Sensor (signal conditioner) · Modbus register map

Shinko Technos SGxL signal conditioner series (Modbus RTU) Modbus register map

Updated 17 November 2026

Short answer

The SGxL family are signal conditioners that turn DC, thermocouple or RTD inputs into analog output signals, with an RS-485 Modbus RTU port. Every item is a signed 16-bit register. The map covers input and output range settings, filtering, manual output, communication settings, the measured input, output value and the status word.

This page lists 46 Modbus registers for the Shinko Technos SGxL signal conditioner series (Modbus RTU) — 41 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Shinko Technos’s own free documentation (linked below) and checked against it.

Manufacturer
Shinko Technos
Model
SGxL signal conditioner series (Modbus RTU)
Equipment type
Sensor (signal conditioner)
Registers
46 (41 writable)
Transport
Modbus RTU
Default unit ID
1
Default serial
38400 baud, 8O1
Documented addressing
hexadecimal, 0-based
Also known as
SGBL, SGCL, SGDL, SGIL, SGLL, SGML, SGPL, SGRL, SGSL, SGTL, SGUL
Source document
Communication Instruction Manual SGxL · No. SGxL1CE3 · rev. 2022-03
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Shinko Technos SGxL signal conditioner series (Modbus RTU)

Integration in brief

Wire RS-485, set the instrument number on the keypad (default 1, 38400 bps, 8 bits odd parity), then read input value 00B0H, output value 00B1H and status 00B2H.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 176Input valueINT16Measured input valueRead
HR 177Output 1 output valueINT16Output 1 valueRead
HR 178Status flagBITMAP16Over/underscale and mode statusRead
HR 19Decimal point placeINT16Input decimal pointRead/write
HR 20Output 0% valueINT16Input value at 0% outputRead/write
HR 21Output 100% valueINT16Input value at 100% outputRead/write

Enable Modbus control & writes

Modbus RTU is always on. Set instrument number, speed, data bit/parity, stop bit and response delay in Communication setting mode, then choose Save.

Byte order & addressing

Network setup

Watch out for

Shinko Technos SGxL signal conditioner series (Modbus RTU) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

46 of 46 shown
Shinko Technos SGxL signal conditioner series (Modbus RTU) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR1doc 0001HDefault Display/Manual modeManual mode needs Auto/Manual (0064H) set to Manual.INT16Read/write0 = Default Display; 1 = Manual mode
HR2doc 0002HOutput 1 output valueManual output value; not stored in non-volatile memory.INT16Read/write
HR16doc 0010HInput groupModel-dependent; reads 0 where not available.INT16Read/write0 = DC signal input; 1 = Thermocouple input; 2 = RTD input
HR17doc 0011HInput typeCode list depends on model and input group; see manual p. 15-16.INT16Read/write
HR18doc 0012HInput unitModel-dependent; reads 0 where not available.INT16Read/write0 = °C; 1 = °F
HR19doc 0013HDecimal point placeTC/RTD models allow only 0 or 1.INT16Read/write0 = No decimal point; 1 = 1 digit; 2 = 2 digits; 3 = 3 digits
HR20doc 0014HOutput 0% valueInput value giving 0% output; decimal point ignored.INT16Read/write
HR21doc 0015HOutput 100% valueInput value giving 100% output; decimal point ignored.INT16Read/write
HR22doc 0016HIndication unitINT16Read/write0 = No unit; 1 = %; 2 = mA; 3 = V; 4 = °C
HR23doc 0017HSquare root functionModel-dependent; reads 0 where not available.INT16Read/write0 = Disabled; 1 = Enabled
HR24doc 0018HLow level cutoffModel-dependent; reads 0 where not available.INT16Read/write
HR32doc 0020HOutput 1 typeCodes for all models except SGI. On SGI: 0 = 4-20 mA, 1 = 1-5 V.INT16Read/write0 = 4 to 20 mA; 1 = 0 to 20 mA; 2 = 0 to 16 mA; 3 = 2 to 10 mA; 4 = 0 to 10 mA; 5 = 0 to 10 mV; 6 = 0 to 100 mV; 7 = 0 to 1 V; 8 = 0 to 5 V; 9 = 1 to 5 V; 10 = 0 to 10 V; 11 = -5 to 5 V
HR33doc 0021HOutput 1 decimal point placeINT16Read/write0 = No decimal point; 1 = 1 digit; 2 = 2 digits; 3 = 3 digits
HR34doc 0022HOutput 1 indication at 0%INT16Read/write
HR35doc 0023HOutput 1 indication at 100%INT16Read/write
HR36doc 0024HOutput 1 low limitModel-dependent; reads 0 where not available.INT16Read/write
HR37doc 0025HOutput 1 high limitModel-dependent; reads 0 where not available.INT16Read/write
HR38doc 0026HOutput 1 low limit (outside rating)Model-dependent; reads 0 where not available.INT16Read/write
HR39doc 0027HOutput 1 high limit (outside rating)Model-dependent; reads 0 where not available.INT16Read/write
HR40doc 0028HI/O characteristicsModel-dependent; reads 0 where not available.INT16Read/write0 = V characteristics; 1 = Parallel characteristics
HR41doc 0029HOutput 1 split valueModel-dependent; reads 0 where not available.INT16Read/write
HR42doc 002AHOutput 1 Normal/ReverseINT16Read/write0 = Normal; 1 = Reverse
HR43doc 002BHOutput 1 ratioModel-dependent; reads 0 where not available.INT16Read/write
HR44doc 002CHOutput 1 biasModel-dependent; reads 0 where not available.INT16Read/write
HR45doc 002DHInput point 1Model-dependent; reads 0 where not available.INT16Read/write
HR46doc 002EHOutput 1 output value 1Model-dependent; reads 0 where not available.INT16Read/write
HR47doc 002FHInput point 2Model-dependent; reads 0 where not available.INT16Read/write
HR48doc 0030HOutput 1 output value 2Model-dependent; reads 0 where not available.INT16Read/write
HR96doc 0060HFilter time constantINT16Read/write
HR97doc 0061HSensor correctionINT16Read/write
HR98doc 0062HInput disconnection statusBurnout direction. Model-dependent; reads 0 where not available.INT16Read/write0 = Overscale; 1 = Underscale
HR99doc 0063HIndication timeINT16Read/write
HR100doc 0064HAuto/ManualINT16Read/write0 = Auto; 1 = Manual
HR101doc 0065HRatio setting methodModel-dependent; reads 0 where not available.INT16Read/write0 = Ratio setting; 1 = Output value setting
HR105doc 0069HManual mode auto return timeINT16Read/write
HR128doc 0080HInstrument numberSlave address 1-247. Change the master to match after writing.INT16Read/write
HR129doc 0081HCommunication speedINT16Read/write0 = 9600 bps; 1 = 19200 bps; 2 = 38400 bps
HR130doc 0082HData bit/ParityINT16Read/write0 = 8 bits/No parity; 1 = 8 bits/Even; 2 = 8 bits/Odd
HR131doc 0083HStop bitINT16Read/write0 = 1 bit; 1 = 2 bits
HR132doc 0084HResponse delay timeINT16msRead/write
HR160doc 00A0HKey operation change flag clearingWrite-only (function 06); any value other than 1 is rejected.INT16Write1 = Clear key operation change flag
HR176doc 00B0HInput valueMeasured input; decimal point ignored, apply 0013H.INT16Read
HR177doc 00B1HOutput 1 output valueDecimal point ignored, apply 0021H.INT16Read
HR178doc 00B2HStatus flagBITMAP16Readbit 0 = Input overscale; bit 1 = Input underscale; bit 11 = USB connection; bit 12 = Setting mode (0 = Default Display); bit 13 = Manual mode (0 = Default Display); bit 14 = Locked; bit 15 = Changed by key operation
HR208doc 00D0HSoftware versionINT16Read
HR210doc 00D2HKey operation changed itemData item last changed on the keypad.INT16Read

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Shinko Technos SGxL signal conditioner series (Modbus RTU)

What Modbus registers does the Shinko Technos SGxL signal conditioner series (Modbus RTU) have?

This map lists 46 registers: 46 holding registers. 41 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Shinko Technos SGxL signal conditioner series (Modbus RTU) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Registers are listed as hex data items (0001H) that go into the request unchanged. The manual adds that the matching Modicon holding-register number is the item in decimal plus 40001 (0001H = 40002).

What are the minimum Modbus registers to integrate the Shinko Technos SGxL signal conditioner series (Modbus RTU)?

Start with HR 176 Input value (Measured input value); HR 177 Output 1 output value (Output 1 value); HR 178 Status flag (Over/underscale and mode status); HR 19 Decimal point place (Input decimal point); HR 20 Output 0% value (Input value at 0% output); HR 21 Output 100% value (Input value at 100% output).

How do I enable Modbus control of the Shinko Technos SGxL signal conditioner series (Modbus RTU)?

Modbus RTU is always on. Set instrument number, speed, data bit/parity, stop bit and response delay in Communication setting mode, then choose Save.

Where is the official Shinko Technos SGxL signal conditioner series (Modbus RTU) Modbus documentation?

The source is Communication Instruction Manual SGxL (No. SGxL1CE3), revision 2022-03, published free by Shinko Technos at https://shinko-technos.co.jp/e/manual/english/SGxL1CE3.pdf.

More Shinko Technos Modbus register maps

Other valves, actuators & sensors register maps

All valves, actuators & sensors Modbus register maps →

Source: Communication Instruction Manual SGxL · No. SGxL1CE3 · rev. 2022-03. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.