Sensor (programmable temperature controller) · Modbus register map

Shinko Technos PCA1 programmable controller (C/C5 option) Modbus register map

Updated 17 November 2026

Short answer

The PCA1 is a ramp/soak controller with 16 patterns of 16 steps that draw their PID, wait, alarm, output and time-signal settings from numbered blocks. On RS-485 it speaks Shinko protocol or Modbus ASCII/RTU; every item is a signed 16-bit holding register. The map covers general settings, run/hold/advance commands, monitor values, every block table and the per-pattern repeat/link items; step items are listed for pattern 0, step 0 with the rule for the rest.

This page lists 328 Modbus registers for the Shinko Technos PCA1 programmable controller (C/C5 option) — 318 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Shinko Technos’s own free documentation (linked below) and checked against it.

Manufacturer
Shinko Technos
Model
PCA1 programmable controller (C/C5 option)
Equipment type
Sensor (programmable temperature controller)
Registers
328 (318 writable)
Transport
Modbus RTU, Modbus ASCII
Default unit ID
0
Default serial
9600 baud, 7E1
Documented addressing
hexadecimal, 0-based
Also known as
PCA1
Source document
Communication Instruction Manual PCA1 (C, C5) · No. PCA1CE3 · rev. 2019-12
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Shinko Technos PCA1 programmable controller (C/C5 option)

Integration in brief

Select MODBUS RTU in the Communication Parameter Setting Group and give the unit a non-zero instrument number; then poll PV 0080H, current step SV 0083H, pattern/step 0085H and status 0086H-0088H, and run/stop the program with 0042H.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 128PVINT16Process valueRead
HR 131Current step SVINT16Current step SVRead
HR 133Current pattern and stepINT16Running pattern and stepRead
HR 136Current unit statusBITMAP16Run/hold/wait statusRead
HR 134Status flag 1BITMAP16Output, alarm and error flagsRead
HR 66Program control Run/StopINT16Program Run/StopWrite
HR 63Pattern number for operationINT16Pattern to runRead/write
HR 46Decimal point placeINT16Decimal point for scalingRead/write

Enable Modbus control & writes

Requires the C or C5 option. In the Communication Parameter Setting Group set Communication protocol to MODBUS RTU (or ASCII), then instrument number, speed, data bit/parity and stop bit; these are keypad-only.

Byte order & addressing

Network setup

Watch out for

Shinko Technos PCA1 programmable controller (C/C5 option) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

328 of 328 shown
Shinko Technos PCA1 programmable controller (C/C5 option) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR1doc 0001HSV (fixed value control)Raw integer; apply decimal point place (002EH). Marked (*1): may read 0 and ignore writes.INT16Read/write
HR2doc 0002HOUT1 proportional band (fixed value)Decimal point ignored. Marked (*1): may read 0 and ignore writes.INT16Read/write
HR3doc 0003HIntegral time (fixed value)Marked (*1): may read 0 and ignore writes.INT16Read/write
HR4doc 0004HDerivative time (fixed value)Marked (*1): may read 0 and ignore writes.INT16Read/write
HR5doc 0005HARW (fixed value)Marked (*1): may read 0 and ignore writes.INT16Read/write
HR6doc 0006HOUT2 proportional band (fixed value)Decimal point ignored. Marked (*1): may read 0 and ignore writes.INT16Read/write
HR7doc 0007HAlarm 1 value (fixed value)Raw integer; apply decimal point place (002EH). Marked (*1): may read 0 and ignore writes.INT16Read/write
HR8doc 0008HAlarm 2 value (fixed value)Raw integer; apply decimal point place (002EH). Marked (*1): may read 0 and ignore writes.INT16Read/write
HR9doc 0009HAlarm 3 value (fixed value)Raw integer; apply decimal point place (002EH). Marked (*1): may read 0 and ignore writes.INT16Read/write
HR10doc 000AHAlarm 4 value (fixed value)Raw integer; apply decimal point place (002EH). Marked (*1): may read 0 and ignore writes.INT16Read/write
HR11doc 000BHAuto/Manual controlINT16Read/write0 = Automatic; 1 = Manual
HR12doc 000CHManual MVEffective in manual control; rejected (exception 17) in automatic.INT16Read/write
HR13doc 000DHAT modeINT16Read/write0 = Normal mode; 1 = Multi mode
HR14doc 000EHAT Perform/CancelRejected in program standby or manual control.INT16Read/write0 = AT Cancel; 1 = AT Perform
HR15doc 000FHEvent output EV3 allocationINT16Read/write0 = No event; 1 = High limit alarm; 2 = High limit with standby; 3 = Low limit alarm; 4 = Low limit with standby; 5 = High/Low limits alarm; 6 = High/Low limits alarm with standby; 7 = High/Low limit range alarm; 8 = High/Low limit range with standby; 9 = Process high alarm; 10 = Process high alarm with standby; 11 = Process low alarm; 12 = Process low alarm with standby; 13 = Pattern end output; 14 = Loop break alarm output; 15 = Output during AT
HR16doc 0010HEvent output EV4 allocationINT16Read/write0 = No event; 1 = High limit alarm; 2 = High limit with standby; 3 = Low limit alarm; 4 = Low limit with standby; 5 = High/Low limits alarm; 6 = High/Low limits alarm with standby; 7 = High/Low limit range alarm; 8 = High/Low limit range with standby; 9 = Process high alarm; 10 = Process high alarm with standby; 11 = Process low alarm; 12 = Process low alarm with standby; 13 = Pattern end output; 14 = Loop break alarm output; 15 = Output during AT
HR17doc 0011HEV1 alarm hysteresisRaw integer; apply decimal point place (002EH).INT16Read/write
HR18doc 0012HEV2 alarm hysteresisRaw integer; apply decimal point place (002EH).INT16Read/write
HR19doc 0013HEV3 alarm hysteresisRaw integer; apply decimal point place (002EH).INT16Read/write
HR20doc 0014HEV4 alarm hysteresisRaw integer; apply decimal point place (002EH).INT16Read/write
HR21doc 0015HEV1 alarm delay timeINT16Read/write
HR22doc 0016HEV2 alarm delay timeINT16Read/write
HR23doc 0017HEV3 alarm delay timeINT16Read/write
HR24doc 0018HEV4 alarm delay timeINT16Read/write
HR25doc 0019HLoop break alarm timeINT16Read/write
HR26doc 001AHLoop break alarm bandRaw integer; apply decimal point place (002EH).INT16Read/write
HR27doc 001BHOUT1 proportional cycleINT16Read/write
HR28doc 001CHOUT1 high limitMarked (*1): may read 0 and ignore writes.INT16Read/write
HR29doc 001DHOUT1 low limitMarked (*1): may read 0 and ignore writes.INT16Read/write
HR30doc 001EHOUT1 ON/OFF hysteresisRaw integer; apply decimal point place (002EH).INT16Read/write
HR31doc 001FHOUT1 rate-of-changeDecimal point ignored. Marked (*1): may read 0 and ignore writes.INT16Read/write
HR32doc 0020HOUT2 proportional cycleINT16Read/write
HR33doc 0021HOUT2 cooling methodINT16Read/write0 = Air cooling; 1 = Oil cooling; 2 = Water cooling
HR34doc 0022HOUT2 high limitMarked (*1): may read 0 and ignore writes.INT16Read/write
HR35doc 0023HOUT2 low limitMarked (*1): may read 0 and ignore writes.INT16Read/write
HR36doc 0024HOUT2 ON/OFF hysteresisRaw integer; apply decimal point place (002EH).INT16Read/write
HR37doc 0025HOverlap/Dead bandRaw integer; apply decimal point place (002EH).INT16Read/write
HR38doc 0026HOpen/Closed output dead bandMarked (*1): may read 0 and ignore writes.INT16Read/write
HR39doc 0027HSV high limitRaw integer; apply decimal point place (002EH).INT16Read/write
HR40doc 0028HSV low limitRaw integer; apply decimal point place (002EH).INT16Read/write
HR41doc 0029HTransmission output typeINT16Read/write0 = PV transmission; 1 = SV transmission; 2 = MV transmission
HR42doc 002AHTransmission output high limitRaw integer; apply decimal point place (002EH).INT16Read/write
HR43doc 002BHTransmission output low limitRaw integer; apply decimal point place (002EH).INT16Read/write
HR44doc 002CHScaling high limitRaw integer; apply decimal point place (002EH).INT16Read/write
HR45doc 002DHScaling low limitRaw integer; apply decimal point place (002EH).INT16Read/write
HR46doc 002EHDecimal point placeINT16Read/write0 = No decimal point; 1 = 1 digit; 2 = 2 digits; 3 = 3 digits; 4 = 4 digits
HR47doc 002FHSensor correctionRaw integer; apply decimal point place (002EH).INT16Read/write
HR48doc 0030HPV filter time constantDecimal point ignored.INT16Read/write
HR49doc 0031HSet value lockINT16Read/write0 = Unlock; 1 = Lock
HR50doc 0032HStep SV when program control startsRaw integer; apply decimal point place (002EH).INT16Read/write
HR51doc 0033HProgram control start typeINT16Read/write0 = PV start; 1 = PVR start; 2 = SV start
HR52doc 0034HPower restore actionINT16Read/write0 = Stops; 1 = Continues; 2 = Suspends (on hold)
HR53doc 0035HStep time unitINT16Read/write0 = Hours:Minutes; 1 = Minutes:Seconds
HR54doc 0036HStep time indicationINT16Read/write0 = Remaining time; 1 = Step time
HR55doc 0037HStep SV indicationINT16Read/write0 = SV following step progress; 1 = Step SV
HR56doc 0038HPattern end output timeINT16Read/write
HR57doc 0039HStep SV hold when program endsINT16Read/write0 = Not holding; 1 = Holding
HR58doc 003AHTS1 / status (RUN) outputINT16Read/write0 = Time signal output TS1; 1 = Status (RUN) output
HR59doc 003BHTS2 / status (HOLD) outputINT16Read/write0 = Time signal output TS2; 1 = Status (HOLD) output
HR60doc 003CHTS3 / status (WAIT) outputINT16Read/write0 = Time signal output TS3; 1 = Status (WAIT) output
HR61doc 003DHTS4 / status (FAST) outputINT16Read/write0 = Time signal output TS4; 1 = Status (FAST) output
HR62doc 003EHTS5 / status (STOP) outputINT16Read/write0 = Time signal output TS5; 1 = Status (STOP) output
HR63doc 003FHPattern number for operationEffective when pattern 0 is selected externally, in program standby.INT16Read/write0 = Pattern 0; 1 = Pattern 1; 2 = Pattern 2; 3 = Pattern 3; 4 = Pattern 4; 5 = Pattern 5; 6 = Pattern 6; 7 = Pattern 7; 8 = Pattern 8; 9 = Pattern 9; 10 = Pattern 10; 11 = Pattern 11; 12 = Pattern 12; 13 = Pattern 13; 14 = Pattern 14; 15 = Pattern 15
HR64doc 0040HPattern number for settingINT16Read/write0 = Pattern 0; 1 = Pattern 1; 2 = Pattern 2; 3 = Pattern 3; 4 = Pattern 4; 5 = Pattern 5; 6 = Pattern 6; 7 = Pattern 7; 8 = Pattern 8; 9 = Pattern 9; 10 = Pattern 10; 11 = Pattern 11; 12 = Pattern 12; 13 = Pattern 13; 14 = Pattern 14; 15 = Pattern 15
HR65doc 0041HControl modeWrite-only (06/10H).INT16Write0 = Fixed value control; 1 = Program control
HR66doc 0042HProgram control Run/StopWrite-only (06/10H).INT16Write0 = Stop; 1 = Run (cancels HOLD)
HR67doc 0043HProgram control HOLDWrite-only; rejected in standby.INT16Write1 = HOLD
HR68doc 0044HProgram control ADVANCEWrite-only; rejected in standby.INT16Write1 = ADVANCE
HR69doc 0045HProgram control PREVIOUS STEPWrite-only; rejected in standby.INT16Write1 = PREVIOUS STEP
HR70doc 0046HOpen output timeMarked (*1): may read 0 and ignore writes.INT16Read/write
HR71doc 0047HClosed output timeMarked (*1): may read 0 and ignore writes.INT16Read/write
HR72doc 0048HInput typeDC inputs scale -2000 to 10000.INT16Read/write0 = K -200 to 1370 C; 1 = K -200.0 to 400.0 C; 2 = J -200 to 1000 C; 3 = R 0 to 1760 C; 4 = S 0 to 1760 C; 5 = B 0 to 1820 C; 6 = E -200 to 800 C; 7 = T -200.0 to 400.0 C; 8 = N -200 to 1300 C; 9 = PL-II 0 to 1390 C; 10 = C (W/Re5-26) 0 to 2315 C; 11 = Pt100 -200.0 to 850.0 C; 12 = JPt100 -200.0 to 500.0 C; 13 = Pt100 -200 to 850 C; 14 = JPt100 -200 to 500 C; 15 = Pt100 -100.0 to 100.0 C; 16 = Pt100 -100.0 to 500.0 C; 17 = K -328 to 2498 F; 18 = K -328.0 to 752.0 F; 19 = J -328 to 1832 F; 20 = R 32 to 3200 F; 21 = S 32 to 3200 F; 22 = B 32 to 3308 F; 23 = E -328 to 1472 F; 24 = T -328.0 to 752.0 F; 25 = N -328 to 2372 F; 26 = PL-II 32 to 2534 F; 27 = C (W/Re5-26) 32 to 4199 F; 28 = Pt100 -328.0 to 1562.0 F; 29 = JPt100 -328.0 to 932.0 F; 30 = Pt100 -328 to 1562 F; 31 = JPt100 -328 to 932 F; 32 = Pt100 -148.0 to 212.0 F; 33 = Pt100 -148.0 to 932.0 F; 34 = 4 to 20 mA; 35 = 0 to 20 mA; 36 = 0 to 10 mV; 37 = -10 to 10 mV; 38 = 0 to 50 mV; 39 = 0 to 100 mV; 40 = 0 to 1 V; 41 = 0 to 5 V; 42 = 1 to 5 V; 43 = 0 to 10 V
HR73doc 0049HAT biasRaw integer; apply decimal point place (002EH).INT16Read/write
HR74doc 004AHDirect/Reverse actionINT16Read/write0 = Reverse action; 1 = Direct action
HR75doc 004BHEvent output EV1 allocationINT16Read/write0 = No event; 1 = High limit alarm; 2 = High limit with standby; 3 = Low limit alarm; 4 = Low limit with standby; 5 = High/Low limits alarm; 6 = High/Low limits alarm with standby; 7 = High/Low limit range alarm; 8 = High/Low limit range with standby; 9 = Process high alarm; 10 = Process high alarm with standby; 11 = Process low alarm; 12 = Process low alarm with standby; 13 = Pattern end output; 14 = Loop break alarm output; 15 = Output during AT
HR76doc 004CHEvent output EV2 allocationINT16Read/write0 = No event; 1 = High limit alarm; 2 = High limit with standby; 3 = Low limit alarm; 4 = Low limit with standby; 5 = High/Low limits alarm; 6 = High/Low limits alarm with standby; 7 = High/Low limit range alarm; 8 = High/Low limit range with standby; 9 = Process high alarm; 10 = Process high alarm with standby; 11 = Process low alarm; 12 = Process low alarm with standby; 13 = Pattern end output; 14 = Loop break alarm output; 15 = Output during AT
HR77doc 004DHEV1 alarm energized/de-energizedINT16Read/write0 = Energized; 1 = De-energized
HR78doc 004EHEV2 alarm energized/de-energizedINT16Read/write0 = Energized; 1 = De-energized
HR79doc 004FHEV3 alarm energized/de-energizedINT16Read/write0 = Energized; 1 = De-energized
HR80doc 0050HEV4 alarm energized/de-energizedINT16Read/write0 = Energized; 1 = De-energized
HR81doc 0051HProgram start Auto/ManualINT16Read/write0 = Manual start; 1 = Automatic start
HR82doc 0052HOvershoot suppressionINT16Read/write0 = Disabled; 1 = Enabled
HR83doc 0053HOvershoot suppression factorDecimal point ignored.INT16Read/write
HR84doc 0054HOutput status on input errorINT16Read/write0 = Output OFF; 1 = Output ON
HR85doc 0055HBacklight selectionINT16Read/write0 = All are backlit; 1 = PV display is backlit
HR86doc 0056HPV colorINT16Read/write0 = Green; 1 = Red; 2 = Orange; 3 = Alarm ON: green to red; 4 = Alarm ON: orange to red; 5 = Changes continuously; 6 = Changes continuously + alarm ON red
HR87doc 0057HPV color rangeDecimal point ignored.INT16Read/write
HR88doc 0058HBacklight timeINT16Read/write
HR89doc 0059HResponse delay timeINT16msRead/write
HR112doc 0070HKey operation change flag clearingINT16Write1 = Clear flag
HR128doc 0080HPVProcess value. Raw integer; apply decimal point place (002EH).INT16Read
HR129doc 0081HOUT1 MVINT16Read
HR130doc 0082HOUT2 MVINT16Read
HR131doc 0083HCurrent step SVRaw integer; apply decimal point place (002EH).INT16Read
HR132doc 0084HCurrent step remaining timeINT16Read
HR133doc 0085HCurrent pattern and stepLowest hex digit = pattern, next hex digit = step (0 when stopped).INT16Read
HR134doc 0086HStatus flag 1BITMAP16Readbit 0 = OUT1 on; bit 1 = OUT2 on; bit 2 = EV1 output on; bit 3 = EV2 output on; bit 4 = EV3 output on; bit 5 = EV4 output on; bit 6 = Loop break alarm; bit 7 = Overscale; bit 8 = Underscale; bit 15 = Changed by keypad
HR135doc 0087HStatus flag 2BITMAP16Readbit 0 = Time signal 1 (RUN) output; bit 1 = Time signal 2 (HOLD) output; bit 2 = Time signal 3 (WAIT) output; bit 3 = Time signal 4 (FAST) output; bit 4 = Time signal 5 (STOP) output; bit 5 = Time signal 6 output; bit 6 = Time signal 7 output; bit 7 = Time signal 8 output
HR136doc 0088HCurrent unit statusBITMAP16Readbit 0 = Program control (fixed); bit 1 = Manual; bit 2 = AT performing; bit 3 = Program control running; bit 4 = HOLD; bit 5 = WAIT; bit 6 = Pattern end output on; bit 7 = SV hold
HR137doc 0089HPattern selected by event inputINT16Read
HR4096doc 1000HP0 step 0 SVRaw integer; apply decimal point place (002EH).INT16Read/write
HR4097doc 1001HP0 step 0 timeSmaller unit of 0035H; FFFFH = hold step.INT16Read/write
HR4098doc 1002HP0 step 0 PID blockINT16Read/write0 = Block 0; 1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9
HR4099doc 1003HP0 step 0 time signal 1 blockINT16Read/write0 = Block 0; 1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10; 11 = Block 11; 12 = Block 12; 13 = Block 13; 14 = Block 14; 15 = Block 15
HR4100doc 1004HP0 step 0 time signal 2 blockINT16Read/write0 = Block 0; 1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10; 11 = Block 11; 12 = Block 12; 13 = Block 13; 14 = Block 14; 15 = Block 15
HR4101doc 1005HP0 step 0 time signal 3 blockINT16Read/write0 = Block 0; 1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10; 11 = Block 11; 12 = Block 12; 13 = Block 13; 14 = Block 14; 15 = Block 15
HR4102doc 1006HP0 step 0 time signal 4 blockINT16Read/write0 = Block 0; 1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10; 11 = Block 11; 12 = Block 12; 13 = Block 13; 14 = Block 14; 15 = Block 15
HR4103doc 1007HP0 step 0 time signal 5 blockINT16Read/write0 = Block 0; 1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10; 11 = Block 11; 12 = Block 12; 13 = Block 13; 14 = Block 14; 15 = Block 15
HR4104doc 1008HP0 step 0 time signal 6 blockINT16Read/write0 = Block 0; 1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10; 11 = Block 11; 12 = Block 12; 13 = Block 13; 14 = Block 14; 15 = Block 15
HR4105doc 1009HP0 step 0 time signal 7 blockINT16Read/write0 = Block 0; 1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10; 11 = Block 11; 12 = Block 12; 13 = Block 13; 14 = Block 14; 15 = Block 15
HR4106doc 100AHP0 step 0 time signal 8 blockINT16Read/write0 = Block 0; 1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9; 10 = Block 10; 11 = Block 11; 12 = Block 12; 13 = Block 13; 14 = Block 14; 15 = Block 15
HR4107doc 100BHP0 step 0 wait blockINT16Read/write0 = Block 0; 1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9
HR4108doc 100CHP0 step 0 alarm blockINT16Read/write0 = Block 0; 1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9
HR4109doc 100DHP0 step 0 output blockINT16Read/write0 = Block 0; 1 = Block 1; 2 = Block 2; 3 = Block 3; 4 = Block 4; 5 = Block 5; 6 = Block 6; 7 = Block 7; 8 = Block 8; 9 = Block 9
HR8192doc 2000HPID block 0 OUT1 proportional bandDecimal point ignored.INT16Read/write
HR8193doc 2001HPID block 0 integral timeINT16Read/write
HR8194doc 2002HPID block 0 derivative timeINT16Read/write
HR8195doc 2003HPID block 0 ARWINT16Read/write
HR8196doc 2004HPID block 0 OUT2 proportional bandINT16Read/write
HR8448doc 2100HPID block 1 OUT1 proportional bandDecimal point ignored.INT16Read/write
HR8449doc 2101HPID block 1 integral timeINT16Read/write
HR8450doc 2102HPID block 1 derivative timeINT16Read/write
HR8451doc 2103HPID block 1 ARWINT16Read/write
HR8452doc 2104HPID block 1 OUT2 proportional bandINT16Read/write
HR8704doc 2200HPID block 2 OUT1 proportional bandDecimal point ignored.INT16Read/write
HR8705doc 2201HPID block 2 integral timeINT16Read/write
HR8706doc 2202HPID block 2 derivative timeINT16Read/write
HR8707doc 2203HPID block 2 ARWINT16Read/write
HR8708doc 2204HPID block 2 OUT2 proportional bandINT16Read/write
HR8960doc 2300HPID block 3 OUT1 proportional bandDecimal point ignored.INT16Read/write
HR8961doc 2301HPID block 3 integral timeINT16Read/write
HR8962doc 2302HPID block 3 derivative timeINT16Read/write
HR8963doc 2303HPID block 3 ARWINT16Read/write
HR8964doc 2304HPID block 3 OUT2 proportional bandINT16Read/write
HR9216doc 2400HPID block 4 OUT1 proportional bandDecimal point ignored.INT16Read/write
HR9217doc 2401HPID block 4 integral timeINT16Read/write
HR9218doc 2402HPID block 4 derivative timeINT16Read/write
HR9219doc 2403HPID block 4 ARWINT16Read/write
HR9220doc 2404HPID block 4 OUT2 proportional bandINT16Read/write
HR9472doc 2500HPID block 5 OUT1 proportional bandDecimal point ignored.INT16Read/write
HR9473doc 2501HPID block 5 integral timeINT16Read/write
HR9474doc 2502HPID block 5 derivative timeINT16Read/write
HR9475doc 2503HPID block 5 ARWINT16Read/write
HR9476doc 2504HPID block 5 OUT2 proportional bandINT16Read/write
HR9728doc 2600HPID block 6 OUT1 proportional bandDecimal point ignored.INT16Read/write
HR9729doc 2601HPID block 6 integral timeINT16Read/write
HR9730doc 2602HPID block 6 derivative timeINT16Read/write
HR9731doc 2603HPID block 6 ARWINT16Read/write
HR9732doc 2604HPID block 6 OUT2 proportional bandINT16Read/write
HR9984doc 2700HPID block 7 OUT1 proportional bandDecimal point ignored.INT16Read/write
HR9985doc 2701HPID block 7 integral timeINT16Read/write
HR9986doc 2702HPID block 7 derivative timeINT16Read/write
HR9987doc 2703HPID block 7 ARWINT16Read/write
HR9988doc 2704HPID block 7 OUT2 proportional bandINT16Read/write
HR10240doc 2800HPID block 8 OUT1 proportional bandDecimal point ignored.INT16Read/write
HR10241doc 2801HPID block 8 integral timeINT16Read/write
HR10242doc 2802HPID block 8 derivative timeINT16Read/write
HR10243doc 2803HPID block 8 ARWINT16Read/write
HR10244doc 2804HPID block 8 OUT2 proportional bandINT16Read/write
HR10496doc 2900HPID block 9 OUT1 proportional bandDecimal point ignored.INT16Read/write
HR10497doc 2901HPID block 9 integral timeINT16Read/write
HR10498doc 2902HPID block 9 derivative timeINT16Read/write
HR10499doc 2903HPID block 9 ARWINT16Read/write
HR10500doc 2904HPID block 9 OUT2 proportional bandINT16Read/write
HR12288doc 3000HWait block 0 wait valueRaw integer; apply decimal point place (002EH).INT16Read/write
HR12544doc 3100HWait block 1 wait valueRaw integer; apply decimal point place (002EH).INT16Read/write
HR12800doc 3200HWait block 2 wait valueRaw integer; apply decimal point place (002EH).INT16Read/write
HR13056doc 3300HWait block 3 wait valueRaw integer; apply decimal point place (002EH).INT16Read/write
HR13312doc 3400HWait block 4 wait valueRaw integer; apply decimal point place (002EH).INT16Read/write
HR13568doc 3500HWait block 5 wait valueRaw integer; apply decimal point place (002EH).INT16Read/write
HR13824doc 3600HWait block 6 wait valueRaw integer; apply decimal point place (002EH).INT16Read/write
HR14080doc 3700HWait block 7 wait valueRaw integer; apply decimal point place (002EH).INT16Read/write
HR14336doc 3800HWait block 8 wait valueRaw integer; apply decimal point place (002EH).INT16Read/write
HR14592doc 3900HWait block 9 wait valueRaw integer; apply decimal point place (002EH).INT16Read/write
HR16384doc 4000HAlarm block 0 EV1 alarm valueRaw integer; apply decimal point place (002EH).INT16Read/write
HR16385doc 4001HAlarm block 0 EV2 alarm valueRaw integer; apply decimal point place (002EH).INT16Read/write
HR16386doc 4002HAlarm block 0 EV3 alarm valueRaw integer; apply decimal point place (002EH).INT16Read/write
HR16387doc 4003HAlarm block 0 EV4 alarm valueRaw integer; apply decimal point place (002EH).INT16Read/write
HR16640doc 4100HAlarm block 1 EV1 alarm valueRaw integer; apply decimal point place (002EH).INT16Read/write
HR16641doc 4101HAlarm block 1 EV2 alarm valueRaw integer; apply decimal point place (002EH).INT16Read/write
HR16642doc 4102HAlarm block 1 EV3 alarm valueRaw integer; apply decimal point place (002EH).INT16Read/write
HR16643doc 4103HAlarm block 1 EV4 alarm valueRaw integer; apply decimal point place (002EH).INT16Read/write
HR16896doc 4200HAlarm block 2 EV1 alarm valueRaw integer; apply decimal point place (002EH).INT16Read/write
HR16897doc 4201HAlarm block 2 EV2 alarm valueRaw integer; apply decimal point place (002EH).INT16Read/write
HR16898doc 4202HAlarm block 2 EV3 alarm valueRaw integer; apply decimal point place (002EH).INT16Read/write
HR16899doc 4203HAlarm block 2 EV4 alarm valueRaw integer; apply decimal point place (002EH).INT16Read/write
HR17152doc 4300HAlarm block 3 EV1 alarm valueRaw integer; apply decimal point place (002EH).INT16Read/write
HR17153doc 4301HAlarm block 3 EV2 alarm valueRaw integer; apply decimal point place (002EH).INT16Read/write
HR17154doc 4302HAlarm block 3 EV3 alarm valueRaw integer; apply decimal point place (002EH).INT16Read/write
HR17155doc 4303HAlarm block 3 EV4 alarm valueRaw integer; apply decimal point place (002EH).INT16Read/write
HR17408doc 4400HAlarm block 4 EV1 alarm valueRaw integer; apply decimal point place (002EH).INT16Read/write
HR17409doc 4401HAlarm block 4 EV2 alarm valueRaw integer; apply decimal point place (002EH).INT16Read/write
HR17410doc 4402HAlarm block 4 EV3 alarm valueRaw integer; apply decimal point place (002EH).INT16Read/write
HR17411doc 4403HAlarm block 4 EV4 alarm valueRaw integer; apply decimal point place (002EH).INT16Read/write
HR17664doc 4500HAlarm block 5 EV1 alarm valueRaw integer; apply decimal point place (002EH).INT16Read/write
HR17665doc 4501HAlarm block 5 EV2 alarm valueRaw integer; apply decimal point place (002EH).INT16Read/write
HR17666doc 4502HAlarm block 5 EV3 alarm valueRaw integer; apply decimal point place (002EH).INT16Read/write
HR17667doc 4503HAlarm block 5 EV4 alarm valueRaw integer; apply decimal point place (002EH).INT16Read/write
HR17920doc 4600HAlarm block 6 EV1 alarm valueRaw integer; apply decimal point place (002EH).INT16Read/write
HR17921doc 4601HAlarm block 6 EV2 alarm valueRaw integer; apply decimal point place (002EH).INT16Read/write
HR17922doc 4602HAlarm block 6 EV3 alarm valueRaw integer; apply decimal point place (002EH).INT16Read/write
HR17923doc 4603HAlarm block 6 EV4 alarm valueRaw integer; apply decimal point place (002EH).INT16Read/write
HR18176doc 4700HAlarm block 7 EV1 alarm valueRaw integer; apply decimal point place (002EH).INT16Read/write
HR18177doc 4701HAlarm block 7 EV2 alarm valueRaw integer; apply decimal point place (002EH).INT16Read/write
HR18178doc 4702HAlarm block 7 EV3 alarm valueRaw integer; apply decimal point place (002EH).INT16Read/write
HR18179doc 4703HAlarm block 7 EV4 alarm valueRaw integer; apply decimal point place (002EH).INT16Read/write
HR18432doc 4800HAlarm block 8 EV1 alarm valueRaw integer; apply decimal point place (002EH).INT16Read/write
HR18433doc 4801HAlarm block 8 EV2 alarm valueRaw integer; apply decimal point place (002EH).INT16Read/write
HR18434doc 4802HAlarm block 8 EV3 alarm valueRaw integer; apply decimal point place (002EH).INT16Read/write
HR18435doc 4803HAlarm block 8 EV4 alarm valueRaw integer; apply decimal point place (002EH).INT16Read/write
HR18688doc 4900HAlarm block 9 EV1 alarm valueRaw integer; apply decimal point place (002EH).INT16Read/write
HR18689doc 4901HAlarm block 9 EV2 alarm valueRaw integer; apply decimal point place (002EH).INT16Read/write
HR18690doc 4902HAlarm block 9 EV3 alarm valueRaw integer; apply decimal point place (002EH).INT16Read/write
HR18691doc 4903HAlarm block 9 EV4 alarm valueRaw integer; apply decimal point place (002EH).INT16Read/write
HR20480doc 5000HOutput block 0 OUT1 high limitINT16Read/write
HR20481doc 5001HOutput block 0 OUT1 low limitINT16Read/write
HR20482doc 5002HOutput block 0 OUT2 high limitINT16Read/write
HR20483doc 5003HOutput block 0 OUT2 low limitINT16Read/write
HR20484doc 5004HOutput block 0 OUT1 rate-of-changeDecimal point ignored.INT16Read/write
HR20736doc 5100HOutput block 1 OUT1 high limitINT16Read/write
HR20737doc 5101HOutput block 1 OUT1 low limitINT16Read/write
HR20738doc 5102HOutput block 1 OUT2 high limitINT16Read/write
HR20739doc 5103HOutput block 1 OUT2 low limitINT16Read/write
HR20740doc 5104HOutput block 1 OUT1 rate-of-changeDecimal point ignored.INT16Read/write
HR20992doc 5200HOutput block 2 OUT1 high limitINT16Read/write
HR20993doc 5201HOutput block 2 OUT1 low limitINT16Read/write
HR20994doc 5202HOutput block 2 OUT2 high limitINT16Read/write
HR20995doc 5203HOutput block 2 OUT2 low limitINT16Read/write
HR20996doc 5204HOutput block 2 OUT1 rate-of-changeDecimal point ignored.INT16Read/write
HR21248doc 5300HOutput block 3 OUT1 high limitINT16Read/write
HR21249doc 5301HOutput block 3 OUT1 low limitINT16Read/write
HR21250doc 5302HOutput block 3 OUT2 high limitINT16Read/write
HR21251doc 5303HOutput block 3 OUT2 low limitINT16Read/write
HR21252doc 5304HOutput block 3 OUT1 rate-of-changeDecimal point ignored.INT16Read/write
HR21504doc 5400HOutput block 4 OUT1 high limitINT16Read/write
HR21505doc 5401HOutput block 4 OUT1 low limitINT16Read/write
HR21506doc 5402HOutput block 4 OUT2 high limitINT16Read/write
HR21507doc 5403HOutput block 4 OUT2 low limitINT16Read/write
HR21508doc 5404HOutput block 4 OUT1 rate-of-changeDecimal point ignored.INT16Read/write
HR21760doc 5500HOutput block 5 OUT1 high limitINT16Read/write
HR21761doc 5501HOutput block 5 OUT1 low limitINT16Read/write
HR21762doc 5502HOutput block 5 OUT2 high limitINT16Read/write
HR21763doc 5503HOutput block 5 OUT2 low limitINT16Read/write
HR21764doc 5504HOutput block 5 OUT1 rate-of-changeDecimal point ignored.INT16Read/write
HR22016doc 5600HOutput block 6 OUT1 high limitINT16Read/write
HR22017doc 5601HOutput block 6 OUT1 low limitINT16Read/write
HR22018doc 5602HOutput block 6 OUT2 high limitINT16Read/write
HR22019doc 5603HOutput block 6 OUT2 low limitINT16Read/write
HR22020doc 5604HOutput block 6 OUT1 rate-of-changeDecimal point ignored.INT16Read/write
HR22272doc 5700HOutput block 7 OUT1 high limitINT16Read/write
HR22273doc 5701HOutput block 7 OUT1 low limitINT16Read/write
HR22274doc 5702HOutput block 7 OUT2 high limitINT16Read/write
HR22275doc 5703HOutput block 7 OUT2 low limitINT16Read/write
HR22276doc 5704HOutput block 7 OUT1 rate-of-changeDecimal point ignored.INT16Read/write
HR22528doc 5800HOutput block 8 OUT1 high limitINT16Read/write
HR22529doc 5801HOutput block 8 OUT1 low limitINT16Read/write
HR22530doc 5802HOutput block 8 OUT2 high limitINT16Read/write
HR22531doc 5803HOutput block 8 OUT2 low limitINT16Read/write
HR22532doc 5804HOutput block 8 OUT1 rate-of-changeDecimal point ignored.INT16Read/write
HR22784doc 5900HOutput block 9 OUT1 high limitINT16Read/write
HR22785doc 5901HOutput block 9 OUT1 low limitINT16Read/write
HR22786doc 5902HOutput block 9 OUT2 high limitINT16Read/write
HR22787doc 5903HOutput block 9 OUT2 low limitINT16Read/write
HR22788doc 5904HOutput block 9 OUT1 rate-of-changeDecimal point ignored.INT16Read/write
HR24576doc 6000HTime signal block 0 OFF timeSmaller unit of 0035H.INT16Read/write
HR24577doc 6001HTime signal block 0 ON timeSmaller unit of 0035H.INT16Read/write
HR24832doc 6100HTime signal block 1 OFF timeSmaller unit of 0035H.INT16Read/write
HR24833doc 6101HTime signal block 1 ON timeSmaller unit of 0035H.INT16Read/write
HR25088doc 6200HTime signal block 2 OFF timeSmaller unit of 0035H.INT16Read/write
HR25089doc 6201HTime signal block 2 ON timeSmaller unit of 0035H.INT16Read/write
HR25344doc 6300HTime signal block 3 OFF timeSmaller unit of 0035H.INT16Read/write
HR25345doc 6301HTime signal block 3 ON timeSmaller unit of 0035H.INT16Read/write
HR25600doc 6400HTime signal block 4 OFF timeSmaller unit of 0035H.INT16Read/write
HR25601doc 6401HTime signal block 4 ON timeSmaller unit of 0035H.INT16Read/write
HR25856doc 6500HTime signal block 5 OFF timeSmaller unit of 0035H.INT16Read/write
HR25857doc 6501HTime signal block 5 ON timeSmaller unit of 0035H.INT16Read/write
HR26112doc 6600HTime signal block 6 OFF timeSmaller unit of 0035H.INT16Read/write
HR26113doc 6601HTime signal block 6 ON timeSmaller unit of 0035H.INT16Read/write
HR26368doc 6700HTime signal block 7 OFF timeSmaller unit of 0035H.INT16Read/write
HR26369doc 6701HTime signal block 7 ON timeSmaller unit of 0035H.INT16Read/write
HR26624doc 6800HTime signal block 8 OFF timeSmaller unit of 0035H.INT16Read/write
HR26625doc 6801HTime signal block 8 ON timeSmaller unit of 0035H.INT16Read/write
HR26880doc 6900HTime signal block 9 OFF timeSmaller unit of 0035H.INT16Read/write
HR26881doc 6901HTime signal block 9 ON timeSmaller unit of 0035H.INT16Read/write
HR27136doc 6A00HTime signal block 10 OFF timeSmaller unit of 0035H.INT16Read/write
HR27137doc 6A01HTime signal block 10 ON timeSmaller unit of 0035H.INT16Read/write
HR27392doc 6B00HTime signal block 11 OFF timeSmaller unit of 0035H.INT16Read/write
HR27393doc 6B01HTime signal block 11 ON timeSmaller unit of 0035H.INT16Read/write
HR27648doc 6C00HTime signal block 12 OFF timeSmaller unit of 0035H.INT16Read/write
HR27649doc 6C01HTime signal block 12 ON timeSmaller unit of 0035H.INT16Read/write
HR27904doc 6D00HTime signal block 13 OFF timeSmaller unit of 0035H.INT16Read/write
HR27905doc 6D01HTime signal block 13 ON timeSmaller unit of 0035H.INT16Read/write
HR28160doc 6E00HTime signal block 14 OFF timeSmaller unit of 0035H.INT16Read/write
HR28161doc 6E01HTime signal block 14 ON timeSmaller unit of 0035H.INT16Read/write
HR28416doc 6F00HTime signal block 15 OFF timeSmaller unit of 0035H.INT16Read/write
HR28417doc 6F01HTime signal block 15 ON timeSmaller unit of 0035H.INT16Read/write
HR28672doc 7000HPattern 0 number of repetitionsINT16Read/write
HR28673doc 7001HPattern 0 to 1 linkINT16Read/write0 = Disabled; 1 = Enabled
HR28928doc 7100HPattern 1 number of repetitionsINT16Read/write
HR28929doc 7101HPattern 1 to 2 linkINT16Read/write0 = Disabled; 1 = Enabled
HR29184doc 7200HPattern 2 number of repetitionsINT16Read/write
HR29185doc 7201HPattern 2 to 3 linkINT16Read/write0 = Disabled; 1 = Enabled
HR29440doc 7300HPattern 3 number of repetitionsINT16Read/write
HR29441doc 7301HPattern 3 to 4 linkINT16Read/write0 = Disabled; 1 = Enabled
HR29696doc 7400HPattern 4 number of repetitionsINT16Read/write
HR29697doc 7401HPattern 4 to 5 linkINT16Read/write0 = Disabled; 1 = Enabled
HR29952doc 7500HPattern 5 number of repetitionsINT16Read/write
HR29953doc 7501HPattern 5 to 6 linkINT16Read/write0 = Disabled; 1 = Enabled
HR30208doc 7600HPattern 6 number of repetitionsINT16Read/write
HR30209doc 7601HPattern 6 to 7 linkINT16Read/write0 = Disabled; 1 = Enabled
HR30464doc 7700HPattern 7 number of repetitionsINT16Read/write
HR30465doc 7701HPattern 7 to 8 linkINT16Read/write0 = Disabled; 1 = Enabled
HR30720doc 7800HPattern 8 number of repetitionsINT16Read/write
HR30721doc 7801HPattern 8 to 9 linkINT16Read/write0 = Disabled; 1 = Enabled
HR30976doc 7900HPattern 9 number of repetitionsINT16Read/write
HR30977doc 7901HPattern 9 to 10 linkINT16Read/write0 = Disabled; 1 = Enabled
HR31232doc 7A00HPattern 10 number of repetitionsINT16Read/write
HR31233doc 7A01HPattern 10 to 11 linkINT16Read/write0 = Disabled; 1 = Enabled
HR31488doc 7B00HPattern 11 number of repetitionsINT16Read/write
HR31489doc 7B01HPattern 11 to 12 linkINT16Read/write0 = Disabled; 1 = Enabled
HR31744doc 7C00HPattern 12 number of repetitionsINT16Read/write
HR31745doc 7C01HPattern 12 to 13 linkINT16Read/write0 = Disabled; 1 = Enabled
HR32000doc 7D00HPattern 13 number of repetitionsINT16Read/write
HR32001doc 7D01HPattern 13 to 14 linkINT16Read/write0 = Disabled; 1 = Enabled
HR32256doc 7E00HPattern 14 number of repetitionsINT16Read/write
HR32257doc 7E01HPattern 14 to 15 linkINT16Read/write0 = Disabled; 1 = Enabled
HR32512doc 7F00HPattern 15 number of repetitionsINT16Read/write
HR32513doc 7F01HPattern 15 to 0 linkINT16Read/write0 = Disabled; 1 = Enabled

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Shinko Technos PCA1 programmable controller (C/C5 option)

What Modbus registers does the Shinko Technos PCA1 programmable controller (C/C5 option) have?

This map lists 328 registers: 328 holding registers. 318 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Shinko Technos PCA1 programmable controller (C/C5 option) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Data items are hex (0080H, 1000H) and are sent unchanged as the Modbus holding-register address. The manual says the Modicon number is the data item plus 40001. The RTU examples read PV at 0080H and pattern 0 step 0 SV at 1000H (CRCs 85E2H and 80CAH checked).

What are the minimum Modbus registers to integrate the Shinko Technos PCA1 programmable controller (C/C5 option)?

Start with HR 128 PV (Process value); HR 131 Current step SV (Current step SV); HR 133 Current pattern and step (Running pattern and step); HR 136 Current unit status (Run/hold/wait status); HR 134 Status flag 1 (Output, alarm and error flags); HR 66 Program control Run/Stop (Program Run/Stop); HR 63 Pattern number for operation (Pattern to run); HR 46 Decimal point place (Decimal point for scaling).

How do I enable Modbus control of the Shinko Technos PCA1 programmable controller (C/C5 option)?

Requires the C or C5 option. In the Communication Parameter Setting Group set Communication protocol to MODBUS RTU (or ASCII), then instrument number, speed, data bit/parity and stop bit; these are keypad-only.

Where is the official Shinko Technos PCA1 programmable controller (C/C5 option) Modbus documentation?