- GR200 paperless recorder (Modbus RTU / Modbus TCP)
Sensor (paperless recorder) · Modbus register map
Shinko Technos GR200 paperless recorder (Modbus RTU / Modbus TCP) Modbus register map
Updated 17 November 2026
The GR200 is an up-to-18-channel paperless recorder. It is a Modbus RTU slave on RS-485 and also answers Modbus TCP on port 502 over Ethernet. This map covers the read-only measured values and channel status for all 18 channels plus the per-channel range, scaling and decimal point settings needed to interpret them.
This page lists 145 Modbus registers for the Shinko Technos GR200 paperless recorder (Modbus RTU / Modbus TCP) — 108 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Shinko Technos’s own free documentation (linked below) and checked against it.
- Manufacturer
- Shinko Technos
- Model
- GR200 paperless recorder (Modbus RTU / Modbus TCP)
- Equipment type
- Sensor (paperless recorder)
- Registers
- 145 (108 writable)
- Transport
- Modbus RTU, Modbus TCP
- Default unit ID
- 1
- Default serial
- 19200 baud, 8O1
- TCP port
- 502
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- Also known as
- GR200
Integration notes: Shinko Technos GR200 paperless recorder (Modbus RTU / Modbus TCP)
Read input registers 30101-30118 for the measured values and 30131-30148 for channel status in one block each with function 04, and read each channel's decimal point setting once with function 03.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| IR 100 | CH1 measured value | INT16 | CH1 measured value | Read |
| IR 130 | CH1 status | UINT16 | CH1 status | Read |
| HR 17 | CH1 decimal point | UINT16 | CH1 decimal point | Read/write |
| HR 15 | CH1 engineering start | INT16 | CH1 engineering start | Read/write |
| HR 16 | CH1 engineering end | INT16 | CH1 engineering end | Read/write |
| IR 85 | Memory card utilization | UINT16 | Memory card utilization | Read |
Enable Modbus control & writes
Set MODBUS Station No. (0-255; 0 stops communication), speed and parity on the front panel. For Modbus TCP (port 502) also turn the MODBUS TCP/IP function ON (factory OFF) and cycle power.
Byte order & addressing
- Out-of-range readings come back as 32767 (over), -32767 (under) or -32768 (burnout/error); check the status registers.
- The recorder accepts written values outside the setting range without complaint.
Network setup
- Factory defaults: station 1, 19200 bps, odd parity, 8 data bits, 1 stop bit (8 bits and 1 stop bit are fixed). Up to 31 units per RS-485 line.
Watch out for
- A read is limited to 64 registers per message.
Shinko Technos GR200 paperless recorder (Modbus RTU / Modbus TCP) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| IR | 85doc 30086 | Memory card utilization | 0-1000 = 0.0-100.0 %; 1000 means full. | UINT16 | × 0.1 | % | Read | ||
| IR | 100doc 30101 | CH1 measured value | No decimal point sent; 32767 over, -32767 under, -32768 burnout/error. | INT16 | Read | ||||
| IR | 101doc 30102 | CH2 measured value | No decimal point sent; 32767 over, -32767 under, -32768 burnout/error. | INT16 | Read | ||||
| IR | 102doc 30103 | CH3 measured value | No decimal point sent; 32767 over, -32767 under, -32768 burnout/error. | INT16 | Read | ||||
| IR | 103doc 30104 | CH4 measured value | No decimal point sent; 32767 over, -32767 under, -32768 burnout/error. | INT16 | Read | ||||
| IR | 104doc 30105 | CH5 measured value | No decimal point sent; 32767 over, -32767 under, -32768 burnout/error. | INT16 | Read | ||||
| IR | 105doc 30106 | CH6 measured value | No decimal point sent; 32767 over, -32767 under, -32768 burnout/error. | INT16 | Read | ||||
| IR | 106doc 30107 | CH7 measured value | No decimal point sent; 32767 over, -32767 under, -32768 burnout/error. | INT16 | Read | ||||
| IR | 107doc 30108 | CH8 measured value | No decimal point sent; 32767 over, -32767 under, -32768 burnout/error. | INT16 | Read | ||||
| IR | 108doc 30109 | CH9 measured value | No decimal point sent; 32767 over, -32767 under, -32768 burnout/error. | INT16 | Read | ||||
| IR | 109doc 30110 | CH10 measured value | No decimal point sent; 32767 over, -32767 under, -32768 burnout/error. | INT16 | Read | ||||
| IR | 110doc 30111 | CH11 measured value | No decimal point sent; 32767 over, -32767 under, -32768 burnout/error. | INT16 | Read | ||||
| IR | 111doc 30112 | CH12 measured value | No decimal point sent; 32767 over, -32767 under, -32768 burnout/error. | INT16 | Read | ||||
| IR | 112doc 30113 | CH13 measured value | No decimal point sent; 32767 over, -32767 under, -32768 burnout/error. | INT16 | Read | ||||
| IR | 113doc 30114 | CH14 measured value | No decimal point sent; 32767 over, -32767 under, -32768 burnout/error. | INT16 | Read | ||||
| IR | 114doc 30115 | CH15 measured value | No decimal point sent; 32767 over, -32767 under, -32768 burnout/error. | INT16 | Read | ||||
| IR | 115doc 30116 | CH16 measured value | No decimal point sent; 32767 over, -32767 under, -32768 burnout/error. | INT16 | Read | ||||
| IR | 116doc 30117 | CH17 measured value | No decimal point sent; 32767 over, -32767 under, -32768 burnout/error. | INT16 | Read | ||||
| IR | 117doc 30118 | CH18 measured value | No decimal point sent; 32767 over, -32767 under, -32768 burnout/error. | INT16 | Read | ||||
| IR | 130doc 30131 | CH1 status | UINT16 | Read | 0 = Normal; 1 = Burnout; 2 = Over; 3 = Under; 4 = Error | ||||
| IR | 131doc 30132 | CH2 status | UINT16 | Read | 0 = Normal; 1 = Burnout; 2 = Over; 3 = Under; 4 = Error | ||||
| IR | 132doc 30133 | CH3 status | UINT16 | Read | 0 = Normal; 1 = Burnout; 2 = Over; 3 = Under; 4 = Error | ||||
| IR | 133doc 30134 | CH4 status | UINT16 | Read | 0 = Normal; 1 = Burnout; 2 = Over; 3 = Under; 4 = Error | ||||
| IR | 134doc 30135 | CH5 status | UINT16 | Read | 0 = Normal; 1 = Burnout; 2 = Over; 3 = Under; 4 = Error | ||||
| IR | 135doc 30136 | CH6 status | UINT16 | Read | 0 = Normal; 1 = Burnout; 2 = Over; 3 = Under; 4 = Error | ||||
| IR | 136doc 30137 | CH7 status | UINT16 | Read | 0 = Normal; 1 = Burnout; 2 = Over; 3 = Under; 4 = Error | ||||
| IR | 137doc 30138 | CH8 status | UINT16 | Read | 0 = Normal; 1 = Burnout; 2 = Over; 3 = Under; 4 = Error | ||||
| IR | 138doc 30139 | CH9 status | UINT16 | Read | 0 = Normal; 1 = Burnout; 2 = Over; 3 = Under; 4 = Error | ||||
| IR | 139doc 30140 | CH10 status | UINT16 | Read | 0 = Normal; 1 = Burnout; 2 = Over; 3 = Under; 4 = Error | ||||
| IR | 140doc 30141 | CH11 status | UINT16 | Read | 0 = Normal; 1 = Burnout; 2 = Over; 3 = Under; 4 = Error | ||||
| IR | 141doc 30142 | CH12 status | UINT16 | Read | 0 = Normal; 1 = Burnout; 2 = Over; 3 = Under; 4 = Error | ||||
| IR | 142doc 30143 | CH13 status | UINT16 | Read | 0 = Normal; 1 = Burnout; 2 = Over; 3 = Under; 4 = Error | ||||
| IR | 143doc 30144 | CH14 status | UINT16 | Read | 0 = Normal; 1 = Burnout; 2 = Over; 3 = Under; 4 = Error | ||||
| IR | 144doc 30145 | CH15 status | UINT16 | Read | 0 = Normal; 1 = Burnout; 2 = Over; 3 = Under; 4 = Error | ||||
| IR | 145doc 30146 | CH16 status | UINT16 | Read | 0 = Normal; 1 = Burnout; 2 = Over; 3 = Under; 4 = Error | ||||
| IR | 146doc 30147 | CH17 status | UINT16 | Read | 0 = Normal; 1 = Burnout; 2 = Over; 3 = Under; 4 = Error | ||||
| IR | 147doc 30148 | CH18 status | UINT16 | Read | 0 = Normal; 1 = Burnout; 2 = Over; 3 = Under; 4 = Error | ||||
| HR | 9doc 40010 | CH1 input type | Code 0-40, see manual Table 2. | UINT16 | Read/write | ||||
| HR | 12doc 40013 | CH1 scaling | UINT16 | Read/write | 0 = OFF; 1 = ON | ||||
| HR | 15doc 40016 | CH1 engineering start | Scaled low end; decimal point per 'decimal point' item. | INT16 | Read/write | ||||
| HR | 16doc 40017 | CH1 engineering end | Scaled high end; decimal point per 'decimal point' item. | INT16 | Read/write | ||||
| HR | 17doc 40018 | CH1 decimal point | Code 0-4 (manual Table 5); places the measured value decimal point. | UINT16 | Read/write | ||||
| HR | 25doc 40026 | CH1 recording mode | UINT16 | Read/write | 0 = With record; 1 = Display only | ||||
| HR | 73doc 40074 | CH2 input type | Code 0-40, see manual Table 2. | UINT16 | Read/write | ||||
| HR | 76doc 40077 | CH2 scaling | UINT16 | Read/write | 0 = OFF; 1 = ON | ||||
| HR | 79doc 40080 | CH2 engineering start | Scaled low end; decimal point per 'decimal point' item. | INT16 | Read/write | ||||
| HR | 80doc 40081 | CH2 engineering end | Scaled high end; decimal point per 'decimal point' item. | INT16 | Read/write | ||||
| HR | 81doc 40082 | CH2 decimal point | Code 0-4 (manual Table 5); places the measured value decimal point. | UINT16 | Read/write | ||||
| HR | 89doc 40090 | CH2 recording mode | UINT16 | Read/write | 0 = With record; 1 = Display only | ||||
| HR | 137doc 40138 | CH3 input type | Code 0-40, see manual Table 2. | UINT16 | Read/write | ||||
| HR | 140doc 40141 | CH3 scaling | UINT16 | Read/write | 0 = OFF; 1 = ON | ||||
| HR | 143doc 40144 | CH3 engineering start | Scaled low end; decimal point per 'decimal point' item. | INT16 | Read/write | ||||
| HR | 144doc 40145 | CH3 engineering end | Scaled high end; decimal point per 'decimal point' item. | INT16 | Read/write | ||||
| HR | 145doc 40146 | CH3 decimal point | Code 0-4 (manual Table 5); places the measured value decimal point. | UINT16 | Read/write | ||||
| HR | 153doc 40154 | CH3 recording mode | UINT16 | Read/write | 0 = With record; 1 = Display only | ||||
| HR | 201doc 40202 | CH4 input type | Code 0-40, see manual Table 2. | UINT16 | Read/write | ||||
| HR | 204doc 40205 | CH4 scaling | UINT16 | Read/write | 0 = OFF; 1 = ON | ||||
| HR | 207doc 40208 | CH4 engineering start | Scaled low end; decimal point per 'decimal point' item. | INT16 | Read/write | ||||
| HR | 208doc 40209 | CH4 engineering end | Scaled high end; decimal point per 'decimal point' item. | INT16 | Read/write | ||||
| HR | 209doc 40210 | CH4 decimal point | Code 0-4 (manual Table 5); places the measured value decimal point. | UINT16 | Read/write | ||||
| HR | 217doc 40218 | CH4 recording mode | UINT16 | Read/write | 0 = With record; 1 = Display only | ||||
| HR | 265doc 40266 | CH5 input type | Code 0-40, see manual Table 2. | UINT16 | Read/write | ||||
| HR | 268doc 40269 | CH5 scaling | UINT16 | Read/write | 0 = OFF; 1 = ON | ||||
| HR | 271doc 40272 | CH5 engineering start | Scaled low end; decimal point per 'decimal point' item. | INT16 | Read/write | ||||
| HR | 272doc 40273 | CH5 engineering end | Scaled high end; decimal point per 'decimal point' item. | INT16 | Read/write | ||||
| HR | 273doc 40274 | CH5 decimal point | Code 0-4 (manual Table 5); places the measured value decimal point. | UINT16 | Read/write | ||||
| HR | 281doc 40282 | CH5 recording mode | UINT16 | Read/write | 0 = With record; 1 = Display only | ||||
| HR | 329doc 40330 | CH6 input type | Code 0-40, see manual Table 2. | UINT16 | Read/write | ||||
| HR | 332doc 40333 | CH6 scaling | UINT16 | Read/write | 0 = OFF; 1 = ON | ||||
| HR | 335doc 40336 | CH6 engineering start | Scaled low end; decimal point per 'decimal point' item. | INT16 | Read/write | ||||
| HR | 336doc 40337 | CH6 engineering end | Scaled high end; decimal point per 'decimal point' item. | INT16 | Read/write | ||||
| HR | 337doc 40338 | CH6 decimal point | Code 0-4 (manual Table 5); places the measured value decimal point. | UINT16 | Read/write | ||||
| HR | 345doc 40346 | CH6 recording mode | UINT16 | Read/write | 0 = With record; 1 = Display only | ||||
| HR | 393doc 40394 | CH7 input type | Code 0-40, see manual Table 2. | UINT16 | Read/write | ||||
| HR | 396doc 40397 | CH7 scaling | UINT16 | Read/write | 0 = OFF; 1 = ON | ||||
| HR | 399doc 40400 | CH7 engineering start | Scaled low end; decimal point per 'decimal point' item. | INT16 | Read/write | ||||
| HR | 400doc 40401 | CH7 engineering end | Scaled high end; decimal point per 'decimal point' item. | INT16 | Read/write | ||||
| HR | 401doc 40402 | CH7 decimal point | Code 0-4 (manual Table 5); places the measured value decimal point. | UINT16 | Read/write | ||||
| HR | 409doc 40410 | CH7 recording mode | UINT16 | Read/write | 0 = With record; 1 = Display only | ||||
| HR | 457doc 40458 | CH8 input type | Code 0-40, see manual Table 2. | UINT16 | Read/write | ||||
| HR | 460doc 40461 | CH8 scaling | UINT16 | Read/write | 0 = OFF; 1 = ON | ||||
| HR | 463doc 40464 | CH8 engineering start | Scaled low end; decimal point per 'decimal point' item. | INT16 | Read/write | ||||
| HR | 464doc 40465 | CH8 engineering end | Scaled high end; decimal point per 'decimal point' item. | INT16 | Read/write | ||||
| HR | 465doc 40466 | CH8 decimal point | Code 0-4 (manual Table 5); places the measured value decimal point. | UINT16 | Read/write | ||||
| HR | 473doc 40474 | CH8 recording mode | UINT16 | Read/write | 0 = With record; 1 = Display only | ||||
| HR | 521doc 40522 | CH9 input type | Code 0-40, see manual Table 2. | UINT16 | Read/write | ||||
| HR | 524doc 40525 | CH9 scaling | UINT16 | Read/write | 0 = OFF; 1 = ON | ||||
| HR | 527doc 40528 | CH9 engineering start | Scaled low end; decimal point per 'decimal point' item. | INT16 | Read/write | ||||
| HR | 528doc 40529 | CH9 engineering end | Scaled high end; decimal point per 'decimal point' item. | INT16 | Read/write | ||||
| HR | 529doc 40530 | CH9 decimal point | Code 0-4 (manual Table 5); places the measured value decimal point. | UINT16 | Read/write | ||||
| HR | 537doc 40538 | CH9 recording mode | UINT16 | Read/write | 0 = With record; 1 = Display only | ||||
| HR | 585doc 40586 | CH10 input type | Code 0-40, see manual Table 2. | UINT16 | Read/write | ||||
| HR | 588doc 40589 | CH10 scaling | UINT16 | Read/write | 0 = OFF; 1 = ON | ||||
| HR | 591doc 40592 | CH10 engineering start | Scaled low end; decimal point per 'decimal point' item. | INT16 | Read/write | ||||
| HR | 592doc 40593 | CH10 engineering end | Scaled high end; decimal point per 'decimal point' item. | INT16 | Read/write | ||||
| HR | 593doc 40594 | CH10 decimal point | Code 0-4 (manual Table 5); places the measured value decimal point. | UINT16 | Read/write | ||||
| HR | 601doc 40602 | CH10 recording mode | UINT16 | Read/write | 0 = With record; 1 = Display only | ||||
| HR | 649doc 40650 | CH11 input type | Code 0-40, see manual Table 2. | UINT16 | Read/write | ||||
| HR | 652doc 40653 | CH11 scaling | UINT16 | Read/write | 0 = OFF; 1 = ON | ||||
| HR | 655doc 40656 | CH11 engineering start | Scaled low end; decimal point per 'decimal point' item. | INT16 | Read/write | ||||
| HR | 656doc 40657 | CH11 engineering end | Scaled high end; decimal point per 'decimal point' item. | INT16 | Read/write | ||||
| HR | 657doc 40658 | CH11 decimal point | Code 0-4 (manual Table 5); places the measured value decimal point. | UINT16 | Read/write | ||||
| HR | 665doc 40666 | CH11 recording mode | UINT16 | Read/write | 0 = With record; 1 = Display only | ||||
| HR | 713doc 40714 | CH12 input type | Code 0-40, see manual Table 2. | UINT16 | Read/write | ||||
| HR | 716doc 40717 | CH12 scaling | UINT16 | Read/write | 0 = OFF; 1 = ON | ||||
| HR | 719doc 40720 | CH12 engineering start | Scaled low end; decimal point per 'decimal point' item. | INT16 | Read/write | ||||
| HR | 720doc 40721 | CH12 engineering end | Scaled high end; decimal point per 'decimal point' item. | INT16 | Read/write | ||||
| HR | 721doc 40722 | CH12 decimal point | Code 0-4 (manual Table 5); places the measured value decimal point. | UINT16 | Read/write | ||||
| HR | 729doc 40730 | CH12 recording mode | UINT16 | Read/write | 0 = With record; 1 = Display only | ||||
| HR | 777doc 40778 | CH13 input type | Code 0-40, see manual Table 2. | UINT16 | Read/write | ||||
| HR | 780doc 40781 | CH13 scaling | UINT16 | Read/write | 0 = OFF; 1 = ON | ||||
| HR | 783doc 40784 | CH13 engineering start | Scaled low end; decimal point per 'decimal point' item. | INT16 | Read/write | ||||
| HR | 784doc 40785 | CH13 engineering end | Scaled high end; decimal point per 'decimal point' item. | INT16 | Read/write | ||||
| HR | 785doc 40786 | CH13 decimal point | Code 0-4 (manual Table 5); places the measured value decimal point. | UINT16 | Read/write | ||||
| HR | 793doc 40794 | CH13 recording mode | UINT16 | Read/write | 0 = With record; 1 = Display only | ||||
| HR | 841doc 40842 | CH14 input type | Code 0-40, see manual Table 2. | UINT16 | Read/write | ||||
| HR | 844doc 40845 | CH14 scaling | UINT16 | Read/write | 0 = OFF; 1 = ON | ||||
| HR | 847doc 40848 | CH14 engineering start | Scaled low end; decimal point per 'decimal point' item. | INT16 | Read/write | ||||
| HR | 848doc 40849 | CH14 engineering end | Scaled high end; decimal point per 'decimal point' item. | INT16 | Read/write | ||||
| HR | 849doc 40850 | CH14 decimal point | Code 0-4 (manual Table 5); places the measured value decimal point. | UINT16 | Read/write | ||||
| HR | 857doc 40858 | CH14 recording mode | UINT16 | Read/write | 0 = With record; 1 = Display only | ||||
| HR | 905doc 40906 | CH15 input type | Code 0-40, see manual Table 2. | UINT16 | Read/write | ||||
| HR | 908doc 40909 | CH15 scaling | UINT16 | Read/write | 0 = OFF; 1 = ON | ||||
| HR | 911doc 40912 | CH15 engineering start | Scaled low end; decimal point per 'decimal point' item. | INT16 | Read/write | ||||
| HR | 912doc 40913 | CH15 engineering end | Scaled high end; decimal point per 'decimal point' item. | INT16 | Read/write | ||||
| HR | 913doc 40914 | CH15 decimal point | Code 0-4 (manual Table 5); places the measured value decimal point. | UINT16 | Read/write | ||||
| HR | 921doc 40922 | CH15 recording mode | UINT16 | Read/write | 0 = With record; 1 = Display only | ||||
| HR | 969doc 40970 | CH16 input type | Code 0-40, see manual Table 2. | UINT16 | Read/write | ||||
| HR | 972doc 40973 | CH16 scaling | UINT16 | Read/write | 0 = OFF; 1 = ON | ||||
| HR | 975doc 40976 | CH16 engineering start | Scaled low end; decimal point per 'decimal point' item. | INT16 | Read/write | ||||
| HR | 976doc 40977 | CH16 engineering end | Scaled high end; decimal point per 'decimal point' item. | INT16 | Read/write | ||||
| HR | 977doc 40978 | CH16 decimal point | Code 0-4 (manual Table 5); places the measured value decimal point. | UINT16 | Read/write | ||||
| HR | 985doc 40986 | CH16 recording mode | UINT16 | Read/write | 0 = With record; 1 = Display only | ||||
| HR | 1033doc 41034 | CH17 input type | Code 0-40, see manual Table 2. | UINT16 | Read/write | ||||
| HR | 1036doc 41037 | CH17 scaling | UINT16 | Read/write | 0 = OFF; 1 = ON | ||||
| HR | 1039doc 41040 | CH17 engineering start | Scaled low end; decimal point per 'decimal point' item. | INT16 | Read/write | ||||
| HR | 1040doc 41041 | CH17 engineering end | Scaled high end; decimal point per 'decimal point' item. | INT16 | Read/write | ||||
| HR | 1041doc 41042 | CH17 decimal point | Code 0-4 (manual Table 5); places the measured value decimal point. | UINT16 | Read/write | ||||
| HR | 1049doc 41050 | CH17 recording mode | UINT16 | Read/write | 0 = With record; 1 = Display only | ||||
| HR | 1097doc 41098 | CH18 input type | Code 0-40, see manual Table 2. | UINT16 | Read/write | ||||
| HR | 1100doc 41101 | CH18 scaling | UINT16 | Read/write | 0 = OFF; 1 = ON | ||||
| HR | 1103doc 41104 | CH18 engineering start | Scaled low end; decimal point per 'decimal point' item. | INT16 | Read/write | ||||
| HR | 1104doc 41105 | CH18 engineering end | Scaled high end; decimal point per 'decimal point' item. | INT16 | Read/write | ||||
| HR | 1105doc 41106 | CH18 decimal point | Code 0-4 (manual Table 5); places the measured value decimal point. | UINT16 | Read/write | ||||
| HR | 1113doc 41114 | CH18 recording mode | UINT16 | Read/write | 0 = With record; 1 = Display only |
Notes on this map
- Long (2-register) values such as totalizer counts and totalizing times are left out: the manual says one value spans two registers but never states which word comes first.
- Channel setting blocks are 64 registers apart: CH1 starts at 40001, CH2 at 40065 ... CH18 at 41089.
- Holding registers are read with function 03 and written with 10H; the map lists no single-register write (06).
- Tags, colours, totalizer, alarm, display and network settings are omitted; the manual's Table 2 and Table 5 code lists are not reproduced.
- Measured values carry no decimal point; place it from the channel's decimal point setting.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Shinko Technos GR200 paperless recorder (Modbus RTU / Modbus TCP)
What Modbus registers does the Shinko Technos GR200 paperless recorder (Modbus RTU / Modbus TCP) have?
This map lists 145 registers: 37 input registers, 108 holding registers. 108 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Shinko Technos GR200 paperless recorder (Modbus RTU / Modbus TCP) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Registers are printed as 30xxx/40xxx numbers; the manual says the address in the message is the lower four digits minus 1 (40003 is sent as 0002). The manual's example reads CH2 measured value (30102) at relative address 0065H.
What are the minimum Modbus registers to integrate the Shinko Technos GR200 paperless recorder (Modbus RTU / Modbus TCP)?
Start with IR 100 CH1 measured value (CH1 measured value); IR 130 CH1 status (CH1 status); HR 17 CH1 decimal point (CH1 decimal point); HR 15 CH1 engineering start (CH1 engineering start); HR 16 CH1 engineering end (CH1 engineering end); IR 85 Memory card utilization (Memory card utilization).
How do I enable Modbus control of the Shinko Technos GR200 paperless recorder (Modbus RTU / Modbus TCP)?
Set MODBUS Station No. (0-255; 0 stops communication), speed and parity on the front panel. For Modbus TCP (port 502) also turn the MODBUS TCP/IP function ON (factory OFF) and cycle power.
Where is the official Shinko Technos GR200 paperless recorder (Modbus RTU / Modbus TCP) Modbus documentation?
The source is Instruction Manual Paperless Recorder Communication Functions (RS-485 MODBUS/Ethernet) Type GR200 (GR2CE1), revision 2008-07, published free by Shinko Technos at https://shinko-technos.co.jp/e/manual/english/GR2CE1.pdf.
More Shinko Technos Modbus register maps
- Sensor (digital temperature controller)
Shinko Technos ACD-13A / ACR-13A / ACD-15A / ACR-15A digital indicating controller (C, C5 options)
Shinko ACD/ACR-13A (PID) and ACD/ACR-15A (valve positioning) with the C or C5 communication option; manual No.ACDR1CE8.
Also known as: ACD-13A, ACR-13A, ACD-15A, ACR-15A - Sensor (digital temperature controller)
Shinko Technos ACS-13A digital indicating controller (C5 option)
Shinko ACS-13A with the C5 serial communication option; communication manual No.ACS12CE5.
Also known as: ACS-13A-C5, ACS-13A C5 - Sensor (digital temperature controller)
Shinko Technos ACS2 digital indicating controller (C5, C5W options)
Shinko ACS2 with the C5 or C5W serial option, Shinko protocol / MODBUS RTU command set; manual No.ACS2CE3.
Also known as: ACS2-C5, ACS2-C5W - Sensor (conductivity controller)
Shinko Technos AER-102-ECH conductivity indicating controller (C5 option)
Shinko AER-102-ECH electrical conductivity controller with the C5 RS-485 option; manual No. AER11CECE5.
Also known as: AER-102-ECH - Sensor (digital temperature controller)
Shinko Technos BCS2 / BCR2 / BCD2 digital indicating controller (C5, C5W options)
Shinko BCx2 series (BCS2, BCR2, BCD2) with the C5 or C5W communication option, standard (not JC-allocated) command set; manual No.BCx2CE6.
Also known as: BCS2, BCR2, BCD2, BCx2 - Sensor (digital temperature controller)
Shinko Technos DCL-33A DC digital indicating controller (C5 option)
Shinko DCL-33A DC with the C5 option; communication manual No.DCL3CDCE2.
Also known as: DCL-33A DC, DCL-33A-DC-C5 - Sensor (digital temperature controller)
Shinko Technos DCL-33A digital indicating controller (C5 option)
Shinko DCL-33A with the C5 serial option, plain (non-block) Modbus protocol setting; manual No.DCL32CE3.
Also known as: DCL-33A-C5, DCL-33A C5 - Sensor (digital temperature controller)
Shinko Technos FC series digital indicating controller (C/C5 option, Modbus ASCII)
Shinko FCS-23A, FCR-13A, FCR-23A and FCD-13A with the C or C5 serial option; FCR-15A and FCD-15A have no Modbus (Shinko protocol only). Manual No.FC1CE11.
Also known as: FCS-23A, FCR-13A, FCR-23A, FCD-13A - Sensor (chart recorder)
Shinko Technos HR-700 hybrid recorder (Modbus RTU, firmware 4.00+)
Shinko HR-700 hybrid recorders (multipoint and pen types), body version 4.00 or later, Modbus map version 01; manual No. HR7CE4.
Also known as: HR-700 - Sensor (digital temperature controller)
Shinko Technos JCL-33A digital indicating controller (C5 option)
Shinko JCL-33A with the C5 option, protocol set to plain 'Modbus RTU mode' or 'Modbus ASCII mode' (not the Block Read/Write modes, which use another layout); manual No.JCL3CE3.
Also known as: JCL-33A-C5, JCL-33A C5 - Sensor (digital temperature controller)
Shinko Technos JCS-33A / JCM-33A / JCR-33A / JCD-33A digital indicating controller (C5 option)
Shinko JCx-33A series (JCS, JCM, JCR, JCD-33A) with the C5 option; communication manual No.JC3CE11.
Also known as: JCS-33A, JCM-33A, JCR-33A, JCD-33A, JCx-33A - Sensor (digital temperature controller)
Shinko Technos JIR-301-M digital indicator (C5 option)
Shinko JIR-301-M with the C5 option, plain (non-block) Modbus protocol setting; manual No.JIR32CE4.
Also known as: JIR-301-M-C5, JIR-301-M C5 - Sensor (programmable temperature controller)
Shinko Technos PCA1 programmable controller (C/C5 option)
Shinko PCA1 programmable controllers with the C or C5 serial option; manual No. PCA1CE3.
Also known as: PCA1 - Sensor (programmable temperature controller)
Shinko Technos PCB1 programmable controller (C5W/C5 option)
Shinko PCB1 programmable controllers with the C5W or C5 RS-485 option, native PCB1 command set; manual No. PCB1CE3.
Also known as: PCB1 - Sensor (digital temperature controller)
Shinko Technos PCD-33A programmable controller (C5 option)
Shinko PCD-33A program controller with the C5 RS-485 option; manual printed No.PCD3CE1 2003.02 (file PCD3CE2).
Also known as: PCD-33A-R/M, PCD-33A-S/M - Sensor (signal conditioner)
Shinko Technos SGxL signal conditioner series (Modbus RTU)
Shinko SGxL signal conditioners (SGBL, SGCL, SGDL, SGIL, SGLL, SGML, SGPL, SGRL, SGSL, SGTL, SGUL); SGFL and SGJL are not covered. Manual No.SGxL1CE3.
Also known as: SGBL, SGCL, SGDL, SGIL, SGLL, SGML, SGPL, SGRL, SGSL, SGTL, SGUL - Sensor (digital temperature controller)
Shinko Technos WCL-13A 2-channel digital indicating controller (C5 option)
Shinko WCL-13A two-loop controller with the C5 option; communication manual No.WCL1CE3.
Also known as: WCL-13A-C5, WCL-13A C5
Other valves, actuators & sensors register maps
- Actuator / valve (ventilation damper and VAV actuator)
Swegon REACT damper / VAV actuator (Modbus RTU, 2018 sheet)
Swegon REACT demand-controlled-ventilation dampers with the Modbus actuators named in the sheet (309C-024-150-MB/SL8/ST15/SWE, 227VM-024-**-MB/SWE), sheet dated 2018-11-08.
Also known as: REACT A, REACT Modbus, Swegon REACT damper, 309C-024-150-MB/SL8/ST15/SWE, 227VM-024-MB/SWE - Sensor (humidity / temperature)
Teracom TSH331 IP54 Modbus RTU humidity and temperature sensor
TSH331 per the Teracom TSH331 user manual Rev. 1.5, firmware v1.08 or later.
Also known as: TSH331 - Sensor (dew point probe)
Vaisala DMP Series dew point probes (DMP5, DMP6, DMP7, DMP8) (Modbus RTU)
Vaisala DMP5, DMP6, DMP7 and DMP8 dew point and temperature probes, Modbus RTU interface (user guide M212357EN-F).
Also known as: DMP5, DMP6, DMP7, DMP8, DRYCAP DMP series - Sensor (humidity and temperature transmitter)
Vaisala HMDW110 series humidity and temperature transmitters with TMI110 (Modbus RTU)
HMDW110-series duct, wall and outdoor transmitters and TMI110 ordered with the Modbus RTU option (user guide M211726EN-L).
Also known as: HMD110, HMD112, HMW110, HMW112, HMW112D, HMS110, HMS112, TMW110, TMW112, TMW112D, TMI110 - Sensor transmitter (host for Vaisala probes)
Vaisala Indigo510 / Indigo520 transmitters (Modbus TCP)
Indigo510 and Indigo520 transmitter registers (unit ID 240) over Modbus TCP (user guide M212287EN-AJ).
Also known as: Indigo510, Indigo520, Indigo500 series - Sensor (CO2/humidity wall transmitter)
Vaisala XMW85 CO2, humidity and temperature wall transmitter (Modbus RTU)
XMW85 wall transmitter, Modbus RTU interface (user guide M213257EN-B).
Also known as: XMW85
All valves, actuators & sensors Modbus register maps →
Source: Instruction Manual Paperless Recorder Communication Functions (RS-485 MODBUS/Ethernet) Type GR200 · GR2CE1 · rev. 2008-07. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.