Easy Modbus
  1. Home
  2. Modbus register maps
  3. Shinko Technos
  4. WCL-13A 2-channel digital indicating controller (C5 option)

Sensor (digital temperature controller) · Modbus register map

Shinko Technos WCL-13A 2-channel digital indicating controller (C5 option) Modbus register map

Updated 17 November 2026

Short answer

The WCL-13A is a two-channel PID temperature controller (one unit, two loops); CH1 also has a heat/cool OUT2. With the C5 option it speaks Shinko protocol, Modbus ASCII or Modbus RTU on RS485, and all items are signed 16-bit holding registers. The map covers both channels' SV, PID, alarm and output settings, shared timer and transmission settings, and each channel's PV, MV, SV, heater current and status words.

This page lists 146 Modbus registers for the Shinko Technos WCL-13A 2-channel digital indicating controller (C5 option) — 130 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Shinko Technos’s own free documentation (linked below) and checked against it.

Manufacturer
Shinko Technos
Model
WCL-13A 2-channel digital indicating controller (C5 option)
Equipment type
Sensor (digital temperature controller)
Registers
146 (130 writable)
Transport
Modbus RTU, Modbus ASCII
Default unit ID
0
Default serial
9600 baud, 7E1
Documented addressing
hexadecimal, 0-based
Also known as
WCL-13A-C5, WCL-13A C5
Source document
Communication Instruction Manual WCL-13A (C5) · No.WCL1CE3 · rev. 2011-11
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Shinko Technos WCL-13A 2-channel digital indicating controller (C5 option)

Integration in brief

Select Modbus RTU with an 8-bit format on the keypad and set an instrument number. Poll 0080H-0083H for CH1 and 0090H-0093H for CH2 (PV, MV, SV, status); write SVs at 0001H and 0051H.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 128CH1 PVINT16CH1 PVRead
HR 131CH1 Status flagBITMAP16CH1 statusRead
HR 144CH2 PVINT16CH2 PVRead
HR 147CH2 Status flagBITMAP16CH2 statusRead
HR 1CH1 SVINT16CH1 SVRead/write
HR 81CH2 SVINT16CH2 SVRead/write

Enable Modbus control & writes

Requires the C5 option. Set Communication protocol to Modbus RTU and an 8-bit data bit/parity choice on the keypad, then the instrument number and speed.

Byte order & addressing

Network setup

Watch out for

Shinko Technos WCL-13A 2-channel digital indicating controller (C5 option) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

146 of 146 shown
Shinko Technos WCL-13A 2-channel digital indicating controller (C5 option) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR1doc 0001HCH1 SVSet value. Raw integer; apply the decimal point setting.INT16Read/write
HR2doc 0002HCH1 AT/Auto-resetINT16Read/write0 = Cancel; 1 = Perform
HR3doc 0003HCH1 Proportional bandINT16Read/write
HR4doc 0004HCH1 OUT2 proportional bandINT16Read/write
HR5doc 0005HCH1 Integral timeINT16Read/write
HR6doc 0006HCH1 Derivative timeINT16Read/write
HR7doc 0007HCH1 ARWAnti-reset windup.INT16Read/write
HR8doc 0008HCH1 Manual reset valueINT16Read/write
HR9doc 0009HCH1 Proportional cycleINT16Read/write
HR10doc 000AHCH1 OUT2 proportional cycleINT16Read/write
HR11doc 000BHCH1 Alarm 1 valueRaw integer; apply the decimal point setting.INT16Read/write
HR12doc 000CHCH1 Heater burnout alarm 1 valueINT16Read/write
HR13doc 000DHCH1 Heater burnout alarm 2 valueINT16Read/write
HR14doc 000EHCH1 Loop break alarm spanINT16Read/write
HR15doc 000FHCH1 Loop break alarm timeINT16Read/write
HR16doc 0010HCH1 Input typeCode list depends on the input variant (multi-range or infrared); see the manual.INT16Read/write
HR17doc 0011HCH1 Scaling high limitINT16Read/write
HR18doc 0012HCH1 Scaling low limitINT16Read/write
HR19doc 0013HCH1 Decimal point placeINT16Read/write0 = xxxx; 1 = xxx.x; 2 = xx.xx; 3 = x.xxx
HR20doc 0014HCH1 PV filter time constantINT16Read/write
HR21doc 0015HCH1 Sensor correctionINT16Read/write
HR22doc 0016HCH1 EmissivityInfrared thermocouple input.INT16Read/write
HR23doc 0017HCH1 Output high limitINT16Read/write
HR24doc 0018HCH1 Output low limitINT16Read/write
HR25doc 0019HCH1 Output ON/OFF hysteresisINT16Read/write
HR26doc 001AHCH1 OUT2 action modeINT16Read/write0 = Air cooling (linear); 1 = Oil cooling (1.5th power); 2 = Water cooling (2nd power)
HR27doc 001BHCH1 OUT2 high limitINT16Read/write
HR28doc 001CHCH1 OUT2 low limitINT16Read/write
HR29doc 001DHCH1 OUT2 ON/OFF hysteresisINT16Read/write
HR30doc 001EHCH1 Overlap/dead bandINT16Read/write
HR31doc 001FHCH1 Output rate-of-changeINT16Read/write
HR32doc 0020HCH1 Output when input abnormalINT16Read/write
HR33doc 0021HCH1 Alarm 1 typeChanging it resets the alarm value to 0.INT16Read/write0 = No alarm action; 1 = High limit alarm; 2 = Low limit alarm; 3 = High/Low limits alarm; 4 = High/Low limit range alarm; 5 = Process high alarm; 6 = Process low alarm; 7 = High limit with standby; 8 = Low limit with standby; 9 = High/Low limits with standby
HR34doc 0022HCH1 Alarm 1 hysteresisINT16Read/write
HR35doc 0023HCH1 Alarm 1 action delay timerINT16Read/write
HR36doc 0024HCH1 SV rise rateINT16Read/write
HR37doc 0025HCH1 SV fall rateINT16Read/write
HR38doc 0026HCH1 Direct/reverse actionINT16Read/write0 = Reverse (heating); 1 = Direct (cooling)
HR39doc 0027HCH1 AT biasINT16Read/write
HR40doc 0028HCH1 Control allowed/prohibitedINT16Read/write0 = Control allowed; 1 = Control prohibited
HR41doc 0029HCH1 Auto/manual controlINT16Read/write0 = Automatic control; 1 = Manual control
HR42doc 002AHCH1 Manual MVINT16Read/write
HR43doc 002BHCH1 SV (temporary storage)Reverts to the previous value after power off.INT16Read/write
HR44doc 002CHCH1 Difference/addition indication high limitINT16Read/write
HR45doc 002DHCH1 Difference/addition indication low limitINT16Read/write
HR48doc 0030HSet value lockINT16Read/write0 = Unlock; 1 = Lock 1; 2 = Lock 2; 3 = Lock 3
HR49doc 0031HRemote/localINT16Read/write0 = Local; 1 = Remote
HR50doc 0032HExternal setting scaling high limitINT16Read/write
HR51doc 0033HExternal setting scaling low limitINT16Read/write
HR52doc 0034HRemote biasINT16Read/write
HR53doc 0035HTransmission outputINT16Read/write0 = PV transmission; 1 = SV transmission; 2 = MV transmission
HR54doc 0036HTransmission output high limitINT16Read/write
HR55doc 0037HTransmission output low limitINT16Read/write
HR56doc 0038HTimer actionINT16Read/write0 = Control timer; 1 = Delay timer 1; 2 = Delay timer 2
HR57doc 0039HTimer action time unitINT16Read/write0 = Minute; 1 = Second
HR58doc 003AHON delay timerINT16Read/write
HR59doc 003BHOFF delay timerINT16Read/write
HR60doc 003CHControl timer start temperatureINT16Read/write
HR61doc 003DHControl timer timeINT16Read/write
HR62doc 003EHAuto-light functionINT16Read/write0 = Ineffective; 1 = Effective
HR63doc 003FHDisplay selectionCodes 0-12 choose which channel values are shown; see manual p. 16.INT16Read/write
HR64doc 0040HIndication timeINT16Read/write
HR65doc 0041HInput sampling periodINT16Read/write0 = 25 ms; 1 = 125 ms; 2 = 250 ms
HR81doc 0051HCH2 SVSet value. Raw integer; apply the decimal point setting.INT16Read/write
HR82doc 0052HCH2 AT/Auto-resetINT16Read/write0 = Cancel; 1 = Perform
HR83doc 0053HCH2 Proportional bandINT16Read/write
HR85doc 0055HCH2 Integral timeINT16Read/write
HR86doc 0056HCH2 Derivative timeINT16Read/write
HR87doc 0057HCH2 ARWAnti-reset windup.INT16Read/write
HR88doc 0058HCH2 Manual reset valueINT16Read/write
HR89doc 0059HCH2 Proportional cycleINT16Read/write
HR91doc 005BHCH2 Alarm 1 valueRaw integer; apply the decimal point setting.INT16Read/write
HR92doc 005CHCH2 Heater burnout alarm 1 valueINT16Read/write
HR93doc 005DHCH2 Heater burnout alarm 2 valueINT16Read/write
HR94doc 005EHCH2 Loop break alarm spanINT16Read/write
HR95doc 005FHCH2 Loop break alarm timeINT16Read/write
HR96doc 0060HCH2 Input typeCode list depends on the input variant (multi-range or infrared); see the manual.INT16Read/write
HR97doc 0061HCH2 Scaling high limitINT16Read/write
HR98doc 0062HCH2 Scaling low limitINT16Read/write
HR99doc 0063HCH2 Decimal point placeINT16Read/write0 = xxxx; 1 = xxx.x; 2 = xx.xx; 3 = x.xxx
HR100doc 0064HCH2 PV filter time constantINT16Read/write
HR101doc 0065HCH2 Sensor correctionINT16Read/write
HR102doc 0066HCH2 EmissivityInfrared thermocouple input.INT16Read/write
HR103doc 0067HCH2 Output high limitINT16Read/write
HR104doc 0068HCH2 Output low limitINT16Read/write
HR105doc 0069HCH2 Output ON/OFF hysteresisINT16Read/write
HR111doc 006FHCH2 Output rate-of-changeINT16Read/write
HR112doc 0070HCH2 Output when input abnormalINT16Read/write
HR113doc 0071HCH2 Alarm 1 typeChanging it resets the alarm value to 0.INT16Read/write0 = No alarm action; 1 = High limit alarm; 2 = Low limit alarm; 3 = High/Low limits alarm; 4 = High/Low limit range alarm; 5 = Process high alarm; 6 = Process low alarm; 7 = High limit with standby; 8 = Low limit with standby; 9 = High/Low limits with standby
HR114doc 0072HCH2 Alarm 1 hysteresisINT16Read/write
HR115doc 0073HCH2 Alarm 1 action delay timerINT16Read/write
HR116doc 0074HCH2 SV rise rateINT16Read/write
HR117doc 0075HCH2 SV fall rateINT16Read/write
HR118doc 0076HCH2 Direct/reverse actionINT16Read/write0 = Reverse (heating); 1 = Direct (cooling)
HR119doc 0077HCH2 AT biasINT16Read/write
HR120doc 0078HCH2 Control allowed/prohibitedINT16Read/write0 = Control allowed; 1 = Control prohibited
HR121doc 0079HCH2 Auto/manual controlINT16Read/write0 = Automatic control; 1 = Manual control
HR122doc 007AHCH2 Manual MVINT16Read/write
HR123doc 007BHCH2 SV (temporary storage)Reverts to the previous value after power off.INT16Read/write
HR124doc 007CHCH2 Difference/addition indication high limitINT16Read/write
HR125doc 007DHCH2 Difference/addition indication low limitINT16Read/write
HR127doc 007FHKey operation change flag clearingINT16Write1 = Clear change flag
HR128doc 0080HCH1 PVProcess value (or difference/addition value). Raw integer; apply the decimal point setting.INT16Read
HR129doc 0081HCH1 Output MVINT16Read
HR130doc 0082HCH1 SV readingRaw integer; apply the decimal point setting.INT16Read
HR131doc 0083HCH1 Status flagBITMAP16Readbit 0 = Output on; bit 2 = Alarm 1 output on; bit 5 = CT1 heater burnout; bit 6 = CT2 heater burnout; bit 7 = Heater burnout alarm; bit 8 = Loop break alarm; bit 9 = Overscale; bit 10 = Underscale; bit 11 = Standby mode; bit 12 = Setting mode; bit 13 = AT/Auto-reset running; bit 14 = Manual control; bit 15 = Settings changed by keypad
HR132doc 0084HCH1 CT1 current valueINT16Read
HR133doc 0085HCH1 CT2 current valueINT16Read
HR134doc 0086HCH1 Current PVRaw integer; apply the decimal point setting.INT16Read
HR135doc 0087HCH1 Status flag 2BITMAP16Readbit 0 = Alarm 1 output; bit 1 = Alarm 2 output; bit 2 = Alarm 3 output; bit 3 = Alarm 4 output; bit 4 = Difference/addition overscale; bit 5 = Difference/addition underscale
HR144doc 0090HCH2 PVProcess value (or difference/addition value). Raw integer; apply the decimal point setting.INT16Read
HR145doc 0091HCH2 Output MVINT16Read
HR146doc 0092HCH2 SV readingRaw integer; apply the decimal point setting.INT16Read
HR147doc 0093HCH2 Status flagBITMAP16Readbit 0 = Output on; bit 2 = Alarm 1 output on; bit 5 = CT3 heater burnout; bit 6 = CT4 heater burnout; bit 7 = Heater burnout alarm; bit 8 = Loop break alarm; bit 9 = Overscale; bit 10 = Underscale; bit 11 = Standby mode; bit 12 = Setting mode; bit 13 = AT/Auto-reset running; bit 14 = Manual control; bit 15 = Settings changed by keypad
HR148doc 0094HCH2 CT3 current valueINT16Read
HR149doc 0095HCH2 CT4 current valueINT16Read
HR150doc 0096HCH2 Current PVRaw integer; apply the decimal point setting.INT16Read
HR151doc 0097HCH2 Status flag 2BITMAP16Readbit 0 = Alarm 1 output; bit 1 = Alarm 2 output; bit 2 = Alarm 3 output; bit 3 = Alarm 4 output; bit 4 = Difference/addition overscale; bit 5 = Difference/addition underscale
HR208doc 00D0HCH1 Alarm 2 valueRaw integer; apply the decimal point setting.INT16Read/write
HR209doc 00D1HCH1 Alarm 3 valueRaw integer; apply the decimal point setting.INT16Read/write
HR210doc 00D2HCH1 Alarm 4 valueRaw integer; apply the decimal point setting.INT16Read/write
HR211doc 00D3HCH1 Alarm 2 typeINT16Read/write0 = No alarm action; 1 = High limit alarm; 2 = Low limit alarm; 3 = High/Low limits alarm; 4 = High/Low limit range alarm; 5 = Process high alarm; 6 = Process low alarm; 7 = High limit with standby; 8 = Low limit with standby; 9 = High/Low limits with standby
HR212doc 00D4HCH1 Alarm 3 typeINT16Read/write0 = No alarm action; 1 = High limit alarm; 2 = Low limit alarm; 3 = High/Low limits alarm; 4 = High/Low limit range alarm; 5 = Process high alarm; 6 = Process low alarm; 7 = High limit with standby; 8 = Low limit with standby; 9 = High/Low limits with standby
HR213doc 00D5HCH1 Alarm 4 typeINT16Read/write0 = No alarm action; 1 = High limit alarm; 2 = Low limit alarm; 3 = High/Low limits alarm; 4 = High/Low limit range alarm; 5 = Process high alarm; 6 = Process low alarm; 7 = High limit with standby; 8 = Low limit with standby; 9 = High/Low limits with standby
HR214doc 00D6HCH1 Alarm 2 hysteresisINT16Read/write
HR215doc 00D7HCH1 Alarm 3 hysteresisINT16Read/write
HR216doc 00D8HCH1 Alarm 4 hysteresisINT16Read/write
HR217doc 00D9HCH1 Alarm 2 action delay timerINT16Read/write
HR218doc 00DAHCH1 Alarm 3 action delay timerINT16Read/write
HR219doc 00DBHCH1 Alarm 4 action delay timerINT16Read/write
HR220doc 00DCHCH1 Event 1 outputINT16Read/write0 = Alarm (temperature); 1 = Loop break alarm; 2 = Alarm + loop break alarm
HR221doc 00DDHCH1 Event 2 outputINT16Read/write0 = Alarm (temperature); 1 = Loop break alarm; 2 = Alarm + loop break alarm; 3 = Heater burnout alarm; 4 = Alarm + heater burnout; 5 = Loop break + heater burnout; 6 = Alarm + loop break + heater burnout
HR224doc 00E0HCH2 Alarm 2 valueRaw integer; apply the decimal point setting.INT16Read/write
HR225doc 00E1HCH2 Alarm 3 valueRaw integer; apply the decimal point setting.INT16Read/write
HR226doc 00E2HCH2 Alarm 4 valueRaw integer; apply the decimal point setting.INT16Read/write
HR227doc 00E3HCH2 Alarm 2 typeINT16Read/write0 = No alarm action; 1 = High limit alarm; 2 = Low limit alarm; 3 = High/Low limits alarm; 4 = High/Low limit range alarm; 5 = Process high alarm; 6 = Process low alarm; 7 = High limit with standby; 8 = Low limit with standby; 9 = High/Low limits with standby
HR228doc 00E4HCH2 Alarm 3 typeINT16Read/write0 = No alarm action; 1 = High limit alarm; 2 = Low limit alarm; 3 = High/Low limits alarm; 4 = High/Low limit range alarm; 5 = Process high alarm; 6 = Process low alarm; 7 = High limit with standby; 8 = Low limit with standby; 9 = High/Low limits with standby
HR229doc 00E5HCH2 Alarm 4 typeINT16Read/write0 = No alarm action; 1 = High limit alarm; 2 = Low limit alarm; 3 = High/Low limits alarm; 4 = High/Low limit range alarm; 5 = Process high alarm; 6 = Process low alarm; 7 = High limit with standby; 8 = Low limit with standby; 9 = High/Low limits with standby
HR230doc 00E6HCH2 Alarm 2 hysteresisINT16Read/write
HR231doc 00E7HCH2 Alarm 3 hysteresisINT16Read/write
HR232doc 00E8HCH2 Alarm 4 hysteresisINT16Read/write
HR233doc 00E9HCH2 Alarm 2 action delay timerINT16Read/write
HR234doc 00EAHCH2 Alarm 3 action delay timerINT16Read/write
HR235doc 00EBHCH2 Alarm 4 action delay timerINT16Read/write
HR236doc 00ECHCH2 Event 1 outputINT16Read/write0 = Alarm (temperature); 1 = Loop break alarm; 2 = Alarm + loop break alarm
HR237doc 00EDHCH2 Event 2 outputINT16Read/write0 = Alarm (temperature); 1 = Loop break alarm; 2 = Alarm + loop break alarm; 3 = Heater burnout alarm; 4 = Alarm + heater burnout; 5 = Loop break + heater burnout; 6 = Alarm + loop break + heater burnout

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Shinko Technos WCL-13A 2-channel digital indicating controller (C5 option)

What Modbus registers does the Shinko Technos WCL-13A 2-channel digital indicating controller (C5 option) have?

This map lists 146 registers: 146 holding registers. 130 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Shinko Technos WCL-13A 2-channel digital indicating controller (C5 option) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Registers are listed as hex data items (0001H) that go into the request unchanged. The manual's RTU example reads CH1 SV with data item 0001H, and its CRC (D5CAH) confirms 0001H is the wire address.

What are the minimum Modbus registers to integrate the Shinko Technos WCL-13A 2-channel digital indicating controller (C5 option)?

Start with HR 128 CH1 PV (CH1 PV); HR 131 CH1 Status flag (CH1 status); HR 144 CH2 PV (CH2 PV); HR 147 CH2 Status flag (CH2 status); HR 1 CH1 SV (CH1 SV); HR 81 CH2 SV (CH2 SV).

How do I enable Modbus control of the Shinko Technos WCL-13A 2-channel digital indicating controller (C5 option)?

Requires the C5 option. Set Communication protocol to Modbus RTU and an 8-bit data bit/parity choice on the keypad, then the instrument number and speed.

Where is the official Shinko Technos WCL-13A 2-channel digital indicating controller (C5 option) Modbus documentation?

The source is Communication Instruction Manual WCL-13A (C5) (No.WCL1CE3), revision 2011-11, published free by Shinko Technos at https://shinko-technos.co.jp/e/manual/english/WCL1CE3.pdf.

More Shinko Technos Modbus register maps

Other temperature & process controllers register maps

All temperature & process controllers Modbus register maps →

Source: Communication Instruction Manual WCL-13A (C5) · No.WCL1CE3 · rev. 2011-11. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.