- DCL-33A DC digital indicating controller (C5 option)
Sensor (digital temperature controller) · Modbus register map
Shinko Technos DCL-33A DC digital indicating controller (C5 option) Modbus register map
Updated 17 November 2026
The DCL-33A DC is a Shinko PID temperature controller variant with its own communication manual and command table. With the C5 option it speaks Shinko protocol, Modbus ASCII or Modbus RTU on RS485; all items are signed 16-bit holding registers. The map covers SV, PID, alarm, heater burnout and loop break settings, input type, PV, MV, status and heater current.
This page lists 43 Modbus registers for the Shinko Technos DCL-33A DC digital indicating controller (C5 option) — 38 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Shinko Technos’s own free documentation (linked below) and checked against it.
- Manufacturer
- Shinko Technos
- Model
- DCL-33A DC digital indicating controller (C5 option)
- Equipment type
- Sensor (digital temperature controller)
- Registers
- 43 (38 writable)
- Transport
- Modbus RTU, Modbus ASCII
- Default unit ID
- 0
- Default serial
- 9600 baud, 8E1
- Documented addressing
- hexadecimal, 0-based
- Also known as
- DCL-33A DC, DCL-33A-DC-C5
Integration notes: Shinko Technos DCL-33A DC digital indicating controller (C5 option)
Choose Modbus RTU in Auxiliary function setting mode 1 and set a non-zero instrument number, then poll PV 0080H, MV 0081H/0082H and status 0085H; write SV at 0001H.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 128 | PV | INT16 | Process value | Read |
| HR 1 | SV | INT16 | Set value | Read/write |
| HR 129 | OUT1 MV | INT16 | OUT1 manipulated value | Read |
| HR 133 | Status flag | BITMAP16 | Status bits | Read |
| HR 26 | Decimal point place | INT16 | Decimal point for scaling | Read/write |
Enable Modbus control & writes
Requires the C5 option. Hold the key pair shown on p. 2 for 3 s to enter Auxiliary function setting mode 1, press the advance key twice to reach Communication protocol, choose Modbus RTU, then set instrument number, speed, parity and stop bit.
Byte order & addressing
- Instrument number defaults to 0, the Modbus broadcast address; set 1-95.
Network setup
- Factory defaults: Shinko protocol, instrument 0, 9600 bps, even parity, 1 stop bit.
- Speeds 2400, 4800, 9600, 19200 bps.
Watch out for
- This map differs from the DCL-33A manual DCL32CE3; check which manual matches the unit.
Shinko Technos DCL-33A DC digital indicating controller (C5 option) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 1doc 0001H | SV | Set value. Raw integer; apply the decimal point setting. | INT16 | Read/write | ||||
| HR | 3doc 0003H | AT perform/cancel | INT16 | Read/write | 0 = Cancel; 1 = Perform | ||||
| HR | 4doc 0004H | OUT1 proportional band | INT16 | Read/write | |||||
| HR | 5doc 0005H | OUT2 proportional band | INT16 | Read/write | |||||
| HR | 6doc 0006H | Integral time | INT16 | Read/write | |||||
| HR | 7doc 0007H | Derivative time | INT16 | Read/write | |||||
| HR | 8doc 0008H | OUT1 proportional cycle | INT16 | Read/write | |||||
| HR | 9doc 0009H | OUT2 proportional cycle | INT16 | Read/write | |||||
| HR | 10doc 000AH | Manual reset | INT16 | Read/write | |||||
| HR | 11doc 000BH | Alarm value | Raw integer; apply the decimal point setting. | INT16 | Read/write | ||||
| HR | 15doc 000FH | Heater burnout alarm value | INT16 | Read/write | |||||
| HR | 16doc 0010H | Loop break alarm time | INT16 | Read/write | |||||
| HR | 17doc 0011H | Loop break alarm span | INT16 | Read/write | |||||
| HR | 18doc 0012H | Set value lock | INT16 | Read/write | 0 = Unlock; 1 = Lock 1; 2 = Lock 2; 3 = Lock 3 | ||||
| HR | 21doc 0015H | Sensor correction value | INT16 | Read/write | |||||
| HR | 22doc 0016H | Overlap/dead band | INT16 | Read/write | |||||
| HR | 24doc 0018H | Scaling high limit | INT16 | Read/write | |||||
| HR | 25doc 0019H | Scaling low limit | INT16 | Read/write | |||||
| HR | 26doc 001AH | Decimal point place | INT16 | Read/write | 0 = XXXX; 1 = XXX.X; 2 = XX.XX; 3 = X.XXX | ||||
| HR | 27doc 001BH | PV filter time constant | INT16 | Read/write | |||||
| HR | 28doc 001CH | OUT1 high limit | INT16 | Read/write | |||||
| HR | 29doc 001DH | OUT1 low limit | INT16 | Read/write | |||||
| HR | 30doc 001EH | OUT1 ON/OFF hysteresis | INT16 | Read/write | |||||
| HR | 31doc 001FH | OUT2 action mode | INT16 | Read/write | 0 = Air cooling (linear); 1 = Oil cooling (1.5th power); 2 = Water cooling (2nd power) | ||||
| HR | 32doc 0020H | OUT2 high limit | INT16 | Read/write | |||||
| HR | 33doc 0021H | OUT2 low limit | INT16 | Read/write | |||||
| HR | 34doc 0022H | OUT2 ON/OFF hysteresis | INT16 | Read/write | |||||
| HR | 35doc 0023H | Alarm type | Changing it resets the alarm value to 0. | INT16 | Read/write | 0 = No alarm action; 1 = High limit alarm; 2 = Low limit alarm; 3 = High/Low limits alarm; 4 = High/Low limit range alarm; 5 = Process high alarm; 6 = Process low alarm; 7 = High limit with standby; 8 = Low limit with standby; 9 = High/Low limits with standby | |||
| HR | 37doc 0025H | Alarm hysteresis | INT16 | Read/write | |||||
| HR | 41doc 0029H | Alarm action delay time | INT16 | Read/write | |||||
| HR | 64doc 0040H | Alarm energized/de-energized | INT16 | Read/write | 0 = Energized; 1 = De-energized | ||||
| HR | 66doc 0042H | Alarm HOLD function | INT16 | Read/write | 0 = Alarm not holding; 1 = Alarm holding | ||||
| HR | 68doc 0044H | Input type | INT16 | Read/write | 0 = K -200 to 1370 C; 1 = K -199.9 to 400.0 C; 2 = J -200 to 1000 C; 3 = R 0 to 1760 C; 4 = S 0 to 1760 C; 5 = B 0 to 1820 C; 6 = E -200 to 800 C; 7 = T -199.9 to 400.0 C; 8 = N -200 to 1300 C; 9 = PL-II 0 to 1390 C; 10 = C (W/Re5-26) 0 to 2315 C; 11 = Pt100 -199.9 to 850.0 C; 12 = JPt100 -199.9 to 500.0 C; 13 = Pt100 -200 to 850 C; 14 = JPt100 -200 to 500 C; 15 = K -320 to 2500 F; 16 = K -199.9 to 750.0 F; 17 = J -320 to 1800 F; 18 = R 0 to 3200 F; 19 = S 0 to 3200 F; 20 = B 0 to 3300 F; 21 = E -320 to 1500 F; 22 = T -199.9 to 750.0 F; 23 = N -320 to 2300 F; 24 = PL-II 0 to 2500 F; 25 = C (W/Re5-26) 0 to 4200 F; 26 = Pt100 -199.9 to 999.9 F; 27 = JPt100 -199.9 to 900.0 F; 28 = Pt100 -300 to 1500 F; 29 = JPt100 -300 to 900 F; 30 = 4-20 mA DC; 31 = 0-20 mA DC; 32 = 0-1 V DC; 33 = 0-5 V DC; 34 = 1-5 V DC; 35 = 0-10 V DC | ||||
| HR | 69doc 0045H | Direct/reverse control action | INT16 | Read/write | 0 = Heating (reverse); 1 = Cooling (direct) | ||||
| HR | 71doc 0047H | AT bias | INT16 | Read/write | |||||
| HR | 72doc 0048H | ARW | Anti-reset windup. | INT16 | Read/write | ||||
| HR | 111doc 006FH | Key lock | INT16 | Read/write | 0 = Key enabled; 1 = Key locked | ||||
| HR | 112doc 0070H | Key operation change flag clearing | INT16 | Write | 0 = No action; 1 = Clear all | ||||
| HR | 128doc 0080H | PV | Process value. Raw integer; apply the decimal point setting. | INT16 | Read | ||||
| HR | 129doc 0081H | OUT1 MV | INT16 | Read | |||||
| HR | 130doc 0082H | OUT2 MV | INT16 | Read | |||||
| HR | 133doc 0085H | Status flag | BITMAP16 | Read | bit 0 = OUT1 on; bit 1 = OUT2 on; bit 2 = Alarm output on; bit 6 = Heater burnout alarm output; bit 7 = Loop break alarm output; bit 8 = Overscale; bit 9 = Underscale; bit 11 = AT running; bit 13 = 1 = converter, 0 = controller; bit 15 = Settings changed by keypad | ||||
| HR | 134doc 0086H | Heater current value | Held value while OUT1 is on. | INT16 | Read |
Notes on this map
- All data are 16-bit two's complement. Values with a decimal point are sent as whole numbers; apply the decimal point place (001AH).
- Units of PID times, cycles and MV are not printed in the command table.
- Protocol, instrument number, speed, parity and stop bit are keypad-only settings.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Shinko Technos DCL-33A DC digital indicating controller (C5 option)
What Modbus registers does the Shinko Technos DCL-33A DC digital indicating controller (C5 option) have?
This map lists 43 registers: 43 holding registers. 38 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Shinko Technos DCL-33A DC digital indicating controller (C5 option) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Registers are listed as hex data items (0001H) that go into the request unchanged. The manual adds that the matching Modicon holding-register number is the item in decimal plus 40001 (0001H = 40002).
What are the minimum Modbus registers to integrate the Shinko Technos DCL-33A DC digital indicating controller (C5 option)?
Start with HR 128 PV (Process value); HR 1 SV (Set value); HR 129 OUT1 MV (OUT1 manipulated value); HR 133 Status flag (Status bits); HR 26 Decimal point place (Decimal point for scaling).
How do I enable Modbus control of the Shinko Technos DCL-33A DC digital indicating controller (C5 option)?
Requires the C5 option. Hold the key pair shown on p. 2 for 3 s to enter Auxiliary function setting mode 1, press the advance key twice to reach Communication protocol, choose Modbus RTU, then set instrument number, speed, parity and stop bit.
Where is the official Shinko Technos DCL-33A DC digital indicating controller (C5 option) Modbus documentation?
The source is Communication Instruction Manual DCL-33A DC (C5) (No.DCL3CDCE2), revision 2014-03, published free by Shinko Technos at https://shinko-technos.co.jp/e/manual/english/DCL3CDCE2.pdf.
More Shinko Technos Modbus register maps
- Sensor (digital temperature controller)
Shinko Technos ACD-13A / ACR-13A / ACD-15A / ACR-15A digital indicating controller (C, C5 options)
Shinko ACD/ACR-13A (PID) and ACD/ACR-15A (valve positioning) with the C or C5 communication option; manual No.ACDR1CE8.
Also known as: ACD-13A, ACR-13A, ACD-15A, ACR-15A - Sensor (digital temperature controller)
Shinko Technos ACS-13A digital indicating controller (C5 option)
Shinko ACS-13A with the C5 serial communication option; communication manual No.ACS12CE5.
Also known as: ACS-13A-C5, ACS-13A C5 - Sensor (digital temperature controller)
Shinko Technos ACS2 digital indicating controller (C5, C5W options)
Shinko ACS2 with the C5 or C5W serial option, Shinko protocol / MODBUS RTU command set; manual No.ACS2CE3.
Also known as: ACS2-C5, ACS2-C5W - Sensor (conductivity controller)
Shinko Technos AER-102-ECH conductivity indicating controller (C5 option)
Shinko AER-102-ECH electrical conductivity controller with the C5 RS-485 option; manual No. AER11CECE5.
Also known as: AER-102-ECH - Sensor (digital temperature controller)
Shinko Technos BCS2 / BCR2 / BCD2 digital indicating controller (C5, C5W options)
Shinko BCx2 series (BCS2, BCR2, BCD2) with the C5 or C5W communication option, standard (not JC-allocated) command set; manual No.BCx2CE6.
Also known as: BCS2, BCR2, BCD2, BCx2 - Sensor (digital temperature controller)
Shinko Technos DCL-33A digital indicating controller (C5 option)
Shinko DCL-33A with the C5 serial option, plain (non-block) Modbus protocol setting; manual No.DCL32CE3.
Also known as: DCL-33A-C5, DCL-33A C5 - Sensor (digital temperature controller)
Shinko Technos FC series digital indicating controller (C/C5 option, Modbus ASCII)
Shinko FCS-23A, FCR-13A, FCR-23A and FCD-13A with the C or C5 serial option; FCR-15A and FCD-15A have no Modbus (Shinko protocol only). Manual No.FC1CE11.
Also known as: FCS-23A, FCR-13A, FCR-23A, FCD-13A - Sensor (paperless recorder)
Shinko Technos GR200 paperless recorder (Modbus RTU / Modbus TCP)
Shinko GR200 paperless recorder with RS-485 Modbus RTU or Ethernet Modbus TCP; manual GR2CE1.
Also known as: GR200 - Sensor (chart recorder)
Shinko Technos HR-700 hybrid recorder (Modbus RTU, firmware 4.00+)
Shinko HR-700 hybrid recorders (multipoint and pen types), body version 4.00 or later, Modbus map version 01; manual No. HR7CE4.
Also known as: HR-700 - Sensor (digital temperature controller)
Shinko Technos JCL-33A digital indicating controller (C5 option)
Shinko JCL-33A with the C5 option, protocol set to plain 'Modbus RTU mode' or 'Modbus ASCII mode' (not the Block Read/Write modes, which use another layout); manual No.JCL3CE3.
Also known as: JCL-33A-C5, JCL-33A C5 - Sensor (digital temperature controller)
Shinko Technos JCS-33A / JCM-33A / JCR-33A / JCD-33A digital indicating controller (C5 option)
Shinko JCx-33A series (JCS, JCM, JCR, JCD-33A) with the C5 option; communication manual No.JC3CE11.
Also known as: JCS-33A, JCM-33A, JCR-33A, JCD-33A, JCx-33A - Sensor (digital temperature controller)
Shinko Technos JIR-301-M digital indicator (C5 option)
Shinko JIR-301-M with the C5 option, plain (non-block) Modbus protocol setting; manual No.JIR32CE4.
Also known as: JIR-301-M-C5, JIR-301-M C5 - Sensor (programmable temperature controller)
Shinko Technos PCA1 programmable controller (C/C5 option)
Shinko PCA1 programmable controllers with the C or C5 serial option; manual No. PCA1CE3.
Also known as: PCA1 - Sensor (programmable temperature controller)
Shinko Technos PCB1 programmable controller (C5W/C5 option)
Shinko PCB1 programmable controllers with the C5W or C5 RS-485 option, native PCB1 command set; manual No. PCB1CE3.
Also known as: PCB1 - Sensor (digital temperature controller)
Shinko Technos PCD-33A programmable controller (C5 option)
Shinko PCD-33A program controller with the C5 RS-485 option; manual printed No.PCD3CE1 2003.02 (file PCD3CE2).
Also known as: PCD-33A-R/M, PCD-33A-S/M - Sensor (signal conditioner)
Shinko Technos SGxL signal conditioner series (Modbus RTU)
Shinko SGxL signal conditioners (SGBL, SGCL, SGDL, SGIL, SGLL, SGML, SGPL, SGRL, SGSL, SGTL, SGUL); SGFL and SGJL are not covered. Manual No.SGxL1CE3.
Also known as: SGBL, SGCL, SGDL, SGIL, SGLL, SGML, SGPL, SGRL, SGSL, SGTL, SGUL - Sensor (digital temperature controller)
Shinko Technos WCL-13A 2-channel digital indicating controller (C5 option)
Shinko WCL-13A two-loop controller with the C5 option; communication manual No.WCL1CE3.
Also known as: WCL-13A-C5, WCL-13A C5
Other temperature & process controllers register maps
- Sensor (digital indicating temperature controller)
Yokogawa UTAdvanced UT75A digital indicating controller
Yokogawa UT75A one- or two-loop controller with RS-485 or Ethernet communication; D-register map from IM 05P07A01-01EN chapter 14.
Also known as: UT75A - Sensor (digital temperature controller)
Omron E5CC / E5EC / E5AC / E5DC digital temperature controllers (E5_C series)
Omron E5CC, E5EC, E5AC, E5DC and E5CC-U controllers with RS-485, per the E5_C Communications Manual H175; registers present depend on model and options.
Also known as: E5CC, E5EC, E5AC, E5DC, E5CC-U, E5@C, E5_C - Sensor (digital indicating temperature controller)
Yokogawa UTAdvanced UT55A / UT52A digital indicating controller
Yokogawa UT55A and UT52A one- or two-loop controllers with RS-485 or Ethernet communication; D-register map from IM 05P07A01-01EN chapter 6 (UP55A program items excluded).
Also known as: UT55A, UT52A - Sensor (process / temperature controller)
Novus N20K48 modular process controller (Modbus RTU)
N20K48 controllers with the optional RS-485 interface, communication protocol V1.0x.
Also known as: Novus N20K48, N20K48 modular controller - Sensor (digital indicating temperature controller)
Yokogawa UTAdvanced UT35A / UT32A digital indicating controller
Yokogawa UT35A and UT32A single-loop controllers with RS-485 or Ethernet communication; D-register map from IM 05P07A01-01EN chapter 8 (UT32A-D loop 2 and UP35A/UP32A program items excluded).
Also known as: UT35A, UT32A, UT35A/MDL, UT32A/MDL - Sensor (digital temperature controller)
Fuji Electric PXR micro controller X (RS-485 Modbus option)
Fuji Electric PXR series controllers with the RS-485 Modbus communication option; manual INP-TN512642d-E.
Also known as: PXR3, PXR4, PXR5, PXR9
All temperature & process controllers Modbus register maps →
Source: Communication Instruction Manual DCL-33A DC (C5) · No.DCL3CDCE2 · rev. 2014-03. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.