- BCS2 / BCR2 / BCD2 digital indicating controller (C5, C5W options)
Sensor (digital temperature controller) · Modbus register map
Shinko Technos BCS2 / BCR2 / BCD2 digital indicating controller (C5, C5W options) Modbus register map
Updated 17 November 2026
The BCx2 series are PID temperature controllers sharing one command set. With the C5/C5W option they talk Shinko protocol, Modbus ASCII or Modbus RTU on RS485; every item is a 16-bit holding register. This map covers the setup and PID settings, SV memories, event outputs, heater burnout and loop break alarms, run modes, PV, MV, current SV, heater current and the status words.
This page lists 91 Modbus registers for the Shinko Technos BCS2 / BCR2 / BCD2 digital indicating controller (C5, C5W options) — 78 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Shinko Technos’s own free documentation (linked below) and checked against it.
- Manufacturer
- Shinko Technos
- Model
- BCS2 / BCR2 / BCD2 digital indicating controller (C5, C5W options)
- Equipment type
- Sensor (digital temperature controller)
- Registers
- 91 (78 writable)
- Transport
- Modbus RTU, Modbus ASCII
- Default unit ID
- 0
- Default serial
- 9600 baud, 7E1
- Documented addressing
- hexadecimal, 0-based
- Also known as
- BCS2, BCR2, BCD2, BCx2
Integration notes: Shinko Technos BCS2 / BCR2 / BCD2 digital indicating controller (C5, C5W options)
In Engineering mode 1 choose MODBUS RTU, an 8-bit data format and a non-zero instrument number. Then poll PV 0100H, OUT1 MV 0101H and status flags 010DH/010EH; write SV1 at 0001H.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 256 | PV | INT16 | Process value | Read |
| HR 1 | SV1 | INT16 | Set value SV1 | Read/write |
| HR 257 | OUT1 MV | INT16 | OUT1 manipulated value | Read |
| HR 269 | Status flag 1 | BITMAP16 | Output and alarm status | Read |
| HR 270 | Status flag 2 | BITMAP16 | Run mode status | Read |
| HR 5 | Decimal point place | INT16 | Decimal point for scaling | Read/write |
Enable Modbus control & writes
Requires the C5 or C5W option. Hold the up and down keys for 3 s in RUN mode to enter Engineering mode 1, then set Communication protocol to MODBUS RTU (not the JC command allocated variant), instrument number, speed, data bit/parity and stop bit.
Byte order & addressing
- Factory data format is 7 bits/Even; Modbus RTU needs one of the 8-bit choices.
- Instrument number defaults to 0, the Modbus broadcast address; set 1-95.
- Response delay time (default 10 ms) adds to every reply.
Network setup
- Factory defaults: Shinko protocol, instrument 0, 9600 bps, 7 bits/Even, 1 stop bit, response delay 10 ms.
- Speeds 9600, 19200 or 38400 bps.
Watch out for
- Writing 1234H to 00FEH returns every setting to factory default.
- Settings are stored in non-volatile memory; avoid cyclic writes.
Shinko Technos BCS2 / BCR2 / BCD2 digital indicating controller (C5, C5W options) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 1doc 0001H | SV1 | Set value. Decimal point ignored: Raw integer; apply the decimal point setting. | INT16 | Read/write | ||||
| HR | 2doc 0002H | Input type | INT16 | Read/write | 0 = K -200 to 1370; 1 = K -200.0 to 400.0; 2 = J -200 to 1000; 3 = R 0 to 1760; 4 = S 0 to 1760; 5 = B 0 to 1820; 6 = E -200 to 800; 7 = T -200.0 to 400.0; 8 = N -200 to 1300; 9 = PL-II 0 to 1390; 10 = C (W/Re5-26) 0 to 2315; 11 = Pt100 -200.0 to 850.0; 12 = JPt100 -200.0 to 500.0; 13 = Pt100 -200 to 850; 14 = JPt100 -200 to 500; 15 = K -328 to 2498; 16 = K -328.0 to 752.0; 17 = J -328 to 1832; 18 = R 32 to 3200; 19 = S 32 to 3200; 20 = B 32 to 3308; 21 = E -328 to 1472; 22 = T -328.0 to 752.0; 23 = N -328 to 2372; 24 = PL-II 32 to 2534; 25 = C (W/Re5-26) 32 to 4199; 26 = Pt100 -328.0 to 1562.0; 27 = JPt100 -328.0 to 932.0; 28 = Pt100 -328 to 1562; 29 = JPt100 -328 to 932; 30 = 4-20 mA DC -2000 to 10000; 31 = 0-20 mA DC -2000 to 10000; 32 = 0-1 V DC -2000 to 10000; 33 = 0-5 V DC -2000 to 10000; 34 = 1-5 V DC -2000 to 10000; 35 = 0-10 V DC -2000 to 10000 | ||||
| HR | 3doc 0003H | Scaling high limit | Decimal point ignored: Raw integer; apply the decimal point setting. | INT16 | Read/write | ||||
| HR | 4doc 0004H | Scaling low limit | Decimal point ignored: Raw integer; apply the decimal point setting. | INT16 | Read/write | ||||
| HR | 5doc 0005H | Decimal point place | INT16 | Read/write | 0 = No decimal point; 1 = 1 decimal place; 2 = 2 decimal places; 3 = 3 decimal places | ||||
| HR | 6doc 0006H | Event output EV1 allocation | INT16 | Read/write | 0 = No event; 1 = High limit alarm; 2 = Low limit alarm; 3 = High/Low limits alarm; 4 = High/Low limits independent alarm; 5 = High/Low limit range alarm; 6 = High/Low limit range independent alarm; 7 = Process high alarm; 8 = Process low alarm; 9 = High limit with standby; 10 = Low limit with standby; 11 = High/Low limits with standby; 12 = High/Low limits with standby independent; 13 = Heater burnout alarm output; 14 = Loop break alarm output; 15 = Time signal output; 16 = Output during AT; 17 = Pattern end output; 18 = Output by communication command | ||||
| HR | 7doc 0007H | Event output EV2 allocation | INT16 | Read/write | 0 = No event; 1 = High limit alarm; 2 = Low limit alarm; 3 = High/Low limits alarm; 4 = High/Low limits independent alarm; 5 = High/Low limit range alarm; 6 = High/Low limit range independent alarm; 7 = Process high alarm; 8 = Process low alarm; 9 = High limit with standby; 10 = Low limit with standby; 11 = High/Low limits with standby; 12 = High/Low limits with standby independent; 13 = Heater burnout alarm output; 14 = Loop break alarm output; 15 = Time signal output; 16 = Output during AT; 17 = Pattern end output; 18 = Output by communication command; 19 = Heating/cooling control relay contact output | ||||
| HR | 11doc 000BH | Transmission output type | INT16 | Read/write | 0 = PV; 1 = SV; 2 = MV; 3 = DV | ||||
| HR | 12doc 000CH | Transmission output high limit | Decimal point ignored: Raw integer; apply the decimal point setting. | INT16 | Read/write | ||||
| HR | 13doc 000DH | Transmission output low limit | Decimal point ignored: Raw integer; apply the decimal point setting. | INT16 | Read/write | ||||
| HR | 14doc 000EH | SV1 (memory) | Set value memory 1. Decimal point ignored: Raw integer; apply the decimal point setting. | INT16 | Read/write | ||||
| HR | 15doc 000FH | SV2 (memory) | Set value memory 2. Decimal point ignored: Raw integer; apply the decimal point setting. | INT16 | Read/write | ||||
| HR | 16doc 0010H | SV3 (memory) | Set value memory 3. Decimal point ignored: Raw integer; apply the decimal point setting. | INT16 | Read/write | ||||
| HR | 17doc 0011H | SV4 (memory) | Set value memory 4. Decimal point ignored: Raw integer; apply the decimal point setting. | INT16 | Read/write | ||||
| HR | 18doc 0012H | EV1 alarm value | Decimal point ignored: Raw integer; apply the decimal point setting. | INT16 | Read/write | ||||
| HR | 19doc 0013H | EV1 high limit alarm value | Decimal point ignored: Raw integer; apply the decimal point setting. | INT16 | Read/write | ||||
| HR | 20doc 0014H | EV2 alarm value | Decimal point ignored: Raw integer; apply the decimal point setting. | INT16 | Read/write | ||||
| HR | 21doc 0015H | EV2 high limit alarm value | Decimal point ignored: Raw integer; apply the decimal point setting. | INT16 | Read/write | ||||
| HR | 28doc 001CH | Heater burnout alarm 1 value | Decimal point ignored: Raw integer; apply the decimal point setting. | INT16 | Read/write | ||||
| HR | 29doc 001DH | Heater burnout alarm 2 value | Decimal point ignored: Raw integer; apply the decimal point setting. | INT16 | Read/write | ||||
| HR | 30doc 001EH | Loop break alarm time | INT16 | Read/write | |||||
| HR | 31doc 001FH | Loop break alarm band | Decimal point ignored: Raw integer; apply the decimal point setting. | INT16 | Read/write | ||||
| HR | 32doc 0020H | Event input DI1 allocation | INT16 | Read/write | 0 = No event; 1 = Set value memory; 2 = Control ON/OFF; 3 = Direct/Reverse action; 4 = Preset output 1 ON/OFF; 5 = Preset output 2 ON/OFF; 6 = Auto/Manual control; 7 = Remote/Local; 8 = Program control RUN/STOP; 9 = Program control holding/not holding; 10 = Program control advance; 11 = Integral action holding | ||||
| HR | 33doc 0021H | Event input DI2 allocation | INT16 | Read/write | 0 = No event; 1 = Set value memory; 2 = Control ON/OFF; 3 = Direct/Reverse action; 4 = Preset output 1 ON/OFF; 5 = Preset output 2 ON/OFF; 6 = Auto/Manual control; 7 = Remote/Local; 8 = Program control RUN/STOP; 9 = Program control holding/not holding; 10 = Program control advance; 11 = Integral action holding | ||||
| HR | 36doc 0024H | EV1 alarm value 0 enabled/disabled | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 37doc 0025H | EV1 alarm hysteresis | Decimal point ignored: Raw integer; apply the decimal point setting. | INT16 | Read/write | ||||
| HR | 38doc 0026H | EV1 alarm delay time | INT16 | Read/write | |||||
| HR | 39doc 0027H | EV1 alarm energized/de-energized | INT16 | Read/write | 0 = Energized; 1 = De-energized | ||||
| HR | 40doc 0028H | EV2 alarm value 0 enabled/disabled | INT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 41doc 0029H | EV2 alarm hysteresis | Decimal point ignored: Raw integer; apply the decimal point setting. | INT16 | Read/write | ||||
| HR | 42doc 002AH | EV2 alarm delay time | INT16 | Read/write | |||||
| HR | 43doc 002BH | EV2 alarm energized/de-energized | INT16 | Read/write | 0 = Energized; 1 = De-energized | ||||
| HR | 60doc 003CH | OUT1 proportional band | Decimal point ignored: Raw integer; apply the decimal point setting. | INT16 | Read/write | ||||
| HR | 61doc 003DH | Integral time | INT16 | Read/write | |||||
| HR | 62doc 003EH | Derivative time | INT16 | Read/write | |||||
| HR | 63doc 003FH | ARW | Anti-reset windup. | INT16 | Read/write | ||||
| HR | 64doc 0040H | Manual reset | Decimal point ignored: Raw integer; apply the decimal point setting. | INT16 | Read/write | ||||
| HR | 65doc 0041H | OUT1 proportional cycle | INT16 | Read/write | |||||
| HR | 66doc 0042H | OUT1 ON/OFF hysteresis | Decimal point ignored: Raw integer; apply the decimal point setting. | INT16 | Read/write | ||||
| HR | 67doc 0043H | OUT1 high limit | INT16 | Read/write | |||||
| HR | 68doc 0044H | OUT1 low limit | INT16 | Read/write | |||||
| HR | 69doc 0045H | OUT1 rate-of-change | INT16 | Read/write | |||||
| HR | 70doc 0046H | OUT2 cooling method | INT16 | Read/write | 0 = Air cooling; 1 = Oil cooling; 2 = Water cooling | ||||
| HR | 71doc 0047H | OUT2 proportional band | Decimal point ignored: Raw integer; apply the decimal point setting. | INT16 | Read/write | ||||
| HR | 72doc 0048H | OUT2 proportional cycle | INT16 | Read/write | |||||
| HR | 73doc 0049H | OUT2 ON/OFF hysteresis | Decimal point ignored: Raw integer; apply the decimal point setting. | INT16 | Read/write | ||||
| HR | 74doc 004AH | OUT2 high limit | INT16 | Read/write | |||||
| HR | 75doc 004BH | OUT2 low limit | INT16 | Read/write | |||||
| HR | 76doc 004CH | Overlap band/dead band | Decimal point ignored: Raw integer; apply the decimal point setting. | INT16 | Read/write | ||||
| HR | 77doc 004DH | Direct/reverse action | INT16 | Read/write | 0 = Reverse (heating); 1 = Direct (cooling) | ||||
| HR | 78doc 004EH | Set value lock | INT16 | Read/write | 0 = Unlock; 1 = Lock 1; 2 = Lock 2; 3 = Lock 3; 4 = Lock 4; 5 = Lock 5 | ||||
| HR | 79doc 004FH | Sensor correction coefficient | Decimal point ignored: Raw integer; apply the decimal point setting. | INT16 | Read/write | ||||
| HR | 80doc 0050H | Sensor correction | Decimal point ignored: Raw integer; apply the decimal point setting. | INT16 | Read/write | ||||
| HR | 81doc 0051H | PV filter time constant | Decimal point ignored: Raw integer; apply the decimal point setting. | INT16 | Read/write | ||||
| HR | 82doc 0052H | Response delay time | Comm response delay. | INT16 | Read/write | ||||
| HR | 83doc 0053H | SVTC bias | Decimal point ignored: Raw integer; apply the decimal point setting. | INT16 | Read/write | ||||
| HR | 84doc 0054H | External setting input high limit | Decimal point ignored: Raw integer; apply the decimal point setting. | INT16 | Read/write | ||||
| HR | 85doc 0055H | External setting input low limit | Decimal point ignored: Raw integer; apply the decimal point setting. | INT16 | Read/write | ||||
| HR | 86doc 0056H | Remote bias | Decimal point ignored: Raw integer; apply the decimal point setting. | INT16 | Read/write | ||||
| HR | 87doc 0057H | SV rise/fall rate start type | INT16 | Read/write | 0 = SV start; 1 = PV start | ||||
| HR | 88doc 0058H | SV rise rate | Decimal point ignored: Raw integer; apply the decimal point setting. | INT16 | Read/write | ||||
| HR | 89doc 0059H | SV fall rate | Decimal point ignored: Raw integer; apply the decimal point setting. | INT16 | Read/write | ||||
| HR | 90doc 005AH | Indication when control output OFF | INT16 | Read/write | 0 = OFF indication; 1 = No indication; 2 = PV indication; 3 = PV indication + any alarm active | ||||
| HR | 91doc 005BH | AT bias | Decimal point ignored: Raw integer; apply the decimal point setting. | INT16 | Read/write | ||||
| HR | 92doc 005CH | Output status when input errors occur | INT16 | Read/write | 0 = Output OFF; 1 = Output ON | ||||
| HR | 93doc 005DH | Auto/manual after power ON | INT16 | Read/write | 0 = Automatic control; 1 = Manual control | ||||
| HR | 224doc 00E0H | OUT/OFF key function | INT16 | Read/write | 0 = Control output OFF function; 1 = Auto/Manual control; 2 = Program control | ||||
| HR | 225doc 00E1H | Remote/local | INT16 | Read/write | 0 = Local; 1 = Remote | ||||
| HR | 226doc 00E2H | Output OFF / Auto-Manual / Program RUN | Meaning follows the OUT/OFF key function (00E0H); see notes. | INT16 | Read/write | ||||
| HR | 227doc 00E3H | Program control holding | INT16 | Read/write | 0 = Not holding; 1 = Holding | ||||
| HR | 228doc 00E4H | Output by communication command | BITMAP16 | Read/write | bit 0 = EV1 output on; bit 1 = EV2 output on | ||||
| HR | 229doc 00E5H | Manual control MV | INT16 | Read/write | |||||
| HR | 230doc 00E6H | AT/Auto-reset perform/cancel | INT16 | Read/write | 0 = Cancel AT / AT on startup / auto-reset; 1 = AT/Auto-reset perform; 2 = AT on startup perform | ||||
| HR | 231doc 00E7H | Controller/converter | INT16 | Read/write | 0 = Controller; 1 = Converter | ||||
| HR | 232doc 00E8H | AT gain | Decimal point ignored: Raw integer; apply the decimal point setting. | INT16 | Read/write | ||||
| HR | 233doc 00E9H | Program control advance | INT16 | Write | 1 = Advance perform | ||||
| HR | 254doc 00FEH | Data clear | Resets all settings to factory defaults. | INT16 | Write | 4660 = Clear data (1234H) | |||
| HR | 255doc 00FFH | Key operation change flag clearing | INT16 | Write | 1 = Clear the flag | ||||
| HR | 256doc 0100H | PV | Process value. Decimal point ignored: Raw integer; apply the decimal point setting. | INT16 | Read | ||||
| HR | 257doc 0101H | OUT1 MV | Decimal point ignored: Raw integer; apply the decimal point setting. | INT16 | Read | ||||
| HR | 258doc 0102H | OUT2 MV | Decimal point ignored: Raw integer; apply the decimal point setting. | INT16 | Read | ||||
| HR | 259doc 0103H | Current SV | Decimal point ignored: Raw integer; apply the decimal point setting. | INT16 | Read | ||||
| HR | 260doc 0104H | Set value memory number | INT16 | Read | |||||
| HR | 261doc 0105H | Remaining time (program) | INT16 | Read | |||||
| HR | 263doc 0107H | Step number (program) | INT16 | Read | |||||
| HR | 264doc 0108H | Number of repetitions (program) | INT16 | Read | |||||
| HR | 265doc 0109H | CT1 current value | Decimal point ignored: Raw integer; apply the decimal point setting. | INT16 | Read | ||||
| HR | 266doc 010AH | CT2 current value | Decimal point ignored: Raw integer; apply the decimal point setting. | INT16 | Read | ||||
| HR | 268doc 010CH | Key operation changed item | Data item last changed from the keypad. | INT16 | Read | ||||
| HR | 269doc 010DH | Status flag 1 | BITMAP16 | Read | bit 0 = OUT1 output on; bit 1 = OUT2 output on; bit 2 = EV1 output on; bit 3 = EV2 output on; bit 9 = AT/auto-reset/AT on startup performing; bit 10 = 1 = AT on startup, 0 = AT/auto-reset; bit 11 = Heater burnout alarm; bit 12 = Loop break alarm; bit 13 = Overscale; bit 14 = Underscale; bit 15 = Settings changed by keypad | ||||
| HR | 270doc 010EH | Status flag 2 | BITMAP16 | Read | bit 0 = DI1 input on; bit 1 = DI2 input on; bit 5 = Program control RUN (unit status 1); bit 6 = Setting mode (unit status 2); bit 7 = Warm-up; bit 8 = USB connection; bit 9 = Control output OFF; bit 10 = Manual control; bit 11 = Program control mode; bit 12 = Program control RUN; bit 13 = Wait function on; bit 14 = Hold function on; bit 15 = Pattern end function on |
Notes on this map
- This map is for the standard 'MODBUS RTU' / 'MODBUS ASCII' protocol settings. The 'JC command allocated' protocol settings switch the unit to the older JC-series layout (section 7.2) and are not covered.
- All data are 16-bit; negatives are two's complement. Items marked 'decimal point ignored' are sent as whole numbers; apply the decimal point place (0005H).
- Read-only items from 0100H can be read with function 03 or 04.
- 00E2H means control output ON/OFF, auto/manual, or program STOP/RUN depending on the OUT/OFF key function in 00E0H; in each case 0 is the first state (output ON / automatic / STOP) and 1 the second (output OFF / manual / RUN).
- The table lists SV1 at both 0001H and 000EH (followed by SV2-SV4 at 000FH-0011H).
- Left out: program-pattern settings (005EH-0077H), unit model and error status words, and section 8 SV digital transmission.
- Units of PID times, cycles and MV are not printed in the command table.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Shinko Technos BCS2 / BCR2 / BCD2 digital indicating controller (C5, C5W options)
What Modbus registers does the Shinko Technos BCS2 / BCR2 / BCD2 digital indicating controller (C5, C5W options) have?
This map lists 91 registers: 91 holding registers. 78 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Shinko Technos BCS2 / BCR2 / BCD2 digital indicating controller (C5, C5W options) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Registers are listed as hex data items (0001H) that go into the request unchanged. The manual adds that the matching Modicon holding-register number is the item in decimal plus 40001 (0001H = 40002).
What are the minimum Modbus registers to integrate the Shinko Technos BCS2 / BCR2 / BCD2 digital indicating controller (C5, C5W options)?
Start with HR 256 PV (Process value); HR 1 SV1 (Set value SV1); HR 257 OUT1 MV (OUT1 manipulated value); HR 269 Status flag 1 (Output and alarm status); HR 270 Status flag 2 (Run mode status); HR 5 Decimal point place (Decimal point for scaling).
How do I enable Modbus control of the Shinko Technos BCS2 / BCR2 / BCD2 digital indicating controller (C5, C5W options)?
Requires the C5 or C5W option. Hold the up and down keys for 3 s in RUN mode to enter Engineering mode 1, then set Communication protocol to MODBUS RTU (not the JC command allocated variant), instrument number, speed, data bit/parity and stop bit.
Where is the official Shinko Technos BCS2 / BCR2 / BCD2 digital indicating controller (C5, C5W options) Modbus documentation?
The source is Communication Instruction Manual BCD2, BCR2, BCS2 (C5W, C5) (No.BCx2CE6), revision 2019-12, published free by Shinko Technos at https://shinko-technos.co.jp/e/manual/english/BCx2CE6.pdf.
More Shinko Technos Modbus register maps
- Sensor (digital temperature controller)
Shinko Technos ACD-13A / ACR-13A / ACD-15A / ACR-15A digital indicating controller (C, C5 options)
Shinko ACD/ACR-13A (PID) and ACD/ACR-15A (valve positioning) with the C or C5 communication option; manual No.ACDR1CE8.
Also known as: ACD-13A, ACR-13A, ACD-15A, ACR-15A - Sensor (digital temperature controller)
Shinko Technos ACS-13A digital indicating controller (C5 option)
Shinko ACS-13A with the C5 serial communication option; communication manual No.ACS12CE5.
Also known as: ACS-13A-C5, ACS-13A C5 - Sensor (digital temperature controller)
Shinko Technos ACS2 digital indicating controller (C5, C5W options)
Shinko ACS2 with the C5 or C5W serial option, Shinko protocol / MODBUS RTU command set; manual No.ACS2CE3.
Also known as: ACS2-C5, ACS2-C5W - Sensor (conductivity controller)
Shinko Technos AER-102-ECH conductivity indicating controller (C5 option)
Shinko AER-102-ECH electrical conductivity controller with the C5 RS-485 option; manual No. AER11CECE5.
Also known as: AER-102-ECH - Sensor (digital temperature controller)
Shinko Technos DCL-33A DC digital indicating controller (C5 option)
Shinko DCL-33A DC with the C5 option; communication manual No.DCL3CDCE2.
Also known as: DCL-33A DC, DCL-33A-DC-C5 - Sensor (digital temperature controller)
Shinko Technos DCL-33A digital indicating controller (C5 option)
Shinko DCL-33A with the C5 serial option, plain (non-block) Modbus protocol setting; manual No.DCL32CE3.
Also known as: DCL-33A-C5, DCL-33A C5 - Sensor (digital temperature controller)
Shinko Technos FC series digital indicating controller (C/C5 option, Modbus ASCII)
Shinko FCS-23A, FCR-13A, FCR-23A and FCD-13A with the C or C5 serial option; FCR-15A and FCD-15A have no Modbus (Shinko protocol only). Manual No.FC1CE11.
Also known as: FCS-23A, FCR-13A, FCR-23A, FCD-13A - Sensor (paperless recorder)
Shinko Technos GR200 paperless recorder (Modbus RTU / Modbus TCP)
Shinko GR200 paperless recorder with RS-485 Modbus RTU or Ethernet Modbus TCP; manual GR2CE1.
Also known as: GR200 - Sensor (chart recorder)
Shinko Technos HR-700 hybrid recorder (Modbus RTU, firmware 4.00+)
Shinko HR-700 hybrid recorders (multipoint and pen types), body version 4.00 or later, Modbus map version 01; manual No. HR7CE4.
Also known as: HR-700 - Sensor (digital temperature controller)
Shinko Technos JCL-33A digital indicating controller (C5 option)
Shinko JCL-33A with the C5 option, protocol set to plain 'Modbus RTU mode' or 'Modbus ASCII mode' (not the Block Read/Write modes, which use another layout); manual No.JCL3CE3.
Also known as: JCL-33A-C5, JCL-33A C5 - Sensor (digital temperature controller)
Shinko Technos JCS-33A / JCM-33A / JCR-33A / JCD-33A digital indicating controller (C5 option)
Shinko JCx-33A series (JCS, JCM, JCR, JCD-33A) with the C5 option; communication manual No.JC3CE11.
Also known as: JCS-33A, JCM-33A, JCR-33A, JCD-33A, JCx-33A - Sensor (digital temperature controller)
Shinko Technos JIR-301-M digital indicator (C5 option)
Shinko JIR-301-M with the C5 option, plain (non-block) Modbus protocol setting; manual No.JIR32CE4.
Also known as: JIR-301-M-C5, JIR-301-M C5 - Sensor (programmable temperature controller)
Shinko Technos PCA1 programmable controller (C/C5 option)
Shinko PCA1 programmable controllers with the C or C5 serial option; manual No. PCA1CE3.
Also known as: PCA1 - Sensor (programmable temperature controller)
Shinko Technos PCB1 programmable controller (C5W/C5 option)
Shinko PCB1 programmable controllers with the C5W or C5 RS-485 option, native PCB1 command set; manual No. PCB1CE3.
Also known as: PCB1 - Sensor (digital temperature controller)
Shinko Technos PCD-33A programmable controller (C5 option)
Shinko PCD-33A program controller with the C5 RS-485 option; manual printed No.PCD3CE1 2003.02 (file PCD3CE2).
Also known as: PCD-33A-R/M, PCD-33A-S/M - Sensor (signal conditioner)
Shinko Technos SGxL signal conditioner series (Modbus RTU)
Shinko SGxL signal conditioners (SGBL, SGCL, SGDL, SGIL, SGLL, SGML, SGPL, SGRL, SGSL, SGTL, SGUL); SGFL and SGJL are not covered. Manual No.SGxL1CE3.
Also known as: SGBL, SGCL, SGDL, SGIL, SGLL, SGML, SGPL, SGRL, SGSL, SGTL, SGUL - Sensor (digital temperature controller)
Shinko Technos WCL-13A 2-channel digital indicating controller (C5 option)
Shinko WCL-13A two-loop controller with the C5 option; communication manual No.WCL1CE3.
Also known as: WCL-13A-C5, WCL-13A C5
Other temperature & process controllers register maps
- Sensor (digital indicating temperature controller)
Yokogawa UTAdvanced UT55A / UT52A digital indicating controller
Yokogawa UT55A and UT52A one- or two-loop controllers with RS-485 or Ethernet communication; D-register map from IM 05P07A01-01EN chapter 6 (UP55A program items excluded).
Also known as: UT55A, UT52A - Sensor (process / temperature controller)
Novus N20K48 modular process controller (Modbus RTU)
N20K48 controllers with the optional RS-485 interface, communication protocol V1.0x.
Also known as: Novus N20K48, N20K48 modular controller - Sensor (digital indicating temperature controller)
Yokogawa UTAdvanced UT35A / UT32A digital indicating controller
Yokogawa UT35A and UT32A single-loop controllers with RS-485 or Ethernet communication; D-register map from IM 05P07A01-01EN chapter 8 (UT32A-D loop 2 and UP35A/UP32A program items excluded).
Also known as: UT35A, UT32A, UT35A/MDL, UT32A/MDL - Sensor (digital temperature controller)
Fuji Electric PXR micro controller X (RS-485 Modbus option)
Fuji Electric PXR series controllers with the RS-485 Modbus communication option; manual INP-TN512642d-E.
Also known as: PXR3, PXR4, PXR5, PXR9 - Sensor (program temperature controller)
Yokogawa UTAdvanced UP55A program controller
Yokogawa UP55A program controller with RS-485 or Ethernet communication; D-register map from IM 05P07A01-01EN chapter 6 (UP55A column).
Also known as: UP55A - Sensor (digital process controller)
Fuji Electric PXH digital controller (Modbus RTU, monitoring map)
Fuji Electric PXH digital controllers on the RS-485 Modbus port; read-only monitoring registers from manual INP-TN514207c-E.
Also known as: PXH
All temperature & process controllers Modbus register maps →
Source: Communication Instruction Manual BCD2, BCR2, BCS2 (C5W, C5) · No.BCx2CE6 · rev. 2019-12. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.