- Home
- Modbus register maps
- Shinko Technos
- SGxL signal conditioner series (Modbus RTU)
Sensor (signal conditioner) · Modbus register map
Shinko Technos SGxL signal conditioner series (Modbus RTU) Modbus register map
Updated 17 November 2026
The SGxL family are signal conditioners that turn DC, thermocouple or RTD inputs into analog output signals, with an RS-485 Modbus RTU port. Every item is a signed 16-bit register. The map covers input and output range settings, filtering, manual output, communication settings, the measured input, output value and the status word.
This page lists 46 Modbus registers for the Shinko Technos SGxL signal conditioner series (Modbus RTU) — 41 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Shinko Technos’s own free documentation (linked below) and checked against it.
- Manufacturer
- Shinko Technos
- Model
- SGxL signal conditioner series (Modbus RTU)
- Equipment type
- Sensor (signal conditioner)
- Registers
- 46 (41 writable)
- Transport
- Modbus RTU
- Default unit ID
- 1
- Default serial
- 38400 baud, 8O1
- Documented addressing
- hexadecimal, 0-based
- Also known as
- SGBL, SGCL, SGDL, SGIL, SGLL, SGML, SGPL, SGRL, SGSL, SGTL, SGUL
Integration notes: Shinko Technos SGxL signal conditioner series (Modbus RTU)
Wire RS-485, set the instrument number on the keypad (default 1, 38400 bps, 8 bits odd parity), then read input value 00B0H, output value 00B1H and status 00B2H.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 176 | Input value | INT16 | Measured input value | Read |
| HR 177 | Output 1 output value | INT16 | Output 1 value | Read |
| HR 178 | Status flag | BITMAP16 | Over/underscale and mode status | Read |
| HR 19 | Decimal point place | INT16 | Input decimal point | Read/write |
| HR 20 | Output 0% value | INT16 | Input value at 0% output | Read/write |
| HR 21 | Output 100% value | INT16 | Input value at 100% output | Read/write |
Enable Modbus control & writes
Modbus RTU is always on. Set instrument number, speed, data bit/parity, stop bit and response delay in Communication setting mode, then choose Save.
Byte order & addressing
- Serial RS-485 and the console (USB tool cable) cannot be used together; unplug the tool cable for Modbus.
- Writing communication settings over the bus takes effect on the unit; update the master to match.
Network setup
- Factory defaults: instrument number 1, 38400 bps, 8 data bits, odd parity, 1 stop bit, 10 ms response delay.
- Speeds 9600, 19200 or 38400 bps; up to 31 units on one line.
Watch out for
- Exception 18 (12H) is returned while the keypad is in setting mode.
- Non-volatile memory is good for about one million writes; 0002H is the exception and is not stored.
Shinko Technos SGxL signal conditioner series (Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 1doc 0001H | Default Display/Manual mode | Manual mode needs Auto/Manual (0064H) set to Manual. | INT16 | Read/write | 0 = Default Display; 1 = Manual mode | |||
| HR | 2doc 0002H | Output 1 output value | Manual output value; not stored in non-volatile memory. | INT16 | Read/write | ||||
| HR | 16doc 0010H | Input group | Model-dependent; reads 0 where not available. | INT16 | Read/write | 0 = DC signal input; 1 = Thermocouple input; 2 = RTD input | |||
| HR | 17doc 0011H | Input type | Code list depends on model and input group; see manual p. 15-16. | INT16 | Read/write | ||||
| HR | 18doc 0012H | Input unit | Model-dependent; reads 0 where not available. | INT16 | Read/write | 0 = °C; 1 = °F | |||
| HR | 19doc 0013H | Decimal point place | TC/RTD models allow only 0 or 1. | INT16 | Read/write | 0 = No decimal point; 1 = 1 digit; 2 = 2 digits; 3 = 3 digits | |||
| HR | 20doc 0014H | Output 0% value | Input value giving 0% output; decimal point ignored. | INT16 | Read/write | ||||
| HR | 21doc 0015H | Output 100% value | Input value giving 100% output; decimal point ignored. | INT16 | Read/write | ||||
| HR | 22doc 0016H | Indication unit | INT16 | Read/write | 0 = No unit; 1 = %; 2 = mA; 3 = V; 4 = °C | ||||
| HR | 23doc 0017H | Square root function | Model-dependent; reads 0 where not available. | INT16 | Read/write | 0 = Disabled; 1 = Enabled | |||
| HR | 24doc 0018H | Low level cutoff | Model-dependent; reads 0 where not available. | INT16 | Read/write | ||||
| HR | 32doc 0020H | Output 1 type | Codes for all models except SGI. On SGI: 0 = 4-20 mA, 1 = 1-5 V. | INT16 | Read/write | 0 = 4 to 20 mA; 1 = 0 to 20 mA; 2 = 0 to 16 mA; 3 = 2 to 10 mA; 4 = 0 to 10 mA; 5 = 0 to 10 mV; 6 = 0 to 100 mV; 7 = 0 to 1 V; 8 = 0 to 5 V; 9 = 1 to 5 V; 10 = 0 to 10 V; 11 = -5 to 5 V | |||
| HR | 33doc 0021H | Output 1 decimal point place | INT16 | Read/write | 0 = No decimal point; 1 = 1 digit; 2 = 2 digits; 3 = 3 digits | ||||
| HR | 34doc 0022H | Output 1 indication at 0% | INT16 | Read/write | |||||
| HR | 35doc 0023H | Output 1 indication at 100% | INT16 | Read/write | |||||
| HR | 36doc 0024H | Output 1 low limit | Model-dependent; reads 0 where not available. | INT16 | Read/write | ||||
| HR | 37doc 0025H | Output 1 high limit | Model-dependent; reads 0 where not available. | INT16 | Read/write | ||||
| HR | 38doc 0026H | Output 1 low limit (outside rating) | Model-dependent; reads 0 where not available. | INT16 | Read/write | ||||
| HR | 39doc 0027H | Output 1 high limit (outside rating) | Model-dependent; reads 0 where not available. | INT16 | Read/write | ||||
| HR | 40doc 0028H | I/O characteristics | Model-dependent; reads 0 where not available. | INT16 | Read/write | 0 = V characteristics; 1 = Parallel characteristics | |||
| HR | 41doc 0029H | Output 1 split value | Model-dependent; reads 0 where not available. | INT16 | Read/write | ||||
| HR | 42doc 002AH | Output 1 Normal/Reverse | INT16 | Read/write | 0 = Normal; 1 = Reverse | ||||
| HR | 43doc 002BH | Output 1 ratio | Model-dependent; reads 0 where not available. | INT16 | Read/write | ||||
| HR | 44doc 002CH | Output 1 bias | Model-dependent; reads 0 where not available. | INT16 | Read/write | ||||
| HR | 45doc 002DH | Input point 1 | Model-dependent; reads 0 where not available. | INT16 | Read/write | ||||
| HR | 46doc 002EH | Output 1 output value 1 | Model-dependent; reads 0 where not available. | INT16 | Read/write | ||||
| HR | 47doc 002FH | Input point 2 | Model-dependent; reads 0 where not available. | INT16 | Read/write | ||||
| HR | 48doc 0030H | Output 1 output value 2 | Model-dependent; reads 0 where not available. | INT16 | Read/write | ||||
| HR | 96doc 0060H | Filter time constant | INT16 | Read/write | |||||
| HR | 97doc 0061H | Sensor correction | INT16 | Read/write | |||||
| HR | 98doc 0062H | Input disconnection status | Burnout direction. Model-dependent; reads 0 where not available. | INT16 | Read/write | 0 = Overscale; 1 = Underscale | |||
| HR | 99doc 0063H | Indication time | INT16 | Read/write | |||||
| HR | 100doc 0064H | Auto/Manual | INT16 | Read/write | 0 = Auto; 1 = Manual | ||||
| HR | 101doc 0065H | Ratio setting method | Model-dependent; reads 0 where not available. | INT16 | Read/write | 0 = Ratio setting; 1 = Output value setting | |||
| HR | 105doc 0069H | Manual mode auto return time | INT16 | Read/write | |||||
| HR | 128doc 0080H | Instrument number | Slave address 1-247. Change the master to match after writing. | INT16 | Read/write | ||||
| HR | 129doc 0081H | Communication speed | INT16 | Read/write | 0 = 9600 bps; 1 = 19200 bps; 2 = 38400 bps | ||||
| HR | 130doc 0082H | Data bit/Parity | INT16 | Read/write | 0 = 8 bits/No parity; 1 = 8 bits/Even; 2 = 8 bits/Odd | ||||
| HR | 131doc 0083H | Stop bit | INT16 | Read/write | 0 = 1 bit; 1 = 2 bits | ||||
| HR | 132doc 0084H | Response delay time | INT16 | ms | Read/write | ||||
| HR | 160doc 00A0H | Key operation change flag clearing | Write-only (function 06); any value other than 1 is rejected. | INT16 | Write | 1 = Clear key operation change flag | |||
| HR | 176doc 00B0H | Input value | Measured input; decimal point ignored, apply 0013H. | INT16 | Read | ||||
| HR | 177doc 00B1H | Output 1 output value | Decimal point ignored, apply 0021H. | INT16 | Read | ||||
| HR | 178doc 00B2H | Status flag | BITMAP16 | Read | bit 0 = Input overscale; bit 1 = Input underscale; bit 11 = USB connection; bit 12 = Setting mode (0 = Default Display); bit 13 = Manual mode (0 = Default Display); bit 14 = Locked; bit 15 = Changed by key operation | ||||
| HR | 208doc 00D0H | Software version | INT16 | Read | |||||
| HR | 210doc 00D2H | Key operation changed item | Data item last changed on the keypad. | INT16 | Read |
Notes on this map
- Output 2 items (0040H-0050H) are left out: the manual marks them as console-software data that cannot be used.
- Input type codes are not listed here because the code table changes with model and input group (pp. 15-16).
- 0001H-0002H accept single-register function 03/06 only; 0010H-0084H also accept function 10H; read-only items accept 03 or 04.
- All data are 16-bit two's complement and values with a decimal point are sent without it.
- Multi-Display character registers 0070H-0077H are omitted (front-panel label characters).
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Shinko Technos SGxL signal conditioner series (Modbus RTU)
What Modbus registers does the Shinko Technos SGxL signal conditioner series (Modbus RTU) have?
This map lists 46 registers: 46 holding registers. 41 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Shinko Technos SGxL signal conditioner series (Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Registers are listed as hex data items (0001H) that go into the request unchanged. The manual adds that the matching Modicon holding-register number is the item in decimal plus 40001 (0001H = 40002).
What are the minimum Modbus registers to integrate the Shinko Technos SGxL signal conditioner series (Modbus RTU)?
Start with HR 176 Input value (Measured input value); HR 177 Output 1 output value (Output 1 value); HR 178 Status flag (Over/underscale and mode status); HR 19 Decimal point place (Input decimal point); HR 20 Output 0% value (Input value at 0% output); HR 21 Output 100% value (Input value at 100% output).
How do I enable Modbus control of the Shinko Technos SGxL signal conditioner series (Modbus RTU)?
Modbus RTU is always on. Set instrument number, speed, data bit/parity, stop bit and response delay in Communication setting mode, then choose Save.
Where is the official Shinko Technos SGxL signal conditioner series (Modbus RTU) Modbus documentation?
The source is Communication Instruction Manual SGxL (No. SGxL1CE3), revision 2022-03, published free by Shinko Technos at https://shinko-technos.co.jp/e/manual/english/SGxL1CE3.pdf.
More Shinko Technos Modbus register maps
- Sensor (digital temperature controller)
Shinko Technos ACD-13A / ACR-13A / ACD-15A / ACR-15A digital indicating controller (C, C5 options)
Shinko ACD/ACR-13A (PID) and ACD/ACR-15A (valve positioning) with the C or C5 communication option; manual No.ACDR1CE8.
Also known as: ACD-13A, ACR-13A, ACD-15A, ACR-15A - Sensor (digital temperature controller)
Shinko Technos ACS-13A digital indicating controller (C5 option)
Shinko ACS-13A with the C5 serial communication option; communication manual No.ACS12CE5.
Also known as: ACS-13A-C5, ACS-13A C5 - Sensor (digital temperature controller)
Shinko Technos ACS2 digital indicating controller (C5, C5W options)
Shinko ACS2 with the C5 or C5W serial option, Shinko protocol / MODBUS RTU command set; manual No.ACS2CE3.
Also known as: ACS2-C5, ACS2-C5W - Sensor (conductivity controller)
Shinko Technos AER-102-ECH conductivity indicating controller (C5 option)
Shinko AER-102-ECH electrical conductivity controller with the C5 RS-485 option; manual No. AER11CECE5.
Also known as: AER-102-ECH - Sensor (digital temperature controller)
Shinko Technos BCS2 / BCR2 / BCD2 digital indicating controller (C5, C5W options)
Shinko BCx2 series (BCS2, BCR2, BCD2) with the C5 or C5W communication option, standard (not JC-allocated) command set; manual No.BCx2CE6.
Also known as: BCS2, BCR2, BCD2, BCx2 - Sensor (digital temperature controller)
Shinko Technos DCL-33A DC digital indicating controller (C5 option)
Shinko DCL-33A DC with the C5 option; communication manual No.DCL3CDCE2.
Also known as: DCL-33A DC, DCL-33A-DC-C5 - Sensor (digital temperature controller)
Shinko Technos DCL-33A digital indicating controller (C5 option)
Shinko DCL-33A with the C5 serial option, plain (non-block) Modbus protocol setting; manual No.DCL32CE3.
Also known as: DCL-33A-C5, DCL-33A C5 - Sensor (digital temperature controller)
Shinko Technos FC series digital indicating controller (C/C5 option, Modbus ASCII)
Shinko FCS-23A, FCR-13A, FCR-23A and FCD-13A with the C or C5 serial option; FCR-15A and FCD-15A have no Modbus (Shinko protocol only). Manual No.FC1CE11.
Also known as: FCS-23A, FCR-13A, FCR-23A, FCD-13A - Sensor (paperless recorder)
Shinko Technos GR200 paperless recorder (Modbus RTU / Modbus TCP)
Shinko GR200 paperless recorder with RS-485 Modbus RTU or Ethernet Modbus TCP; manual GR2CE1.
Also known as: GR200 - Sensor (chart recorder)
Shinko Technos HR-700 hybrid recorder (Modbus RTU, firmware 4.00+)
Shinko HR-700 hybrid recorders (multipoint and pen types), body version 4.00 or later, Modbus map version 01; manual No. HR7CE4.
Also known as: HR-700 - Sensor (digital temperature controller)
Shinko Technos JCL-33A digital indicating controller (C5 option)
Shinko JCL-33A with the C5 option, protocol set to plain 'Modbus RTU mode' or 'Modbus ASCII mode' (not the Block Read/Write modes, which use another layout); manual No.JCL3CE3.
Also known as: JCL-33A-C5, JCL-33A C5 - Sensor (digital temperature controller)
Shinko Technos JCS-33A / JCM-33A / JCR-33A / JCD-33A digital indicating controller (C5 option)
Shinko JCx-33A series (JCS, JCM, JCR, JCD-33A) with the C5 option; communication manual No.JC3CE11.
Also known as: JCS-33A, JCM-33A, JCR-33A, JCD-33A, JCx-33A - Sensor (digital temperature controller)
Shinko Technos JIR-301-M digital indicator (C5 option)
Shinko JIR-301-M with the C5 option, plain (non-block) Modbus protocol setting; manual No.JIR32CE4.
Also known as: JIR-301-M-C5, JIR-301-M C5 - Sensor (programmable temperature controller)
Shinko Technos PCA1 programmable controller (C/C5 option)
Shinko PCA1 programmable controllers with the C or C5 serial option; manual No. PCA1CE3.
Also known as: PCA1 - Sensor (programmable temperature controller)
Shinko Technos PCB1 programmable controller (C5W/C5 option)
Shinko PCB1 programmable controllers with the C5W or C5 RS-485 option, native PCB1 command set; manual No. PCB1CE3.
Also known as: PCB1 - Sensor (digital temperature controller)
Shinko Technos PCD-33A programmable controller (C5 option)
Shinko PCD-33A program controller with the C5 RS-485 option; manual printed No.PCD3CE1 2003.02 (file PCD3CE2).
Also known as: PCD-33A-R/M, PCD-33A-S/M - Sensor (digital temperature controller)
Shinko Technos WCL-13A 2-channel digital indicating controller (C5 option)
Shinko WCL-13A two-loop controller with the C5 option; communication manual No.WCL1CE3.
Also known as: WCL-13A-C5, WCL-13A C5
Other valves, actuators & sensors register maps
- Sensor (flame detector)
Teledyne Gas and Flame Detection Spyglass SG50-F flame detector (Modbus RTU)
Teledyne Spyglass SG50-F optical flame detectors (IR3, UV-IR, IR3-H2 and HD video variants) with RS-485 Modbus RTU, communication manual SG50FMODBUS-EN rev 1.0.
Also known as: SG50-F, Spyglass SG50-F, IR3-HD, UV-IR, IR3, UV-IR-HD, IR3-H2-HD, IR3-H2, UV-IR-F, UV-IR-F-HD - Sensor (CO2 / humidity / temperature / pressure)
Teracom TSM400-4-CPTH Modbus CO2, humidity, temperature and pressure multi-sensor
TSM400-4-CPTH per the Teracom TSM400-4-CPTH user manual TSM400-4-CPTH-R1.9.
Also known as: TSM400-4-CPTH - Sensor (dew point transmitter)
Vaisala DMT153 dew point transmitter (Modbus RTU)
DMT153 trace-moisture dew point transmitter, Modbus RTU interface (user guide M213149EN-B).
Also known as: DMT153, DRYCAP DMT153 - Sensor (humidity and temperature probe)
Vaisala HMP Series (HMP1-HMP9) with MMP8 and TMP1 probes (Modbus RTU)
Vaisala HMP1/3/4/5/7/8/9, TMP1 and MMP8 probes with the Modbus RTU interface (user guide M212022EN-M).
Also known as: HMP1, HMP3, HMP4, HMP5, HMP7, HMP8, HMP9, TMP1, MMP8 - Sensor (moisture in oil transmitter)
Vaisala MMT143 moisture in oil transmitter (Modbus RTU)
MMT143 moisture-in-oil transmitter ordered with the Modbus RTU option (user guide M213308EN-B).
Also known as: MMT143 - Sensor
VTS RH+T-SENS-D-MODRTU humidity and temperature transducer
VTS RH+T-SENS-D-MODRTU duct humidity and temperature transducer (Sensirion SHT31-DIS-B), manual ver. 2.0 (11.2021).
Also known as: RH&T-SENS-D-MODRTU, VTS duct humidity sensor
All valves, actuators & sensors Modbus register maps →
Source: Communication Instruction Manual SGxL · No. SGxL1CE3 · rev. 2022-03. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.