Sensor (digital indicating temperature controller) · Modbus register map
Yokogawa UTAdvanced UT35A / UT32A digital indicating controller Modbus register map
Updated 17 November 2026
The UT35A and UT32A are single-loop PID controllers in Yokogawa's UTAdvanced family. Their data live in D registers that map one-to-one onto Modbus holding registers, reachable over RS-485 (Modbus RTU/ASCII) or, on Ethernet models, Modbus/TCP. This map covers the process data block (PV, setpoint, outputs, status words), the current SP/PID group and the operation-mode switches.
This page lists 52 Modbus registers for the Yokogawa UTAdvanced UT35A / UT32A digital indicating controller — 29 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Yokogawa’s own free documentation (linked below) and checked against it.
- Manufacturer
- Yokogawa
- Model
- UTAdvanced UT35A / UT32A digital indicating controller
- Equipment type
- Sensor (digital indicating temperature controller)
- Registers
- 52 (29 writable)
- Transport
- Modbus RTU, Modbus ASCII, Modbus TCP
- Default unit ID
- 1
- Default serial
- 19200 baud, 8E1
- TCP port
- 502
- Documented addressing
- 1-based (subtract 1 for the wire address)
- Also known as
- UT35A, UT32A, UT35A/MDL, UT32A/MDL
Integration notes: Yokogawa UTAdvanced UT35A / UT32A digital indicating controller
Set protocol MBRTU (factory default) and an address, then read D2001-D2012 in one block for status, PV, SP and output, write the target setpoint to D2101 and switch AUTO/MAN and RUN/STOP with D2301 and D2304.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 2002 | PV_L1 measured value | INT16 | PV (D2003) | Read |
| HR 2003 | CSP_L1 control setpoint | INT16 | Control setpoint (D2004) | Read |
| HR 2004 | OUT_L1 control output | INT16 | Control output (D2005) | Read |
| HR 2007 | MOD_L1 operation mode status | BITMAP16 | Operation mode status (D2008) | Read |
| HR 2010 | ALM_L1 alarm status | BITMAP16 | Alarm status (D2011) | Read |
| HR 2100 | SP_L1 target setpoint | INT16 | Target setpoint (D2101) | Read/write |
| HR 2300 | A.M AUTO/MAN switch | UINT16 | AUTO/MAN (D2301) | Read/write |
| HR 2303 | S.R STOP/RUN switch | UINT16 | RUN/STOP (D2304) | Read/write |
Enable Modbus control & writes
Set the communication setup parameters PSL (protocol, MBRTU or MBASC), BPS, PRI, STP, DLN and ADR on the keypad. Ethernet models use Modbus/TCP on port 502 by default.
Byte order & addressing
- Address D register n at wire address n-1 (D2101 = 0834H).
- Writing values with a decimal point: send the integer without it (50.0 with one decimal place = 500).
Network setup
- Factory defaults: Modbus RTU, 19200 bps, even parity, 1 stop bit, 8 data bits, address 1. Speeds 600-38400 bps (38400 only on suffix types that allow it).
Watch out for
- Available registers depend on the suffix code and parameter settings; check the model before writing.
Yokogawa UTAdvanced UT35A / UT32A digital indicating controller Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 2000doc D2001 | AD1.E A/D converter error status 1 | BITMAP16 | Read | bit 0 = PV input A/D converter error; bit 5 = PV input RJC error; bit 8 = PV input burnout error | ||||
| HR | 2001doc D2002 | PV1.E_L1 PV input error status | BITMAP16 | Read | bit 0 = PV input burnout; bit 4 = PV over-scale; bit 5 = PV under-scale; bit 14 = Auto-tuning timeout error | ||||
| HR | 2002doc D2003 | PV_L1 measured value | Engineering value without decimal point; position set by the PV decimal point parameter. | INT16 | Read | ||||
| HR | 2003doc D2004 | CSP_L1 control setpoint | Engineering value without decimal point; position set by the PV decimal point parameter. | INT16 | Read | ||||
| HR | 2004doc D2005 | OUT_L1 control output | -5.0 to 105.0 %; valve opening in position-proportional control. | INT16 | × 0.1 | % | Read | ||
| HR | 2005doc D2006 | H.OUT_L1 heating-side output | Heating/cooling control. | INT16 | × 0.1 | % | Read | ||
| HR | 2006doc D2007 | C.OUT_L1 cooling-side output | Heating/cooling control. | INT16 | × 0.1 | % | Read | ||
| HR | 2007doc D2008 | MOD_L1 operation mode status | BITMAP16 | Read | bit 0 = Manual (0 = AUTO); bit 1 = Remote (0 = Local); bit 2 = Stop (0 = Run); bit 8 = Output tracking; bit 14 = Auto-tuning on | ||||
| HR | 2008doc D2009 | PID_L1 current PID number | Bits 0-2 give the PID number; 0 when reference PID (R) is used. | UINT16 | Read | ||||
| HR | 2009doc D2010 | CSPNO. current SP number | Bits 0-2 give the control setpoint number. | UINT16 | Read | ||||
| HR | 2010doc D2011 | ALM_L1 alarm status | BITMAP16 | Read | bit 0 = Alarm 1 ON; bit 1 = Alarm 2 ON; bit 2 = Alarm 3 ON; bit 4 = Alarm 4 ON | ||||
| HR | 2011doc D2012 | LA.ER ladder error status | BITMAP16 | Read | bit 0 = Corrupted ladder program; bit 1 = Ladder calculation overflow; bit 2 = Ladder program error; bit 4 = Load factor over 100 %; bit 5 = Load factor over 200 % (forced end) | ||||
| HR | 2034doc D2035 | DEV_L1 deviation | -105.0 to 105.0 % of PV span; no decimal point sent. | INT16 | Read | ||||
| HR | 2036doc D2037 | ALO_L1 alarm output status | BITMAP16 | Read | bit 0 = Alarm output 1 contact closed; bit 1 = Alarm output 2 contact closed; bit 2 = Alarm output 3 contact closed; bit 4 = Alarm output 4 contact closed | ||||
| HR | 2060doc D2061 | HC1 heater break current 1 | 0.0 to 360.0 A rms. | INT16 | × 0.1 | A | Read | ||
| HR | 2061doc D2062 | HC2 heater break current 2 | 0.0 to 360.0 A rms. | INT16 | × 0.1 | A | Read | ||
| HR | 2062doc D2063 | CT_AL heater break alarm status | BITMAP16 | Read | bit 0 = Heater break alarm 1 ON; bit 1 = Heater break alarm 2 ON | ||||
| HR | 2063doc D2064 | VALV valve status | BITMAP16 | Read | bit 0 = Estimating-type operation (0 = feedback); bit 1 = Open output on; bit 2 = Close output on; bit 3 = Automatic valve position adjustment | ||||
| HR | 2064doc D2065 | AD2.E A/D converter error status 2 | BITMAP16 | Read | bit 0 = Feedback input burnout; bit 1 = Valve position auto adjustment error | ||||
| HR | 2067doc D2068 | PA.ER parameter error status | BITMAP16 | Read | bit 0 = System data error; bit 1 = Calibration value error; bit 2 = User default value error; bit 4 = Setup parameter error; bit 5 = Operation parameter error; bit 8 = Faulty FRAM; bit 10 = Control parameter error | ||||
| HR | 2069doc D2070 | OP.ER option error status | BITMAP16 | Read | bit 0 = E1 terminal hardware not responding; bit 2 = E3 terminal hardware not responding; bit 4 = E4 terminal hardware not responding; bit 8 = E1 communication error (UT32A); bit 10 = E3 communication error (UT35A) | ||||
| HR | 2070doc D2071 | ALOLA1_L1 alarm latch-1 output status | BITMAP16 | Read | bit 0 = Alarm 1 latch-1; bit 1 = Alarm 2 latch-1; bit 2 = Alarm 3 latch-1; bit 4 = Alarm 4 latch-1 | ||||
| HR | 2072doc D2073 | ALOLA2_L1 alarm latch-2 output status | BITMAP16 | Read | bit 0 = Alarm 1 latch-2; bit 1 = Alarm 2 latch-2; bit 2 = Alarm 3 latch-2; bit 4 = Alarm 4 latch-2 | ||||
| HR | 2100doc D2101 | SP_L1 target setpoint | Engineering value without decimal point; position set by the PV decimal point parameter. | INT16 | Read/write | ||||
| HR | 2101doc D2102 | SUB sub-target setpoint | Offset from SP, two-position two-level control. | INT16 | Read/write | ||||
| HR | 2102doc D2103 | PIDN_L1 PID number selection | PID group 1-4 used by the current SP group. | UINT16 | Read/write | ||||
| HR | 2103doc D2104 | A1_L1 alarm-1 setpoint | -19999 to 30000; decimal point follows the input. | INT16 | Read/write | ||||
| HR | 2104doc D2105 | A2_L1 alarm-2 setpoint | -19999 to 30000; decimal point follows the input. | INT16 | Read/write | ||||
| HR | 2105doc D2106 | A3_L1 alarm-3 setpoint | -19999 to 30000; decimal point follows the input. | INT16 | Read/write | ||||
| HR | 2106doc D2107 | A4_L1 alarm-4 setpoint | -19999 to 30000; decimal point follows the input. | INT16 | Read/write | ||||
| HR | 2113doc D2114 | P_L1 proportional band | 0.0-999.9 %. Current SP/PID group. | UINT16 | × 0.1 | % | Read/write | ||
| HR | 2114doc D2115 | I_L1 integral time | 0 = OFF, 1-6000 s. Current SP/PID group. | UINT16 | s | Read/write | |||
| HR | 2115doc D2116 | D_L1 derivative time | 0 = OFF, 1-6000 s. Current SP/PID group. | UINT16 | s | Read/write | |||
| HR | 2116doc D2117 | OH_L1 output high limit | -4.9 to 105.0 %. | INT16 | × 0.1 | % | Read/write | ||
| HR | 2117doc D2118 | OL_L1 output low limit | -5.0 to 104.9 %. | INT16 | × 0.1 | % | Read/write | ||
| HR | 2118doc D2119 | MR_L1 manual reset | Used when integral time is OFF. | INT16 | × 0.1 | % | Read/write | ||
| HR | 2123doc D2124 | DR_L1 direct/reverse action | UINT16 | Read/write | 0 = RVS (reverse); 1 = DIR (direct) | ||||
| HR | 2125doc D2126 | Pc_L1 cooling-side proportional band | UINT16 | × 0.1 | % | Read/write | |||
| HR | 2126doc D2127 | Ic_L1 cooling-side integral time | 0 = OFF. | UINT16 | s | Read/write | |||
| HR | 2127doc D2128 | Dc_L1 cooling-side derivative time | 0 = OFF. | UINT16 | s | Read/write | |||
| HR | 2128doc D2129 | OHc_L1 cooling-side output high limit | INT16 | × 0.1 | % | Read/write | |||
| HR | 2129doc D2130 | OLc_L1 cooling-side output low limit | INT16 | × 0.1 | % | Read/write | |||
| HR | 2132doc D2133 | PO_L1 preset output | Output used in STOP mode. | INT16 | × 0.1 | % | Read/write | ||
| HR | 2300doc D2301 | A.M AUTO/MAN switch | UINT16 | Read/write | 0 = AUTO; 1 = MAN | ||||
| HR | 2303doc D2304 | S.R STOP/RUN switch | Preset output is used in STOP. | UINT16 | Read/write | 0 = RUN; 1 = STOP | |||
| HR | 2305doc D2306 | R.L_L1 REMOTE/LOCAL switch | UINT16 | Read/write | 0 = LCL (local); 1 = REM (remote) | ||||
| HR | 2307doc D2308 | AT_L1 auto-tuning switch | UINT16 | Read/write | 0 = OFF; 1 = AT to PID 1; 2 = AT to PID 2; 3 = AT to PID 3; 4 = AT to PID 4; 9 = AT to reference PID (R) | ||||
| HR | 2311doc D2312 | SPNO. SP number selection | 1-4, limited by the SPGR. setup parameter. | UINT16 | Read/write | ||||
| HR | 2313doc D2314 | TRK_ON_L1 output tracking | UINT16 | Read/write | 0 = OFF; 1 = ON | ||||
| HR | 2330doc D2331 | C.RSP_L1 communication remote setpoint | Engineering value without decimal point; position set by the PV decimal point parameter. | INT16 | Read/write | ||||
| HR | 2332doc D2333 | MOUT_L1 manual output | Output in MAN mode (heating side in heat/cool). | INT16 | × 0.1 | % | Read/write | ||
| HR | 2333doc D2334 | MOUTc_L1 cooling-side manual output | Heating/cooling control. | INT16 | × 0.1 | % | Read/write |
Notes on this map
- All registers are 16-bit. Values are sent without their decimal point: PV/SP-type values follow the input's decimal point setting, percentages carry one decimal (scale 0.1).
- D2001-D2100 are read-only; registers marked as group items (D2101-D2135) act on the SP/PID group currently in use.
- UT32A-D loop-2, UP35A/UP32A program-pattern and GREEN-series compatible (D0001-D2000) registers are not included.
- Only part of the D-register space is listed; setup and operation parameter areas (D2501 onward) are left out.
- Up to 100 registers per read and 50 per multi-register write; blank (undefined) addresses must not be read or written.
- Modbus/TCP applies only to UT35A units with the Ethernet option; the UT32A is serial only.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Yokogawa UTAdvanced UT35A / UT32A digital indicating controller
What Modbus registers does the Yokogawa UTAdvanced UT35A / UT32A digital indicating controller have?
This map lists 52 registers: 52 holding registers. 29 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Yokogawa UTAdvanced UT35A / UT32A digital indicating controller Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual lists D register numbers (D2003). The Modbus reference number replaces the D with 4 (42003) and the wire address is that minus 40001, printed in the table's H No. column (D2003 = 07D2H).
What are the minimum Modbus registers to integrate the Yokogawa UTAdvanced UT35A / UT32A digital indicating controller?
Start with HR 2002 PV_L1 measured value (PV (D2003)); HR 2003 CSP_L1 control setpoint (Control setpoint (D2004)); HR 2004 OUT_L1 control output (Control output (D2005)); HR 2007 MOD_L1 operation mode status (Operation mode status (D2008)); HR 2010 ALM_L1 alarm status (Alarm status (D2011)); HR 2100 SP_L1 target setpoint (Target setpoint (D2101)); HR 2300 A.M AUTO/MAN switch (AUTO/MAN (D2301)); HR 2303 S.R STOP/RUN switch (RUN/STOP (D2304)).
How do I enable Modbus control of the Yokogawa UTAdvanced UT35A / UT32A digital indicating controller?
Set the communication setup parameters PSL (protocol, MBRTU or MBASC), BPS, PRI, STP, DLN and ADR on the keypad. Ethernet models use Modbus/TCP on port 502 by default.
Where is the official Yokogawa UTAdvanced UT35A / UT32A digital indicating controller Modbus documentation?
The source is UTAdvanced Series Communication Interface (RS-485, Ethernet) User's Manual (IM 05P07A01-01EN 13th Edition), revision 2026-03, published free by Yokogawa at https://web-material3.yokogawa.com/IM05P07A01-01EN.pdf.
More Yokogawa Modbus register maps
- Sensor (digital indicator with alarms)
Yokogawa UTAdvanced UM33A digital indicator with alarms
Yokogawa UM33A indicators with RS-485 (Modbus RTU/ASCII); process monitoring D registers from IM 05P07A01-01EN chapter 10.
Also known as: UM33A - Sensor (program temperature controller)
Yokogawa UTAdvanced UP35A / UP32A program controller
Yokogawa UP35A and UP32A single-loop program controllers with RS-485 or Ethernet communication; D-register map from IM 05P07A01-01EN chapter 8 (UP35A/UP32A columns).
Also known as: UP35A, UP32A - Sensor (program temperature controller)
Yokogawa UTAdvanced UP55A program controller
Yokogawa UP55A program controller with RS-485 or Ethernet communication; D-register map from IM 05P07A01-01EN chapter 6 (UP55A column).
Also known as: UP55A - Sensor (limit controller)
Yokogawa UTAdvanced UT35A-L limit controller
Yokogawa UT35A-L limit controllers with RS-485 (Modbus RTU/ASCII); process monitoring D registers from IM 05P07A01-01EN chapter 12.
Also known as: UT35A-L - Sensor (digital indicating temperature controller)
Yokogawa UTAdvanced UT55A / UT52A digital indicating controller
Yokogawa UT55A and UT52A one- or two-loop controllers with RS-485 or Ethernet communication; D-register map from IM 05P07A01-01EN chapter 6 (UP55A program items excluded).
Also known as: UT55A, UT52A - Sensor (digital indicating temperature controller)
Yokogawa UTAdvanced UT75A digital indicating controller
Yokogawa UT75A one- or two-loop controller with RS-485 or Ethernet communication; D-register map from IM 05P07A01-01EN chapter 14.
Also known as: UT75A
Other temperature & process controllers register maps
- Sensor (digital temperature controller)
Fuji Electric PXR micro controller X (RS-485 Modbus option)
Fuji Electric PXR series controllers with the RS-485 Modbus communication option; manual INP-TN512642d-E.
Also known as: PXR3, PXR4, PXR5, PXR9 - Sensor (digital temperature controller)
Shinko Technos ACS-13A digital indicating controller (C5 option)
Shinko ACS-13A with the C5 serial communication option; communication manual No.ACS12CE5.
Also known as: ACS-13A-C5, ACS-13A C5 - Sensor (digital temperature controller)
Shinko Technos JCS-33A / JCM-33A / JCR-33A / JCD-33A digital indicating controller (C5 option)
Shinko JCx-33A series (JCS, JCM, JCR, JCD-33A) with the C5 option; communication manual No.JC3CE11.
Also known as: JCS-33A, JCM-33A, JCR-33A, JCD-33A, JCx-33A - Sensor (digital process controller)
Fuji Electric PXH digital controller (Modbus RTU, monitoring map)
Fuji Electric PXH digital controllers on the RS-485 Modbus port; read-only monitoring registers from manual INP-TN514207c-E.
Also known as: PXH - Sensor (digital temperature controller)
Shinko Technos ACD-13A / ACR-13A / ACD-15A / ACR-15A digital indicating controller (C, C5 options)
Shinko ACD/ACR-13A (PID) and ACD/ACR-15A (valve positioning) with the C or C5 communication option; manual No.ACDR1CE8.
Also known as: ACD-13A, ACR-13A, ACD-15A, ACR-15A - Sensor (digital temperature controller)
Shinko Technos JCL-33A digital indicating controller (C5 option)
Shinko JCL-33A with the C5 option, protocol set to plain 'Modbus RTU mode' or 'Modbus ASCII mode' (not the Block Read/Write modes, which use another layout); manual No.JCL3CE3.
Also known as: JCL-33A-C5, JCL-33A C5
All temperature & process controllers Modbus register maps →
Source: UTAdvanced Series Communication Interface (RS-485, Ethernet) User's Manual · IM 05P07A01-01EN 13th Edition · rev. 2026-03. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.