Sensor (program temperature controller) · Modbus register map

Yokogawa UTAdvanced UP35A / UP32A program controller Modbus register map

Updated 19 November 2026

Short answer

The UP35A and UP32A are compact UTAdvanced program (ramp/soak) controllers with up to 2 patterns (4 with option /AP) and one loop. Its D registers map one-to-one onto Modbus holding registers over RS-485 (Modbus RTU/ASCII) or Modbus/TCP on Ethernet models. This map covers process data, program status and events, local-mode settings and the program operation commands.

This page lists 40 Modbus registers for the Yokogawa UTAdvanced UP35A / UP32A program controller — 13 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Yokogawa’s own free documentation (linked below) and checked against it.

Manufacturer
Yokogawa
Model
UTAdvanced UP35A / UP32A program controller
Equipment type
Sensor (program temperature controller)
Registers
40 (13 writable)
Transport
Modbus RTU, Modbus ASCII, Modbus TCP
Default unit ID
1
Default serial
19200 baud, 8E1
TCP port
502
Documented addressing
1-based (subtract 1 for the wire address)
Also known as
UP35A, UP32A
Source document
UTAdvanced Series Communication Interface (RS-485, Ethernet) User's Manual · IM 05P07A01-01EN 13th Edition · rev. 2026-03
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Yokogawa UTAdvanced UP35A / UP32A program controller

Integration in brief

Select a pattern with D2322 and start it with D2316 = 1 (PROG); stop with 0 (RESET). Poll D2003-D2008 for PV, SP, output and mode, D2015-D2017 for pattern, segment and remaining time, and D2040 for time events.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 2002PV_L1 measured valueINT16Loop-1 PV (D2003)Read
HR 2003CSP_L1 control setpointINT16Loop-1 SP (D2004)Read
HR 2007MOD_L1 operation mode status (UP35A/UP32A)BITMAP16Operation mode status (D2008)Read
HR 2015SEG.N current segment numberUINT16Current segment (D2016)Read
HR 2010ALM_L1 alarm statusBITMAP16Alarm status (D2011)Read
HR 2315MODE program operation modeUINT16Program MODE (D2316)Read/write
HR 2321PTNO. program pattern number selectionUINT16Pattern number (D2322)Read/write

Enable Modbus control & writes

Set the communication setup parameters (protocol MBRTU or MBASC, baud, parity, stop bits, data length, address) on the keypad. Ethernet models use Modbus/TCP on port 502 by default.

Byte order & addressing

Network setup

Watch out for

Yokogawa UTAdvanced UP35A / UP32A program controller Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

40 of 40 shown
Yokogawa UTAdvanced UP35A / UP32A program controller Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR2000doc D2001AD1.E A/D converter error status 1BITMAP16Readbit 0 = PV input A/D converter error; bit 5 = PV input RJC error; bit 8 = PV input burnout error
HR2001doc D2002PV1.E_L1 PV input error statusBITMAP16Readbit 0 = PV input burnout; bit 4 = PV over-scale; bit 5 = PV under-scale; bit 14 = Auto-tuning timeout error
HR2002doc D2003PV_L1 measured valueEngineering value without decimal point; position set by the PV input decimal point.INT16Read
HR2003doc D2004CSP_L1 control setpointEngineering value without decimal point; position set by the PV input decimal point.INT16Read
HR2004doc D2005OUT_L1 control output-5.0 to 105.0 %.INT16× 0.1%Read
HR2005doc D2006H.OUT_L1 heating-side outputHeating/cooling control.INT16× 0.1%Read
HR2006doc D2007C.OUT_L1 cooling-side output0.0 to 105.0 %.INT16× 0.1%Read
HR2007doc D2008MOD_L1 operation mode status (UP35A/UP32A)BITMAP16Readbit 0 = A.M (0 AUTO, 1 MAN); bit 4 = Program reset; bit 5 = Program operation; bit 6 = Local operation; bit 10 = Advance of segment; bit 12 = Pause (hold); bit 13 = Wait; bit 14 = Auto-tuning ON
HR2008doc D2009PID_L1 current PID numberBits 0-2 hold the PID number; reads 0 for reference PID.UINT16Read
HR2010doc D2011ALM_L1 alarm statusUP35A/UP32A use alarms 1 and 2.BITMAP16Readbit 0 = Alarm 1 ON; bit 1 = Alarm 2 ON
HR2011doc D2012LA.ER ladder error statusBITMAP16Readbit 0 = Corrupted ladder program; bit 1 = Ladder calculation overflow; bit 2 = Ladder program error; bit 4 = Load factor over 100 %; bit 5 = Load factor over 200 % (forced end)
HR2014doc D2015C.PTNO. current program pattern number0-2 (0-4 with option /AP).UINT16Read
HR2015doc D2016SEG.N current segment number0 = not executing, 1-20 (40 with /AP).UINT16Read
HR2016doc D2017SEG_RTIME remaining segment time0-59999; elapsed time during wait. Unit set by TMU.UINT16Read
HR2032doc D2033CTSP_L1 final target setpointEngineering value without decimal point; position set by the PV input decimal point.INT16Read
HR2034doc D2035DEV_L1 deviationEngineering value of span without decimal point.INT16Read
HR2038doc D2039PV_EV PV event statusBITMAP16Readbit 0 = PV event 1 ON; bit 1 = PV event 2 ON
HR2039doc D2040TIME_EV_1 time event statusBITMAP16Readbit 0 = Time event 1 ON; bit 1 = Time event 2 ON; bit 2 = Time event 3 ON; bit 4 = Time event 4 ON
HR2043doc D2044SEG_USE segments in selected pattern0-20 (40 with /AP).UINT16Read
HR2047doc D2048NOW_RST repeat start segmentUINT16Read
HR2048doc D2049NOW_REN repeat end segmentUINT16Read
HR2049doc D2050PV_EV_OUT PV event output statusBITMAP16Readbit 0 = PV event 1 output ON; bit 1 = PV event 2 output ON
HR2060doc D2061HC1 heater break alarm-1 current0.0-360.0 A rms.INT16× 0.1ARead
HR2061doc D2062HC2 heater break alarm-2 current0.0-360.0 A rms.INT16× 0.1ARead
HR2062doc D2063CT_AL heater break alarm statusBITMAP16Readbit 0 = Heater break alarm 1 ON; bit 1 = Heater break alarm 2 ON
HR2063doc D2064VALV valve statusBITMAP16Readbit 0 = Estimating-type operation (0 = feedback input); bit 1 = Open output on; bit 2 = Close output on; bit 3 = Automatic valve position adjustment running
HR2067doc D2068PA.ER parameter error statusBITMAP16Readbit 0 = System data error; bit 1 = Calibration value error; bit 2 = User default value error; bit 4 = Setup parameter error; bit 5 = Operation parameter error; bit 6 = Program pattern error (UP35A); bit 8 = Faulty FRAM; bit 10 = Control parameter error
HR2200doc D2201LSP_L1 local target setpointSetpoint for local-mode operation. Engineering value without decimal point; position set by the PV input decimal point.INT16Read/write
HR2202doc D2203L.PID PID number for local-mode operationUINT16Read/write
HR2307doc D2308AT_L1 auto-tuning switch0 = off, 1-4 = tune into that PID, 9 = reference PID.UINT16Read/write
HR2313doc D2314TRK_ON_L1 output trackingUINT16Read/write0 = OFF; 1 = ON
HR2315doc D2316MODE program operation modeUINT16Read/write0 = RESET (stop program); 1 = PROG (start program); 2 = LOCAL (start local-mode operation)
HR2316doc D2317HOLD program pauseUINT16Read/write0 = OFF (release pause); 1 = ON (pause)
HR2317doc D2318ADV advance segmentWrite 1 to jump to the next segment.UINT16Read/write1 = Advance
HR2318doc D2319A.M_L1 AUTO/MAN switchUINT16Read/write0 = AUTO; 1 = MAN
HR2321doc D2322PTNO. program pattern number selection0 = none.UINT16Read/write
HR2332doc D2333MOUT_L1 manual outputOutput in MAN mode.INT16× 0.1%Read/write
HR2333doc D2334MOUTc_L1 cooling-side manual outputCooling-side output in MAN mode.INT16× 0.1%Read/write
HR2336doc D2337H.SP_L1 SP for HOLD stateEngineering value without decimal point; position set by the PV input decimal point.INT16Read/write
HR2338doc D2339H.TSP_L1 TSP for HOLD stateEngineering value without decimal point; position set by the PV input decimal point.INT16Read/write

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Yokogawa UTAdvanced UP35A / UP32A program controller

What Modbus registers does the Yokogawa UTAdvanced UP35A / UP32A program controller have?

This map lists 40 registers: 40 holding registers. 13 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Yokogawa UTAdvanced UP35A / UP32A program controller Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual lists D register numbers (D2003). The Modbus reference number replaces the D with 4 (42003) and the wire address is that minus 40001, printed in the table's H No. column (D2003 = 07D2H).

What are the minimum Modbus registers to integrate the Yokogawa UTAdvanced UP35A / UP32A program controller?

Start with HR 2002 PV_L1 measured value (Loop-1 PV (D2003)); HR 2003 CSP_L1 control setpoint (Loop-1 SP (D2004)); HR 2007 MOD_L1 operation mode status (UP35A/UP32A) (Operation mode status (D2008)); HR 2015 SEG.N current segment number (Current segment (D2016)); HR 2010 ALM_L1 alarm status (Alarm status (D2011)); HR 2315 MODE program operation mode (Program MODE (D2316)); HR 2321 PTNO. program pattern number selection (Pattern number (D2322)).

How do I enable Modbus control of the Yokogawa UTAdvanced UP35A / UP32A program controller?

Set the communication setup parameters (protocol MBRTU or MBASC, baud, parity, stop bits, data length, address) on the keypad. Ethernet models use Modbus/TCP on port 502 by default.

Where is the official Yokogawa UTAdvanced UP35A / UP32A program controller Modbus documentation?

The source is UTAdvanced Series Communication Interface (RS-485, Ethernet) User's Manual (IM 05P07A01-01EN 13th Edition), revision 2026-03, published free by Yokogawa at https://web-material3.yokogawa.com/IM05P07A01-01EN.pdf.

More Yokogawa Modbus register maps

Other temperature & process controllers register maps

All temperature & process controllers Modbus register maps →

Source: UTAdvanced Series Communication Interface (RS-485, Ethernet) User's Manual · IM 05P07A01-01EN 13th Edition · rev. 2026-03. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.