- E5CC / E5EC / E5AC / E5DC digital temperature controllers (E5_C series)
Sensor (digital temperature controller) · Modbus register map
Omron E5CC / E5EC / E5AC / E5DC digital temperature controllers (E5_C series) Modbus register map
Updated 17 November 2026
Omron's E5_C temperature controllers speak CompoWay/F or Modbus RTU on their RS-485 option. The variable area can be read in 4-byte mode (two registers per value) or 2-byte mode (one register per value, addresses from 0x2000); this map uses 2-byte mode for PV, set points, MV, heater current, alarms and status, plus the operation-command register for RUN/STOP, auto/manual and auto-tune.
This page lists 20 Modbus registers for the Omron E5CC / E5EC / E5AC / E5DC digital temperature controllers (E5_C series) — 10 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Omron’s own free documentation (linked below) and checked against it.
- Manufacturer
- Omron
- Model
- E5CC / E5EC / E5AC / E5DC digital temperature controllers (E5_C series)
- Equipment type
- Sensor (digital temperature controller)
- Registers
- 20 (10 writable)
- Transport
- Modbus RTU
- Default unit ID
- 1
- Documented addressing
- hexadecimal, 0-based
- Also known as
- E5CC, E5EC, E5AC, E5DC, E5CC-U, E5@C, E5_C
Integration notes: Omron E5CC / E5EC / E5AC / E5DC digital temperature controllers (E5_C series)
Read 0x2000-0x2005 with FC03 for PV, status, internal SP, heater current and MV; read 0x2410 once for the decimal point. To change the set point, first write 0x0001 to 0xFFFF (communications writing ON), then write 0x2103.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 8192 | PV | INT16 | PV | Read |
| HR 8193 | Status (low word) | BITMAP16 | Status low word (alarms, errors, outputs) | Read |
| HR 8196 | MV monitor (heating) | INT16 | Heating MV | Read |
| HR 8451 | Set point | INT16 | Set point | Read/write |
| HR 9223 | Status (high word) | BITMAP16 | Status high word (run/stop, auto/manual) | Read |
| HR 9232 | Decimal point monitor | INT16 | Decimal point | Read |
| HR 65535 | Operation command | UINT16 | Operation command (write enable, RUN/STOP) | Write |
Enable Modbus control & writes
Set Protocol Setting (psel) to Modbus in the communications setting level, set unit number and baud, then cycle power. Writes need 'communications writing ON' via the operation command.
Byte order & addressing
- Values carry no decimal point; check 2410.
- Use 2-byte mode addresses (0x2000+) for 16-bit tools; 4-byte mode needs even addresses and even counts.
- Reading in setup area 1 freezes or clears some status bits.
Network setup
- Protocol (psel), unit no. (u-no, default 1), baud (bps), parity (prty) and send data wait (sdwt, default 20 ms) are set on the front panel in the communications setting level; reset the controller to apply changes.
- Up to 106 registers per read in 2-byte mode.
Watch out for
- In backup mode every communications write of an operation/adjustment parameter is also saved to non-volatile memory; RAM write mode (0x0401) skips that until backup mode or 'save RAM data'.
Omron E5CC / E5EC / E5AC / E5DC digital temperature controllers (E5_C series) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 8192doc 2000 | PV | Process value. Raw value without decimal point; decimal places per 2410. | INT16 | Read | ||||
| HR | 8193doc 2001 | Status (low word) | Bits 0-15 of the 32-bit status. | BITMAP16 | Read | bit 0 = Heater overcurrent (CT1); bit 1 = Heater current hold (CT1); bit 2 = A/D converter error; bit 3 = HS alarm (CT1); bit 4 = RSP input error; bit 6 = Input error; bit 7 = Potentiometer input error; bit 8 = Control output (heating) / open output ON; bit 9 = Control output (cooling) / close output ON; bit 10 = HB alarm (CT1); bit 11 = HB alarm (CT2); bit 12 = Alarm 1; bit 13 = Alarm 2; bit 14 = Alarm 3; bit 15 = Program end output | |||
| HR | 8194doc 2002 | Internal set point | Raw value without decimal point; decimal places per 2410. | INT16 | Read | ||||
| HR | 8195doc 2003 | Heater current 1 | INT16 | × 0.1 | A | Read | |||
| HR | 8196doc 2004 | MV monitor (heating) | INT16 | × 0.1 | % | Read | |||
| HR | 8197doc 2005 | MV monitor (cooling) | INT16 | × 0.1 | % | Read | |||
| HR | 8451doc 2103 | Set point | Raw value without decimal point; decimal places per 2410. | INT16 | Read/write | ||||
| HR | 8452doc 2104 | Alarm value 1 | Raw value without decimal point; decimal places per 2410. | INT16 | Read/write | ||||
| HR | 8453doc 2105 | Alarm 1 upper limit | Raw value without decimal point; decimal places per 2410. | INT16 | Read/write | ||||
| HR | 8454doc 2106 | Alarm 1 lower limit | Raw value without decimal point; decimal places per 2410. | INT16 | Read/write | ||||
| HR | 8455doc 2107 | Alarm value 2 | Raw value without decimal point; decimal places per 2410. | INT16 | Read/write | ||||
| HR | 8456doc 2108 | Alarm 2 upper limit | Raw value without decimal point; decimal places per 2410. | INT16 | Read/write | ||||
| HR | 8457doc 2109 | Alarm 2 lower limit | Raw value without decimal point; decimal places per 2410. | INT16 | Read/write | ||||
| HR | 9220doc 2404 | Multi-SP number | Active set point 0-7. | INT16 | Read | ||||
| HR | 9223doc 2407 | Status (high word) | Bits 16-31 of the 32-bit status, shown here as bits 0-15. | BITMAP16 | Read | bit 0 = Event input 1; bit 1 = Event input 2; bit 2 = Event input 3; bit 3 = Event input 4; bit 4 = Write mode (1 = RAM write mode); bit 5 = Non-volatile memory differs from RAM; bit 6 = Setup area 1; bit 7 = AT in progress; bit 8 = Stop (0 = Run); bit 9 = Communications writing enabled; bit 10 = Manual mode (0 = automatic); bit 11 = Program start; bit 12 = Heater overcurrent (CT2); bit 13 = Heater current hold (CT2); bit 15 = HS alarm (CT2) | |||
| HR | 9232doc 2410 | Decimal point monitor | Decimal places (0-3) used by PV, SP and alarm values. | INT16 | Read | ||||
| HR | 9728doc 2600 | Manual MV | Output in manual mode. | INT16 | × 0.1 | % | Read/write | ||
| HR | 9729doc 2601 | Set point (operation level) | Raw value without decimal point; decimal places per 2410. | INT16 | Read/write | ||||
| HR | 9730doc 2602 | Remote SP monitor | Raw value without decimal point; decimal places per 2410. | INT16 | Read | ||||
| HR | 65535doc FFFF | Operation command | FC06 only: command code in the high byte, related information in the low byte. | UINT16 | Write | 0 = 0x0000: communications writing OFF; 1 = 0x0001: communications writing ON; 256 = 0x0100: RUN; 257 = 0x0101: STOP; 768 = 0x0300: AT cancel; 769 = 0x0301: 100% AT execute; 770 = 0x0302: 40% AT execute; 1024 = 0x0400: backup write mode; 1025 = 0x0401: RAM write mode; 1280 = 0x0500: save RAM data; 1536 = 0x0600: software reset; 2304 = 0x0900: automatic mode; 2305 = 0x0901: manual mode; 3087 = 0x0C0F: cancel all alarm latches; 3328 = 0x0D00: local SP mode; 3329 = 0x0D01: remote SP mode |
Notes on this map
- Values are sent without the decimal point (105.0 is sent as 1050). PV, set points and alarm values use the decimal places reported by 2410; MV (x0.1 %) and heater current (x0.1 A) have fixed scaling per the setting ranges.
- In 2-byte mode 2001 and 2406 return the low 16 bits of the 32-bit status and 2407 the high 16 bits; bit meanings come from the status table on pp. 3-23 to 3-25.
- Before any write, send operation command 'communications writing ON' (0x0001 to address FFFF). FC06 single writes work only in 2-byte mode; FC16 works in both.
- The manual states a default unit number of 1 and a default send data wait of 20 ms; default baud rate and parity are only shown as highlighted cells, so they are not listed. With Modbus the data length is fixed at 8 bits, with 1 stop bit for even/odd parity or 2 for none.
- Left out: the rest of the adjustment, initial-setting and advanced levels (PID, scaling, input type and so on), alarm 3/4 values, valve opening, and program/SP ramp parameters.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Omron E5CC / E5EC / E5AC / E5DC digital temperature controllers (E5_C series)
What Modbus registers does the Omron E5CC / E5EC / E5AC / E5DC digital temperature controllers (E5_C series) have?
This map lists 20 registers: 20 holding registers. 10 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Omron E5CC / E5EC / E5AC / E5DC digital temperature controllers (E5_C series) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Addresses are printed in hex and sent as-is: the manual's 2-byte example reads PV with 01 03 20 00 00 01. 4-byte mode addresses (0000, 0002, ...) hold the same data as two registers each; only 2-byte mode addresses are listed here.
What are the minimum Modbus registers to integrate the Omron E5CC / E5EC / E5AC / E5DC digital temperature controllers (E5_C series)?
Start with HR 8192 PV (PV); HR 8193 Status (low word) (Status low word (alarms, errors, outputs)); HR 8196 MV monitor (heating) (Heating MV); HR 8451 Set point (Set point); HR 9223 Status (high word) (Status high word (run/stop, auto/manual)); HR 9232 Decimal point monitor (Decimal point); HR 65535 Operation command (Operation command (write enable, RUN/STOP)).
How do I enable Modbus control of the Omron E5CC / E5EC / E5AC / E5DC digital temperature controllers (E5_C series)?
Set Protocol Setting (psel) to Modbus in the communications setting level, set unit number and baud, then cycle power. Writes need 'communications writing ON' via the operation command.
Where is the official Omron E5CC / E5EC / E5AC / E5DC digital temperature controllers (E5_C series) Modbus documentation?
The source is E5@C Digital Temperature Controllers Communications Manual (H175-E1-17), revision 2022-09, published free by Omron at https://files.omron.eu/downloads/latest/manual/en/h175_e5_c_communications_manual_en.pdf.
More Omron Modbus register maps
- Power meter (multi-circuit power monitor)
Omron KM-N2-FLK multi-circuit power monitor
Omron KM-N2-FLK power monitor (catalog N200-E1-04).
Also known as: KM-N2-FLK, KM-N2 - Power meter (multi-circuit power monitor)
Omron KM-N3-FLK on-panel power monitor
Omron KM-N3-FLK power monitor (catalog N214-E1-04).
Also known as: KM-N3-FLK, KM-N3
Other temperature & process controllers register maps
- Sensor (digital temperature controller)
Shinko Technos BCS2 / BCR2 / BCD2 digital indicating controller (C5, C5W options)
Shinko BCx2 series (BCS2, BCR2, BCD2) with the C5 or C5W communication option, standard (not JC-allocated) command set; manual No.BCx2CE6.
Also known as: BCS2, BCR2, BCD2, BCx2 - Sensor (programmable temperature controller)
Shinko Technos PCA1 programmable controller (C/C5 option)
Shinko PCA1 programmable controllers with the C or C5 serial option; manual No. PCA1CE3.
Also known as: PCA1 - Sensor (digital indicating temperature controller)
Yokogawa UTAdvanced UT55A / UT52A digital indicating controller
Yokogawa UT55A and UT52A one- or two-loop controllers with RS-485 or Ethernet communication; D-register map from IM 05P07A01-01EN chapter 6 (UP55A program items excluded).
Also known as: UT55A, UT52A - Sensor (process / temperature controller)
Novus N20K48 modular process controller (Modbus RTU)
N20K48 controllers with the optional RS-485 interface, communication protocol V1.0x.
Also known as: Novus N20K48, N20K48 modular controller - Sensor (digital temperature controller)
Shinko Technos ACS2 digital indicating controller (C5, C5W options)
Shinko ACS2 with the C5 or C5W serial option, Shinko protocol / MODBUS RTU command set; manual No.ACS2CE3.
Also known as: ACS2-C5, ACS2-C5W - Sensor (digital temperature controller)
Shinko Technos JIR-301-M digital indicator (C5 option)
Shinko JIR-301-M with the C5 option, plain (non-block) Modbus protocol setting; manual No.JIR32CE4.
Also known as: JIR-301-M-C5, JIR-301-M C5
All temperature & process controllers Modbus register maps →
Source: E5@C Digital Temperature Controllers Communications Manual · H175-E1-17 · rev. 2022-09. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.