only fits 0-based protocol addresses; send the printed number unchanged. Add 1 (or 40001) for a 1-based or Modicon tool.
What are the minimum Modbus registers to integrate the Novus N20K48 modular process controller (Modbus RTU)?
Start with HR 201 CTRL_PV1 process variable (Process variable); HR 200 CTRL_SP control setpoint (Setpoint); HR 202 CTRL_MV1 control output power (Output power 0.1 %); HR 214 CTRL_RUN run (Run control); HR 213 CTRL_AUTO control mode (Manual/automatic); HR 279 INPUT_DPPO decimal point position (Decimal point position).
How do I enable Modbus control of the Novus N20K48 modular process controller (Modbus RTU)?
Fit the RS-485 option and set address and serial parameters on the controller.
Where is the official Novus N20K48 modular process controller (Modbus RTU) Modbus documentation?
The source is N20K48 Modular Controller - Communication Protocol V1.0x. Novus doesn't publish it on its own website, so this map was re-typed from a free copy at https://cdn.shopify.com/s/files/1/2586/3536/files/n20k48_communication_protocol.pdf. It may be an older revision, so check it against the live unit.
Other temperature & process controllers register maps
- Sensor (digital temperature controller)
Shinko Technos ACS2 digital indicating controller (C5, C5W options)
Shinko ACS2 with the C5 or C5W serial option, Shinko protocol / MODBUS RTU command set; manual No.ACS2CE3.
Also known as: ACS2-C5, ACS2-C5W - Sensor (digital temperature controller)
Shinko Technos JIR-301-M digital indicator (C5 option)
Shinko JIR-301-M with the C5 option, plain (non-block) Modbus protocol setting; manual No.JIR32CE4.
Also known as: JIR-301-M-C5, JIR-301-M C5 - Sensor (digital indicating temperature controller)
Yokogawa UTAdvanced UT35A / UT32A digital indicating controller
Yokogawa UT35A and UT32A single-loop controllers with RS-485 or Ethernet communication; D-register map from IM 05P07A01-01EN chapter 8 (UT32A-D loop 2 and UP35A/UP32A program items excluded).
Also known as: UT35A, UT32A, UT35A/MDL, UT32A/MDL - Sensor (digital temperature controller)
Fuji Electric PXR micro controller X (RS-485 Modbus option)
Fuji Electric PXR series controllers with the RS-485 Modbus communication option; manual INP-TN512642d-E.
Also known as: PXR3, PXR4, PXR5, PXR9 - Sensor (digital temperature controller)
Shinko Technos ACS-13A digital indicating controller (C5 option)
Shinko ACS-13A with the C5 serial communication option; communication manual No.ACS12CE5.
Also known as: ACS-13A-C5, ACS-13A C5 - Sensor (digital temperature controller)
Shinko Technos JCS-33A / JCM-33A / JCR-33A / JCD-33A digital indicating controller (C5 option)
Shinko JCx-33A series (JCS, JCM, JCR, JCD-33A) with the C5 option; communication manual No.JC3CE11.
Also known as: JCS-33A, JCM-33A, JCR-33A, JCD-33A, JCx-33A
All temperature & process controllers Modbus register maps →
Source: N20K48 Modular Controller - Communication Protocol V1.0x · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.