Easy Modbus
  1. Home
  2. Modbus register maps
  3. Yokogawa
  4. UTAdvanced UT35A / UT32A digital indicating controller

Sensor (digital indicating temperature controller) · Modbus register map

Yokogawa UTAdvanced UT35A / UT32A digital indicating controller Modbus register map

Updated 17 November 2026

Short answer

The UT35A and UT32A are single-loop PID controllers in Yokogawa's UTAdvanced family. Their data live in D registers that map one-to-one onto Modbus holding registers, reachable over RS-485 (Modbus RTU/ASCII) or, on Ethernet models, Modbus/TCP. This map covers the process data block (PV, setpoint, outputs, status words), the current SP/PID group and the operation-mode switches.

This page lists 52 Modbus registers for the Yokogawa UTAdvanced UT35A / UT32A digital indicating controller — 29 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Yokogawa’s own free documentation (linked below) and checked against it.

Manufacturer
Yokogawa
Model
UTAdvanced UT35A / UT32A digital indicating controller
Equipment type
Sensor (digital indicating temperature controller)
Registers
52 (29 writable)
Transport
Modbus RTU, Modbus ASCII, Modbus TCP
Default unit ID
1
Default serial
19200 baud, 8E1
TCP port
502
Documented addressing
1-based (subtract 1 for the wire address)
Also known as
UT35A, UT32A, UT35A/MDL, UT32A/MDL
Source document
UTAdvanced Series Communication Interface (RS-485, Ethernet) User's Manual · IM 05P07A01-01EN 13th Edition · rev. 2026-03
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Yokogawa UTAdvanced UT35A / UT32A digital indicating controller

Integration in brief

Set protocol MBRTU (factory default) and an address, then read D2001-D2012 in one block for status, PV, SP and output, write the target setpoint to D2101 and switch AUTO/MAN and RUN/STOP with D2301 and D2304.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 2002PV_L1 measured valueINT16PV (D2003)Read
HR 2003CSP_L1 control setpointINT16Control setpoint (D2004)Read
HR 2004OUT_L1 control outputINT16Control output (D2005)Read
HR 2007MOD_L1 operation mode statusBITMAP16Operation mode status (D2008)Read
HR 2010ALM_L1 alarm statusBITMAP16Alarm status (D2011)Read
HR 2100SP_L1 target setpointINT16Target setpoint (D2101)Read/write
HR 2300A.M AUTO/MAN switchUINT16AUTO/MAN (D2301)Read/write
HR 2303S.R STOP/RUN switchUINT16RUN/STOP (D2304)Read/write

Enable Modbus control & writes

Set the communication setup parameters PSL (protocol, MBRTU or MBASC), BPS, PRI, STP, DLN and ADR on the keypad. Ethernet models use Modbus/TCP on port 502 by default.

Byte order & addressing

Network setup

Watch out for

Yokogawa UTAdvanced UT35A / UT32A digital indicating controller Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

52 of 52 shown
Yokogawa UTAdvanced UT35A / UT32A digital indicating controller Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR2000doc D2001AD1.E A/D converter error status 1BITMAP16Readbit 0 = PV input A/D converter error; bit 5 = PV input RJC error; bit 8 = PV input burnout error
HR2001doc D2002PV1.E_L1 PV input error statusBITMAP16Readbit 0 = PV input burnout; bit 4 = PV over-scale; bit 5 = PV under-scale; bit 14 = Auto-tuning timeout error
HR2002doc D2003PV_L1 measured valueEngineering value without decimal point; position set by the PV decimal point parameter.INT16Read
HR2003doc D2004CSP_L1 control setpointEngineering value without decimal point; position set by the PV decimal point parameter.INT16Read
HR2004doc D2005OUT_L1 control output-5.0 to 105.0 %; valve opening in position-proportional control.INT16× 0.1%Read
HR2005doc D2006H.OUT_L1 heating-side outputHeating/cooling control.INT16× 0.1%Read
HR2006doc D2007C.OUT_L1 cooling-side outputHeating/cooling control.INT16× 0.1%Read
HR2007doc D2008MOD_L1 operation mode statusBITMAP16Readbit 0 = Manual (0 = AUTO); bit 1 = Remote (0 = Local); bit 2 = Stop (0 = Run); bit 8 = Output tracking; bit 14 = Auto-tuning on
HR2008doc D2009PID_L1 current PID numberBits 0-2 give the PID number; 0 when reference PID (R) is used.UINT16Read
HR2009doc D2010CSPNO. current SP numberBits 0-2 give the control setpoint number.UINT16Read
HR2010doc D2011ALM_L1 alarm statusBITMAP16Readbit 0 = Alarm 1 ON; bit 1 = Alarm 2 ON; bit 2 = Alarm 3 ON; bit 4 = Alarm 4 ON
HR2011doc D2012LA.ER ladder error statusBITMAP16Readbit 0 = Corrupted ladder program; bit 1 = Ladder calculation overflow; bit 2 = Ladder program error; bit 4 = Load factor over 100 %; bit 5 = Load factor over 200 % (forced end)
HR2034doc D2035DEV_L1 deviation-105.0 to 105.0 % of PV span; no decimal point sent.INT16Read
HR2036doc D2037ALO_L1 alarm output statusBITMAP16Readbit 0 = Alarm output 1 contact closed; bit 1 = Alarm output 2 contact closed; bit 2 = Alarm output 3 contact closed; bit 4 = Alarm output 4 contact closed
HR2060doc D2061HC1 heater break current 10.0 to 360.0 A rms.INT16× 0.1ARead
HR2061doc D2062HC2 heater break current 20.0 to 360.0 A rms.INT16× 0.1ARead
HR2062doc D2063CT_AL heater break alarm statusBITMAP16Readbit 0 = Heater break alarm 1 ON; bit 1 = Heater break alarm 2 ON
HR2063doc D2064VALV valve statusBITMAP16Readbit 0 = Estimating-type operation (0 = feedback); bit 1 = Open output on; bit 2 = Close output on; bit 3 = Automatic valve position adjustment
HR2064doc D2065AD2.E A/D converter error status 2BITMAP16Readbit 0 = Feedback input burnout; bit 1 = Valve position auto adjustment error
HR2067doc D2068PA.ER parameter error statusBITMAP16Readbit 0 = System data error; bit 1 = Calibration value error; bit 2 = User default value error; bit 4 = Setup parameter error; bit 5 = Operation parameter error; bit 8 = Faulty FRAM; bit 10 = Control parameter error
HR2069doc D2070OP.ER option error statusBITMAP16Readbit 0 = E1 terminal hardware not responding; bit 2 = E3 terminal hardware not responding; bit 4 = E4 terminal hardware not responding; bit 8 = E1 communication error (UT32A); bit 10 = E3 communication error (UT35A)
HR2070doc D2071ALOLA1_L1 alarm latch-1 output statusBITMAP16Readbit 0 = Alarm 1 latch-1; bit 1 = Alarm 2 latch-1; bit 2 = Alarm 3 latch-1; bit 4 = Alarm 4 latch-1
HR2072doc D2073ALOLA2_L1 alarm latch-2 output statusBITMAP16Readbit 0 = Alarm 1 latch-2; bit 1 = Alarm 2 latch-2; bit 2 = Alarm 3 latch-2; bit 4 = Alarm 4 latch-2
HR2100doc D2101SP_L1 target setpointEngineering value without decimal point; position set by the PV decimal point parameter.INT16Read/write
HR2101doc D2102SUB sub-target setpointOffset from SP, two-position two-level control.INT16Read/write
HR2102doc D2103PIDN_L1 PID number selectionPID group 1-4 used by the current SP group.UINT16Read/write
HR2103doc D2104A1_L1 alarm-1 setpoint-19999 to 30000; decimal point follows the input.INT16Read/write
HR2104doc D2105A2_L1 alarm-2 setpoint-19999 to 30000; decimal point follows the input.INT16Read/write
HR2105doc D2106A3_L1 alarm-3 setpoint-19999 to 30000; decimal point follows the input.INT16Read/write
HR2106doc D2107A4_L1 alarm-4 setpoint-19999 to 30000; decimal point follows the input.INT16Read/write
HR2113doc D2114P_L1 proportional band0.0-999.9 %. Current SP/PID group.UINT16× 0.1%Read/write
HR2114doc D2115I_L1 integral time0 = OFF, 1-6000 s. Current SP/PID group.UINT16sRead/write
HR2115doc D2116D_L1 derivative time0 = OFF, 1-6000 s. Current SP/PID group.UINT16sRead/write
HR2116doc D2117OH_L1 output high limit-4.9 to 105.0 %.INT16× 0.1%Read/write
HR2117doc D2118OL_L1 output low limit-5.0 to 104.9 %.INT16× 0.1%Read/write
HR2118doc D2119MR_L1 manual resetUsed when integral time is OFF.INT16× 0.1%Read/write
HR2123doc D2124DR_L1 direct/reverse actionUINT16Read/write0 = RVS (reverse); 1 = DIR (direct)
HR2125doc D2126Pc_L1 cooling-side proportional bandUINT16× 0.1%Read/write
HR2126doc D2127Ic_L1 cooling-side integral time0 = OFF.UINT16sRead/write
HR2127doc D2128Dc_L1 cooling-side derivative time0 = OFF.UINT16sRead/write
HR2128doc D2129OHc_L1 cooling-side output high limitINT16× 0.1%Read/write
HR2129doc D2130OLc_L1 cooling-side output low limitINT16× 0.1%Read/write
HR2132doc D2133PO_L1 preset outputOutput used in STOP mode.INT16× 0.1%Read/write
HR2300doc D2301A.M AUTO/MAN switchUINT16Read/write0 = AUTO; 1 = MAN
HR2303doc D2304S.R STOP/RUN switchPreset output is used in STOP.UINT16Read/write0 = RUN; 1 = STOP
HR2305doc D2306R.L_L1 REMOTE/LOCAL switchUINT16Read/write0 = LCL (local); 1 = REM (remote)
HR2307doc D2308AT_L1 auto-tuning switchUINT16Read/write0 = OFF; 1 = AT to PID 1; 2 = AT to PID 2; 3 = AT to PID 3; 4 = AT to PID 4; 9 = AT to reference PID (R)
HR2311doc D2312SPNO. SP number selection1-4, limited by the SPGR. setup parameter.UINT16Read/write
HR2313doc D2314TRK_ON_L1 output trackingUINT16Read/write0 = OFF; 1 = ON
HR2330doc D2331C.RSP_L1 communication remote setpointEngineering value without decimal point; position set by the PV decimal point parameter.INT16Read/write
HR2332doc D2333MOUT_L1 manual outputOutput in MAN mode (heating side in heat/cool).INT16× 0.1%Read/write
HR2333doc D2334MOUTc_L1 cooling-side manual outputHeating/cooling control.INT16× 0.1%Read/write

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Yokogawa UTAdvanced UT35A / UT32A digital indicating controller

What Modbus registers does the Yokogawa UTAdvanced UT35A / UT32A digital indicating controller have?

This map lists 52 registers: 52 holding registers. 29 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Yokogawa UTAdvanced UT35A / UT32A digital indicating controller Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual lists D register numbers (D2003). The Modbus reference number replaces the D with 4 (42003) and the wire address is that minus 40001, printed in the table's H No. column (D2003 = 07D2H).

What are the minimum Modbus registers to integrate the Yokogawa UTAdvanced UT35A / UT32A digital indicating controller?

Start with HR 2002 PV_L1 measured value (PV (D2003)); HR 2003 CSP_L1 control setpoint (Control setpoint (D2004)); HR 2004 OUT_L1 control output (Control output (D2005)); HR 2007 MOD_L1 operation mode status (Operation mode status (D2008)); HR 2010 ALM_L1 alarm status (Alarm status (D2011)); HR 2100 SP_L1 target setpoint (Target setpoint (D2101)); HR 2300 A.M AUTO/MAN switch (AUTO/MAN (D2301)); HR 2303 S.R STOP/RUN switch (RUN/STOP (D2304)).

How do I enable Modbus control of the Yokogawa UTAdvanced UT35A / UT32A digital indicating controller?

Set the communication setup parameters PSL (protocol, MBRTU or MBASC), BPS, PRI, STP, DLN and ADR on the keypad. Ethernet models use Modbus/TCP on port 502 by default.

Where is the official Yokogawa UTAdvanced UT35A / UT32A digital indicating controller Modbus documentation?

The source is UTAdvanced Series Communication Interface (RS-485, Ethernet) User's Manual (IM 05P07A01-01EN 13th Edition), revision 2026-03, published free by Yokogawa at https://web-material3.yokogawa.com/IM05P07A01-01EN.pdf.

More Yokogawa Modbus register maps

Other temperature & process controllers register maps

All temperature & process controllers Modbus register maps →

Source: UTAdvanced Series Communication Interface (RS-485, Ethernet) User's Manual · IM 05P07A01-01EN 13th Edition · rev. 2026-03. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.