Shinko Technos GR200 paperless recorder (Modbus RTU / Modbus TCP) Modbus register map

Updated 17 November 2026

Short answer

The GR200 is an up-to-18-channel paperless recorder. It is a Modbus RTU slave on RS-485 and also answers Modbus TCP on port 502 over Ethernet. This map covers the read-only measured values and channel status for all 18 channels plus the per-channel range, scaling and decimal point settings needed to interpret them.

This page lists 145 Modbus registers for the Shinko Technos GR200 paperless recorder (Modbus RTU / Modbus TCP) — 108 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Shinko Technos’s own free documentation (linked below) and checked against it.

Manufacturer
Shinko Technos
Model
GR200 paperless recorder (Modbus RTU / Modbus TCP)
Equipment type
Sensor (paperless recorder)
Registers
145 (108 writable)
Transport
Modbus RTU, Modbus TCP
Default unit ID
1
Default serial
19200 baud, 8O1
TCP port
502
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
Also known as
GR200
Source document
Instruction Manual Paperless Recorder Communication Functions (RS-485 MODBUS/Ethernet) Type GR200 · GR2CE1 · rev. 2008-07
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Shinko Technos GR200 paperless recorder (Modbus RTU / Modbus TCP)

Integration in brief

Read input registers 30101-30118 for the measured values and 30131-30148 for channel status in one block each with function 04, and read each channel's decimal point setting once with function 03.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
IR 100CH1 measured valueINT16CH1 measured valueRead
IR 130CH1 statusUINT16CH1 statusRead
HR 17CH1 decimal pointUINT16CH1 decimal pointRead/write
HR 15CH1 engineering startINT16CH1 engineering startRead/write
HR 16CH1 engineering endINT16CH1 engineering endRead/write
IR 85Memory card utilizationUINT16Memory card utilizationRead

Enable Modbus control & writes

Set MODBUS Station No. (0-255; 0 stops communication), speed and parity on the front panel. For Modbus TCP (port 502) also turn the MODBUS TCP/IP function ON (factory OFF) and cycle power.

Byte order & addressing

Network setup

Watch out for

Shinko Technos GR200 paperless recorder (Modbus RTU / Modbus TCP) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

145 of 145 shown
Shinko Technos GR200 paperless recorder (Modbus RTU / Modbus TCP) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
IR85doc 30086Memory card utilization0-1000 = 0.0-100.0 %; 1000 means full.UINT16× 0.1%Read
IR100doc 30101CH1 measured valueNo decimal point sent; 32767 over, -32767 under, -32768 burnout/error.INT16Read
IR101doc 30102CH2 measured valueNo decimal point sent; 32767 over, -32767 under, -32768 burnout/error.INT16Read
IR102doc 30103CH3 measured valueNo decimal point sent; 32767 over, -32767 under, -32768 burnout/error.INT16Read
IR103doc 30104CH4 measured valueNo decimal point sent; 32767 over, -32767 under, -32768 burnout/error.INT16Read
IR104doc 30105CH5 measured valueNo decimal point sent; 32767 over, -32767 under, -32768 burnout/error.INT16Read
IR105doc 30106CH6 measured valueNo decimal point sent; 32767 over, -32767 under, -32768 burnout/error.INT16Read
IR106doc 30107CH7 measured valueNo decimal point sent; 32767 over, -32767 under, -32768 burnout/error.INT16Read
IR107doc 30108CH8 measured valueNo decimal point sent; 32767 over, -32767 under, -32768 burnout/error.INT16Read
IR108doc 30109CH9 measured valueNo decimal point sent; 32767 over, -32767 under, -32768 burnout/error.INT16Read
IR109doc 30110CH10 measured valueNo decimal point sent; 32767 over, -32767 under, -32768 burnout/error.INT16Read
IR110doc 30111CH11 measured valueNo decimal point sent; 32767 over, -32767 under, -32768 burnout/error.INT16Read
IR111doc 30112CH12 measured valueNo decimal point sent; 32767 over, -32767 under, -32768 burnout/error.INT16Read
IR112doc 30113CH13 measured valueNo decimal point sent; 32767 over, -32767 under, -32768 burnout/error.INT16Read
IR113doc 30114CH14 measured valueNo decimal point sent; 32767 over, -32767 under, -32768 burnout/error.INT16Read
IR114doc 30115CH15 measured valueNo decimal point sent; 32767 over, -32767 under, -32768 burnout/error.INT16Read
IR115doc 30116CH16 measured valueNo decimal point sent; 32767 over, -32767 under, -32768 burnout/error.INT16Read
IR116doc 30117CH17 measured valueNo decimal point sent; 32767 over, -32767 under, -32768 burnout/error.INT16Read
IR117doc 30118CH18 measured valueNo decimal point sent; 32767 over, -32767 under, -32768 burnout/error.INT16Read
IR130doc 30131CH1 statusUINT16Read0 = Normal; 1 = Burnout; 2 = Over; 3 = Under; 4 = Error
IR131doc 30132CH2 statusUINT16Read0 = Normal; 1 = Burnout; 2 = Over; 3 = Under; 4 = Error
IR132doc 30133CH3 statusUINT16Read0 = Normal; 1 = Burnout; 2 = Over; 3 = Under; 4 = Error
IR133doc 30134CH4 statusUINT16Read0 = Normal; 1 = Burnout; 2 = Over; 3 = Under; 4 = Error
IR134doc 30135CH5 statusUINT16Read0 = Normal; 1 = Burnout; 2 = Over; 3 = Under; 4 = Error
IR135doc 30136CH6 statusUINT16Read0 = Normal; 1 = Burnout; 2 = Over; 3 = Under; 4 = Error
IR136doc 30137CH7 statusUINT16Read0 = Normal; 1 = Burnout; 2 = Over; 3 = Under; 4 = Error
IR137doc 30138CH8 statusUINT16Read0 = Normal; 1 = Burnout; 2 = Over; 3 = Under; 4 = Error
IR138doc 30139CH9 statusUINT16Read0 = Normal; 1 = Burnout; 2 = Over; 3 = Under; 4 = Error
IR139doc 30140CH10 statusUINT16Read0 = Normal; 1 = Burnout; 2 = Over; 3 = Under; 4 = Error
IR140doc 30141CH11 statusUINT16Read0 = Normal; 1 = Burnout; 2 = Over; 3 = Under; 4 = Error
IR141doc 30142CH12 statusUINT16Read0 = Normal; 1 = Burnout; 2 = Over; 3 = Under; 4 = Error
IR142doc 30143CH13 statusUINT16Read0 = Normal; 1 = Burnout; 2 = Over; 3 = Under; 4 = Error
IR143doc 30144CH14 statusUINT16Read0 = Normal; 1 = Burnout; 2 = Over; 3 = Under; 4 = Error
IR144doc 30145CH15 statusUINT16Read0 = Normal; 1 = Burnout; 2 = Over; 3 = Under; 4 = Error
IR145doc 30146CH16 statusUINT16Read0 = Normal; 1 = Burnout; 2 = Over; 3 = Under; 4 = Error
IR146doc 30147CH17 statusUINT16Read0 = Normal; 1 = Burnout; 2 = Over; 3 = Under; 4 = Error
IR147doc 30148CH18 statusUINT16Read0 = Normal; 1 = Burnout; 2 = Over; 3 = Under; 4 = Error
HR9doc 40010CH1 input typeCode 0-40, see manual Table 2.UINT16Read/write
HR12doc 40013CH1 scalingUINT16Read/write0 = OFF; 1 = ON
HR15doc 40016CH1 engineering startScaled low end; decimal point per 'decimal point' item.INT16Read/write
HR16doc 40017CH1 engineering endScaled high end; decimal point per 'decimal point' item.INT16Read/write
HR17doc 40018CH1 decimal pointCode 0-4 (manual Table 5); places the measured value decimal point.UINT16Read/write
HR25doc 40026CH1 recording modeUINT16Read/write0 = With record; 1 = Display only
HR73doc 40074CH2 input typeCode 0-40, see manual Table 2.UINT16Read/write
HR76doc 40077CH2 scalingUINT16Read/write0 = OFF; 1 = ON
HR79doc 40080CH2 engineering startScaled low end; decimal point per 'decimal point' item.INT16Read/write
HR80doc 40081CH2 engineering endScaled high end; decimal point per 'decimal point' item.INT16Read/write
HR81doc 40082CH2 decimal pointCode 0-4 (manual Table 5); places the measured value decimal point.UINT16Read/write
HR89doc 40090CH2 recording modeUINT16Read/write0 = With record; 1 = Display only
HR137doc 40138CH3 input typeCode 0-40, see manual Table 2.UINT16Read/write
HR140doc 40141CH3 scalingUINT16Read/write0 = OFF; 1 = ON
HR143doc 40144CH3 engineering startScaled low end; decimal point per 'decimal point' item.INT16Read/write
HR144doc 40145CH3 engineering endScaled high end; decimal point per 'decimal point' item.INT16Read/write
HR145doc 40146CH3 decimal pointCode 0-4 (manual Table 5); places the measured value decimal point.UINT16Read/write
HR153doc 40154CH3 recording modeUINT16Read/write0 = With record; 1 = Display only
HR201doc 40202CH4 input typeCode 0-40, see manual Table 2.UINT16Read/write
HR204doc 40205CH4 scalingUINT16Read/write0 = OFF; 1 = ON
HR207doc 40208CH4 engineering startScaled low end; decimal point per 'decimal point' item.INT16Read/write
HR208doc 40209CH4 engineering endScaled high end; decimal point per 'decimal point' item.INT16Read/write
HR209doc 40210CH4 decimal pointCode 0-4 (manual Table 5); places the measured value decimal point.UINT16Read/write
HR217doc 40218CH4 recording modeUINT16Read/write0 = With record; 1 = Display only
HR265doc 40266CH5 input typeCode 0-40, see manual Table 2.UINT16Read/write
HR268doc 40269CH5 scalingUINT16Read/write0 = OFF; 1 = ON
HR271doc 40272CH5 engineering startScaled low end; decimal point per 'decimal point' item.INT16Read/write
HR272doc 40273CH5 engineering endScaled high end; decimal point per 'decimal point' item.INT16Read/write
HR273doc 40274CH5 decimal pointCode 0-4 (manual Table 5); places the measured value decimal point.UINT16Read/write
HR281doc 40282CH5 recording modeUINT16Read/write0 = With record; 1 = Display only
HR329doc 40330CH6 input typeCode 0-40, see manual Table 2.UINT16Read/write
HR332doc 40333CH6 scalingUINT16Read/write0 = OFF; 1 = ON
HR335doc 40336CH6 engineering startScaled low end; decimal point per 'decimal point' item.INT16Read/write
HR336doc 40337CH6 engineering endScaled high end; decimal point per 'decimal point' item.INT16Read/write
HR337doc 40338CH6 decimal pointCode 0-4 (manual Table 5); places the measured value decimal point.UINT16Read/write
HR345doc 40346CH6 recording modeUINT16Read/write0 = With record; 1 = Display only
HR393doc 40394CH7 input typeCode 0-40, see manual Table 2.UINT16Read/write
HR396doc 40397CH7 scalingUINT16Read/write0 = OFF; 1 = ON
HR399doc 40400CH7 engineering startScaled low end; decimal point per 'decimal point' item.INT16Read/write
HR400doc 40401CH7 engineering endScaled high end; decimal point per 'decimal point' item.INT16Read/write
HR401doc 40402CH7 decimal pointCode 0-4 (manual Table 5); places the measured value decimal point.UINT16Read/write
HR409doc 40410CH7 recording modeUINT16Read/write0 = With record; 1 = Display only
HR457doc 40458CH8 input typeCode 0-40, see manual Table 2.UINT16Read/write
HR460doc 40461CH8 scalingUINT16Read/write0 = OFF; 1 = ON
HR463doc 40464CH8 engineering startScaled low end; decimal point per 'decimal point' item.INT16Read/write
HR464doc 40465CH8 engineering endScaled high end; decimal point per 'decimal point' item.INT16Read/write
HR465doc 40466CH8 decimal pointCode 0-4 (manual Table 5); places the measured value decimal point.UINT16Read/write
HR473doc 40474CH8 recording modeUINT16Read/write0 = With record; 1 = Display only
HR521doc 40522CH9 input typeCode 0-40, see manual Table 2.UINT16Read/write
HR524doc 40525CH9 scalingUINT16Read/write0 = OFF; 1 = ON
HR527doc 40528CH9 engineering startScaled low end; decimal point per 'decimal point' item.INT16Read/write
HR528doc 40529CH9 engineering endScaled high end; decimal point per 'decimal point' item.INT16Read/write
HR529doc 40530CH9 decimal pointCode 0-4 (manual Table 5); places the measured value decimal point.UINT16Read/write
HR537doc 40538CH9 recording modeUINT16Read/write0 = With record; 1 = Display only
HR585doc 40586CH10 input typeCode 0-40, see manual Table 2.UINT16Read/write
HR588doc 40589CH10 scalingUINT16Read/write0 = OFF; 1 = ON
HR591doc 40592CH10 engineering startScaled low end; decimal point per 'decimal point' item.INT16Read/write
HR592doc 40593CH10 engineering endScaled high end; decimal point per 'decimal point' item.INT16Read/write
HR593doc 40594CH10 decimal pointCode 0-4 (manual Table 5); places the measured value decimal point.UINT16Read/write
HR601doc 40602CH10 recording modeUINT16Read/write0 = With record; 1 = Display only
HR649doc 40650CH11 input typeCode 0-40, see manual Table 2.UINT16Read/write
HR652doc 40653CH11 scalingUINT16Read/write0 = OFF; 1 = ON
HR655doc 40656CH11 engineering startScaled low end; decimal point per 'decimal point' item.INT16Read/write
HR656doc 40657CH11 engineering endScaled high end; decimal point per 'decimal point' item.INT16Read/write
HR657doc 40658CH11 decimal pointCode 0-4 (manual Table 5); places the measured value decimal point.UINT16Read/write
HR665doc 40666CH11 recording modeUINT16Read/write0 = With record; 1 = Display only
HR713doc 40714CH12 input typeCode 0-40, see manual Table 2.UINT16Read/write
HR716doc 40717CH12 scalingUINT16Read/write0 = OFF; 1 = ON
HR719doc 40720CH12 engineering startScaled low end; decimal point per 'decimal point' item.INT16Read/write
HR720doc 40721CH12 engineering endScaled high end; decimal point per 'decimal point' item.INT16Read/write
HR721doc 40722CH12 decimal pointCode 0-4 (manual Table 5); places the measured value decimal point.UINT16Read/write
HR729doc 40730CH12 recording modeUINT16Read/write0 = With record; 1 = Display only
HR777doc 40778CH13 input typeCode 0-40, see manual Table 2.UINT16Read/write
HR780doc 40781CH13 scalingUINT16Read/write0 = OFF; 1 = ON
HR783doc 40784CH13 engineering startScaled low end; decimal point per 'decimal point' item.INT16Read/write
HR784doc 40785CH13 engineering endScaled high end; decimal point per 'decimal point' item.INT16Read/write
HR785doc 40786CH13 decimal pointCode 0-4 (manual Table 5); places the measured value decimal point.UINT16Read/write
HR793doc 40794CH13 recording modeUINT16Read/write0 = With record; 1 = Display only
HR841doc 40842CH14 input typeCode 0-40, see manual Table 2.UINT16Read/write
HR844doc 40845CH14 scalingUINT16Read/write0 = OFF; 1 = ON
HR847doc 40848CH14 engineering startScaled low end; decimal point per 'decimal point' item.INT16Read/write
HR848doc 40849CH14 engineering endScaled high end; decimal point per 'decimal point' item.INT16Read/write
HR849doc 40850CH14 decimal pointCode 0-4 (manual Table 5); places the measured value decimal point.UINT16Read/write
HR857doc 40858CH14 recording modeUINT16Read/write0 = With record; 1 = Display only
HR905doc 40906CH15 input typeCode 0-40, see manual Table 2.UINT16Read/write
HR908doc 40909CH15 scalingUINT16Read/write0 = OFF; 1 = ON
HR911doc 40912CH15 engineering startScaled low end; decimal point per 'decimal point' item.INT16Read/write
HR912doc 40913CH15 engineering endScaled high end; decimal point per 'decimal point' item.INT16Read/write
HR913doc 40914CH15 decimal pointCode 0-4 (manual Table 5); places the measured value decimal point.UINT16Read/write
HR921doc 40922CH15 recording modeUINT16Read/write0 = With record; 1 = Display only
HR969doc 40970CH16 input typeCode 0-40, see manual Table 2.UINT16Read/write
HR972doc 40973CH16 scalingUINT16Read/write0 = OFF; 1 = ON
HR975doc 40976CH16 engineering startScaled low end; decimal point per 'decimal point' item.INT16Read/write
HR976doc 40977CH16 engineering endScaled high end; decimal point per 'decimal point' item.INT16Read/write
HR977doc 40978CH16 decimal pointCode 0-4 (manual Table 5); places the measured value decimal point.UINT16Read/write
HR985doc 40986CH16 recording modeUINT16Read/write0 = With record; 1 = Display only
HR1033doc 41034CH17 input typeCode 0-40, see manual Table 2.UINT16Read/write
HR1036doc 41037CH17 scalingUINT16Read/write0 = OFF; 1 = ON
HR1039doc 41040CH17 engineering startScaled low end; decimal point per 'decimal point' item.INT16Read/write
HR1040doc 41041CH17 engineering endScaled high end; decimal point per 'decimal point' item.INT16Read/write
HR1041doc 41042CH17 decimal pointCode 0-4 (manual Table 5); places the measured value decimal point.UINT16Read/write
HR1049doc 41050CH17 recording modeUINT16Read/write0 = With record; 1 = Display only
HR1097doc 41098CH18 input typeCode 0-40, see manual Table 2.UINT16Read/write
HR1100doc 41101CH18 scalingUINT16Read/write0 = OFF; 1 = ON
HR1103doc 41104CH18 engineering startScaled low end; decimal point per 'decimal point' item.INT16Read/write
HR1104doc 41105CH18 engineering endScaled high end; decimal point per 'decimal point' item.INT16Read/write
HR1105doc 41106CH18 decimal pointCode 0-4 (manual Table 5); places the measured value decimal point.UINT16Read/write
HR1113doc 41114CH18 recording modeUINT16Read/write0 = With record; 1 = Display only

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Shinko Technos GR200 paperless recorder (Modbus RTU / Modbus TCP)

What Modbus registers does the Shinko Technos GR200 paperless recorder (Modbus RTU / Modbus TCP) have?

This map lists 145 registers: 37 input registers, 108 holding registers. 108 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Shinko Technos GR200 paperless recorder (Modbus RTU / Modbus TCP) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Registers are printed as 30xxx/40xxx numbers; the manual says the address in the message is the lower four digits minus 1 (40003 is sent as 0002). The manual's example reads CH2 measured value (30102) at relative address 0065H.

What are the minimum Modbus registers to integrate the Shinko Technos GR200 paperless recorder (Modbus RTU / Modbus TCP)?

Start with IR 100 CH1 measured value (CH1 measured value); IR 130 CH1 status (CH1 status); HR 17 CH1 decimal point (CH1 decimal point); HR 15 CH1 engineering start (CH1 engineering start); HR 16 CH1 engineering end (CH1 engineering end); IR 85 Memory card utilization (Memory card utilization).

How do I enable Modbus control of the Shinko Technos GR200 paperless recorder (Modbus RTU / Modbus TCP)?

Set MODBUS Station No. (0-255; 0 stops communication), speed and parity on the front panel. For Modbus TCP (port 502) also turn the MODBUS TCP/IP function ON (factory OFF) and cycle power.

Where is the official Shinko Technos GR200 paperless recorder (Modbus RTU / Modbus TCP) Modbus documentation?

The source is Instruction Manual Paperless Recorder Communication Functions (RS-485 MODBUS/Ethernet) Type GR200 (GR2CE1), revision 2008-07, published free by Shinko Technos at https://shinko-technos.co.jp/e/manual/english/GR2CE1.pdf.

More Shinko Technos Modbus register maps

Other valves, actuators & sensors register maps

All valves, actuators & sensors Modbus register maps →

Source: Instruction Manual Paperless Recorder Communication Functions (RS-485 MODBUS/Ethernet) Type GR200 · GR2CE1 · rev. 2008-07. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.