Sensor (digital temperature controller) · Modbus register map

Shinko Technos BCS2 / BCR2 / BCD2 digital indicating controller (C5, C5W options) Modbus register map

Updated 17 November 2026

Short answer

The BCx2 series are PID temperature controllers sharing one command set. With the C5/C5W option they talk Shinko protocol, Modbus ASCII or Modbus RTU on RS485; every item is a 16-bit holding register. This map covers the setup and PID settings, SV memories, event outputs, heater burnout and loop break alarms, run modes, PV, MV, current SV, heater current and the status words.

This page lists 91 Modbus registers for the Shinko Technos BCS2 / BCR2 / BCD2 digital indicating controller (C5, C5W options) — 78 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Shinko Technos’s own free documentation (linked below) and checked against it.

Manufacturer
Shinko Technos
Model
BCS2 / BCR2 / BCD2 digital indicating controller (C5, C5W options)
Equipment type
Sensor (digital temperature controller)
Registers
91 (78 writable)
Transport
Modbus RTU, Modbus ASCII
Default unit ID
0
Default serial
9600 baud, 7E1
Documented addressing
hexadecimal, 0-based
Also known as
BCS2, BCR2, BCD2, BCx2
Source document
Communication Instruction Manual BCD2, BCR2, BCS2 (C5W, C5) · No.BCx2CE6 · rev. 2019-12
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Shinko Technos BCS2 / BCR2 / BCD2 digital indicating controller (C5, C5W options)

Integration in brief

In Engineering mode 1 choose MODBUS RTU, an 8-bit data format and a non-zero instrument number. Then poll PV 0100H, OUT1 MV 0101H and status flags 010DH/010EH; write SV1 at 0001H.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 256PVINT16Process valueRead
HR 1SV1INT16Set value SV1Read/write
HR 257OUT1 MVINT16OUT1 manipulated valueRead
HR 269Status flag 1BITMAP16Output and alarm statusRead
HR 270Status flag 2BITMAP16Run mode statusRead
HR 5Decimal point placeINT16Decimal point for scalingRead/write

Enable Modbus control & writes

Requires the C5 or C5W option. Hold the up and down keys for 3 s in RUN mode to enter Engineering mode 1, then set Communication protocol to MODBUS RTU (not the JC command allocated variant), instrument number, speed, data bit/parity and stop bit.

Byte order & addressing

Network setup

Watch out for

Shinko Technos BCS2 / BCR2 / BCD2 digital indicating controller (C5, C5W options) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

91 of 91 shown
Shinko Technos BCS2 / BCR2 / BCD2 digital indicating controller (C5, C5W options) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR1doc 0001HSV1Set value. Decimal point ignored: Raw integer; apply the decimal point setting.INT16Read/write
HR2doc 0002HInput typeINT16Read/write0 = K -200 to 1370; 1 = K -200.0 to 400.0; 2 = J -200 to 1000; 3 = R 0 to 1760; 4 = S 0 to 1760; 5 = B 0 to 1820; 6 = E -200 to 800; 7 = T -200.0 to 400.0; 8 = N -200 to 1300; 9 = PL-II 0 to 1390; 10 = C (W/Re5-26) 0 to 2315; 11 = Pt100 -200.0 to 850.0; 12 = JPt100 -200.0 to 500.0; 13 = Pt100 -200 to 850; 14 = JPt100 -200 to 500; 15 = K -328 to 2498; 16 = K -328.0 to 752.0; 17 = J -328 to 1832; 18 = R 32 to 3200; 19 = S 32 to 3200; 20 = B 32 to 3308; 21 = E -328 to 1472; 22 = T -328.0 to 752.0; 23 = N -328 to 2372; 24 = PL-II 32 to 2534; 25 = C (W/Re5-26) 32 to 4199; 26 = Pt100 -328.0 to 1562.0; 27 = JPt100 -328.0 to 932.0; 28 = Pt100 -328 to 1562; 29 = JPt100 -328 to 932; 30 = 4-20 mA DC -2000 to 10000; 31 = 0-20 mA DC -2000 to 10000; 32 = 0-1 V DC -2000 to 10000; 33 = 0-5 V DC -2000 to 10000; 34 = 1-5 V DC -2000 to 10000; 35 = 0-10 V DC -2000 to 10000
HR3doc 0003HScaling high limitDecimal point ignored: Raw integer; apply the decimal point setting.INT16Read/write
HR4doc 0004HScaling low limitDecimal point ignored: Raw integer; apply the decimal point setting.INT16Read/write
HR5doc 0005HDecimal point placeINT16Read/write0 = No decimal point; 1 = 1 decimal place; 2 = 2 decimal places; 3 = 3 decimal places
HR6doc 0006HEvent output EV1 allocationINT16Read/write0 = No event; 1 = High limit alarm; 2 = Low limit alarm; 3 = High/Low limits alarm; 4 = High/Low limits independent alarm; 5 = High/Low limit range alarm; 6 = High/Low limit range independent alarm; 7 = Process high alarm; 8 = Process low alarm; 9 = High limit with standby; 10 = Low limit with standby; 11 = High/Low limits with standby; 12 = High/Low limits with standby independent; 13 = Heater burnout alarm output; 14 = Loop break alarm output; 15 = Time signal output; 16 = Output during AT; 17 = Pattern end output; 18 = Output by communication command
HR7doc 0007HEvent output EV2 allocationINT16Read/write0 = No event; 1 = High limit alarm; 2 = Low limit alarm; 3 = High/Low limits alarm; 4 = High/Low limits independent alarm; 5 = High/Low limit range alarm; 6 = High/Low limit range independent alarm; 7 = Process high alarm; 8 = Process low alarm; 9 = High limit with standby; 10 = Low limit with standby; 11 = High/Low limits with standby; 12 = High/Low limits with standby independent; 13 = Heater burnout alarm output; 14 = Loop break alarm output; 15 = Time signal output; 16 = Output during AT; 17 = Pattern end output; 18 = Output by communication command; 19 = Heating/cooling control relay contact output
HR11doc 000BHTransmission output typeINT16Read/write0 = PV; 1 = SV; 2 = MV; 3 = DV
HR12doc 000CHTransmission output high limitDecimal point ignored: Raw integer; apply the decimal point setting.INT16Read/write
HR13doc 000DHTransmission output low limitDecimal point ignored: Raw integer; apply the decimal point setting.INT16Read/write
HR14doc 000EHSV1 (memory)Set value memory 1. Decimal point ignored: Raw integer; apply the decimal point setting.INT16Read/write
HR15doc 000FHSV2 (memory)Set value memory 2. Decimal point ignored: Raw integer; apply the decimal point setting.INT16Read/write
HR16doc 0010HSV3 (memory)Set value memory 3. Decimal point ignored: Raw integer; apply the decimal point setting.INT16Read/write
HR17doc 0011HSV4 (memory)Set value memory 4. Decimal point ignored: Raw integer; apply the decimal point setting.INT16Read/write
HR18doc 0012HEV1 alarm valueDecimal point ignored: Raw integer; apply the decimal point setting.INT16Read/write
HR19doc 0013HEV1 high limit alarm valueDecimal point ignored: Raw integer; apply the decimal point setting.INT16Read/write
HR20doc 0014HEV2 alarm valueDecimal point ignored: Raw integer; apply the decimal point setting.INT16Read/write
HR21doc 0015HEV2 high limit alarm valueDecimal point ignored: Raw integer; apply the decimal point setting.INT16Read/write
HR28doc 001CHHeater burnout alarm 1 valueDecimal point ignored: Raw integer; apply the decimal point setting.INT16Read/write
HR29doc 001DHHeater burnout alarm 2 valueDecimal point ignored: Raw integer; apply the decimal point setting.INT16Read/write
HR30doc 001EHLoop break alarm timeINT16Read/write
HR31doc 001FHLoop break alarm bandDecimal point ignored: Raw integer; apply the decimal point setting.INT16Read/write
HR32doc 0020HEvent input DI1 allocationINT16Read/write0 = No event; 1 = Set value memory; 2 = Control ON/OFF; 3 = Direct/Reverse action; 4 = Preset output 1 ON/OFF; 5 = Preset output 2 ON/OFF; 6 = Auto/Manual control; 7 = Remote/Local; 8 = Program control RUN/STOP; 9 = Program control holding/not holding; 10 = Program control advance; 11 = Integral action holding
HR33doc 0021HEvent input DI2 allocationINT16Read/write0 = No event; 1 = Set value memory; 2 = Control ON/OFF; 3 = Direct/Reverse action; 4 = Preset output 1 ON/OFF; 5 = Preset output 2 ON/OFF; 6 = Auto/Manual control; 7 = Remote/Local; 8 = Program control RUN/STOP; 9 = Program control holding/not holding; 10 = Program control advance; 11 = Integral action holding
HR36doc 0024HEV1 alarm value 0 enabled/disabledINT16Read/write0 = Disabled; 1 = Enabled
HR37doc 0025HEV1 alarm hysteresisDecimal point ignored: Raw integer; apply the decimal point setting.INT16Read/write
HR38doc 0026HEV1 alarm delay timeINT16Read/write
HR39doc 0027HEV1 alarm energized/de-energizedINT16Read/write0 = Energized; 1 = De-energized
HR40doc 0028HEV2 alarm value 0 enabled/disabledINT16Read/write0 = Disabled; 1 = Enabled
HR41doc 0029HEV2 alarm hysteresisDecimal point ignored: Raw integer; apply the decimal point setting.INT16Read/write
HR42doc 002AHEV2 alarm delay timeINT16Read/write
HR43doc 002BHEV2 alarm energized/de-energizedINT16Read/write0 = Energized; 1 = De-energized
HR60doc 003CHOUT1 proportional bandDecimal point ignored: Raw integer; apply the decimal point setting.INT16Read/write
HR61doc 003DHIntegral timeINT16Read/write
HR62doc 003EHDerivative timeINT16Read/write
HR63doc 003FHARWAnti-reset windup.INT16Read/write
HR64doc 0040HManual resetDecimal point ignored: Raw integer; apply the decimal point setting.INT16Read/write
HR65doc 0041HOUT1 proportional cycleINT16Read/write
HR66doc 0042HOUT1 ON/OFF hysteresisDecimal point ignored: Raw integer; apply the decimal point setting.INT16Read/write
HR67doc 0043HOUT1 high limitINT16Read/write
HR68doc 0044HOUT1 low limitINT16Read/write
HR69doc 0045HOUT1 rate-of-changeINT16Read/write
HR70doc 0046HOUT2 cooling methodINT16Read/write0 = Air cooling; 1 = Oil cooling; 2 = Water cooling
HR71doc 0047HOUT2 proportional bandDecimal point ignored: Raw integer; apply the decimal point setting.INT16Read/write
HR72doc 0048HOUT2 proportional cycleINT16Read/write
HR73doc 0049HOUT2 ON/OFF hysteresisDecimal point ignored: Raw integer; apply the decimal point setting.INT16Read/write
HR74doc 004AHOUT2 high limitINT16Read/write
HR75doc 004BHOUT2 low limitINT16Read/write
HR76doc 004CHOverlap band/dead bandDecimal point ignored: Raw integer; apply the decimal point setting.INT16Read/write
HR77doc 004DHDirect/reverse actionINT16Read/write0 = Reverse (heating); 1 = Direct (cooling)
HR78doc 004EHSet value lockINT16Read/write0 = Unlock; 1 = Lock 1; 2 = Lock 2; 3 = Lock 3; 4 = Lock 4; 5 = Lock 5
HR79doc 004FHSensor correction coefficientDecimal point ignored: Raw integer; apply the decimal point setting.INT16Read/write
HR80doc 0050HSensor correctionDecimal point ignored: Raw integer; apply the decimal point setting.INT16Read/write
HR81doc 0051HPV filter time constantDecimal point ignored: Raw integer; apply the decimal point setting.INT16Read/write
HR82doc 0052HResponse delay timeComm response delay.INT16Read/write
HR83doc 0053HSVTC biasDecimal point ignored: Raw integer; apply the decimal point setting.INT16Read/write
HR84doc 0054HExternal setting input high limitDecimal point ignored: Raw integer; apply the decimal point setting.INT16Read/write
HR85doc 0055HExternal setting input low limitDecimal point ignored: Raw integer; apply the decimal point setting.INT16Read/write
HR86doc 0056HRemote biasDecimal point ignored: Raw integer; apply the decimal point setting.INT16Read/write
HR87doc 0057HSV rise/fall rate start typeINT16Read/write0 = SV start; 1 = PV start
HR88doc 0058HSV rise rateDecimal point ignored: Raw integer; apply the decimal point setting.INT16Read/write
HR89doc 0059HSV fall rateDecimal point ignored: Raw integer; apply the decimal point setting.INT16Read/write
HR90doc 005AHIndication when control output OFFINT16Read/write0 = OFF indication; 1 = No indication; 2 = PV indication; 3 = PV indication + any alarm active
HR91doc 005BHAT biasDecimal point ignored: Raw integer; apply the decimal point setting.INT16Read/write
HR92doc 005CHOutput status when input errors occurINT16Read/write0 = Output OFF; 1 = Output ON
HR93doc 005DHAuto/manual after power ONINT16Read/write0 = Automatic control; 1 = Manual control
HR224doc 00E0HOUT/OFF key functionINT16Read/write0 = Control output OFF function; 1 = Auto/Manual control; 2 = Program control
HR225doc 00E1HRemote/localINT16Read/write0 = Local; 1 = Remote
HR226doc 00E2HOutput OFF / Auto-Manual / Program RUNMeaning follows the OUT/OFF key function (00E0H); see notes.INT16Read/write
HR227doc 00E3HProgram control holdingINT16Read/write0 = Not holding; 1 = Holding
HR228doc 00E4HOutput by communication commandBITMAP16Read/writebit 0 = EV1 output on; bit 1 = EV2 output on
HR229doc 00E5HManual control MVINT16Read/write
HR230doc 00E6HAT/Auto-reset perform/cancelINT16Read/write0 = Cancel AT / AT on startup / auto-reset; 1 = AT/Auto-reset perform; 2 = AT on startup perform
HR231doc 00E7HController/converterINT16Read/write0 = Controller; 1 = Converter
HR232doc 00E8HAT gainDecimal point ignored: Raw integer; apply the decimal point setting.INT16Read/write
HR233doc 00E9HProgram control advanceINT16Write1 = Advance perform
HR254doc 00FEHData clearResets all settings to factory defaults.INT16Write4660 = Clear data (1234H)
HR255doc 00FFHKey operation change flag clearingINT16Write1 = Clear the flag
HR256doc 0100HPVProcess value. Decimal point ignored: Raw integer; apply the decimal point setting.INT16Read
HR257doc 0101HOUT1 MVDecimal point ignored: Raw integer; apply the decimal point setting.INT16Read
HR258doc 0102HOUT2 MVDecimal point ignored: Raw integer; apply the decimal point setting.INT16Read
HR259doc 0103HCurrent SVDecimal point ignored: Raw integer; apply the decimal point setting.INT16Read
HR260doc 0104HSet value memory numberINT16Read
HR261doc 0105HRemaining time (program)INT16Read
HR263doc 0107HStep number (program)INT16Read
HR264doc 0108HNumber of repetitions (program)INT16Read
HR265doc 0109HCT1 current valueDecimal point ignored: Raw integer; apply the decimal point setting.INT16Read
HR266doc 010AHCT2 current valueDecimal point ignored: Raw integer; apply the decimal point setting.INT16Read
HR268doc 010CHKey operation changed itemData item last changed from the keypad.INT16Read
HR269doc 010DHStatus flag 1BITMAP16Readbit 0 = OUT1 output on; bit 1 = OUT2 output on; bit 2 = EV1 output on; bit 3 = EV2 output on; bit 9 = AT/auto-reset/AT on startup performing; bit 10 = 1 = AT on startup, 0 = AT/auto-reset; bit 11 = Heater burnout alarm; bit 12 = Loop break alarm; bit 13 = Overscale; bit 14 = Underscale; bit 15 = Settings changed by keypad
HR270doc 010EHStatus flag 2BITMAP16Readbit 0 = DI1 input on; bit 1 = DI2 input on; bit 5 = Program control RUN (unit status 1); bit 6 = Setting mode (unit status 2); bit 7 = Warm-up; bit 8 = USB connection; bit 9 = Control output OFF; bit 10 = Manual control; bit 11 = Program control mode; bit 12 = Program control RUN; bit 13 = Wait function on; bit 14 = Hold function on; bit 15 = Pattern end function on

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Shinko Technos BCS2 / BCR2 / BCD2 digital indicating controller (C5, C5W options)

What Modbus registers does the Shinko Technos BCS2 / BCR2 / BCD2 digital indicating controller (C5, C5W options) have?

This map lists 91 registers: 91 holding registers. 78 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Shinko Technos BCS2 / BCR2 / BCD2 digital indicating controller (C5, C5W options) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Registers are listed as hex data items (0001H) that go into the request unchanged. The manual adds that the matching Modicon holding-register number is the item in decimal plus 40001 (0001H = 40002).

What are the minimum Modbus registers to integrate the Shinko Technos BCS2 / BCR2 / BCD2 digital indicating controller (C5, C5W options)?

Start with HR 256 PV (Process value); HR 1 SV1 (Set value SV1); HR 257 OUT1 MV (OUT1 manipulated value); HR 269 Status flag 1 (Output and alarm status); HR 270 Status flag 2 (Run mode status); HR 5 Decimal point place (Decimal point for scaling).

How do I enable Modbus control of the Shinko Technos BCS2 / BCR2 / BCD2 digital indicating controller (C5, C5W options)?

Requires the C5 or C5W option. Hold the up and down keys for 3 s in RUN mode to enter Engineering mode 1, then set Communication protocol to MODBUS RTU (not the JC command allocated variant), instrument number, speed, data bit/parity and stop bit.

Where is the official Shinko Technos BCS2 / BCR2 / BCD2 digital indicating controller (C5, C5W options) Modbus documentation?

The source is Communication Instruction Manual BCD2, BCR2, BCS2 (C5W, C5) (No.BCx2CE6), revision 2019-12, published free by Shinko Technos at https://shinko-technos.co.jp/e/manual/english/BCx2CE6.pdf.

More Shinko Technos Modbus register maps

Other temperature & process controllers register maps

All temperature & process controllers Modbus register maps →

Source: Communication Instruction Manual BCD2, BCR2, BCS2 (C5W, C5) · No.BCx2CE6 · rev. 2019-12. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.