Sensor (digital temperature controller) · Modbus register map

Omron E5CC / E5EC / E5AC / E5DC digital temperature controllers (E5_C series) Modbus register map

Updated 17 November 2026

Short answer

Omron's E5_C temperature controllers speak CompoWay/F or Modbus RTU on their RS-485 option. The variable area can be read in 4-byte mode (two registers per value) or 2-byte mode (one register per value, addresses from 0x2000); this map uses 2-byte mode for PV, set points, MV, heater current, alarms and status, plus the operation-command register for RUN/STOP, auto/manual and auto-tune.

This page lists 20 Modbus registers for the Omron E5CC / E5EC / E5AC / E5DC digital temperature controllers (E5_C series) — 10 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Omron’s own free documentation (linked below) and checked against it.

Manufacturer
Omron
Model
E5CC / E5EC / E5AC / E5DC digital temperature controllers (E5_C series)
Equipment type
Sensor (digital temperature controller)
Registers
20 (10 writable)
Transport
Modbus RTU
Default unit ID
1
Documented addressing
hexadecimal, 0-based
Also known as
E5CC, E5EC, E5AC, E5DC, E5CC-U, E5@C, E5_C
Source document
E5@C Digital Temperature Controllers Communications Manual · H175-E1-17 · rev. 2022-09
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Omron E5CC / E5EC / E5AC / E5DC digital temperature controllers (E5_C series)

Integration in brief

Read 0x2000-0x2005 with FC03 for PV, status, internal SP, heater current and MV; read 0x2410 once for the decimal point. To change the set point, first write 0x0001 to 0xFFFF (communications writing ON), then write 0x2103.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 8192PVINT16PVRead
HR 8193Status (low word)BITMAP16Status low word (alarms, errors, outputs)Read
HR 8196MV monitor (heating)INT16Heating MVRead
HR 8451Set pointINT16Set pointRead/write
HR 9223Status (high word)BITMAP16Status high word (run/stop, auto/manual)Read
HR 9232Decimal point monitorINT16Decimal pointRead
HR 65535Operation commandUINT16Operation command (write enable, RUN/STOP)Write

Enable Modbus control & writes

Set Protocol Setting (psel) to Modbus in the communications setting level, set unit number and baud, then cycle power. Writes need 'communications writing ON' via the operation command.

Byte order & addressing

Network setup

Watch out for

Omron E5CC / E5EC / E5AC / E5DC digital temperature controllers (E5_C series) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

20 of 20 shown
Omron E5CC / E5EC / E5AC / E5DC digital temperature controllers (E5_C series) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR8192doc 2000PVProcess value. Raw value without decimal point; decimal places per 2410.INT16Read
HR8193doc 2001Status (low word)Bits 0-15 of the 32-bit status.BITMAP16Readbit 0 = Heater overcurrent (CT1); bit 1 = Heater current hold (CT1); bit 2 = A/D converter error; bit 3 = HS alarm (CT1); bit 4 = RSP input error; bit 6 = Input error; bit 7 = Potentiometer input error; bit 8 = Control output (heating) / open output ON; bit 9 = Control output (cooling) / close output ON; bit 10 = HB alarm (CT1); bit 11 = HB alarm (CT2); bit 12 = Alarm 1; bit 13 = Alarm 2; bit 14 = Alarm 3; bit 15 = Program end output
HR8194doc 2002Internal set pointRaw value without decimal point; decimal places per 2410.INT16Read
HR8195doc 2003Heater current 1INT16× 0.1ARead
HR8196doc 2004MV monitor (heating)INT16× 0.1%Read
HR8197doc 2005MV monitor (cooling)INT16× 0.1%Read
HR8451doc 2103Set pointRaw value without decimal point; decimal places per 2410.INT16Read/write
HR8452doc 2104Alarm value 1Raw value without decimal point; decimal places per 2410.INT16Read/write
HR8453doc 2105Alarm 1 upper limitRaw value without decimal point; decimal places per 2410.INT16Read/write
HR8454doc 2106Alarm 1 lower limitRaw value without decimal point; decimal places per 2410.INT16Read/write
HR8455doc 2107Alarm value 2Raw value without decimal point; decimal places per 2410.INT16Read/write
HR8456doc 2108Alarm 2 upper limitRaw value without decimal point; decimal places per 2410.INT16Read/write
HR8457doc 2109Alarm 2 lower limitRaw value without decimal point; decimal places per 2410.INT16Read/write
HR9220doc 2404Multi-SP numberActive set point 0-7.INT16Read
HR9223doc 2407Status (high word)Bits 16-31 of the 32-bit status, shown here as bits 0-15.BITMAP16Readbit 0 = Event input 1; bit 1 = Event input 2; bit 2 = Event input 3; bit 3 = Event input 4; bit 4 = Write mode (1 = RAM write mode); bit 5 = Non-volatile memory differs from RAM; bit 6 = Setup area 1; bit 7 = AT in progress; bit 8 = Stop (0 = Run); bit 9 = Communications writing enabled; bit 10 = Manual mode (0 = automatic); bit 11 = Program start; bit 12 = Heater overcurrent (CT2); bit 13 = Heater current hold (CT2); bit 15 = HS alarm (CT2)
HR9232doc 2410Decimal point monitorDecimal places (0-3) used by PV, SP and alarm values.INT16Read
HR9728doc 2600Manual MVOutput in manual mode.INT16× 0.1%Read/write
HR9729doc 2601Set point (operation level)Raw value without decimal point; decimal places per 2410.INT16Read/write
HR9730doc 2602Remote SP monitorRaw value without decimal point; decimal places per 2410.INT16Read
HR65535doc FFFFOperation commandFC06 only: command code in the high byte, related information in the low byte.UINT16Write0 = 0x0000: communications writing OFF; 1 = 0x0001: communications writing ON; 256 = 0x0100: RUN; 257 = 0x0101: STOP; 768 = 0x0300: AT cancel; 769 = 0x0301: 100% AT execute; 770 = 0x0302: 40% AT execute; 1024 = 0x0400: backup write mode; 1025 = 0x0401: RAM write mode; 1280 = 0x0500: save RAM data; 1536 = 0x0600: software reset; 2304 = 0x0900: automatic mode; 2305 = 0x0901: manual mode; 3087 = 0x0C0F: cancel all alarm latches; 3328 = 0x0D00: local SP mode; 3329 = 0x0D01: remote SP mode

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Omron E5CC / E5EC / E5AC / E5DC digital temperature controllers (E5_C series)

What Modbus registers does the Omron E5CC / E5EC / E5AC / E5DC digital temperature controllers (E5_C series) have?

This map lists 20 registers: 20 holding registers. 10 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Omron E5CC / E5EC / E5AC / E5DC digital temperature controllers (E5_C series) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Addresses are printed in hex and sent as-is: the manual's 2-byte example reads PV with 01 03 20 00 00 01. 4-byte mode addresses (0000, 0002, ...) hold the same data as two registers each; only 2-byte mode addresses are listed here.

What are the minimum Modbus registers to integrate the Omron E5CC / E5EC / E5AC / E5DC digital temperature controllers (E5_C series)?

Start with HR 8192 PV (PV); HR 8193 Status (low word) (Status low word (alarms, errors, outputs)); HR 8196 MV monitor (heating) (Heating MV); HR 8451 Set point (Set point); HR 9223 Status (high word) (Status high word (run/stop, auto/manual)); HR 9232 Decimal point monitor (Decimal point); HR 65535 Operation command (Operation command (write enable, RUN/STOP)).

How do I enable Modbus control of the Omron E5CC / E5EC / E5AC / E5DC digital temperature controllers (E5_C series)?

Set Protocol Setting (psel) to Modbus in the communications setting level, set unit number and baud, then cycle power. Writes need 'communications writing ON' via the operation command.

Where is the official Omron E5CC / E5EC / E5AC / E5DC digital temperature controllers (E5_C series) Modbus documentation?

The source is E5@C Digital Temperature Controllers Communications Manual (H175-E1-17), revision 2022-09, published free by Omron at https://files.omron.eu/downloads/latest/manual/en/h175_e5_c_communications_manual_en.pdf.

More Omron Modbus register maps

Other temperature & process controllers register maps

All temperature & process controllers Modbus register maps →

Source: E5@C Digital Temperature Controllers Communications Manual · H175-E1-17 · rev. 2022-09. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.