Sensor (digital temperature controller) · Modbus register map
Shinko Technos WCL-13A 2-channel digital indicating controller (C5 option) Modbus register map
Updated 17 November 2026
The WCL-13A is a two-channel PID temperature controller (one unit, two loops); CH1 also has a heat/cool OUT2. With the C5 option it speaks Shinko protocol, Modbus ASCII or Modbus RTU on RS485, and all items are signed 16-bit holding registers. The map covers both channels' SV, PID, alarm and output settings, shared timer and transmission settings, and each channel's PV, MV, SV, heater current and status words.
This page lists 146 Modbus registers for the Shinko Technos WCL-13A 2-channel digital indicating controller (C5 option) — 130 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Shinko Technos’s own free documentation (linked below) and checked against it.
- Manufacturer
- Shinko Technos
- Model
- WCL-13A 2-channel digital indicating controller (C5 option)
- Equipment type
- Sensor (digital temperature controller)
- Registers
- 146 (130 writable)
- Transport
- Modbus RTU, Modbus ASCII
- Default unit ID
- 0
- Default serial
- 9600 baud, 7E1
- Documented addressing
- hexadecimal, 0-based
- Also known as
- WCL-13A-C5, WCL-13A C5
Integration notes: Shinko Technos WCL-13A 2-channel digital indicating controller (C5 option)
Select Modbus RTU with an 8-bit format on the keypad and set an instrument number. Poll 0080H-0083H for CH1 and 0090H-0093H for CH2 (PV, MV, SV, status); write SVs at 0001H and 0051H.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 128 | CH1 PV | INT16 | CH1 PV | Read |
| HR 131 | CH1 Status flag | BITMAP16 | CH1 status | Read |
| HR 144 | CH2 PV | INT16 | CH2 PV | Read |
| HR 147 | CH2 Status flag | BITMAP16 | CH2 status | Read |
| HR 1 | CH1 SV | INT16 | CH1 SV | Read/write |
| HR 81 | CH2 SV | INT16 | CH2 SV | Read/write |
Enable Modbus control & writes
Requires the C5 option. Set Communication protocol to Modbus RTU and an 8-bit data bit/parity choice on the keypad, then the instrument number and speed.
Byte order & addressing
- Factory data format is 7 bits/Even; RTU needs an 8-bit choice.
- SV temporary storage (002BH/007BH) is lost at power off; use SV (0001H/0051H) for permanent changes.
Network setup
- Factory defaults: Shinko protocol, instrument 0, 9600 bps, 7 bits/Even, 1 stop bit.
- Speeds 9600, 19200, 38400 bps.
Watch out for
- Non-volatile memory is rated about 1,000,000 writes; use the temporary SV for frequent setpoint changes.
Shinko Technos WCL-13A 2-channel digital indicating controller (C5 option) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 1doc 0001H | CH1 SV | Set value. Raw integer; apply the decimal point setting. | INT16 | Read/write | ||||
| HR | 2doc 0002H | CH1 AT/Auto-reset | INT16 | Read/write | 0 = Cancel; 1 = Perform | ||||
| HR | 3doc 0003H | CH1 Proportional band | INT16 | Read/write | |||||
| HR | 4doc 0004H | CH1 OUT2 proportional band | INT16 | Read/write | |||||
| HR | 5doc 0005H | CH1 Integral time | INT16 | Read/write | |||||
| HR | 6doc 0006H | CH1 Derivative time | INT16 | Read/write | |||||
| HR | 7doc 0007H | CH1 ARW | Anti-reset windup. | INT16 | Read/write | ||||
| HR | 8doc 0008H | CH1 Manual reset value | INT16 | Read/write | |||||
| HR | 9doc 0009H | CH1 Proportional cycle | INT16 | Read/write | |||||
| HR | 10doc 000AH | CH1 OUT2 proportional cycle | INT16 | Read/write | |||||
| HR | 11doc 000BH | CH1 Alarm 1 value | Raw integer; apply the decimal point setting. | INT16 | Read/write | ||||
| HR | 12doc 000CH | CH1 Heater burnout alarm 1 value | INT16 | Read/write | |||||
| HR | 13doc 000DH | CH1 Heater burnout alarm 2 value | INT16 | Read/write | |||||
| HR | 14doc 000EH | CH1 Loop break alarm span | INT16 | Read/write | |||||
| HR | 15doc 000FH | CH1 Loop break alarm time | INT16 | Read/write | |||||
| HR | 16doc 0010H | CH1 Input type | Code list depends on the input variant (multi-range or infrared); see the manual. | INT16 | Read/write | ||||
| HR | 17doc 0011H | CH1 Scaling high limit | INT16 | Read/write | |||||
| HR | 18doc 0012H | CH1 Scaling low limit | INT16 | Read/write | |||||
| HR | 19doc 0013H | CH1 Decimal point place | INT16 | Read/write | 0 = xxxx; 1 = xxx.x; 2 = xx.xx; 3 = x.xxx | ||||
| HR | 20doc 0014H | CH1 PV filter time constant | INT16 | Read/write | |||||
| HR | 21doc 0015H | CH1 Sensor correction | INT16 | Read/write | |||||
| HR | 22doc 0016H | CH1 Emissivity | Infrared thermocouple input. | INT16 | Read/write | ||||
| HR | 23doc 0017H | CH1 Output high limit | INT16 | Read/write | |||||
| HR | 24doc 0018H | CH1 Output low limit | INT16 | Read/write | |||||
| HR | 25doc 0019H | CH1 Output ON/OFF hysteresis | INT16 | Read/write | |||||
| HR | 26doc 001AH | CH1 OUT2 action mode | INT16 | Read/write | 0 = Air cooling (linear); 1 = Oil cooling (1.5th power); 2 = Water cooling (2nd power) | ||||
| HR | 27doc 001BH | CH1 OUT2 high limit | INT16 | Read/write | |||||
| HR | 28doc 001CH | CH1 OUT2 low limit | INT16 | Read/write | |||||
| HR | 29doc 001DH | CH1 OUT2 ON/OFF hysteresis | INT16 | Read/write | |||||
| HR | 30doc 001EH | CH1 Overlap/dead band | INT16 | Read/write | |||||
| HR | 31doc 001FH | CH1 Output rate-of-change | INT16 | Read/write | |||||
| HR | 32doc 0020H | CH1 Output when input abnormal | INT16 | Read/write | |||||
| HR | 33doc 0021H | CH1 Alarm 1 type | Changing it resets the alarm value to 0. | INT16 | Read/write | 0 = No alarm action; 1 = High limit alarm; 2 = Low limit alarm; 3 = High/Low limits alarm; 4 = High/Low limit range alarm; 5 = Process high alarm; 6 = Process low alarm; 7 = High limit with standby; 8 = Low limit with standby; 9 = High/Low limits with standby | |||
| HR | 34doc 0022H | CH1 Alarm 1 hysteresis | INT16 | Read/write | |||||
| HR | 35doc 0023H | CH1 Alarm 1 action delay timer | INT16 | Read/write | |||||
| HR | 36doc 0024H | CH1 SV rise rate | INT16 | Read/write | |||||
| HR | 37doc 0025H | CH1 SV fall rate | INT16 | Read/write | |||||
| HR | 38doc 0026H | CH1 Direct/reverse action | INT16 | Read/write | 0 = Reverse (heating); 1 = Direct (cooling) | ||||
| HR | 39doc 0027H | CH1 AT bias | INT16 | Read/write | |||||
| HR | 40doc 0028H | CH1 Control allowed/prohibited | INT16 | Read/write | 0 = Control allowed; 1 = Control prohibited | ||||
| HR | 41doc 0029H | CH1 Auto/manual control | INT16 | Read/write | 0 = Automatic control; 1 = Manual control | ||||
| HR | 42doc 002AH | CH1 Manual MV | INT16 | Read/write | |||||
| HR | 43doc 002BH | CH1 SV (temporary storage) | Reverts to the previous value after power off. | INT16 | Read/write | ||||
| HR | 44doc 002CH | CH1 Difference/addition indication high limit | INT16 | Read/write | |||||
| HR | 45doc 002DH | CH1 Difference/addition indication low limit | INT16 | Read/write | |||||
| HR | 48doc 0030H | Set value lock | INT16 | Read/write | 0 = Unlock; 1 = Lock 1; 2 = Lock 2; 3 = Lock 3 | ||||
| HR | 49doc 0031H | Remote/local | INT16 | Read/write | 0 = Local; 1 = Remote | ||||
| HR | 50doc 0032H | External setting scaling high limit | INT16 | Read/write | |||||
| HR | 51doc 0033H | External setting scaling low limit | INT16 | Read/write | |||||
| HR | 52doc 0034H | Remote bias | INT16 | Read/write | |||||
| HR | 53doc 0035H | Transmission output | INT16 | Read/write | 0 = PV transmission; 1 = SV transmission; 2 = MV transmission | ||||
| HR | 54doc 0036H | Transmission output high limit | INT16 | Read/write | |||||
| HR | 55doc 0037H | Transmission output low limit | INT16 | Read/write | |||||
| HR | 56doc 0038H | Timer action | INT16 | Read/write | 0 = Control timer; 1 = Delay timer 1; 2 = Delay timer 2 | ||||
| HR | 57doc 0039H | Timer action time unit | INT16 | Read/write | 0 = Minute; 1 = Second | ||||
| HR | 58doc 003AH | ON delay timer | INT16 | Read/write | |||||
| HR | 59doc 003BH | OFF delay timer | INT16 | Read/write | |||||
| HR | 60doc 003CH | Control timer start temperature | INT16 | Read/write | |||||
| HR | 61doc 003DH | Control timer time | INT16 | Read/write | |||||
| HR | 62doc 003EH | Auto-light function | INT16 | Read/write | 0 = Ineffective; 1 = Effective | ||||
| HR | 63doc 003FH | Display selection | Codes 0-12 choose which channel values are shown; see manual p. 16. | INT16 | Read/write | ||||
| HR | 64doc 0040H | Indication time | INT16 | Read/write | |||||
| HR | 65doc 0041H | Input sampling period | INT16 | Read/write | 0 = 25 ms; 1 = 125 ms; 2 = 250 ms | ||||
| HR | 81doc 0051H | CH2 SV | Set value. Raw integer; apply the decimal point setting. | INT16 | Read/write | ||||
| HR | 82doc 0052H | CH2 AT/Auto-reset | INT16 | Read/write | 0 = Cancel; 1 = Perform | ||||
| HR | 83doc 0053H | CH2 Proportional band | INT16 | Read/write | |||||
| HR | 85doc 0055H | CH2 Integral time | INT16 | Read/write | |||||
| HR | 86doc 0056H | CH2 Derivative time | INT16 | Read/write | |||||
| HR | 87doc 0057H | CH2 ARW | Anti-reset windup. | INT16 | Read/write | ||||
| HR | 88doc 0058H | CH2 Manual reset value | INT16 | Read/write | |||||
| HR | 89doc 0059H | CH2 Proportional cycle | INT16 | Read/write | |||||
| HR | 91doc 005BH | CH2 Alarm 1 value | Raw integer; apply the decimal point setting. | INT16 | Read/write | ||||
| HR | 92doc 005CH | CH2 Heater burnout alarm 1 value | INT16 | Read/write | |||||
| HR | 93doc 005DH | CH2 Heater burnout alarm 2 value | INT16 | Read/write | |||||
| HR | 94doc 005EH | CH2 Loop break alarm span | INT16 | Read/write | |||||
| HR | 95doc 005FH | CH2 Loop break alarm time | INT16 | Read/write | |||||
| HR | 96doc 0060H | CH2 Input type | Code list depends on the input variant (multi-range or infrared); see the manual. | INT16 | Read/write | ||||
| HR | 97doc 0061H | CH2 Scaling high limit | INT16 | Read/write | |||||
| HR | 98doc 0062H | CH2 Scaling low limit | INT16 | Read/write | |||||
| HR | 99doc 0063H | CH2 Decimal point place | INT16 | Read/write | 0 = xxxx; 1 = xxx.x; 2 = xx.xx; 3 = x.xxx | ||||
| HR | 100doc 0064H | CH2 PV filter time constant | INT16 | Read/write | |||||
| HR | 101doc 0065H | CH2 Sensor correction | INT16 | Read/write | |||||
| HR | 102doc 0066H | CH2 Emissivity | Infrared thermocouple input. | INT16 | Read/write | ||||
| HR | 103doc 0067H | CH2 Output high limit | INT16 | Read/write | |||||
| HR | 104doc 0068H | CH2 Output low limit | INT16 | Read/write | |||||
| HR | 105doc 0069H | CH2 Output ON/OFF hysteresis | INT16 | Read/write | |||||
| HR | 111doc 006FH | CH2 Output rate-of-change | INT16 | Read/write | |||||
| HR | 112doc 0070H | CH2 Output when input abnormal | INT16 | Read/write | |||||
| HR | 113doc 0071H | CH2 Alarm 1 type | Changing it resets the alarm value to 0. | INT16 | Read/write | 0 = No alarm action; 1 = High limit alarm; 2 = Low limit alarm; 3 = High/Low limits alarm; 4 = High/Low limit range alarm; 5 = Process high alarm; 6 = Process low alarm; 7 = High limit with standby; 8 = Low limit with standby; 9 = High/Low limits with standby | |||
| HR | 114doc 0072H | CH2 Alarm 1 hysteresis | INT16 | Read/write | |||||
| HR | 115doc 0073H | CH2 Alarm 1 action delay timer | INT16 | Read/write | |||||
| HR | 116doc 0074H | CH2 SV rise rate | INT16 | Read/write | |||||
| HR | 117doc 0075H | CH2 SV fall rate | INT16 | Read/write | |||||
| HR | 118doc 0076H | CH2 Direct/reverse action | INT16 | Read/write | 0 = Reverse (heating); 1 = Direct (cooling) | ||||
| HR | 119doc 0077H | CH2 AT bias | INT16 | Read/write | |||||
| HR | 120doc 0078H | CH2 Control allowed/prohibited | INT16 | Read/write | 0 = Control allowed; 1 = Control prohibited | ||||
| HR | 121doc 0079H | CH2 Auto/manual control | INT16 | Read/write | 0 = Automatic control; 1 = Manual control | ||||
| HR | 122doc 007AH | CH2 Manual MV | INT16 | Read/write | |||||
| HR | 123doc 007BH | CH2 SV (temporary storage) | Reverts to the previous value after power off. | INT16 | Read/write | ||||
| HR | 124doc 007CH | CH2 Difference/addition indication high limit | INT16 | Read/write | |||||
| HR | 125doc 007DH | CH2 Difference/addition indication low limit | INT16 | Read/write | |||||
| HR | 127doc 007FH | Key operation change flag clearing | INT16 | Write | 1 = Clear change flag | ||||
| HR | 128doc 0080H | CH1 PV | Process value (or difference/addition value). Raw integer; apply the decimal point setting. | INT16 | Read | ||||
| HR | 129doc 0081H | CH1 Output MV | INT16 | Read | |||||
| HR | 130doc 0082H | CH1 SV reading | Raw integer; apply the decimal point setting. | INT16 | Read | ||||
| HR | 131doc 0083H | CH1 Status flag | BITMAP16 | Read | bit 0 = Output on; bit 2 = Alarm 1 output on; bit 5 = CT1 heater burnout; bit 6 = CT2 heater burnout; bit 7 = Heater burnout alarm; bit 8 = Loop break alarm; bit 9 = Overscale; bit 10 = Underscale; bit 11 = Standby mode; bit 12 = Setting mode; bit 13 = AT/Auto-reset running; bit 14 = Manual control; bit 15 = Settings changed by keypad | ||||
| HR | 132doc 0084H | CH1 CT1 current value | INT16 | Read | |||||
| HR | 133doc 0085H | CH1 CT2 current value | INT16 | Read | |||||
| HR | 134doc 0086H | CH1 Current PV | Raw integer; apply the decimal point setting. | INT16 | Read | ||||
| HR | 135doc 0087H | CH1 Status flag 2 | BITMAP16 | Read | bit 0 = Alarm 1 output; bit 1 = Alarm 2 output; bit 2 = Alarm 3 output; bit 3 = Alarm 4 output; bit 4 = Difference/addition overscale; bit 5 = Difference/addition underscale | ||||
| HR | 144doc 0090H | CH2 PV | Process value (or difference/addition value). Raw integer; apply the decimal point setting. | INT16 | Read | ||||
| HR | 145doc 0091H | CH2 Output MV | INT16 | Read | |||||
| HR | 146doc 0092H | CH2 SV reading | Raw integer; apply the decimal point setting. | INT16 | Read | ||||
| HR | 147doc 0093H | CH2 Status flag | BITMAP16 | Read | bit 0 = Output on; bit 2 = Alarm 1 output on; bit 5 = CT3 heater burnout; bit 6 = CT4 heater burnout; bit 7 = Heater burnout alarm; bit 8 = Loop break alarm; bit 9 = Overscale; bit 10 = Underscale; bit 11 = Standby mode; bit 12 = Setting mode; bit 13 = AT/Auto-reset running; bit 14 = Manual control; bit 15 = Settings changed by keypad | ||||
| HR | 148doc 0094H | CH2 CT3 current value | INT16 | Read | |||||
| HR | 149doc 0095H | CH2 CT4 current value | INT16 | Read | |||||
| HR | 150doc 0096H | CH2 Current PV | Raw integer; apply the decimal point setting. | INT16 | Read | ||||
| HR | 151doc 0097H | CH2 Status flag 2 | BITMAP16 | Read | bit 0 = Alarm 1 output; bit 1 = Alarm 2 output; bit 2 = Alarm 3 output; bit 3 = Alarm 4 output; bit 4 = Difference/addition overscale; bit 5 = Difference/addition underscale | ||||
| HR | 208doc 00D0H | CH1 Alarm 2 value | Raw integer; apply the decimal point setting. | INT16 | Read/write | ||||
| HR | 209doc 00D1H | CH1 Alarm 3 value | Raw integer; apply the decimal point setting. | INT16 | Read/write | ||||
| HR | 210doc 00D2H | CH1 Alarm 4 value | Raw integer; apply the decimal point setting. | INT16 | Read/write | ||||
| HR | 211doc 00D3H | CH1 Alarm 2 type | INT16 | Read/write | 0 = No alarm action; 1 = High limit alarm; 2 = Low limit alarm; 3 = High/Low limits alarm; 4 = High/Low limit range alarm; 5 = Process high alarm; 6 = Process low alarm; 7 = High limit with standby; 8 = Low limit with standby; 9 = High/Low limits with standby | ||||
| HR | 212doc 00D4H | CH1 Alarm 3 type | INT16 | Read/write | 0 = No alarm action; 1 = High limit alarm; 2 = Low limit alarm; 3 = High/Low limits alarm; 4 = High/Low limit range alarm; 5 = Process high alarm; 6 = Process low alarm; 7 = High limit with standby; 8 = Low limit with standby; 9 = High/Low limits with standby | ||||
| HR | 213doc 00D5H | CH1 Alarm 4 type | INT16 | Read/write | 0 = No alarm action; 1 = High limit alarm; 2 = Low limit alarm; 3 = High/Low limits alarm; 4 = High/Low limit range alarm; 5 = Process high alarm; 6 = Process low alarm; 7 = High limit with standby; 8 = Low limit with standby; 9 = High/Low limits with standby | ||||
| HR | 214doc 00D6H | CH1 Alarm 2 hysteresis | INT16 | Read/write | |||||
| HR | 215doc 00D7H | CH1 Alarm 3 hysteresis | INT16 | Read/write | |||||
| HR | 216doc 00D8H | CH1 Alarm 4 hysteresis | INT16 | Read/write | |||||
| HR | 217doc 00D9H | CH1 Alarm 2 action delay timer | INT16 | Read/write | |||||
| HR | 218doc 00DAH | CH1 Alarm 3 action delay timer | INT16 | Read/write | |||||
| HR | 219doc 00DBH | CH1 Alarm 4 action delay timer | INT16 | Read/write | |||||
| HR | 220doc 00DCH | CH1 Event 1 output | INT16 | Read/write | 0 = Alarm (temperature); 1 = Loop break alarm; 2 = Alarm + loop break alarm | ||||
| HR | 221doc 00DDH | CH1 Event 2 output | INT16 | Read/write | 0 = Alarm (temperature); 1 = Loop break alarm; 2 = Alarm + loop break alarm; 3 = Heater burnout alarm; 4 = Alarm + heater burnout; 5 = Loop break + heater burnout; 6 = Alarm + loop break + heater burnout | ||||
| HR | 224doc 00E0H | CH2 Alarm 2 value | Raw integer; apply the decimal point setting. | INT16 | Read/write | ||||
| HR | 225doc 00E1H | CH2 Alarm 3 value | Raw integer; apply the decimal point setting. | INT16 | Read/write | ||||
| HR | 226doc 00E2H | CH2 Alarm 4 value | Raw integer; apply the decimal point setting. | INT16 | Read/write | ||||
| HR | 227doc 00E3H | CH2 Alarm 2 type | INT16 | Read/write | 0 = No alarm action; 1 = High limit alarm; 2 = Low limit alarm; 3 = High/Low limits alarm; 4 = High/Low limit range alarm; 5 = Process high alarm; 6 = Process low alarm; 7 = High limit with standby; 8 = Low limit with standby; 9 = High/Low limits with standby | ||||
| HR | 228doc 00E4H | CH2 Alarm 3 type | INT16 | Read/write | 0 = No alarm action; 1 = High limit alarm; 2 = Low limit alarm; 3 = High/Low limits alarm; 4 = High/Low limit range alarm; 5 = Process high alarm; 6 = Process low alarm; 7 = High limit with standby; 8 = Low limit with standby; 9 = High/Low limits with standby | ||||
| HR | 229doc 00E5H | CH2 Alarm 4 type | INT16 | Read/write | 0 = No alarm action; 1 = High limit alarm; 2 = Low limit alarm; 3 = High/Low limits alarm; 4 = High/Low limit range alarm; 5 = Process high alarm; 6 = Process low alarm; 7 = High limit with standby; 8 = Low limit with standby; 9 = High/Low limits with standby | ||||
| HR | 230doc 00E6H | CH2 Alarm 2 hysteresis | INT16 | Read/write | |||||
| HR | 231doc 00E7H | CH2 Alarm 3 hysteresis | INT16 | Read/write | |||||
| HR | 232doc 00E8H | CH2 Alarm 4 hysteresis | INT16 | Read/write | |||||
| HR | 233doc 00E9H | CH2 Alarm 2 action delay timer | INT16 | Read/write | |||||
| HR | 234doc 00EAH | CH2 Alarm 3 action delay timer | INT16 | Read/write | |||||
| HR | 235doc 00EBH | CH2 Alarm 4 action delay timer | INT16 | Read/write | |||||
| HR | 236doc 00ECH | CH2 Event 1 output | INT16 | Read/write | 0 = Alarm (temperature); 1 = Loop break alarm; 2 = Alarm + loop break alarm | ||||
| HR | 237doc 00EDH | CH2 Event 2 output | INT16 | Read/write | 0 = Alarm (temperature); 1 = Loop break alarm; 2 = Alarm + loop break alarm; 3 = Heater burnout alarm; 4 = Alarm + heater burnout; 5 = Loop break + heater burnout; 6 = Alarm + loop break + heater burnout |
Notes on this map
- CH2 items sit 50H above the matching CH1 items (SV 0001H vs 0051H); CH1-only OUT2 items have no CH2 twin. Read-only blocks start at 0080H (CH1) and 0090H (CH2); alarm 2-4 blocks at 00D0H (CH1) and 00E0H (CH2).
- All data are 16-bit two's complement. Values with a decimal point are sent as whole numbers; apply each channel's decimal point place.
- Input type codes differ between the multi-range and infrared thermocouple input versions, so value names are not listed.
- PV may carry a difference or addition value when that block function is enabled in the console software.
- Instrument number and speed can only be set on the keypad.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Shinko Technos WCL-13A 2-channel digital indicating controller (C5 option)
What Modbus registers does the Shinko Technos WCL-13A 2-channel digital indicating controller (C5 option) have?
This map lists 146 registers: 146 holding registers. 130 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Shinko Technos WCL-13A 2-channel digital indicating controller (C5 option) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Registers are listed as hex data items (0001H) that go into the request unchanged. The manual's RTU example reads CH1 SV with data item 0001H, and its CRC (D5CAH) confirms 0001H is the wire address.
What are the minimum Modbus registers to integrate the Shinko Technos WCL-13A 2-channel digital indicating controller (C5 option)?
Start with HR 128 CH1 PV (CH1 PV); HR 131 CH1 Status flag (CH1 status); HR 144 CH2 PV (CH2 PV); HR 147 CH2 Status flag (CH2 status); HR 1 CH1 SV (CH1 SV); HR 81 CH2 SV (CH2 SV).
How do I enable Modbus control of the Shinko Technos WCL-13A 2-channel digital indicating controller (C5 option)?
Requires the C5 option. Set Communication protocol to Modbus RTU and an 8-bit data bit/parity choice on the keypad, then the instrument number and speed.
Where is the official Shinko Technos WCL-13A 2-channel digital indicating controller (C5 option) Modbus documentation?
The source is Communication Instruction Manual WCL-13A (C5) (No.WCL1CE3), revision 2011-11, published free by Shinko Technos at https://shinko-technos.co.jp/e/manual/english/WCL1CE3.pdf.
More Shinko Technos Modbus register maps
- Sensor (digital temperature controller)
Shinko Technos ACD-13A / ACR-13A / ACD-15A / ACR-15A digital indicating controller (C, C5 options)
Shinko ACD/ACR-13A (PID) and ACD/ACR-15A (valve positioning) with the C or C5 communication option; manual No.ACDR1CE8.
Also known as: ACD-13A, ACR-13A, ACD-15A, ACR-15A - Sensor (digital temperature controller)
Shinko Technos ACS-13A digital indicating controller (C5 option)
Shinko ACS-13A with the C5 serial communication option; communication manual No.ACS12CE5.
Also known as: ACS-13A-C5, ACS-13A C5 - Sensor (digital temperature controller)
Shinko Technos ACS2 digital indicating controller (C5, C5W options)
Shinko ACS2 with the C5 or C5W serial option, Shinko protocol / MODBUS RTU command set; manual No.ACS2CE3.
Also known as: ACS2-C5, ACS2-C5W - Sensor (conductivity controller)
Shinko Technos AER-102-ECH conductivity indicating controller (C5 option)
Shinko AER-102-ECH electrical conductivity controller with the C5 RS-485 option; manual No. AER11CECE5.
Also known as: AER-102-ECH - Sensor (digital temperature controller)
Shinko Technos BCS2 / BCR2 / BCD2 digital indicating controller (C5, C5W options)
Shinko BCx2 series (BCS2, BCR2, BCD2) with the C5 or C5W communication option, standard (not JC-allocated) command set; manual No.BCx2CE6.
Also known as: BCS2, BCR2, BCD2, BCx2 - Sensor (digital temperature controller)
Shinko Technos DCL-33A DC digital indicating controller (C5 option)
Shinko DCL-33A DC with the C5 option; communication manual No.DCL3CDCE2.
Also known as: DCL-33A DC, DCL-33A-DC-C5 - Sensor (digital temperature controller)
Shinko Technos DCL-33A digital indicating controller (C5 option)
Shinko DCL-33A with the C5 serial option, plain (non-block) Modbus protocol setting; manual No.DCL32CE3.
Also known as: DCL-33A-C5, DCL-33A C5 - Sensor (digital temperature controller)
Shinko Technos FC series digital indicating controller (C/C5 option, Modbus ASCII)
Shinko FCS-23A, FCR-13A, FCR-23A and FCD-13A with the C or C5 serial option; FCR-15A and FCD-15A have no Modbus (Shinko protocol only). Manual No.FC1CE11.
Also known as: FCS-23A, FCR-13A, FCR-23A, FCD-13A - Sensor (paperless recorder)
Shinko Technos GR200 paperless recorder (Modbus RTU / Modbus TCP)
Shinko GR200 paperless recorder with RS-485 Modbus RTU or Ethernet Modbus TCP; manual GR2CE1.
Also known as: GR200 - Sensor (chart recorder)
Shinko Technos HR-700 hybrid recorder (Modbus RTU, firmware 4.00+)
Shinko HR-700 hybrid recorders (multipoint and pen types), body version 4.00 or later, Modbus map version 01; manual No. HR7CE4.
Also known as: HR-700 - Sensor (digital temperature controller)
Shinko Technos JCL-33A digital indicating controller (C5 option)
Shinko JCL-33A with the C5 option, protocol set to plain 'Modbus RTU mode' or 'Modbus ASCII mode' (not the Block Read/Write modes, which use another layout); manual No.JCL3CE3.
Also known as: JCL-33A-C5, JCL-33A C5 - Sensor (digital temperature controller)
Shinko Technos JCS-33A / JCM-33A / JCR-33A / JCD-33A digital indicating controller (C5 option)
Shinko JCx-33A series (JCS, JCM, JCR, JCD-33A) with the C5 option; communication manual No.JC3CE11.
Also known as: JCS-33A, JCM-33A, JCR-33A, JCD-33A, JCx-33A - Sensor (digital temperature controller)
Shinko Technos JIR-301-M digital indicator (C5 option)
Shinko JIR-301-M with the C5 option, plain (non-block) Modbus protocol setting; manual No.JIR32CE4.
Also known as: JIR-301-M-C5, JIR-301-M C5 - Sensor (programmable temperature controller)
Shinko Technos PCA1 programmable controller (C/C5 option)
Shinko PCA1 programmable controllers with the C or C5 serial option; manual No. PCA1CE3.
Also known as: PCA1 - Sensor (programmable temperature controller)
Shinko Technos PCB1 programmable controller (C5W/C5 option)
Shinko PCB1 programmable controllers with the C5W or C5 RS-485 option, native PCB1 command set; manual No. PCB1CE3.
Also known as: PCB1 - Sensor (digital temperature controller)
Shinko Technos PCD-33A programmable controller (C5 option)
Shinko PCD-33A program controller with the C5 RS-485 option; manual printed No.PCD3CE1 2003.02 (file PCD3CE2).
Also known as: PCD-33A-R/M, PCD-33A-S/M - Sensor (signal conditioner)
Shinko Technos SGxL signal conditioner series (Modbus RTU)
Shinko SGxL signal conditioners (SGBL, SGCL, SGDL, SGIL, SGLL, SGML, SGPL, SGRL, SGSL, SGTL, SGUL); SGFL and SGJL are not covered. Manual No.SGxL1CE3.
Also known as: SGBL, SGCL, SGDL, SGIL, SGLL, SGML, SGPL, SGRL, SGSL, SGTL, SGUL
Other temperature & process controllers register maps
- Sensor / counter-timer (programmable counter and timer)
Autonics CT series programmable counter / timer (Modbus RTU)
Autonics CT series counters/timers with RS-485 communication, communication manual MCC-CTC1-V1.3-EN.
Also known as: CT4S, CT6, CT6S, CT6M, CT6Y, CT6M-2P, CT6S-1P4 - Sensor (modular temperature controller)
RKC Instrument SRV module type controller, TIO temperature control module (Modbus RTU)
RKC SRV two-channel temperature control (TIO) modules, basic and extension type, with Modbus selected.
Also known as: SRV, SRV TIO module, RKC SRV - Process controller (sensor / PID controller)
ABB Protronic 100/500/550 and Digitric 500 process controllers (Modbus RTU)
ABB Protronic 100/500/550 and Digitric 500 universal process controllers with the RS-485/RS-232 Modbus interface module, interface description 42/62-50040 EN Rev. 04.
Also known as: Protronic 100, Protronic 500, Protronic 550, Digitric 500 - Sensor / multi-input controller
ProMinent DULCOMETER AEGIS II controller (Modbus RTU slave)
AEGIS II controllers fitted with the COM module (Modbus RTU slave on XB21/XB22), per manual BA DM 229 08/18.
Also known as: AEGIS II, Aegis II, DULCOMETER AEGIS II, AEGIS II COM module - Sensor (digital indicating temperature controller)
Yokogawa UTAdvanced UT75A digital indicating controller
Yokogawa UT75A one- or two-loop controller with RS-485 or Ethernet communication; D-register map from IM 05P07A01-01EN chapter 14.
Also known as: UT75A - Sensor (digital temperature controller)
Omron E5CC / E5EC / E5AC / E5DC digital temperature controllers (E5_C series)
Omron E5CC, E5EC, E5AC, E5DC and E5CC-U controllers with RS-485, per the E5_C Communications Manual H175; registers present depend on model and options.
Also known as: E5CC, E5EC, E5AC, E5DC, E5CC-U, E5@C, E5_C
All temperature & process controllers Modbus register maps →
Source: Communication Instruction Manual WCL-13A (C5) · No.WCL1CE3 · rev. 2011-11. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.