- UTAdvanced UP35A / UP32A program controller
Sensor (program temperature controller) · Modbus register map
Yokogawa UTAdvanced UP35A / UP32A program controller Modbus register map
Updated 19 November 2026
The UP35A and UP32A are compact UTAdvanced program (ramp/soak) controllers with up to 2 patterns (4 with option /AP) and one loop. Its D registers map one-to-one onto Modbus holding registers over RS-485 (Modbus RTU/ASCII) or Modbus/TCP on Ethernet models. This map covers process data, program status and events, local-mode settings and the program operation commands.
This page lists 40 Modbus registers for the Yokogawa UTAdvanced UP35A / UP32A program controller — 13 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Yokogawa’s own free documentation (linked below) and checked against it.
- Manufacturer
- Yokogawa
- Model
- UTAdvanced UP35A / UP32A program controller
- Equipment type
- Sensor (program temperature controller)
- Registers
- 40 (13 writable)
- Transport
- Modbus RTU, Modbus ASCII, Modbus TCP
- Default unit ID
- 1
- Default serial
- 19200 baud, 8E1
- TCP port
- 502
- Documented addressing
- 1-based (subtract 1 for the wire address)
- Also known as
- UP35A, UP32A
Integration notes: Yokogawa UTAdvanced UP35A / UP32A program controller
Select a pattern with D2322 and start it with D2316 = 1 (PROG); stop with 0 (RESET). Poll D2003-D2008 for PV, SP, output and mode, D2015-D2017 for pattern, segment and remaining time, and D2040 for time events.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 2002 | PV_L1 measured value | INT16 | Loop-1 PV (D2003) | Read |
| HR 2003 | CSP_L1 control setpoint | INT16 | Loop-1 SP (D2004) | Read |
| HR 2007 | MOD_L1 operation mode status (UP35A/UP32A) | BITMAP16 | Operation mode status (D2008) | Read |
| HR 2015 | SEG.N current segment number | UINT16 | Current segment (D2016) | Read |
| HR 2010 | ALM_L1 alarm status | BITMAP16 | Alarm status (D2011) | Read |
| HR 2315 | MODE program operation mode | UINT16 | Program MODE (D2316) | Read/write |
| HR 2321 | PTNO. program pattern number selection | UINT16 | Pattern number (D2322) | Read/write |
Enable Modbus control & writes
Set the communication setup parameters (protocol MBRTU or MBASC, baud, parity, stop bits, data length, address) on the keypad. Ethernet models use Modbus/TCP on port 502 by default.
Byte order & addressing
- Address D register n at wire address n-1.
- Write values without the decimal point (50.0 with one decimal place = 500).
Network setup
- Factory defaults: Modbus RTU, 19200 bps, even parity, 1 stop bit, 8 data bits, address 1.
Watch out for
- HOLD (D2317) and ADV (D2318) are program-operation items: write them while a program is running.
Yokogawa UTAdvanced UP35A / UP32A program controller Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 2000doc D2001 | AD1.E A/D converter error status 1 | BITMAP16 | Read | bit 0 = PV input A/D converter error; bit 5 = PV input RJC error; bit 8 = PV input burnout error | ||||
| HR | 2001doc D2002 | PV1.E_L1 PV input error status | BITMAP16 | Read | bit 0 = PV input burnout; bit 4 = PV over-scale; bit 5 = PV under-scale; bit 14 = Auto-tuning timeout error | ||||
| HR | 2002doc D2003 | PV_L1 measured value | Engineering value without decimal point; position set by the PV input decimal point. | INT16 | Read | ||||
| HR | 2003doc D2004 | CSP_L1 control setpoint | Engineering value without decimal point; position set by the PV input decimal point. | INT16 | Read | ||||
| HR | 2004doc D2005 | OUT_L1 control output | -5.0 to 105.0 %. | INT16 | × 0.1 | % | Read | ||
| HR | 2005doc D2006 | H.OUT_L1 heating-side output | Heating/cooling control. | INT16 | × 0.1 | % | Read | ||
| HR | 2006doc D2007 | C.OUT_L1 cooling-side output | 0.0 to 105.0 %. | INT16 | × 0.1 | % | Read | ||
| HR | 2007doc D2008 | MOD_L1 operation mode status (UP35A/UP32A) | BITMAP16 | Read | bit 0 = A.M (0 AUTO, 1 MAN); bit 4 = Program reset; bit 5 = Program operation; bit 6 = Local operation; bit 10 = Advance of segment; bit 12 = Pause (hold); bit 13 = Wait; bit 14 = Auto-tuning ON | ||||
| HR | 2008doc D2009 | PID_L1 current PID number | Bits 0-2 hold the PID number; reads 0 for reference PID. | UINT16 | Read | ||||
| HR | 2010doc D2011 | ALM_L1 alarm status | UP35A/UP32A use alarms 1 and 2. | BITMAP16 | Read | bit 0 = Alarm 1 ON; bit 1 = Alarm 2 ON | |||
| HR | 2011doc D2012 | LA.ER ladder error status | BITMAP16 | Read | bit 0 = Corrupted ladder program; bit 1 = Ladder calculation overflow; bit 2 = Ladder program error; bit 4 = Load factor over 100 %; bit 5 = Load factor over 200 % (forced end) | ||||
| HR | 2014doc D2015 | C.PTNO. current program pattern number | 0-2 (0-4 with option /AP). | UINT16 | Read | ||||
| HR | 2015doc D2016 | SEG.N current segment number | 0 = not executing, 1-20 (40 with /AP). | UINT16 | Read | ||||
| HR | 2016doc D2017 | SEG_RTIME remaining segment time | 0-59999; elapsed time during wait. Unit set by TMU. | UINT16 | Read | ||||
| HR | 2032doc D2033 | CTSP_L1 final target setpoint | Engineering value without decimal point; position set by the PV input decimal point. | INT16 | Read | ||||
| HR | 2034doc D2035 | DEV_L1 deviation | Engineering value of span without decimal point. | INT16 | Read | ||||
| HR | 2038doc D2039 | PV_EV PV event status | BITMAP16 | Read | bit 0 = PV event 1 ON; bit 1 = PV event 2 ON | ||||
| HR | 2039doc D2040 | TIME_EV_1 time event status | BITMAP16 | Read | bit 0 = Time event 1 ON; bit 1 = Time event 2 ON; bit 2 = Time event 3 ON; bit 4 = Time event 4 ON | ||||
| HR | 2043doc D2044 | SEG_USE segments in selected pattern | 0-20 (40 with /AP). | UINT16 | Read | ||||
| HR | 2047doc D2048 | NOW_RST repeat start segment | UINT16 | Read | |||||
| HR | 2048doc D2049 | NOW_REN repeat end segment | UINT16 | Read | |||||
| HR | 2049doc D2050 | PV_EV_OUT PV event output status | BITMAP16 | Read | bit 0 = PV event 1 output ON; bit 1 = PV event 2 output ON | ||||
| HR | 2060doc D2061 | HC1 heater break alarm-1 current | 0.0-360.0 A rms. | INT16 | × 0.1 | A | Read | ||
| HR | 2061doc D2062 | HC2 heater break alarm-2 current | 0.0-360.0 A rms. | INT16 | × 0.1 | A | Read | ||
| HR | 2062doc D2063 | CT_AL heater break alarm status | BITMAP16 | Read | bit 0 = Heater break alarm 1 ON; bit 1 = Heater break alarm 2 ON | ||||
| HR | 2063doc D2064 | VALV valve status | BITMAP16 | Read | bit 0 = Estimating-type operation (0 = feedback input); bit 1 = Open output on; bit 2 = Close output on; bit 3 = Automatic valve position adjustment running | ||||
| HR | 2067doc D2068 | PA.ER parameter error status | BITMAP16 | Read | bit 0 = System data error; bit 1 = Calibration value error; bit 2 = User default value error; bit 4 = Setup parameter error; bit 5 = Operation parameter error; bit 6 = Program pattern error (UP35A); bit 8 = Faulty FRAM; bit 10 = Control parameter error | ||||
| HR | 2200doc D2201 | LSP_L1 local target setpoint | Setpoint for local-mode operation. Engineering value without decimal point; position set by the PV input decimal point. | INT16 | Read/write | ||||
| HR | 2202doc D2203 | L.PID PID number for local-mode operation | UINT16 | Read/write | |||||
| HR | 2307doc D2308 | AT_L1 auto-tuning switch | 0 = off, 1-4 = tune into that PID, 9 = reference PID. | UINT16 | Read/write | ||||
| HR | 2313doc D2314 | TRK_ON_L1 output tracking | UINT16 | Read/write | 0 = OFF; 1 = ON | ||||
| HR | 2315doc D2316 | MODE program operation mode | UINT16 | Read/write | 0 = RESET (stop program); 1 = PROG (start program); 2 = LOCAL (start local-mode operation) | ||||
| HR | 2316doc D2317 | HOLD program pause | UINT16 | Read/write | 0 = OFF (release pause); 1 = ON (pause) | ||||
| HR | 2317doc D2318 | ADV advance segment | Write 1 to jump to the next segment. | UINT16 | Read/write | 1 = Advance | |||
| HR | 2318doc D2319 | A.M_L1 AUTO/MAN switch | UINT16 | Read/write | 0 = AUTO; 1 = MAN | ||||
| HR | 2321doc D2322 | PTNO. program pattern number selection | 0 = none. | UINT16 | Read/write | ||||
| HR | 2332doc D2333 | MOUT_L1 manual output | Output in MAN mode. | INT16 | × 0.1 | % | Read/write | ||
| HR | 2333doc D2334 | MOUTc_L1 cooling-side manual output | Cooling-side output in MAN mode. | INT16 | × 0.1 | % | Read/write | ||
| HR | 2336doc D2337 | H.SP_L1 SP for HOLD state | Engineering value without decimal point; position set by the PV input decimal point. | INT16 | Read/write | ||||
| HR | 2338doc D2339 | H.TSP_L1 TSP for HOLD state | Engineering value without decimal point; position set by the PV input decimal point. | INT16 | Read/write |
Notes on this map
- All registers are 16-bit. Values are sent without their decimal point: PV/SP-type values follow the input's decimal point setting, percentages carry one decimal (scale 0.1).
- Only registers whose UP35A/UP32A columns show R or R/W are listed. D2001-D2100 are read-only.
- The current PID group registers (D2114 onward) are left out: in the source table the access mark for those rows cannot be placed reliably under the UP35A or UP32A column.
- D2045-D2047 (pattern repeat counters) are left out because the source gives two of them the same description.
- Which of D2061-D2064 (heater break, valve) are present depends on the model suffix and options.
- Program pattern data (D8001-D9000), the GREEN-series compatible area (D0001-D2000) and setup parameters (D2501 onward) are not included.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Yokogawa UTAdvanced UP35A / UP32A program controller
What Modbus registers does the Yokogawa UTAdvanced UP35A / UP32A program controller have?
This map lists 40 registers: 40 holding registers. 13 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Yokogawa UTAdvanced UP35A / UP32A program controller Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual lists D register numbers (D2003). The Modbus reference number replaces the D with 4 (42003) and the wire address is that minus 40001, printed in the table's H No. column (D2003 = 07D2H).
What are the minimum Modbus registers to integrate the Yokogawa UTAdvanced UP35A / UP32A program controller?
Start with HR 2002 PV_L1 measured value (Loop-1 PV (D2003)); HR 2003 CSP_L1 control setpoint (Loop-1 SP (D2004)); HR 2007 MOD_L1 operation mode status (UP35A/UP32A) (Operation mode status (D2008)); HR 2015 SEG.N current segment number (Current segment (D2016)); HR 2010 ALM_L1 alarm status (Alarm status (D2011)); HR 2315 MODE program operation mode (Program MODE (D2316)); HR 2321 PTNO. program pattern number selection (Pattern number (D2322)).
How do I enable Modbus control of the Yokogawa UTAdvanced UP35A / UP32A program controller?
Set the communication setup parameters (protocol MBRTU or MBASC, baud, parity, stop bits, data length, address) on the keypad. Ethernet models use Modbus/TCP on port 502 by default.
Where is the official Yokogawa UTAdvanced UP35A / UP32A program controller Modbus documentation?
The source is UTAdvanced Series Communication Interface (RS-485, Ethernet) User's Manual (IM 05P07A01-01EN 13th Edition), revision 2026-03, published free by Yokogawa at https://web-material3.yokogawa.com/IM05P07A01-01EN.pdf.
More Yokogawa Modbus register maps
- Sensor (digital indicator with alarms)
Yokogawa UTAdvanced UM33A digital indicator with alarms
Yokogawa UM33A indicators with RS-485 (Modbus RTU/ASCII); process monitoring D registers from IM 05P07A01-01EN chapter 10.
Also known as: UM33A - Sensor (program temperature controller)
Yokogawa UTAdvanced UP55A program controller
Yokogawa UP55A program controller with RS-485 or Ethernet communication; D-register map from IM 05P07A01-01EN chapter 6 (UP55A column).
Also known as: UP55A - Sensor (digital indicating temperature controller)
Yokogawa UTAdvanced UT35A / UT32A digital indicating controller
Yokogawa UT35A and UT32A single-loop controllers with RS-485 or Ethernet communication; D-register map from IM 05P07A01-01EN chapter 8 (UT32A-D loop 2 and UP35A/UP32A program items excluded).
Also known as: UT35A, UT32A, UT35A/MDL, UT32A/MDL - Sensor (limit controller)
Yokogawa UTAdvanced UT35A-L limit controller
Yokogawa UT35A-L limit controllers with RS-485 (Modbus RTU/ASCII); process monitoring D registers from IM 05P07A01-01EN chapter 12.
Also known as: UT35A-L - Sensor (digital indicating temperature controller)
Yokogawa UTAdvanced UT55A / UT52A digital indicating controller
Yokogawa UT55A and UT52A one- or two-loop controllers with RS-485 or Ethernet communication; D-register map from IM 05P07A01-01EN chapter 6 (UP55A program items excluded).
Also known as: UT55A, UT52A - Sensor (digital indicating temperature controller)
Yokogawa UTAdvanced UT75A digital indicating controller
Yokogawa UT75A one- or two-loop controller with RS-485 or Ethernet communication; D-register map from IM 05P07A01-01EN chapter 14.
Also known as: UT75A
Other temperature & process controllers register maps
- Sensor / controller (PID temperature controller)
Autonics TK series PID temperature controller (Modbus RTU)
Autonics TK series heating/cooling PID temperature controllers with RS-485, communication manual MCT-TKC1-V2.2-EN.
Also known as: TK4S, TK4M, TK4H, TK4W, TK4L, TK4S-14RR, TK4 - Sensor (modular temperature controller)
RKC Instrument SRX module type controller, TIO temperature control module (Modbus RTU)
RKC SRX two-channel temperature control (TIO) modules, basic type X-TIO-A and extension type X-TIO-B, with Modbus selected; DI and DO module maps are not included.
Also known as: SRX, X-TIO-A, X-TIO-B, SRX TIO module, RKC SRX - Sensor (digital temperature controller)
Shinko Technos FC series digital indicating controller (C/C5 option, Modbus ASCII)
Shinko FCS-23A, FCR-13A, FCR-23A and FCD-13A with the C or C5 serial option; FCR-15A and FCD-15A have no Modbus (Shinko protocol only). Manual No.FC1CE11.
Also known as: FCS-23A, FCR-13A, FCR-23A, FCD-13A - Sensor (digital temperature controller)
Shinko Technos WCL-13A 2-channel digital indicating controller (C5 option)
Shinko WCL-13A two-loop controller with the C5 option; communication manual No.WCL1CE3.
Also known as: WCL-13A-C5, WCL-13A C5 - Sensor / counter-timer (programmable counter and timer)
Autonics CT series programmable counter / timer (Modbus RTU)
Autonics CT series counters/timers with RS-485 communication, communication manual MCC-CTC1-V1.3-EN.
Also known as: CT4S, CT6, CT6S, CT6M, CT6Y, CT6M-2P, CT6S-1P4 - Sensor (modular temperature controller)
RKC Instrument SRV module type controller, TIO temperature control module (Modbus RTU)
RKC SRV two-channel temperature control (TIO) modules, basic and extension type, with Modbus selected.
Also known as: SRV, SRV TIO module, RKC SRV
All temperature & process controllers Modbus register maps →
Source: UTAdvanced Series Communication Interface (RS-485, Ethernet) User's Manual · IM 05P07A01-01EN 13th Edition · rev. 2026-03. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.